4WRPE Re29122 - 2017-05
4WRPE Re29122 - 2017-05
▶▶ Size 10
▶▶ Component series 3X
▶▶ Maximum operating pressure 350 bar
▶▶ Rated flow 50, 80 l/min
H8046+8047
Features Contents
Ordering code
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
4 WRP E 10 S J – 3X / / 24 / *
01 4 main ports 4
04 Size 10 10
Flow characteristic
07 Progressive S
08 Overlap jump (opening point 5 command value with symbols E, E1-, EA, W6- and W8-) J
Seal material
10 NBR seals M
FKM seals V
Observe compatibility of seals with hydraulic fluid used!
12 Supply voltage 24 V 24
Symbols
A B A B A B A B
a 0 b a 0 b a 0 a 0
P T P T P T P T
E
EA
E1-
W6-
W8-
Notice:
Representation according to DIN ISO 1219-1.
Hydraulic interim positions are shown by dashes.
6 5
7 3.1 1 2 3.2
4
T B P A T1
Bosch Rexroth AG, RE 29122, edition: 2017-05
Directional control valve | 4WRPE 5/24
Function Notice:
The integrated electronics (OBE) compares the specified Use of the damping plate is not recommended for
command value to the position actual value. In case of applications with mainly low-frequency excitation
control deviations, the control solenoid will be activated. <300 Hz.
Due to the changed magnetic force, the control spool (2)
is adjusted against the control spring. Stroke/control spool Electronics protection membrane "-967"
cross-section is controlled proportionally to the command To prevent condensate formation in the housing of the
value. With a positive command value presetting, the valve integrated electronics (OBE), an electronics protection
opens from P to B or A to T. Negative command values membrane (8) can be used.
lead to no change in the control spool position. Recommended for use outside industry-standard
conditions with high ambient air humidity and significant
cyclic temperature changes (e. g. outdoors).
6 5
3 1 2
9
4
T B P A T1
Technical data
(For applications outside these parameters, please consult us!)
general
Design Spool valve, direct operated
Actuation Proportional solenoid with position control, OBE
Type of connection Subplate mounting, porting pattern according to
ISO 4401-05-04-0-05
Installation position Any
Ambient temperature range °C –20 … +60
Storage temperature range with UV protection °C +10 … +40
Transport temperature °C –30 … +80
Maximum storage time Years 1 (if the storage conditions are observed; refer to the operating
instructions 07600-B)
Sine test according to ▶▶ Without damping plate 10 ... 2000 Hz / maximum of 10 g / 10 cycles / 3 axes
DIN EN 60068-2-6 ▶▶ With damping plate 1) 10 ... 2000 Hz / maximum of 10 g / 10 cycles / 3 axes
Noise test according to ▶▶ Without damping plate 20 … 2000 Hz / 10 gRMS / 30 g peak / 30 min. / 3 axes
DIN EN 60068-2-64 ▶▶ With damping plate 1) 20 ... 2000 Hz / 10 gRMS / 30 g peak / 24 h / 3 axes
Transport shock according ▶▶ Without damping plate 15 g / 11 ms / 3 shocks / 3 axes
to DIN EN 60068-2-27 ▶▶ With damping plate 1) 15 g / 11 ms / 3 shocks / 3 axes
Shock according to ▶▶ With damping plate 1) 35 g / 6 ms / 1000 shocks / 3 axes
DIN EN 60068-2-27
Weight ▶▶ 4/3 directional design kg 7.6
▶▶ 4/2 directional design kg 6.0
Maximum relative humidity (no condensation) % 95
Maximum solenoid surface temperature °C 150 (individual operation)
MTTFd value according to EN ISO 13849 Years 150 (for further details, see data sheet 08012)
hydraulic
Maximum operating ▶▶ Port A, B, P bar 350
pressure ▶▶ Port T bar 200
Rated flow (∆p = 5 bar/control edge 2)) l/min 50 80
Flow unloading A–T B–T A–T B–T
central position ▶▶ Symbol W6- l/min 0.7 0.7 0.7 0.7
(∆p = 5 bar/control edge)
▶▶ Symbol W8- l/min – – 0.7 0.7
Hydraulic fluid See table page 7
Viscosity range ▶▶ recommended mm2/s 20 … 100
▶▶ maximum admissible mm2/s 10 … 800
Hydraulic fluid temperature range (flown-through) °C –20 … +70
Maximum admissible degree of contamination of the hydraulic fluid Class 18/16/13 3)
1) Not recommended for applications with mainly low-frequency 3) The cleanliness classes specified for the components must be
excitation < 300 Hz adhered to in hydraulic systems. Effective filtration prevents
2) Flow for deviating ∆p (control edge): faults and simultaneously increases the life cycle of the
components.
∆px
qx = qVnom • For the selection of the filters, see www.boschrexroth.com/filter.
5
Notice:
The specified technical data were measured with HLP46 and
ϑOil = 40 ±5 °C.
Technical data
(For applications outside these parameters, please consult us!)
static / dynamic
Hysteresis % < 0.25
Range of inversion % < 0.05
Response sensitivity % < 0.05
Manufacturing tolerance qVmax % < 10
Temperature drift (temperature range 20 °C ... 80 °C) Zero shift < 0.2
Pressure drift %/100 bar Zero shift < 0.2
Zero compensation Set in the plant to ±1%
Technical data
(For applications outside these parameters, please consult us!)
step for overlapped valves
Output
Command stage B
value Position Current
controller controller B
Reference
potential Protection Command value Current
current command B
limitation at value
Cable break detection
4 ... 20 mA inverting
4 ... 20 mA input
input Run/Stop Current
position IA Pilot current A Output measurement
controller stage A A
Undervoltage Current
detection controller A
On/Off Sensitivity
output adjustment actual Demodulator Oscillator for
Over-current identification Enable
Protection stages value position signal position position
output stages
24 VDC circuit transducer transducer transducer
Supply
Voltage supply output
voltage
stages Input circuitry
0V n. c.
signal position
transducer
Block diagram/controller function block (4/3 directional design)
Inverse-
polarity
protection
Power supply unit
Actual value
Reference
potential Protection Output position
circuit actual value
Functional
ground
Housing Notes:
▶▶ Electrical signals provided via control electronics (e.g. actual ▶▶ The factory setting of the potentiometer must not be
value) must not be used for switching off safety-relevant machine changed.
functions.
step for overlapped valves
Command
value Position
controller
Reference
potential Protection Command value
circuit, standardization
current
Output Current
controller stage measurement
Current
controller
On/Off Sensitivity
Undervoltage Output adjustment actual Demodulator Oscillator for
Protection Enable value position signal position position
detection stages
24 VDC circuit transducer transducer transducer
Supply
voltage
Input circuitry
0V n. c.
signal position
transducer
Block diagram/controller function block (4/2 directional design)
Inverse-
polarity
protection
Power supply unit
Actual value
Reference
potential Protection Output
circuit position
Functional
actual value
ground
Housing Notes:
▶▶ Electrical signals provided via control electronics (e.g. actual ▶▶ The factory setting of the potentiometer must not be
value) must not be used for switching off safety-relevant machine changed.
functions.
Directional control valve | 4WRPE 11/24
Notice:
Mating connectors, separate order, see page 23 and data
sheet 08006.
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
∆pA→B [%pp]
∆pB→A [%pp]
Symbol E
50
45
3 1
40
Flow in l/min →
35
4 2
30
25 1) Step compensation
20
1 P–A
15
2 B–T
10
5 3 P–B
0 4 A–T
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Symbol E1-
55
50
1
45
4
40
Flow in l/min →
35
30
25 1) Step compensation
20 3
2 1 P–A
15
2 B–T
10
3 P–B
5
0 4 A–T
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Symbol EA
50
45
3
40
4
Flow in l/min →
35
30
25
20
15 1) Step compensation
10
3 P–B
5
0 4 A–T
1)
0 20 40 60 80 100
← Stroke in % →
0 0.5 1 2 4 6 8 10
← UD-E in V →
4 4.8 6 8 10 12 14 16 18 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Symbol W6-
50
45
40 1
3
Flow in l/min →
35
30 4 2
25 1) Step compensation
20
1 P–A
15
2 B–T
10
3 P–B
5
0 4 A–T
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Symbol V
65
60
3 1
50
4 2
Flow in l/min →
40
30
20 1 P–A
2 B–T
10 3 P–B
4 A–T
0
-10 -8 -6 -4 -2 0 2 4 6 8 10
← UD-E in V →
4 4.8 5.6 6.4 7.2 8 8.8 9.6 10.4 11.2 12 12.8 13.6 14.4 15.2 16 16.8 17.6 18.4 19.2 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Symbol E
80
70 3 1
60
Flow in l/min →
4 2
50
40
1) Step compensation
30
1 P–A
20
2 B–T
10 3 P–B
0 4 A–T
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Symbol E1-
80
70
1
60
Flow in l/min →
4
50
40
1) Step compensation
30 2
1 P–A
20 3
2 B–T
10 3 P–B
4 A–T
0
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Symbol EA
80
70 3
60 4
Flow in l/min →
50
40
30
20 1) Step compensation
10 3 P–B
4 A–T
0
1)
0 20 40 60 80 100
← Stroke in % →
0 0.5 1 2 4 6 8 10
← UD-E in V →
4 4.8 6 8 10 12 14 16 18 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Symbol W6-
80
70
1
60
3
Flow in l/min →
4
50
2
40
30
1) Step compensation
1 P–A
20
2 B–T
10 3 P–B
0 4 A–T
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Symbol W8-
80
70
4 1
60
Flow in l/min →
50
40
3 1) Step compensation
30
2 1 P–A
20 2 B–T
10 3 P–B
4 A–T
0
1)
4 5.6 7.2 8.8 10.4 11.6 12 12.4 13.6 15.2 16.8 18.4 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Symbol V
100
90
3 1
80
4
70
Flow in l/min →
2
60
50
40
30 1 P–A
20 2 B–T
3 P–B
10
0 4 A–T
-10 -8 -6 -4 -2 0 2 4 6 8 10
← UD-E in V →
4 4.8 5.6 6.4 7.2 8 8.8 9.6 10.4 11.2 12 12.8 13.6 14.4 15.2 16 16.8 17.6 18.4 19.2 20
← ID-E in mA →
Symbol V1-
100
90
1
80
4
70
Flow in l/min →
60
50
3 2
40
30 1 P–A
20 2 B–T
3 P–B
10
4 A–T
0
-10 -8 -6 -4 -2 0 2 4 6 8 10
← UD-E in V →
4 4.8 5.6 6.4 7.2 8 8.8 9.6 10.4 11.2 12 12.8 13.6 14.4 15.2 16 16.8 17.6 18.4 19.2 20
← ID-E in mA →
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Transition function with stepped electric input signals (4/3 directional design)
Symbol V
Signal change in %
Stroke in % →
Time in ms →
Symbol V
Amplitude ratio in dB →
Frequency in Hz →
Signal ±1 %
Signal ±5%
Signal ±25%
Signal ±100%
Characteristic curves
(measured with HLP46, ϑOil = 40 ±5 °C)
Flow/load function with maximum valve opening (tolerance ±10 %) (4/3 directional design)
Symbol V
400
3
200
180
Flow in l/min →
2
100
80
60 1
40
Symbol EA
400
7 5.1
4.1
200
180 5.2
Flow in l/min →
4.2 6
100 4.1 50 l/min, with double flow (summated edge)
80 4.2 50 l/min (summated edge)
60 5.1 80 l/min, with double flow (summated edge)
40 5.2 80 l/min (summated edge)
6 Recommended flow limitation with
individual flow (180 l/min)
20
7 Recommended flow limitation with
double flow (360 l/min)
10
6 8 10 20 40 60 80 100 200 400
Pressure differential in bar →
Transition function with stepped electric input signals (4/2 directional design)
Symbol EA
Signal change in %
Stroke in % →
Time in ms →
Bosch Rexroth AG, RE 29122, edition: 2017-05
Directional control valve | 4WRPE 21/24
10
7 8 2
9
139 (161.5)
42
5
74
40
30
61 24 112
88 102 130 12
1 4
70
60
60
21
104
25 6 11
13
0,01/100
F1 F2
Rzmax 4 P
A B
Required surface quality
72
F4 F3
1 Name plate
2 Valve housing
3 Integrated electronics
Notes:
4 Identical seal rings for ports A, B, P, T, T1
▶▶ The dimensions are nominal dimensions which are subject to
5 Control solenoid with position transducer tolerances.
6 Machined valve contact surface, ▶▶ Mating connectors, separate order, see page 23 and data
porting pattern according to ISO 4401-05-04-0-05 sheet 08006.
7 Stroke solenoid
8 ISA adapter, separate order, see page 23
9 Damping plate "D" Valve mounting screws and subplates, see page 23.
10 Dimension in () for version with damping plate "D"
11 Electronics protection membrane "-967"
10
2
9
139 (161.5)
5
74
40
30
24 112
11.1 102 130 12
1 4
70
60
104
25 6 11
13
F1 F2
0,01/100 P
Rzmax 4 A B
72
T T1
Required surface quality
of the valve contact surface
F4 F3
1 Name plate
Notes:
2 Valve housing
▶▶ The dimensions are nominal dimensions which are subject to
3 Integrated electronics tolerances.
4 Identical seal rings for ports A, B, P, T, T1 ▶▶ Mating connectors, separate order, see page 23 and data
5 Control solenoid with position transducer sheet 08006.
Dimensions
Notice:
The tightening torque of the hexagon socket head cap screws
refers to the maximum operating pressure.
Further information
Bosch Rexroth AG © This document, as well as the data, specifications and other information set
Industrial Hydraulics forth in it, are the exclusive property of Bosch Rexroth AG. It may not be
Zum Eisengießer 1 reproduced or given to third parties without its consent.
97816 Lohr am Main, Germany The data specified above only serve to describe the product. No statements
Phone +49 (0) 93 52 / 40 30 20 concerning a certain condition or suitability for a certain application can be
my.support@boschrexroth.de derived from our information. The information given does not release the user
www.boschrexroth.de from the obligation of own judgment and verification. It must be remembered
that our products are subject to a natural process of wear and aging.