Professional Documents
Culture Documents
New Intern Report
New Intern Report
EXECUTIVE SUMMARY
This is internship report is based on one month internship program that I had successfully completed
in KAVIKA from 11-02-2023 to 11-03-2023 as per the requirement of my Bachelor of Engineering
Degree in Department of Electrical and Electronic engineering, at Bangalore Institute of technology.
Distribution transformer places a very important role in an Electrical network as it step-down the low
transmission voltage to distribution voltage or distribution voltage to service voltage for consumer
applications. The company supplies mainly distribution transformer with capacities 25kVA, 63kVA,
100kVA, 250kVA and 500kVA.
This internship covers the study on manufacturing and testing of distribution transformers, the material
used for particular rated transformer kVA. It also explains the tests that the transformer undergoes to
determine the various parameters which interns decides its efficiency and lifestyle.
Initially the designer decides the transformer as per the customer's specification. After which in the
manufacturing unit the raw materials required for manufacturing is imported and the materials are tested
to match Indian standards (IS) before commencing the process. The tested materials are stored in the
storage room. Whenever there is a requirement, the raw materials are procured from the storage mass
and involved in manufacturing of HV and LV winding, core formation, core coil assembly and finally
it is connected to form an active element. This active element is then placed in special chamber called
vacuum chamber. Where the moisture content of the active part is removed. The element is then dried
and bushings were connected . Finally, the active part is low-ward into the tank consisting of calculated
amount of transformer oil and fastened using fasteners.
CHAPTER 1
1.1. INTRODUCTION
KAVIKA (Karnataka Vidyuth Karkhane Limited) was established in 1933 by Maharaja of Mysore as
Government Electrical Factory, the first ever manufacturer of Electrical transformers in India. The
company supplies mainly distribution transformer with capacities 25kVA, 63kVA, 100kVA, 250kVA
and 500kVA.
KAVIKA is one of the largest selling transformers in India as the product goes through strict quality
checks at every stage to ensure best comes out of the factory to reach the customers through the country.
The secret behind the popularity of KAVIKA transformers is the strict adherence quality norms, at
every stage of manufacturing. Starting from the imported prime quality CRGO coil indigenous raw
materials, the product goes through strict quality checks at every stage to ensure that only the best
comes out the factory to reach a select band of customers, across the country.
Today, after 9 decades of successful production and operations, KAVIKA has emerged as a renowned
name for Distribution Transformers in the range of 25 kVA to 500 kVA up to 11 kV/433V Class as well
as for custom built / special type transformers as per specific requirements.
Vision
KAVIKA committed to supply energy efficient transformers as per the agreed specifications in time at
most competitive rate with enhanced customer satisfaction and to put efforts continually to improve the
quality of the products supplied and QMS.
Mission
To become a globally competitive transformer production industry while working as an instrument for
achieving self-reliance in design, manufacture and maintaining the quality of the equipment and
diversifying to related areas, managing the business and commercial lines in a scenario of growing
professional competent.
Products
Energy Efficient 3, 4 & 5 star category transformers Fully as per IS Specifications. All materials used in
the manufacture are as per IS specifications. All the materials are tested to meet the IS requirements.
Sufficient cooling is provided to dissipate the guaranteed losses and to maintain the guaranteed
temperature rises – which gives longer life to Transformer.
Company Profile
1.3.MAJOR MILESTONES
❖ The company was established in 1933 as a Government Electric Factoryfor manufacturing of electrical
accessories.
❖ The company has obtained Approval/Certification from Bureau of Energy Efficiency (BEE) for
manufacture of star rated transformers.
❖ The company is shifting its focus from producing the conventional trans-formers to the star rated
category of transformers of different capacities.
❖ After 1995 onwards, KAVIKA started using Auto Cad for designing thetransformers.
SERVICES
The various services which KAVIKA is currently offering are as follows:
REPAIR SERVICES:
WITHIN WARRANTEE PERIOD: The warrantee period for a distribution transformer is usually 3
years. If there is any problem withinthe warrantee period, then the company provides repair services
to thecustomers.
MORE THAN WARRANTEE PERIOD: If any problem occurs in the transformer after the warrantee
period, the company provides repair ser- vices to consumer with changes.
ENGINEERING SERVICES:
Utilities processing any problems at the time of installation or in operationcondition of the transformers
will be solved by the services engineers.
CLIENTS
The major customer of the state Electricity Company in India. KAVIKA has ESCOM customers all over
India. Frequent customers are given below:
❖ Bangalore Electricity Supply Company Limited
❖ Hubli Electricity Supply Company Limited.
❖ Mangalore Electricity Supply Company Limited.
❖ Gulbarga Electricity Supply Company Limited
❖ Chamundeshwari Electricity Supply Company Limited.
❖ Karnataka Power Corporation Limited.
CHAPTER 2
Purchase Department:
Purchase department purchase the material, needed to manufacturer the transformer as per requirement.
The purchase department is headed by the purchase manager followed by assistant purchase manager
and staffs. All purchase by KAVIKA and order issue by the company are subjected to the terms and
conditions mentioned here under, unless the company confirm them in writing, they are not binding on
the company. The acceptance of the order is deemed as the acceptance of the following terms and
conditions, some exception mutually agreed upon.
Design Department:
The design department gives the design specification of the different types transformers as per quality
standard. Latest technology is being used which is in accordance to BIS and all the designs are computer
generated. By using computer design software, accurate drawings are generated quickly and in less time.
Final document required for production, purchase of material etc. will be generated by the design
department send to the respective departments for further process.
Quality Control:
QC department is headed by the chief quality assurance manager followed deputy manager. Assistant
engineer for final testing, raw materials inspection and stage inspection are under the Deputy Manager.
Under Assistant engineer and junior engineer are present for checking mainly for winding, coil assembly
and core assembly. To ensure quality and to reduce the defective product being further process,
inspection and testing at the following stages is done:
❖ Incoming material inspection.
❖ In process inspection.
❖ Final inspection of outgoing product.
❖ The decision of the inspection department as to the acceptance of otherwise, shall be final and binding
on the supplier. In the end, the supplier company shall have the right on the rejected materials.
❖ To demand the replacement of the rejected materials by the suppliers within the extra cost of the
supplier.
❖ To terminate the contract and buy an equal quantity of goods rejected or others of similar nature
elsewhere at the risk and expenses of the supplier of any further consignments due under the purchase
order, damages for such losses will be recovered by the supplier.
❖ All material provisionally accepted since 100% check of goods is impossible and it is binding on the
supplier to replace or compensate the value for such materials that are rejected during the course of
actual use of materials. The limiting period is one year from the date of receipt of the respective items
in KAVIKA stores.
Store Department:
Storages are used for functions of receiving, storing and issuing materials for assembly of transformers
and proper maintenance of information regarding receipt, issue and requirement of materials. Store
departments headed by deputy general manager- stores/purchase followed by assisted general manager.
Commercial superintendent and store keeper work under them along with supporting staff.
The main objective is to define the procedure for preserving product conformity during internal
processing and delivery to the intended destination. It includes,
❖ Product identification, handling, packing, storage and protection.
❖ It also covers rising of purchase requisition and it applies to all raw materials such as CRGO coils, craft
paper, copper wires, components like studs, capital equipment, spare tools, measuring instruments, in
process items and finished products.
Production department:
❖ HV and LV winding.
❖ Core assembly.
❖ Connection and tapping.
❖ Drying.
❖ Lowering.
❖ Oil filling.
❖ Name plate fixing.
❖ Dispatch.
The general process flow is as follows. The materials process from carpentry section such as press board
sheets and craft paper are sent to the winding and coil assembly process. Core assembly is done for
which the HV and LV coils are assembled and sent to the coil ratio testing area. Passing this test, the
assembly is further sent to connecting process followed by heating the assembly in the heating chamber.
The coils that do not pass the ratio test to rework. Following the heating process, the coils are lowered
rig assembly is into the tanks and filled with oil. The final ring is done along with terminal and bush
assembly and sent to the quality testing area. Transformers passing these tests are sent to dispatch which
others are sent to rework.
Testing department:
After manufacturing, conduct different test to check the operational performance and withstanding
capacity of transformer. Test details are explained later.
Design and quality control manager heads the maintenance department followed by deputy manager,
additional engineer and junior engineer for maintenance. Supervisors for mechanical and electrical
maintenance are under the junior engineer.
To ensure that trained and qualified man power can be made available at the right time, right place and
to right person and reviewing the minimum qualification on the basis of future requirements.
Functions:
The functions of personnel and administration departments are as follows To maintain on personnel functions
of the organization.
❖ Maintaining officer/employees personnel records.
❖ Discussing with the management and top taking guidance in personnel matters.
Working hours for the employees are 8: 15am to 4: 15pm. The employees are provided with uniforms
within two months of joining.
CHAPTER 3
TRANSFORMERS
3.1 INTRODUCTION
When a transformer steps up the voltage level of a circuit, it decreases thecurrent because the power
remains constant. Therefore, ac power can be generated at one central station. The voltage is stepped up
for transmissionover long distances at very low losses. The voltage is stepped down againfor final use.
Since the transmission losses are proportional to the square of the current, raising the voltage by a factor
of 10 will reduce the transmission losses by a factor of 100. Also, when the voltage is increasedby a factor
of 10, the cur- rent is decreased by a factor of 10. This allowsthe use of much thinner conductors to
transmit power.
In modern power stations, power is generated at 12 to 25 kV. Transformers step up the voltage to 110 to
1000 kV for transmission overlong distances at very low losses. Transformers then step it down to 12 to
34.5 kV for local distribution and then permit power to be used in homesand industry at 120 V.
Basically, a transformer consists of two inductive windings and a laminated steel core. The coils are
insulated from each other as well as from the steel core. A transformer may also consist of a container
for winding and core assembly (called as tank), suitable bushings to take theterminals, oil conservator
to provide oil in the transformer tank for cooling purposes etc .In all types of transformers, core is
constructed by assembling (stacking) laminated sheets of steel, with minimum air-gap between them (to
achieve continuous magnetic path). The steel used is having high silicon content and sometimes heat
treated. The sheets are cutin the shape as E, I and L.
3.6WORKING OF A TRANSFORMER
The transformer works on the principle of Faraday’s law of electromagneticinduction and mutual
induction.
There are usually two coils primary coil and secondary coil on the transformer core.The core
laminations are joined in the form of strips. The two coils have high mutual inductance. When an
alternating current pass through the primary coil it creates a varying magnetic flux. As per
faraday’s law of electromagnetic induction, this change in magneticflux induces an emf
(electromotive force) in the secondary coil which is linked to the core having a primary coil.
This is mutual induction.
Overall, a transformer carries the below operations:
The figure shows the formation of varying magnetic flux lines around a wire-wound. The interesting
part is thatreverse is also true, when a magnetic flux line fluctuates around a piece of wire, a current
will be induced in it.
This was what Michael faraday found in1831 which is the fundamental workingprinciple of electric
generators as well as transformers.
3.7.2.1Hysteresis Losses
Each time the magnetic field is reversed, a small amount of energy is lost due to hysteresis within the
core. For a given core material, the transformer losses are proportional to the frequency, and is a function
of the peak flux density to which it is subjected.
Dielectric Loss :-
In the solid insulation or transformer oil i.e. insulation material of the transformer, dielectric loss occurs
when the solid insulation gets damagedor the oil gets deteriorated or its quality decreases over the time.
Hence, the overall efficiency of transformer may be affected due to this loss.
• HYSTERISIS LOSS: In view of minimizing hysteresis losses soft magnetic materials for ex: Si
steel, steel alloys, Mn-Zn ferrite are used because they have high saturation magnetization, Low
coercivity, High magnetic permeability etc. which reduce losses due to hysteresis.
• EDDY CURRENT LOSSES: In view of reducing eddy current losses, the magnetic core of the
transformer is not made from a single magnetic material; because in this case the circulating eddy
currentflowing will be higher. Instead the magnetic core is a stack of thin siliconsteel lamination and
the laminations are insulated from one another by thin layer of varnish to reduce eddy current and
hence eddy current losses.
3. STRAY LOSSES: These types of losses can be reduced by use of smalldimensioned conductors for
windings, use of CTC conductors in case of higher current windings, optimum transposition of the
parallel strands, magnetic shielding of the inner tank walls, use of non-magnetic shield inarea of strong
magnetic fields.
• Instrument transformer: Used in relay and protection purpose indifferent instruments in industries
A current transformer is a device used to produce an alternating current in its secondary, which is
proportional to the AC current in its primary. This is primarilyused when a current or voltage is too
high to measure directly.
CHAPTER 4
MANUFACTURING OF DISTRIBUTIONTRANSFORMER AND
SPECIFICATION OF DISTRIBUTIONTRANSFORMERS
11kV/433– 250V and 33 kV / 433-250V
4.1INTRODUCTION
Manufacturing is the process of translation of raw materials into finishedproducts to perform a specified
function or purpose. Processing describesthe act of taking something through an established and usually
routine setof procedures and at certain times converts from one form to another in aseries of sequence
of operations or events.
The manufacturing capability is the key for reliable transformers. The process must be clearly defined,
and the operator’s skill must have the highest levels. Major stages of manufacturing a transformer are:
ii)The equipment shall conform in all respects to high standards of engineering, design and
workmanship and shall be capable of performing in continuous commercial operation, in a manner
acceptable to the purchaser, who will interpret the meanings of drawings and specification and shall
have the power to reject any work or material which, in his judgment is not in accordance therewith. The
offered equipment shall be complete with all components necessary for their effective andtrouble free
operation. Such components shall be deemed to be within the scope of bidder’s supply irrespective of
whetherthose are specifically brought out in this specification and / orthe commercial order or not.
iii) The transformer and accessories shall be designed to facilitateoperation, inspection, maintenance
and repairs. The design shall incorporate every precaution and provision for the safetyof equipment
as well as staff engaged in operation and maintenance of equipment.
iv) All outdoor apparatus, including bushing insulators with theirmountings, shall be designed so
as to avoid any accumulationof water.
STANDARD RATINGS:
The standard ratings shall be 16, 25, 63, 100,160, 200, 250, 315, 400, 500,
630, 1000, 1250, 1600, 2000 and 2500 kVA for 11 kV distribution
transformers and 100, 160, 200, 315, 400, 500, 630, 1000, 1250,
1600,2000, 2500 kVA for 33 kV distribution transformers
STANDARDS:
The major materials used in the transformer shall conform in all respectsto the relevant/specified Indian
Standards and international Standards with latest amendments thereof as on bid opening date, unless
otherwise specified herein. Some of the applicable Indian Standards are listed.
As per the Indian standards IS 6162 part1;IS 6162 part2 - 1972 Distribution
transformer with HV winding made of copper conductors is less susceptible to metal fatigue
than aluminium. Coper is harder, strongerand more ductile than aluminium, expands less and
does not flow at terminals. Copper displays low levels of creep. Under the conditions of
extreme loading and temperature conditions of distribution transformer windings, creep rates
of aluminium can be up to 25 times higher than copper. This results in aluminium wound
distribution transformers havinga higher propensity than copper.
4.3.2. EPOXY DIAMOND DOTTED INSULATIONPAPER:
As per the Indian standards (amended) IS 9335 part3 of section 1 - 1994
Diamond dotted paper (DDP) is also referred as epoxy adhesivediamond paper or varnished
paper.
The thickness and width of the papercan be
made according to the customer’s
specifications. Diamond dotted paper is made
of electrical grade kraft paper with Bstage
heat curable epoxy resin coating. DDP is
thermally upgrade kraft paper and used in
oilfilled transformer for layer insulation
between the coils.
material for electrical machines, capacitors and particularly oil filled transformers. The material
properties allow classification in insulation class A (105C) and aremanufactured in accordance with
the IEC standard.
the bottom of the conservator so as to create a sump for collection of impurities. The minimum oil
level(corresponding to -5degree Celsius) should be above the sump level.
4.3.9. BREATHER:
The breather tank is fitted with a breather containing
silica gel through which air is expelled when
transformer is loaded with losses causing the oil
temperature to increaseand expand. During light loading
conditionsoil cools down and contract in volume so air
is inhaled from the atmosphere. This air
contains moisture and the moisture is observed by the
silica gel crystals and the allowed to enter the conservator
tank.
4.3.11. BUSHINGS:
LV conductors(rectangular) :-
• 9.8 x 4.2 mm (without insulation)
• 10.13 x 4.53 mm( with insulation)
HV conductors(round/circular) :-
• 1.1 mm (without insulation)
• 1.32 mm ( with insulation)
WINDINGS:
HV and LV windings shall be wound from Super Enamel covered/Double Paper covered
Aluminium / Electrolytic Copper conductor.
➢ Proper bonding of inter layer insulation with theconductor shall be ensured. Test for bonding strength
shall be conducted.
➢ Dimensions of winding coils are very critical. Dimensional tolerances for winding coils shall be within
limits as specifiedin Guaranteed Technical Particulars (GTP Schedule I).
➢ The core/coil assembly shall be securely held in position to avoidany movement under short circuit
conditions.
➢ Joints in the winding shall be avoided. However, if jointing is necessary the joints shall be properly
brazed and the resistance of the joints shall be less than that of parent conductor. In case of foilwindings,
welding of leads to foil can be done within the winding.
• First we want to get the conductor material’s from store department then we want to start
the winding process.
• We want to design the machine aperture as per required winding size for specific KVA
mentioned by the design department
• In the first step, we need to wind the pressboard around the bobbin.
• After that the cotton tape is struck at the edge of the pressboard
for insulation at both ends
• Then the end strip is provided at both the ends for mechanical
support and to hold the LVwinding.
• It is wound in such a way that there should be about 41.25 turns per layer.
• Then it is covered with Epoxy Diamond Dotted Kraft Paper of size 0.1mm thickness around
the first layer of the conductor.
• Then the procedure is repeated four times to get a total of 165 turns.
• After that the cotton tape is pulled and bound tightly to avoid looseningof the setup.
• At the end the press board is bound with the cotton tape tightly.
• The oil duct and pressboard separate the LV and HV windings fromeach other and it will
acts as insulation.
• Then the cotton tape is removed, and gum is applied on the pressboard.
• After this, the cotton tape is stick to both the edges of the pressboard.
• Then the end strips of dimension as per mentioned in the design is wound at both edges of the press
board which wound on the coil to avoid the slipping of the conductor.
• The conductor is wound in such a way that there are 290.4 turns in onelayer.
• Epoxy Diamond Dotted Kraft Paper of thickness 0.1 mm around thefirst layer of the conductor
• The above procedure is repeated 25 times so that there is a total of7260 (290.4*25) turns of
the conductor.
• After that cotton tape is pulled and bound tightly to avoid loosening ofthe winding.
• Then the last layer of Epoxy Diamond Doted Kraft Paper of thesetup.
• Epoxy Diamond Dotted Kraft Paper is highly insulating material, itcan withstand up to 8Kv
without oil and it can go up to 28kV with oil.
The design of core will be like cruciform(different circular blocks), the specialty of cruciform core is it
reduces theleakage flux in the core.
KAVIKA uses CRGO (cold rolled grain oriented) laminations, which isof 0.23 mm thickness and flux
density of 1.7 Tesla.
The core shall be stack / wound type of high grade Cold Rolled Grain Oriented or Amorphous Core
annealed steel lamination having low loss and good grain properties, coated with hot oil proofinsulation,
bolted together and to the frames firmly to prevent vibration or noise. The core shall be stress relieved
by annealing under inert atmosphere if required. The complete design of core must ensure permanency
of the core loss with continuous working of the transformers. The value of the maximum flux density
allowed in the design and grade of lamination used shall be clearly stated in the offer. The transformers
core shall be suitable for over fluxing (due to combined effect of voltage and frequency) up to 12.5%
without injurious heating at full load conditions and shall notget saturated. The bidder shall furnish
necessary design data in support of this situation.
No-load current up to 200kVA shall not exceed 3% of full load current and will be measured by
energizing the transformer at ratedvoltage and frequency. Increase of 12.5% of rated voltage shall not
increase the no-load current by 6% of full load current.
or
No-load current above 200kVA and up to 2500kVA shall not exceed2% of full load current and will be
measured by energizing the transformer at rated voltage and frequency. Increase of 12.5% of rated
voltage shall not increase the no-load current by 5% of full loadcurrent.
4.7.1CORE-COIL ASSEMBLY
Gap between each section of H.V.Coils including top & bottom clearances is maintained with the help
of oil ducts, as per the design/drawings. The Top Yoke is refilled. Top core frame including core bolts
and tie rodsare fixed in position. Primary and secondary windings are connected as per the requirements.
Phase barrier between H.V.phases are placed as per requirement. Connections to the tapping switch or
oltc (if required) are made.
The LV side is star connected and HV side is delta connected. The neutral available on the primary
can be earthed to avoid distortion.
The Star-Delta connection has no problem of third harmonic component due to circulating current in
delta. It is also more stable to unbalancedloads since the delta partially redistributes any imbalances
that occur.
The LV and HV connections in the form of Dyn 11 , D indicatetype of connection of the HV winding. Y
indicates the type of connection of the LV winding, n indicates neutral and according to vector group
11 means 30 phase degree displacement between LV and HV.
The polarity of a winding refers to the direction of the induced emf e.g. inthe winding at a particular
instant, for a three-phase transformer; polarityalone is insufficient to represent the relation between LV
and HV winding. In addition to the terminal marking on HV and LV side voltage vector diagram are
required to show the angular displacement between HV and LV windings.
After connection, active part is kept inside the vacuum chamber to removemoisture contents,
keeping it there for about 8 to 10 hours with continuousheating by thermal oil at 120C to remove
water content.
Vacuum drying method.
This drying method is based on air as the heat
carrier, under atmospheric pressure, the
transformer body or winding is gradually pre
heated to about 105℃, and then vacuum treatment
is started. Due to slow heat transfer and uneven
internal and external heating(internal cooling and
external heating), transformers with high voltage and
large capacity often need more than 100h for
preheating due to thick insulation layer, long
production cycle and incomplete drying, so it is
difficult to meet the insulation requirements of
transformers. But the equipment is simple and
easy to operate.
4.10.LOWERING
After drying, the connections are checked again and tightened before lowering onto the tank.
4.11.BUSHINGS:
The bushings shall conform to the relevant standards specified and shall be of outdoor type. The bushing
rods and nuts shall be made ofbrass material 12 mm diameter for both HT and LT bushings. The bushings
shall be fixed to the transformers on side with straight pockets and in the same plane or the top cover for
transformers above 100 kVA. For transformers of 100 kVA and below the bushing can be mounted on
pipes. The tests as per latest IS 2099 and IS 7421 shallbe conducted on the transformer bushings.
➢ For 33 kV, 52 kV class bushings shall be used for transformers ofratings 500 kVA and above. And
for transformers below 500 KVA,33 kV class bushings, for 11 kV, 17.5 kV class bushings and
for 0.433 kV, 1.1 kV class bushings shall be used.
➢ Bushing can be of porcelain/epoxy material. Polymer insulator bushings conforming with relevant
IEC can also be used.
➢ Bushings of plain shades as per IS 3347 shall be mounted on the side of the Tank and not on top
cover.
➢ Dimensions of the bushings of the voltage class shall conform to the Standards specified and
dimension of clamping arrangement shall be as per IS 4257
➢ Minimum external phase to phase and phase to earth clearances ofbushing terminals shall be as
follows:
Voltage Clearance
33 kV 350mm 320mm
11 kV 255mm 140mm
LV 75mm 40mm
➢ Brazing of all inter connections, jumpers from winding to bushingshall have cross section larger
than the winding conductor. All the Brazes shall be qualified as per ASME, section – IX.
➢ The bushings shall be of reputed make supplied by those manufacturers who are having
manufacturing and testing facilities for insulators.
➢ The terminal arrangement shall not require a separate oil chambernot connected to oil in the main
tank.
4.12. FASTENERS
All fasteners of 12 mm diameter and less, exposed to atmosphere shall beof stainless steel and those
above 12 mm diameter shall preferably be of stainless steel or of mild steel hot dip galvanized. The
material of the stainless steel fasteners shall conform to IS: 1570 (Pt. V) Grade 04, Cr 17Ni 12 Mo 2.
4.13. PAINTING
All steel surfaces in contact with insulating oil shall be painted with heatresistant, oil insoluble insulating
varnish.
TESTING OF DISTRIBUTIONTRANSFORMER
It is important to test the transformer to make sure it can be used inpractical applications. The
tests performed are as follows:
1. ACCEPTANCE TEST
a. Tensile strength test
b. Breakdown voltage test of transformer oil
c. Resistance test for transformer oil
This test is performed only to confirm tensile strength of aluminium wires used for conductor,
pressboard and insulation papers. For conductor up to 3mm tensile strength is 100-110N/m2. This test
is significantly performed on conductor material to judge the strength of this material. A cable conductor
is often subjected to pull from one end during laying , insulating and manufacturing hence it should be
strong enough to tolerate the pulling force as well. Hence it becomes necessary to ensure that the
conductor material has sufficient tensile strength.
A specimen of conductor with length little bit longer than gauge length (gauge length is the length of
the specimen on which test is carried out) is first taken. To be careful that the minimum length of the
entire specimen shall be such that it should have extra length at two ends after its gauge length for
holding the same by grips of tensile testing machine. No preconditioning of the specimen is required for
tensile test.
To access the insulating property of dielectric transformer oil , a sample of the transformer oil is taken
and its breakdown voltage is measured . the lower the resulting breakdown voltage, the poorer the
quality of the transformer oil.
• A test voltage is applied to the electrodes and is continuously increased up to the breakdown voltage
with a constant, standard complaints lenz rate of e.g. 2kv/s.
e.g. 2 kV/s.
• At a certain voltage level breakdown occurs in an electric arc, leading to a collapse of the test voltage.
• An instant after ignition of the arc, the test voltage is switched off automatically by the testing device.
Ultra-fast switch off is highly desirable, as the carbonization due to the electric arc must be limited to
keep the additional pollution as low as possible.
• The transformer oil testing device measures and reports the root mean square value of the breakdown
voltage.
• After the transformer oil test is completed, the insulation oil is stirred automatically, and the test
sequence is performed repeatedly:typically, 5 repetitions, depending on the standard.
• As a result, the breakdown voltage is calculated as mean value of the individual measurements.
• It can be concluded that higher the resulting breakdown voltage,more the quality of the
transformer oil.
2. Then apply 3-phase 415 V supply on HV terminals. Measure the voltages applied on each phase
(Phase-phase) on HV and induced voltages at LV terminals simultaneously.
3. After measuring the voltages at HV and LV terminals, the tap changerof transformer should be raised
by one position and repeat test.
3. Then apply single phase 230 V AC supply across one of the HVwinding terminals and
neutral terminal.
4. Measure the voltage in two other HV terminals in respect of neutralterminal.
➢ Un-balanced current test: The value of unbalanced current indicated by the ammeter shall not be more
than 2% of the full loadcurrent.
➢ Noise-level measurement.
➢ Transformer tank shall be subjected to specified vacuum. The tankdesigned for vacuum shall be tested
at an internal pressure of 0.35 kg per sq cm absolute (250 mm of Hg) for one hour. The permanent
deflection of flat plates after the vacuum has been released shall notexceed the values specified below,
Horizontal length of flat plate (in mm) Permanent deflection (in mm)
➢ Transformer tank together with its radiator and other fittings shall be subjected to pressure
corresponding to twice the normal pressureor 0.35 kg / sq.cm whichever is lower, measured at the base
of the tank and maintained for an hour. The permanent deflection of the flat plates after the excess
pressure has been released, shall not exceed the figures for vacuum test.
➢ Pressure relief device test: The pressure relief device shall be subject to increasing fluid pressure. It
shall operate before reaching the test pressure as specified in the above class. The operating
pressure shall be recorded. The device shall seal-off after the excesspressure has been released.
➢ Short Circuit Test and Impulse Voltage Withstand Tests: The purchaser intends to procure
transformers designed and successfullytested for short circuit and impulse test. In case the transformers
proposed for supply against the order are not exactly as per the tested design, the supplier shall be
required to carry out the short circuit test and impulse voltage withstand test at their own cost in the
presence of the representative of the purchaser.
➢ The supply shall be accepted only after such test is done successfully, as it confirms on successful
withstand of short circuit and healthiness of the active parts thereafter on un-tanking after a short
circuit test.
➢ Apart from dynamic ability test, the transformers shall also be required to withstand thermal ability test
or thermal withstand abilitywill have to be established by way of calculations.
➢ It may also be noted that the purchaser reserves the right to conduct short circuit test and impulse voltage
withstand test in accordance with the IS, afresh on each ordered rating at purchaser cost, even if the
transformers of the same rating and similar design are already tested. This test shall be carried out on
a transformer to be selected by the purchaser either at the manufacturer’s works when they are offered
in a lot for supply or randomly from the supplies already made to purchaser’s stores. The findings and
conclusions of these tests shall be binding on the supplier.
➢ Special test certificates for the tests carried out on prototype of same specifications shall be submitted
along with the bid. Thepurchaser may select the transformer for type tests randomly
1. Visual examination
6. Measurement of impedance voltage on principal tap, short circuit,impedance and load loss
Voltage ratio of primary and secondary winding shall be measured on all tap positions.
losses
Load losses shall be measured with rated maximum current, achieved at lowest primary voltage of 19kV
at ambient temperature and computed at750 C. The percentage impedance voltage at principal tap shall
be measured with rated maximum current, achieved at lowest primary voltage of 19kV at ambient
temperature and computed at 750 C.
In HV test, LV is shorted, and supply is given to the HV. As per Indian standard for 11kVA transformer
28kV is applied to the HV of the transformer. In LV test, HV is shorted, and supply is given to the LV.
Asper Indian standard for 11kVA transformer 3kV is applied to the LV of the transformer. This test is
passed only if the transformer withstands thevoltage for one minute without any tripping of the circuit
breaker. The transformer withstands 28kV (for HV test) and 3kV (for LV supply) supply up to one
minute without any damage it indicates that the withstanding capacity and dielectric strength of the
transformer is more.
High voltage phase windings shall be marked both in the terminal boards inside the tank and on the
outside with capital letter 1U, 1V, 1W and low voltage winding for the same phase marked by
corresponding small letter 2u, 2v, 2w. The neutral point terminal shall be indicated by the letter 2n.
Neutral terminal is to be brought out and connected to local grounding terminal by an earthing strip.
Transformer shall be provided with a rating plate (both in Hindi and English) of weather proof material,
fitted in a visible position, showing theitems indicated below: -
1. Type of transformer.
2. Governing specification.
3. Manufacturer’s name.
4. Manufacturer’s serial number
5. Year of manufacture.
6. Rated output.
7. Rated frequency.
8. Highest voltage for equipment.
9. Rated Voltage.
a)Primary
b) Secondary
10. Rated current.
a)Primary
b)Secondary
11. Maximum temperature rise over an ambient of 500 c.
a) of oil
b) of winding.
12. Total weight
13. Class of insulation.
14. Insulation levels.
15. Connection diagram indicating the taps.
The letters/ figures on the plate shall be indelibly marked by etching,engraving or stamping.
4.23. DISPATCH
Before dispatch the oil level is checked, and the horn gap fuse, breather and name plate are fixed.
• Being in charge of store of responsible to provide all necessary component to different section in
shop floor, store stroke checking done and maintaining the log book for material used for
manufacture.
4.26. Summary:
In this section we have focused on various task performed in the organization like technical and non-
technical skills. In the next chapter we highlighted the technical and non-technical experiences.
CHAPTER 5
REFLECTION NOTES
During this internship we have the opportunity to interact with severalemployees which strengthen our
communication skills and also a taskwhich they are performed further enabled in strengthening our
knowledge in technical aspects. The following are the some of the experience gained.
• Overseeing the planning, operation and interdepartmental functionthat contributes to the smooth
functioning of the organization
• Strategic planning of production that helps in achieves the monthlyand yearly targets with less
discrepancy.
• Chance to work on existing production process with revising anddeveloping the process and
operations.
• Interacting with various staffs such as managers, supervisors,workers and the employees for gaining
their experience and
increasing the practical skills of real time working in anorganization.
• Identifying any drawbacks in the present process and improvingupon it for further optimization of the
production process and betterment of quality.
The discipline followed to achieve customer satisfaction about the quality structure of the
management, management function systemsand the procedures of management adept quality control.
• Learnt safety procedure to be followed while performing each and every task and completing it
without causing and damage to self orothers.
• Learnt about safety procedures to be followed in case ofemergency like first aid.
• Learnt how to manage a store and track the usage of the materialsand how to economically use the
materials available.
• Learnt the working of commercial department, as to how do theyprocure the materials and how to they
choose the best vendor.
• Learnt the functioning of Admin and HR department and gatheredinformation about how do they train
the new employee.
• Handling the work alone did learn to be punctual and completingthe tasks on right time.
• After completion of internship overall confidence was boosted andcould successfully handle the work
and complete it on time.
5.4.Key learning:
After detail study of all the process, departments and overall organization structures, the following
points can be stressed upon for keylearning.
• Sampling process done for inspection of the quality of the procuredmaterials whether they fall within
the prescribed limits of quality dimension or not. This is approved and checked by varies departments
like procurement, quality control and production to ensure the quality.
• The production plan is done monthly, based in the number of ordersand the workers allotted to each
operation so production process is optimized.
• Each transformer assembly route card with a number to specify the operation it has go through the
worker's name who have worked onit observed. It helps in finding out which operation has gone wrong
if the final unit is failed.
• All the workers skilled in performing all the types of operations areseen. Work rotation is being done
efficiently.
• Material transport system used such as roller guide ways, langersand forklift to transfer in-process and
final assemblies quickly andsmoothly.
• Final quality check that is done for different parameters so that thetransformer passes in all aspects.
• Some machine tools that used are obsolete which require tedioussetup process and susceptible to many
problems.
• Use of mechanical countess severely limits the accuracy of thewinding process which results in much
rework.
• There is no accurate guide ways for the wire to be wound perfectlywithout any gaps in the winding.
• Majority of activities are manual which involves co-ordination ofworkers for working on one part of
the assembly which again required much time.
• Coil ratio test accurately tests whether the turns are within thespecified limit or not.
However, much rework is done during the stage.
• There is no specified scale for the length of wire terminals that areattached to the coil. That is left to
worker to make necessary adjustment in this process which again might be responsible for certain
amount of transformer failure.
The company is into the mandatory of only distribution transformer, Product diversification makes it
to face the contingenciesof business market. They are:
• Facilitating the customer to buy and interacting through E- marketing can enhance the scale and also
helps to attract potentialcustomers.
• Frequent participation in interstate and international trade fairs helps in promoting the product and
bringing the branch identity.
• Management should take initiative in building quality circle amongthe employees which would help in
bringing closeness among themand also increased the productivity level of the company In this section
we explained about various technical and non-technical experienced gain in the company is discussed
in detail.
5.6. Summary:
CONCLUSION:
A study was done for every activity of the production process and itshould be mapped. The
unprocessed assemblies of coil were sent to rework because of inaccuracy of winding process. The
core assembly process was studied in detail and steps were suggested to make it moreaccurate and
efficient.
Finally, a study of failure mode and effect of analysis of transformerswas done and also the main
causes for the failure of a transformer was studied. The occurrence of these causes and the severity &
rectification for these causes were found. Some of these causes were found in the production of the
transformer for which alternative method were suggested in order to eliminate the occurrence of
causes of failure.
As one of the oldest serving company today, KAVIKA Limited has emerged as manufacture of
quality transformer which is ISO 9001-2008 certified. The integration of the entire department towards
manufacturingof distribution transformer was well made and efficiently use of staffs, workers and
assists in the key to its success: Integration with all the staffand workers gave an idea of how each and
all operations are involved.
Apart from manager, workers were also well versed with all the processes which were mainly due to
the work rotation Real time experience on production scheduling, labor management and work force
allocation was gained. Even though the company does not use the latest technology, it makes up for it
in skill of the other workers. Preference to quality one of the most important things that help the
company gains reputation. Real time problem arising in the shop floor were observed and step taken
immediately to curb the seen. It also gave an opportunity to study the weakness of some process along
with their strength. Detailedstudy of problem helped in gaining in practical knowledge on how the
improvement process can actually be applied such as QC tools, quality control and improvement
processes.
• Vaccum chamber is used in the process of drying the active parts, which helps to maintain very high
insulation resistance (minimum of 1000M ohm at 900 C) is maintained.
• Good quality lamination of cruciform core from the heart of the transformer.
• Electrolytic conductor grade conductors of proper tensile strength are used. Because of the sufficient
cross section are used on the highvoltage side.
• Multipaper covered copper conductor leads of sufficient cross section are used in low voltage side.
• “S” type jumper of sufficient cross section is used in low voltage connection.
• Solid packing piece made of 100% wood pulp are for supporting thelow voltage and high voltage coils,
which offers sufficient electeicalbreakdown strength between the windings and the earth parts. Also,solid
packing supports the windings better under short circuit conditions.
• Proper arrangements for lifting is provided for job as well as tank for proper handling.
• In addition to the above all the raw materials are conforming to Indian standards.
• In all the stage process quality checks are made and in the final testing stage all the routine tests are
conducted as per BIS on each and every transformer before dispatch.
• Type tests are conducted in CPRI Bengaluru. From time to time (short circuit, high voltage and
temperature rise test)
Conclusion
Thus, the Distribution transformers play a vital role in converting the comparatively high voltage into
distribution voltage, say 11kv to 433v.Thus, demand for distribution transformers is more compared to
any other transformers. Therefore, manufacturing is a very crucial and happens in bulk. The life of the
transformer is the life of insulation. The life of transformer may be introduced as the change of its
condition ofcellulose insulation. Considering all these factors best quality and considerable amount of
insulation must be provided. If more insulationis provided, it then leads to less heat being dissipated
which is an alarming condition as transformer heats tremendously. Thus, to overcome all these adverse
effects transformers are tested after being manufactured. Transformers do not die but are killed due to
poor maintenance, operational accidents and over loading. Overloading is the main cause for all above
factors. Thus, a transformer to some extentcan be prevented from overloading by using a next higher
capacity transformer in place of actual desired capacity if not constraint.
Referances :
2. https://en.m.wikipedia.org/wiki/Transformer - 18:15:10
- 12/8/2022
5. https://electrical-engineering-portal.com/routine-tests-dry- type-
transformer - 08:14:55 - 15/8/2022
6. https://vietnamtransformer.com/our-news/types-of-
transformer-testing - 13:59:08 - 15/8/2022
7. https://esennar.com/core-coil-assembly-for-transformer-in- india.php -
14:50:32 - 15/8/2022
8. https://electricalmag.com/transformer-construction-types- cores/ -
16:23:58 – 15/8/2022
9. https://www.electrical4u.com/transformer-insulating-oil-and- types-of-
transformer-oil/ - 18:22:39 – 15/8/2022