Professional Documents
Culture Documents
Power Cables Sizing & Voltage Drops Calculation
Power Cables Sizing & Voltage Drops Calculation
Power Cables Sizing & Voltage Drops Calculation
3316.A3 D E CA.21117
EARLY POWER GENERATION
JOB NUMBER SHEETS
STATION OIL GAS 1 OF 45
SR 2007 007556 / ATA
OUED ZAR - TUNISIA
CONTRACTOR : PIRECO SUPPLIER: CONTRACTOR DOCUMENT NUMBER: CONTRACTOR JOB N.
S.p.A AR 301-03-07-CN-002 AR 301/07
SUPPLIER DOCUMENTT NUMBER: SUPPLIER JOB N.
TUNISIA B.V. Petroleum & Industrial
Realization Contractor
PI RECO
TECHNICAL REPORT
3316.A3 D E CA.21117
Rev. 1
Mars 2008
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than those for which it has
been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
TABLE OF CONTENTS
1 GENERAL ................................................................................................................................ 3
1.1 SCOPE .......................................................................................................................................... 3
1.2 DEFINITIONS ................................................................................................................................ 3
1.3 CODES AND STANDARDS ............................................................................................................. 3
1.4 REFERENCE DOCUMENT .............................................................................................................. 4
2 DESIGN CRITERIA ................................................................................................................... 5
2.1 VOLTAGE DROP ........................................................................................................................... 5
2.2 VOLTAGE DROP UNDER MOTOR STARTING CONDITIONS ........................................................... 6
2.3 CONTINUOUS CURRENT‐CARRYING CAPACITY ............................................................................ 7
2.3.1 General criteria for the calculation of the de‐rating factor ......................................................................... 7
2.3.2 New Early Power Generation de‐rating factor............................................................................................. 8
2.4 THERMAL SIZING ......................................................................................................................... 8
2.4.1 Protection against overload.......................................................................................................................... 8
2.4.2 Protections against thermal solicitations of short circuit ............................................................................ 9
3 APPENDICES ..........................................................................................................................10
APPENDIX 1 .................................................................................................................................11
APPENDIX 2 .................................................................................................................................17
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
1 GENERAL
1.1 SCOPE
The purpose of this specification is to provide the basic criteria for the sizing of the
power cables to be used at OUED ZAR Oil Centre for the New Early Power
Generation plant.
1.2 DEFINITIONS
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
The following project documents have been referenced to input data for calculations.
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
2 DESIGN CRITERIA
The cables are sized to meet the following electrical and thermal conditions:
• Voltage drops;
• Continuous current-carrying capacity;
• Protection against overload and thermal solicitations of short circuit;
The continuous ratings of XLPE insulated cables are based upon a maximum
operating temperature of 90 °C and accepting 250 °C as a final conductor temperature
at the end of a short circuit.
Beside, the design considers the worst condition of installation, when power cables
run directly underground in groups.
Hereinafter, all de-rating factors shall be listed to define the current-carrying capacity
of the cables according with the following ambient conditions:
In order to ensure correct operation of the electrical system, the feeders to users
voltage drop has been verified.
The admitted voltage drops under full load conditions are the following values:
• Feeders to area substation (From generators to 11KV switchgears and from
Power Transformer to 3.3KV Switchgear) : 1%;
• Feeders to area substation : 3 %;
• Feeders to switchboard : 3 %;
• Motor at rated full load : 5 %;
• Motor at starting : 15 %;
• Lighting circuits : 3 %;
• DC circuits : 2%.
The voltage drop under normal conditions is verified with the following engineering
formula that is derived from the Ohm law for alternating current system:
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
Where:
The voltage drop for three-phase motors under starting conditions is verified with the
following engineering formula:
Where:
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
In order to ensure that maximum permissible temperatures of cables are not exceeded
during steady conditions cable sizing is carried out using rated cable capacities as
reference. Standard conditions, defined in codes generally are:
Where cables are installed in conditions other than standard conditions the rated
capacities Ic have been modified by applying a General Rating Factor (fc). The
general maximum de-rating factor permitted for each cable laid in group, is the
correction factor which shall be used to determine the continuous current-carrying
capacity of the cable (Iz):
Iz= Ic fc
1. f1 “Temperature factor”
Is a rating factor to allow for a different ambient temperature from that
one which ampacities are given.
- f1 = 0.82 for a temperature of 50°C for cables inside closed
concrete trench;
- f1 = 0.93 for a temperature of 30°C for direct buried cables.
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
De-rating factors are indicated in the cable conformity sheet attached in the
appendices.
Thermal sizing have been verified in order to ensure that cable operating temperature
does not exceed the maximum temperatures permitted.
According to referred standards, the capacity (Iz) of a line is the maximum value of the
current that, under permanent and specified conditions, the line can transmit without
the temperature of the conductors exceeding a specified limit value, in relation to the
type of insulation used.
Regardless of their cross-section, the live conductors shall be protected by one or
more devices which automatically cut off the circuit when a dangerous overload or
short circuits generated.
Conditions taken into consideration are as follows:
a) Protection against overload
b) Protection against thermal solicitations of short circuit.
After determining the value of absorbed current load (rated current lb) the cable will be
selected on the ground of the cable sizing de-rating factors explained at the point
2.3.1.
Protective devices, either fuses or circuit breakers shall be provided to break any
overload current flowing in the conductors before such a current should cause a
temperature rise detrimental to insulation, joints, terminations or surroundings of the
conductors.
According to IEC 60364-4-43 the two following conditions shall be satisfied:
a) lb ≤ ln ≤ lz
b) lf ≤ 1.45 lz
Where:
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
Protective devices, either fuses or circuit breakers shall be provided to break any
short- circuit current flowing in the conductors before such a current could cause a
danger due to thermal and mechanical effects produced in the conductors and
connections.
The cables shall have a minimum section, so that it will be able to withstand, without
being damaged all thermal stress derived from short-circuit current for all duration
time, to be identified as intervention time of the protection device.
According to IEC 60364-4-43 the cable sizing shall satisfy the following condition, valid
for short circuit of duration up to 5 s:
K2 S2 ≥ I2 t
Where:
K2 S2 ≥ I2 t
If not, the cross-sectional area of the cable shall be increased to satisfy the above
condition.
When the protection device is not limiting type, the minimum admissible cross-
sectional area of the cable expressed in mm2 is sized as follows:
I t
S2 ≥ I2 t / K2 hence: S ≥
K
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
3 APPENDICES
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
DOCUMENT NR.
3316.A3 D E CA.21117
JOB NUMBER SHEET
APPENDIX 1
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
EARLY POWER GENERATION - OUED
ZAR
0910-EH-001 / 091-EH-002
Carnet de câbles
Repère Tenant Aboutissant Long Fichier câbles Isolant Nb conducteurs Cu / nbCâb SPH
(m) Alu // (mm²)
Repère Tenant Aboutissant Long Fichier câbles Isolant Nb conducteurs Cu / nbCâb SPH
(m) Alu // (mm²)
APPENDIX 2
This document is CONFIDENTIAL and the sole property of the Company. It shall neither be shown to third parties nor used for other purposes than
those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.
CLIENT
Société PIRECO
Responsable HECHMI JBARA
Adresse IMMEUBLE AL BADR - LES BERGES DU LAC
BP331
TABLEAU 0920EP001 NORMAL Code Postal 1080
Ville TUNIS
Tél +216 71 860 066
Fax +216 71 861 801
ETUDE
Société ISEA
Responsable GILLES SALEM / CLAUDE MOREL
ENI TUNISIA B.V Adresse ZAC DES ESCAMPADES
EARLY POWER GENERATION - OUED ZAR
TUNISIA Code Postal 84170
Ville MONTEUX
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 185 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 185 mm² If >= I fonct. Max. 4590 A >= 3062,4 A
DONNEES
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 70 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 2056 A >= 2055,9 A
DONNEES
Section PE(N) 1 x 50 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2419 A >= 2055,9 A
Type T4H 250 K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 100200104 A²s >= 5991334,5 A²s
Prot. CI Prot Base K²S² >= I²t limité 100200104 A²s >= 2396533,8 A²s
Tempo Diff. 0 ms
Ir th 181 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1869 A
Tempo 100 ms Ik min >= I fonct. Max. >= 2055,9 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2055,9 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 51122500 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 51122500 A²s >= 422672,8 A²s
Condition dimensionnement IN! K²S² >= Ik² max x tempo Diff 51122500 A²s >= A²s
Longueur max protégée 110 m (CI) K²S² >= I²t limité 51122500 A²s >= 169069,1 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 70 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 2056 A >= 2055,9 A
DONNEES
Section PE(N) 1 x 50 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2419 A >= 2055,9 A
Type T4H 250 K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 100200104 A²s >= 5991334,5 A²s
Prot. CI Prot Base K²S² >= I²t limité 100200104 A²s >= 2396533,8 A²s
Tempo Diff. 0 ms
Ir th 181 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1869 A
Tempo 100 ms Ik min >= I fonct. Max. >= 2055,9 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2055,9 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 51122500 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 51122500 A²s >= 422672,8 A²s
Condition dimensionnement IN! K²S² >= Ik² max x tempo Diff 51122500 A²s >= A²s
Longueur max protégée 110 m (CI) K²S² >= I²t limité 51122500 A²s >= 169069,1 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 70 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 2056 A >= 2055,9 A
DONNEES
Section PE(N) 1 x 50 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2419 A >= 2055,9 A
Type T4H 250 K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 100200104 A²s >= 5991334,5 A²s
Prot. CI Prot Base K²S² >= I²t limité 100200104 A²s >= 2396533,8 A²s
Tempo Diff. 0 ms
Ir th 181 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1869 A
Tempo 100 ms Ik min >= I fonct. Max. >= 2055,9 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2055,9 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 51122500 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 51122500 A²s >= 422672,8 A²s
Condition dimensionnement IN! K²S² >= Ik² max x tempo Diff 51122500 A²s >= A²s
Longueur max protégée 110 m (CI) K²S² >= I²t limité 51122500 A²s >= 169069,1 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3284 A >= 2810,4 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2810 A >= 2810,4 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 4711449600 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 12298354 A²s
Tempo Diff. 0 ms
Ir th 500 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2342 A
Tempo Ik min >= I fonct. Max. >= 2810,4 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2810,4 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 1784217600 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 1784217600 A²s >= A²s
Condition dimensionnement FORC K²S² >= Ik² max x tempo Diff 1784217600 A²s >= A²s
Longueur max protégée 150 m (CC) K²S² >= I²t limité 1784217600 A²s >= 323618,7 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3284 A >= 2810,4 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2810 A >= 2810,4 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 4711449600 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 12298354 A²s
Tempo Diff. 0 ms
Ir th 500 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2342 A
Tempo Ik min >= I fonct. Max. >= 2810,4 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2810,4 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 1784217600 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 1784217600 A²s >= A²s
Condition dimensionnement FORC K²S² >= Ik² max x tempo Diff 1784217600 A²s >= A²s
Longueur max protégée 150 m (CC) K²S² >= I²t limité 1784217600 A²s >= 323618,7 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 70 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 70 mm² If >= I fonct. Max. 1604 A >= 1603,8 A
DONNEES
Section PE(N) 1 x 50 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 2165 A >= 1603,8 A
Type T4H 250 K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 100200104 A²s >= 3367146 A²s
Prot. CI Prot Base K²S² >= I²t limité 100200104 A²s >= 1346858,4 A²s
Tempo Diff. 0 ms
Ir th 181 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1458 A
Tempo 100 ms Ik min >= I fonct. Max. 1833 A >= 1603,8 A
K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 100200104 A²s >= 841737,2 A²s
Mode de pose 63 K²S² >= I²t limité 100200104 A²s >= 336694,9 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 1833 A >= 1603,8 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 77440000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 77440000 A²s >= 257217,8 A²s
Condition dimensionnement DU-IN K²S² >= Ik² max x tempo Diff 77440000 A²s >= A²s
Longueur max protégée 150 m (CI) K²S² >= I²t limité 77440000 A²s >= 102887,1 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3929 A >= 2958 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2958 A >= 2958 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 4711449600 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 28437314 A²s
Tempo Diff. 0 ms
Ir th 787 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2465 A
Tempo Ik min >= I fonct. Max. >= 2958 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,87 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2958 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 696960000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 696960000 A²s >= A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 696960000 A²s >= A²s
Longueur max protégée 70 m (CC) K²S² >= I²t limité 696960000 A²s >= 463064,4 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3498 A >= 2883,6 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2884 A >= 2883,6 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 4711449600 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 17953710 A²s
Tempo Diff. 0 ms
Ir th 787 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2403 A
Tempo Ik min >= I fonct. Max. >= 2883,6 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,87 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2883,6 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 696960000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 696960000 A²s >= A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 696960000 A²s >= A²s
Longueur max protégée 110 m (CC) K²S² >= I²t limité 696960000 A²s >= 367080,4 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 95 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 95 mm² If >= I fonct. Max. 1681 A >= 1680,8 A
DONNEES
Section PE(N) 1 x 25 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 2595 A >= 1680,8 A
Type T4H 250 K²S² >= Ik² min x tf fusible 184552224 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 184552224 A²s >= 11242061 A²s
Prot. CI Prot Base K²S² >= I²t limité 184552224 A²s >= 4496824 A²s
Tempo Diff. 0 ms
Ir th 200 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1528 A
Tempo 100 ms Ik min >= I fonct. Max. 2806 A >= 1680,8 A
K²S² >= Ik² min x tf fusible 184552224 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 184552224 A²s >= 2810350 A²s
Mode de pose 63 K²S² >= I²t limité 184552224 A²s >= 1124140 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 2806 A >= 1680,8 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 19360000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 19360000 A²s >= 282509,2 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 19360000 A²s >= A²s
Longueur max protégée 100 m (CI) K²S² >= I²t limité 19360000 A²s >= 113003,7 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 185 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 185 mm² If >= I fonct. Max. 2270 A >= 2270,4 A
DONNEES
Section PE(N) 1 x 70 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 2525 A >= 2270,4 A
Type T5H 400 K²S² >= Ik² min x tf fusible 699867008 A²s >= A²s
Calibre 400 A K²S² >= Ik² max x tempo 699867008 A²s >= 12213018 A²s
Prot. CI Prot Base K²S² >= I²t limité 699867008 A²s >= 4885207 A²s
Tempo Diff. 0 ms
Ir th 253 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2064 A
Tempo 100 ms Ik min >= I fonct. Max. 2798 A >= 2270,4 A
K²S² >= Ik² min x tf fusible 699867008 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 699867008 A²s >= 3053075 A²s
Mode de pose 63 K²S² >= I²t limité 699867008 A²s >= 1221230 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 2798 A >= 2270,4 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 151782400 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 151782400 A²s >= 515472 A²s
Condition dimensionnement FORC K²S² >= Ik² max x tempo Diff 151782400 A²s >= A²s
Longueur max protégée 150 m (CI) K²S² >= I²t limité 151782400 A²s >= 206188,8 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 185 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 185 mm² If >= I fonct. Max. 4625 A >= 3072 A
DONNEES
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 70 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 2056 A >= 2055,9 A
DONNEES
Section PE(N) 1 x 50 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2419 A >= 2055,9 A
Type T4H 250 K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 100200104 A²s >= 5991334,5 A²s
Prot. CI Prot Base K²S² >= I²t limité 100200104 A²s >= 2396533,8 A²s
Tempo Diff. 0 ms
Ir th 181 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1869 A
Tempo 100 ms Ik min >= I fonct. Max. >= 2055,9 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2055,9 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 51122500 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 51122500 A²s >= 422672,8 A²s
Condition dimensionnement IN! K²S² >= Ik² max x tempo Diff 51122500 A²s >= A²s
Longueur max protégée 110 m (CI) K²S² >= I²t limité 51122500 A²s >= 169069,1 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 70 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 2056 A >= 2055,9 A
DONNEES
Section PE(N) 1 x 50 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2419 A >= 2055,9 A
Type T4H 250 K²S² >= Ik² min x tf fusible 100200104 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 100200104 A²s >= 5991334,5 A²s
Prot. CI Prot Base K²S² >= I²t limité 100200104 A²s >= 2396533,8 A²s
Tempo Diff. 0 ms
Ir th 181 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1869 A
Tempo 100 ms Ik min >= I fonct. Max. >= 2055,9 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2055,9 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 51122500 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 51122500 A²s >= 422672,8 A²s
Condition dimensionnement IN! K²S² >= Ik² max x tempo Diff 51122500 A²s >= A²s
Longueur max protégée 110 m (CI) K²S² >= I²t limité 51122500 A²s >= 169069,1 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3284 A >= 2810,4 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2810 A >= 2810,4 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 4711449600 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 12298354 A²s
Tempo Diff. 0 ms
Ir th 500 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2342 A
Tempo Ik min >= I fonct. Max. >= 2810,4 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2810,4 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 1784217600 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 1784217600 A²s >= A²s
Condition dimensionnement FORC K²S² >= Ik² max x tempo Diff 1784217600 A²s >= A²s
Longueur max protégée 150 m (CC) K²S² >= I²t limité 1784217600 A²s >= 323618,7 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3706 A >= 2920,8 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2921 A >= 2920,8 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 4711449600 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 22322908 A²s
Tempo Diff. 0 ms
Ir th 787 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2434 A
Tempo Ik min >= I fonct. Max. >= 2920,8 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,87 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2920,8 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 696960000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 696960000 A²s >= A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 696960000 A²s >= A²s
Longueur max protégée 90 m (CC) K²S² >= I²t limité 696960000 A²s >= 411944,4 A²s
* Non Conforme
CIRCUIT
Sélectivité magnétique 19524 A
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 150 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 3930 A >= 2889,6 A
DONNEES
Section PE(N) 1 x 150 mm² T admis. >= Tempo Magn. ou CR 400 ms >=
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2890 A >= 2889,6 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 1840409984 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 1840409984 A²s >= A²s
Prot. CI Prot Base K²S² >= I²t limité 1840409984 A²s >= 15561147 A²s
Tempo Diff. 0 ms
Ir th 520 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 2408 A
Tempo Ik min >= I fonct. Max. >= 2889,6 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 2889,6 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 2787840000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 2787840000 A²s >= A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 2787840000 A²s >= A²s
Longueur max protégée 100 m (CC) K²S² >= I²t limité 2787840000 A²s >= 463347,3 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 95 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre x If >= I fonct. Max. 1681 A >= 1680,8 A
DONNEES
Section PE(N) 1 x 25 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 3P3D Ik min >= I fonct. Max. 2595 A >= 1680,8 A
Type T4H 250 K²S² >= Ik² min x tf fusible 184552224 A²s >= A²s
Calibre 250 A K²S² >= Ik² max x tempo 184552224 A²s >= 11242061 A²s
Prot. CI Prot Base K²S² >= I²t limité 184552224 A²s >= 4496824 A²s
Tempo Diff. 0 ms
Ir th 200 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 1528 A
Tempo 100 ms Ik min >= I fonct. Max. >= 1680,8 A
K²S² >= Ik² min x tf fusible A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo A²s >= A²s
Mode de pose 63 K²S² >= I²t limité A²s >= A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,76 IK PE(N) CABLE
Coefficient température 0,93
Coef. compl. / Coef. symétrie fs (0.8) Ik min >= I fonct. Max. >= 1680,8 A
1,00 / 1,00
K²S² >= Ik² min x tf fusible 19360000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 19360000 A²s >= 282509,2 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 19360000 A²s >= A²s
Longueur max protégée 100 m (CI) K²S² >= I²t limité 19360000 A²s >= 113003,7 A²s
* Non Conforme
Société PIRECO
Responsable HECHMI JBARA
Adresse IMMEUBLE AL BADR - LES BERGES DU LAC
BP331
TABLEAU 0920EP002 Code Postal 1080
Ville TUNIS
Tél +216 71 860 066
Fax +216 71 861 801
ETUDE
Société ISEA
Responsable GILLES SALEM / CLAUDE MOREL
ENI TUNISIA B.V Adresse ZAC DES ESCAMPADES
EARLY POWER GENERATION - OUED ZAR
TUNISIA Code Postal 84170
Ville MONTEUX
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 2 x 240 mm² If >= I fonct. Max. 8019 A >= 6930 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 14348 A >= 6930 A
Type T5H 630 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 630 A K²S² >= Ik² max x tempo 4711449600 A²s >= 36907464 A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 14762984 A²s
Tempo Diff. 0 ms
Ir th 542 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 6300 A
Tempo 100 ms Ik min >= I fonct. Max. 10542 A >= 6930 A
K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 4711449600 A²s >= 15664791 A²s
Mode de pose 63 K²S² >= I²t limité 4711449600 A²s >= 6265916,5 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 10542 A >= 6930 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 1784217600 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 1784217600 A²s >= 6430437,5 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 1784217600 A²s >= A²s
Longueur max protégée 133 m (CI) K²S² >= I²t limité 1784217600 A²s >= 2572175 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 240 mm² If >= I fonct. Max. 7784 A >= 4400 A
DONNEES
Section PE(N) 1 x 70 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 15002 A >= 4400 A
Type T5H 400 K²S² >= Ik² min x tf fusible 1177862400 A²s >= A²s
Calibre 400 A K²S² >= Ik² max x tempo 1177862400 A²s >= 40089596 A²s
Prot. CI Prot Base K²S² >= I²t limité 1177862400 A²s >= 16035839 A²s
Tempo Diff. 0 ms
Ir th 280 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 4000 A
Tempo 100 ms Ik min >= I fonct. Max. 11178 A >= 4400 A
K²S² >= Ik² min x tf fusible 1177862400 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 1177862400 A²s >= 17492906 A²s
Mode de pose 63 K²S² >= I²t limité 1177862400 A²s >= 6997162,5 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 11178 A >= 4400 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 151782400 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 151782400 A²s >= 6058444,5 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 151782400 A²s >= A²s
Longueur max protégée 99 m (CI) K²S² >= I²t limité 151782400 A²s >= 2423377,8 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 3 x 400 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 3 x 400 mm² If >= I fonct. Max. 15224 A >= 15224 A
DONNEES
Section PE(N) 1 x 400 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 35 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 21915 A >= 15224 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 29446559744 A²s >= 27956094 A²s
Prot. CI Prot Base K²S² >= I²t limité 29446559744 A²s >= 23962366 A²s
Tempo Diff. 0 ms
Ir th 875 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 13840 A
Tempo 35 ms Ik min >= I fonct. Max. 19407 A >= 15224 A
K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 29446559744 A²s >= 16756108 A²s
Mode de pose 63 K²S² >= I²t limité 29446559744 A²s >= 14362378 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 19407 A >= 15224 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 4956160000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 4956160000 A²s >= 8111957 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 4956160000 A²s >= A²s
Longueur max protégée 50 m (CI) K²S² >= I²t limité 4956160000 A²s >= 6953106 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 3 x 400 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 3 x 400 mm² If >= I fonct. Max. 15224 A >= 15224 A
DONNEES
Section PE(N) 1 x 400 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 35 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 21915 A >= 15224 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 29446559744 A²s >= 27956094 A²s
Prot. CI Prot Base K²S² >= I²t limité 29446559744 A²s >= 23962366 A²s
Tempo Diff. 0 ms
Ir th 875 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 13840 A
Tempo 35 ms Ik min >= I fonct. Max. 19407 A >= 15224 A
K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 29446559744 A²s >= 16756108 A²s
Mode de pose 63 K²S² >= I²t limité 29446559744 A²s >= 14362378 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 19407 A >= 15224 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 4956160000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 4956160000 A²s >= 8111957 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 4956160000 A²s >= A²s
Longueur max protégée 50 m (CI) K²S² >= I²t limité 4956160000 A²s >= 6953106 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 2 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 2 x 240 mm² If >= I fonct. Max. 8019 A >= 6930 A
DONNEES
Section PE(N) 1 x 240 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P3D Ik min >= I fonct. Max. 14348 A >= 6930 A
Type T5H 630 K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
Calibre 630 A K²S² >= Ik² max x tempo 4711449600 A²s >= 36907464 A²s
Prot. CI Prot Base K²S² >= I²t limité 4711449600 A²s >= 14762984 A²s
Tempo Diff. 0 ms
Ir th 542 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 6300 A
Tempo 100 ms Ik min >= I fonct. Max. 10542 A >= 6930 A
K²S² >= Ik² min x tf fusible 4711449600 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 4711449600 A²s >= 15664791 A²s
Mode de pose 63 K²S² >= I²t limité 4711449600 A²s >= 6265916,5 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 10542 A >= 6930 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 1784217600 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 1784217600 A²s >= 6430437,5 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 1784217600 A²s >= A²s
Longueur max protégée 133 m (CI) K²S² >= I²t limité 1784217600 A²s >= 2572175 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 1 x 240 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 1 x 240 mm² If >= I fonct. Max. 7784 A >= 4400 A
DONNEES
Section PE(N) 1 x 70 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 100 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P3D Ik min >= I fonct. Max. 15002 A >= 4400 A
Type T5H 400 K²S² >= Ik² min x tf fusible 1177862400 A²s >= A²s
Calibre 400 A K²S² >= Ik² max x tempo 1177862400 A²s >= 40089596 A²s
Prot. CI Prot Base K²S² >= I²t limité 1177862400 A²s >= 16035839 A²s
Tempo Diff. 0 ms
Ir th 280 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 4000 A
Tempo 100 ms Ik min >= I fonct. Max. 11178 A >= 4400 A
K²S² >= Ik² min x tf fusible 1177862400 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 1177862400 A²s >= 17492906 A²s
Mode de pose 63 K²S² >= I²t limité 1177862400 A²s >= 6997162,5 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 11178 A >= 4400 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 151782400 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 151782400 A²s >= 6058444,5 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 151782400 A²s >= A²s
Longueur max protégée 99 m (CI) K²S² >= I²t limité 151782400 A²s >= 2423377,8 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 3 x 400 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 3 x 400 mm² If >= I fonct. Max. 15224 A >= 15224 A
DONNEES
Section PE(N) 1 x 400 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 35 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 21915 A >= 15224 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 29446559744 A²s >= 27956094 A²s
Prot. CI Prot Base K²S² >= I²t limité 29446559744 A²s >= 23962366 A²s
Tempo Diff. 0 ms
Ir th 875 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 13840 A
Tempo 35 ms Ik min >= I fonct. Max. 19407 A >= 15224 A
K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 29446559744 A²s >= 16756108 A²s
Mode de pose 63 K²S² >= I²t limité 29446559744 A²s >= 14362378 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 19407 A >= 15224 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 4956160000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 4956160000 A²s >= 8111957 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 4956160000 A²s >= A²s
Longueur max protégée 50 m (CI) K²S² >= I²t limité 4956160000 A²s >= 6953106 A²s
* Non Conforme
CIRCUIT
X Sélectivité magnétique
FICHE DE CONFORMITE
Sélectivité différentielle Non Calculée
Contenu 3P+N+PE SURCHARGES CABLES
CIRCUIT
RESULTATS
Section Phase 3 x 400 mm² T admis. >= Tempo Diff 400 ms >= 0 ms
Section Neutre 3 x 400 mm² If >= I fonct. Max. 15224 A >= 15224 A
DONNEES
Section PE(N) 1 x 400 mm² T admis. >= Tempo Magn. ou CR 400 ms >= 35 ms
T admis. >= T fonct fus. 400 ms >= 0 ms
DISPOSITIF DE PROTECTION Disj. Boitier moulé
Constructeur ab05fr1.dug Ik PHASES CABLE
Déclencheur 4P4D Ik min >= I fonct. Max. 21915 A >= 15224 A
Type E2N 1250 K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
Calibre 1250 A K²S² >= Ik² max x tempo 29446559744 A²s >= 27956094 A²s
Prot. CI Prot Base K²S² >= I²t limité 29446559744 A²s >= 23962366 A²s
Tempo Diff. 0 ms
Ir th 875 A Ik NEUTRE CABLE
Ir mg ou calibre fus. 13840 A
Tempo 35 ms Ik min >= I fonct. Max. 19407 A >= 15224 A
K²S² >= Ik² min x tf fusible 29446559744 A²s >= A²s
SURCHARGES CABLES
K²S² >= Ik² max x tempo 29446559744 A²s >= 16756108 A²s
Mode de pose 63 K²S² >= I²t limité 29446559744 A²s >= 14362378 A²s
Tolérance calculs surcharge 1
Coefficient groupement 0,64 IK PE(N) CABLE
Coefficient température 0,93
Ik min >= I fonct. Max. 19407 A >= 15224 A
Coef. compl. / Coef. symétrie fs (0.8) 1,00 / 1,00
K²S² >= Ik² min x tf fusible 4956160000 A²s >= A²s
ETAT CIRCUIT Circuit conforme K²S² >= Ik² max x tempo 4956160000 A²s >= 8111957 A²s
Condition dimensionnement IN!! K²S² >= Ik² max x tempo Diff 4956160000 A²s >= A²s
Longueur max protégée 50 m (CI) K²S² >= I²t limité 4956160000 A²s >= 6953106 A²s
* Non Conforme