REQ No. : Ref. No.

: 21-PN011001
User / Customer : Page No. : 1 of 6
Title :
Manufacture :

Document Title :

Technical Specification for Armoured Cable


300/500V Instrumentation Armoured Cable
Flame Retardant Low Smoke Cat. C Anti Rodent and Anti Termite
Single Pair/Triad : RE-Y(ST)YRY FR
(CU/PVC/OS/PVC/SWA/PVC-FRLS AT AR) 300/500V Cat.C

Multi Pair/Triad : RE-Y(ST)YRY-PiMF FR


(CU/PVC/IS/OS/PVC/SWA/PVC-FRLS AT AR) 300/500V Cat.C

0.6/1kV Control Armoured Cable


Flame Retardant Low Smoke Cat. C Anti Rodent and Anti Termite
Multi cores : NY(ST)YRY FR
(CU/PVC/OS/PVC/SWA/PVC-FRLS AT AR) 0.6/1kV Cat.C

Rev. No. Date Descriptions Prepared By Reviewed By Approved By


Spec No : 21-PN011001
Issued : 24, Dec. 2021
Page : 2 of 6

1. SCOPE

1.1. This specification covers Instrumentation and Control Armoured Cable with Rated
Voltage 300/500V and 0.6/1kV.
The standard or specification referred shall be the latest issue as of the date of award of
the purchase order.

1.2. The types of instrument and control armoured cable included in this specification :

Cable description Cable type

300/500V Instrumentation Cable PVC RE-Y(ST)YRY FR


(CU/PVC/OS/PVC/SWA/PVC-FRLS AT AR) 300/500V Cat.C
Insulation, individual and Overall Screen
with PVC Flame Retardant Low Smoke RE-Y(ST)YRY-PiMF FR
Cat. C Anti Rodent and Anti Termite (CU/PVC/IS/OS/PVC/SWA/PVC-FRLS AT AR) 300/500V Cat.C

0.6/1kV Control Cable PVC Insulation and


Overall Screen with PVC Flame Retardant NY(ST)YRY-FR
Low Smoke Cat. C Anti Rodent and Anti (CU/PVC/OS/PVC/SWA/PVC-FRLS AT AR) 0.6/1kV Cat.C
Termite

2. REFERENCE STANDARDS

Instrument and control cable as follow:


IEC 60228 : Conductors of insulated cables
IEC 60502-1 : Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1:
Cables for rated voltages from 1 kV (Um = 1,2 kV) up to 3 kV (Um = 3,6
kV)
BS EN 50288-7 : Multi-element Metallic Cables used in analogue and digital
communication
and control
IEC 60811 : Common test methods for insulating and sheathing materials of electric
cables
IEC 60332-3-24 : Test on electric and optical fibre cables under fire conditions (Cat.C)

3. CONSTRUCTION AND MATERIAL

3.1. Conductor
Instrumentation and control cable the conductor shall be plain stranded annealed
copper conductor complying with IEC 60228. General application for pair/triad/core size
1 mm2.
Spec No : 21-PN011001
Issued : 24, Dec. 2021
Page : 3 of 6

3.2. Insulation
4. The insulation of instrumentation and control cable shall be extruded layer of Polyvinyl
Chloride (PVC) A compound complying with IEC 60502-1 (Rated Voltage 0.6/1kV) or
BS EN 50288-7 (Rated Voltage 300/500V).
5. The minimum thickness at any point shall not fall below 90% of the nominal value by
more than 0.1 mm.
5.1. Laying-up and fillers
Pair type cable : Two cores insulated shall be twisted together to form a pair with
suitable lay.
Triad type cable : Three cores insulated shall be twisted together to form a triad
with suitable lay.
Cable make-up of pairs, triads shall be assembled with suitable direction of lay. Where
necessary Non-Hygroscopic filler may be used to give the completed cable substantially
circular cross-section.

5.2. Shield or Screen


a. Individual shield (for multi pair and multi triad cable only).
For Individual shield type of cable. The pair or triad conductors shall be individually
shielded with Aluminium mylar tape (Alu. PET). Alu. PET shall be applied with the
metallic sidedown in electrical contact with a minimum 7/0.25 mm tinned copper drain
wire.

b. Overall shield.
An Alu. PET with 100% coverage shall be applied over the assembly of cores in
electrical contact with a minimum 7/0.25 mm tinned copper drain wire.

5.3. Inner sheath


The inner sheath shall be an extruded layer of black PVC complying with IEC 60502-1
or BS EN 50288-7.
The minimum thickness at any point shall not fall below the value given in the attached
1
till 5. by more than 20% + 0.2mm.

5.4. Armoured
The armoured type of cable covered use galvanized round steel wire armour (SWA).

5.5. Outer sheath


The outer sheath shall be an extruded layer of black PVC/ST1 Flame Retardant Low
Smoke compound with Anti Termite and Anti Rodent complying with IEC 60502-1 or BS
EN 50288-7.
The minimum thickness at any point shall not fall below the value given in the attached
1 till 5. by more than 20% + 0.2mm.

6. CORE IDENTIFICATION
a. For core system of cable shall be identified by color : White with Black numbering
printed.
b. For pairs system of cable shall be identified by color : Black and White with
numbering for Multi Pairs
Spec No : 21-PN011001
Issued : 24, Dec. 2021
Page : 4 of 6

c. For triads system of cable shall be identified by color : Red, Black and White with
numbering for Multi Triads

7. TEST

The test shall be carried out in accordance with IEC 60502-1 rated voltage 0.6/1kV and BS
EN 50288-7 for rated voltage 300/500V. Sample Flame retardant test in accordance with
IEC 60332-3-24. For detail test shall be info in Inspection Test Plan (ITP) document.

8. MARKING

8.1. Cable Marking


The following legend shall be printed on the surface of over sheath throughout the
length of cable (e.g) :
 Ref. standard no. : e.g. BS EN 50288-7
 Brand name
 Cable type : e.g. Cu/PVC/OS/PVC/SWA/PVC-FRLS AT AR
 Flame retardant grade : e.g. Cat. C
 Common Indonesian cable type : e.g. (RE-Y(ST)YRY FR)
 Nos. of core & Conductor size : e.g. 1P X 1.0 mm2
 Rated voltage : e.g. 300/500V
 Year of manufacture
 Length marking per meter

ex) BS EN 50288-7 “Brand Name” CU/PVC/OS/PVC/SWA/PVC-FRLS AT AR Cat.C


(RE-Y(ST)YRY FR) 1P X 1.0 mm2 300/500V 2021 0001M

8.2. Drum Marking


The Following information shall be marked.
 Rated voltage and cable type
 Nos. of core and conductor size
 Cable length
 Net weight
 Gross weight
 Direction of rotation
 End position of cable
 Manufacturer’s name
 Year of manufacture

9. PACKING

The completed cables shall be supplied a non-returnable wooden drum to prevent from
damage during the transportations.
The end of cable shall be sealed to prevent the ingress of moisture.
The diameter of wooden drum shall be complied manufacturer’s standard.
Spec No : 21-PN011001
Issued : 24, Dec. 2021
Page : 5 of 6

Attached 1 : Technical Data and Drawing Instrumentation Cable


RE-Y(ST)YRY FR (CU/PVC/OS/PVC/SWAPVC-FRLS Anti-Termite Anti-Rodent) 300/500V Cat.C
RE-Y(ST)YRY-PiMF FR (CU/PVC/IS/OS/PVC/SWA/PVC-FRLS Anti-Termite Anti-Rodent) 300/500V
Cat.C

Thick.
Conductor Thick. Max. DC
of Overall Approx. Mutual Capacitance
of Conductor Test
No. Over Diameter Cable Capacitance Unbalance
Const Approx. Insulation Resistanc Voltage
of Sze Sheath (Approx.) Weight (Max) (Max)
-ruction Dia. (Nom) e at 20°C
Cores (Nom)
mm2 No./mm mm mm mm mm /km kV kg/km nf/km pf/500m

1P 1.0 7/0.43 1.29 0.6 1.3 17.4 18.1 3.5 560 150 500

5P 1.0 7/0.43 1.29 0.6 1.5 24.1 18.5 3.5 988 150 500

VOLTAGE 300/500V NO. OF CORE 1-5 Pair CONDUCTOR SIZE 1.0 sqmm

1
2
3
4

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor


2 Insulation Extruded PVC compound
3* Individual Shield/Screen Alu. PET and Tin Annealead Copper Drain wire 7/0.25 mm
4* Overall Shield/Screen Alu. PET and Tin Annealead Copper Drain wire 7/0.25 mm
5 Inner Sheath Extruded Black PVC compound
6 Armoured Galvanized Round Steel Wire with Non-Hygroscopic Tape
7 Over Sheath Extruded Black PVC FRLS Cat.C AT AR compound

REMARK : * Suitable binder tape may be applied under or over the screen.
Spec No : 21-PN011001
Issued : 24, Dec. 2021
Page : 6 of 6

Attached 2 : Technical Data and Drawing Control Cable

NY(ST)YRY-FR (CU/PVC/OS/PVC/SWA/PVC-FRLS Anti-Termite Anti-Rodent) 0.6/1kV Cat.C

Thick. Thick. Max. DC


Conductor Overall Approx.
of of Conductor Test
No. Diameter Cable
Const Approx. Insulation Over Sheath Resistance Voltage
of Sze (Approx.) Weight
-ruction Dia. (Nom) (Nom) at 20°C
Cores
mm2 No./mm mm mm mm mm /km kV kg/km

10C 1.0 7/0.43 1.29 0.8 1.8 20.1 18.1 3.5 854

20C 1.0 7/0.43 1.29 0.8 1.8 24.6 18.1 3.5 1332

10-20
VOLTAGE 0.6/1kV NO. OF CORE CONDUCTOR SIZE 1.0 till 2.5 sqmm
Core

1
2

ITEM DESCRIPTION DETAILS

Conductor Annealed copper stranded conductor


1
2 Insulation Extruded PVC compound
3* Overall Shield/Screen Alu. PET and Tin Annealead Copper Drain wire 7/0.25 mm
4 Inner Sheath Extruded Black PVC compound
5 Armoured Galvanized Round Steel Wire with Non-Hygroscopic Tape
6 Over Sheath Extruded Black PVC FRLS Cat.C AT AR compound

REMARK : * Suitable binder tape may be applied under or over the screen.