Professional Documents
Culture Documents
CLAGTEE 2022 - Toledo - Tabares - Resendiz - Eng
CLAGTEE 2022 - Toledo - Tabares - Resendiz - Eng
CLAGTEE 2022 - Toledo - Tabares - Resendiz - Eng
Abstract--The case of unjustified simultaneous operation of to operate with the minimum possible human intervention [2,
protections associated with circuits that share a power bus in an 3], [4]. In the case of the presence of a fault in an element of the
underground medium voltage distribution system is analyzed. The distribution systems, the magnitude of the fault current far
operation of these devices alters the continuity of service of both exceeds the currents under normal operating conditions.
the faulty circuit and adjacent circuits without failure. A
Therefore, a poor protection scheme will lead to the spread of a
characteristic underground distribution system is modeled at 23
kV, with transformers of grounded wye-grounded wye fault through the system and its consequences can cause
distribution and five-legged cores, characteristics of the circuits significant disturbances in areas distant from the point where
that have presented this undesirable condition. A single-phase the failure occurred, increasing the number of affected users.
failure event is recreated that allows the analysis of the interaction
of fault currents in adjacent circuits. From the analysis of the
In the case of unbalanced faults (the most common) in
negative and zero sequence currents, improvements are proposed underground distribution networks, the analysis of negative and
in the adjustments to the protection schemes, and they are zero sequence current profiles are essential when determining
compared with records of anomalies that have occurred in the the causes of simultaneous operation (loss of selectivity)
period from 2019 to 2021. between protection devices against a line-to-ground failure
(single-phase), in underground distribution networks. As a
Keywords: Five Legged, Core Transformer, Grounded Wye, particular case, the 23kV metropolitan network of Mexico City
Overcurrent Protection, Simultaneous Tripping, Underground operates with special characteristics, for example, there are
Distribution. transformers with a five-legged core and a Grounded Wye –
Grounded Wye (YNyn) connection, in addition to using the
I. INTRODUCTION running neutral from the main substation [5, 6].
Distribution Systems (SD) represent an important link
between the generation and use of electrical energy. Its main II. APPROACH OF THE PROBLEM
function is to transport the electrical energy of the power There are different topological configurations of SD that are
substations or in particular cases from the generation sources to used according to the needs of the users, with arrangements of
the points of use under the basic criteria of the quality of the greater or lesser complexity, being a generalized objective to
supply: frequency control, voltage regulation and continuity of maintain the continuity of the electrical service.
service [1].
Within underground distribution systems (RDS), there are
To ensure that the SD provides adequate continuity, it is configurations with 4-, 5- and 6-way disconnectors that connect
necessary that system’s operators know the possible the same number of feeders (Figure 1). This type of
inconveniences or eventualities that may occur, such as short configuration is common in medium voltage facilities in the
circuit failures, the most common among them, the failure of a historic center of Mexico City (CDMX).
phase to earth.
In aerial lines, most failures tend to behave transiently. These
SE 1 SE 2
failures are mainly caused by atmospheric discharges,
maneuvers of switches, contact of the lines with objects outside
the installation such as vegetation and animals, among others.
By the nature of overhead line failures and the insulating
medium (air), these contribute to the failure dissipating
naturally and restoring system operation as normal [2]. NC NA
Fig. 1. Simplified single line diagram of a circuit of 5 underground roads
In underground lines the condition of the fault it’s different, of the CDMX.
since a failure involves damage to the insulating material or loss
of insulation, resulting in a permanent failure. These facts The relevant event for this case study is the activation of the
require repair, or replacement of the damaged component overcurrent protection relay with neutral time delay (51N)
before the electrical power supply is restored [3]. associated with a circuit without the presence of failure.
Coincident in time, a sustained single-phase fault is observed in
For this reason, distribution systems are provided with a circuit adjacent to the healthy circuit; these circuits share the
protection schemes that isolate the fault, quickly, selectively same feed bar.
and reliably, to affect the least number of equipment and users.
The speed of response by these devices is an essential feature The waveforms of the phase currents of the healthy circuit
of protection systems, so protection schemes are implemented show a peculiar anomaly, the tendency to phase each other, that
THE XIV LATIN-AMERICAN CONGRESS ON ELECTRICITY GENERATION AND TRANSMISSION - CLAGTEE 2022 2
Rio de Janeiro, Brazil, November 27th – 30th, 2022
The distribution circuits are made up of two types of feeders: Resistivity of the conductor material
1.853E-8 2.024E-7 2.54E-8
three conductors size 1000 kCM of copper (one conductor per (𝜌) [Ω ∗ 𝑚]
phase) of XLPE insulation and in clover arrangement, in Relative permeability of the
1 1 1
conductor material (𝜇)
addition to a neutral conductor, size 250 kCM of copper, all
Relative permeability of the
circuits have lengths less than 3 km (tables II and III). insulator material outside the 1 1 1
conductor (𝜇𝑟 )
Relative permittivity of the insulator
3.8436 5 2.35
material outside the conductor (𝜀𝑟 )
TR-D4
Bus 5-23 kV 500 kVA
22.86kV Y / 0.22kV Y
S2
Cu -XLP-25kV Z1=5% , Z0=4.25%
/ / 1000 kCM - 1CF X/R=5
PADC 4'' FT
60 MVA 1400m
230 kV YG / 23kV
YRG / 13.2kV D TR-D2
Z=17.5% Bus 6-23 kV 500 kVA
X/R=32 22.86kV Y / 0.22kV Y
S3
Cu -XLP-25kV
Z1=5% , Z0=4.25%
1000 kCM - 1CF X/R=5
PADC 4''
150m 500m
Subestación en 230 kV
TR-D3
Zthevenin Bus 7-23 kV 500 kVA
22.86kV Y / 0.22kV Y
S4
Cu -XLP-25kV
Z1=5% , Z0=4.25%
Equivalente de Thevenin 1000 kCM - 1CF X/R=5
Z(0) = 2.551 + j 6.311 ohm PADC 4''
Z(1) = 1.049 + j 7.106 ohm 500m
TR-D11
Bus 9-23 kV 500 kVA
22.86kV Y / 0.22kV Y
S11
Cu -XLP-25kV Z1=5% , Z0=4.25%
/ / 1000 kCM - 1CF X/R=5
PADC 4''
60 MVA 150m 500m
230 kV YG / 23kV
YRG / 13.2kV D
Z=17.5%
X/R=32
Fig. 2. Single line diagram of the substation and its derived circuits [6].
M
VS1_0 VS1_2
M
M
M
overcurrent protection.
IA_S1 VA_S1
IP_S1
T
T
VP_S1 T
T
S1
TR-D1 500kVA CARGA TR-D1
A sustained single-phase fault in the S4 circuit produced in
Bus2-23kV
T
LCC
V
95% f.p.:0.95
I
A23-S1
D1-H
Y Y
SAT
D1-X
phase b in the circuit that is modeled in ATPDraw is simulated,
I
M
IS2_1
M
VS2_1
M
2.5 km
see Figure 3. The fault starts at the moment t = 0.05s, with a
IS2_0 IS2_2 VS2_0 VS2_2
IA_S2
T
M M
VA_S2
T
M M
S2
peak value close to 5000 A, see figure 4, coincidentally, at the
IP_S2 VP_S2
same moment an increase in the currents of the S2 circuit is
T T
I
A23-S2
D2-H
Y Y
SAT
D2-X
observed (which has zero load), and reaches peak values close
I
M
LCC
H20N
Bus1-230kV V
S2-S S2-L
IS3_1 VS3_1
500. m
to 100 A. The waveforms show a peculiar anomaly, the
TR-A 60MVA M M
A23-S0
IA_S3
IS3_0 IS3_2
M M
VS3_0 VS3_2
VA_S3
M M
tendency to phase each other, that is, the angular difference
Y
SAT
Y
T T
S3
SA-S SA-L IP_S3 T VP_S3 T
I
A23-S3 Y Y
SAT
I
D3-H D3-X
I
M
S3-L H30N
S3-S
500. m
IS4_1 VS4_1
M M
IA_S4 VA_S4
T T
IP_S4 T VP_S4 T
150. m
Equivalente de Thevenin I
IA_S10 VA_S10
M M M M
T T
IP_S10 T
VP_S10 T
IRMS_S1
LCC TR-D10 500kVA CARGA TR-D10
Bus3-23kV
T
V F RMS
I
Y Y
IRMS_S2
D10-H D10-X
SAT
S10-S S10-L
T
F RMS
I
66
M
2650 m
IS11_1 VS11_1 IRMS_S3
TR-B 60MVA H100N
T
F RMS
IS11_0
M
IS11_2 VS11_0 M
VS11_2 66
A23-SB
IA_S11 VA_S11
M M M M
Y Y IRMS_S4
T T
IP_S11 VP_S11
SAT
T
F RMS
SB-S SB-L T T 66
I
IRMS_S10
LCC TR-D11 500kVA CARGA TR-D11
T
F RMS
T
66
A23-S11 25% f.p.:0.95
I
Y Y
IRMS_S11
S11-S S11-L D11-H
SAT
D11-X
a)
T
F RMS
I
66
M
650 m
H110N
a)
b)
Fig. 5. Oscillograms of currents of the S2 circuit. (a) Phase currents and (b)
Residual current.
which the same behavior shown in Figure 8 is observed. TABLE IV. COMPARISON OF MAGNITUDES OF NEGATIVE SEQUENCE
CURRENTS AND ZERO OF MODEL CIRCUITS
Predominance by the zero sequence current is observed.
FAULT
CIRCUIT
CC1FT
S1 I2 < I0
S2 I2 < I0
S3 I2 < I0
S4 I2 ≈ I0
S10 I2 y I0 ≈ 0.0
S11 I2 y I0 ≈ 0.0
Fig. 9. Real current profile of negative sequence and zero sequence for an
external fault. Table IV provides a basis for discrimination of circuits
The behavior of the sequence current profiles of the S1 and without the presence of failure and those that do not have a
S3 circuits is very similar to the profile observed in Figure 8, relationship or interaction with the failed circuit. Those circuits
while the profiles of the remaining circuits (S10 and S11) do that present a greater magnitude of the zero sequence current
not present anomalies due to the interaction of the failure compared to the magnitude of the negative sequence current, it
current of the S4 circuit, see Figure 10. is concluded that they should not be attributed any failure
condition. While the circuit that experiences a single-phase
failure presents values of negative sequence and zero sequence
currents, very similar and of great magnitude.
Table V summarizes the proposed discrimination of the
overcurrent protection element based on the negative and zero
sequence currents, which make up the model in ATPDraw.
TABLE V
PROPOSAL OF DISCRIMINATION BASED ON THE NEGATIVE AND ZERO
SEQUENCE CURRENTS OF THE MODEL CIRCUITS
FAULT
a) CIRCUIT CC1FT
Discrimination
S1 (I2 / I0 ) x 100 : 100% ± 10%
S2 (I2 / I0 ) x 100 : 100% ± 10%
S3 (I2 / I0 ) x 100 : 100% ± 10%
S4 (I2 / I0 ) x 100 : 100% ± 10%
IV. RESULTS
When comparing the magnitudes of the negative and zero
Caso_Tesis_v1 (0.16696/68.697)*100 : 0.243%
sequence currents in each circuit, it is observed that the zero 0.20015
68.6970
sequence current predominates in healthy circuits derived from 0.16696
0.76739
bus 2, while the circuit with single-phase failure presents
similar magnitudes between the negative sequence and zero.
The magnitudes of the negative and zero sequence currents
of the circuits of bus 3 are negligible, due to the null interaction
with the failed circuit.
Fig. 11. Sequence current profile of the S2 circuit and fault condition
A comparison is made between the values of the magnitudes discrimination.
of the negative and zero sequence currents, see table IV. Therefore, the device is not activated and the selectivity of
the device is correct.
THE XIV LATIN-AMERICAN CONGRESS ON ELECTRICITY GENERATION AND TRANSMISSION - CLAGTEE 2022 6
Rio de Janeiro, Brazil, November 27th – 30th, 2022
AUTHORS
Fernando Toledo Toledo. Industrial Engineer in Electricity from ITRO. He
completed masters and doctoral studies in sciences (Electrical Engineering) at
Caso_Tesis_v1 (1195.2/1195.3)*100 : 99.99% SEPI-ESIME-IPN. Since 1981 he has been a research professor in the Electrical
0.20010
1195.3 Area of the UAM-A where he develops software for the analysis of industrial
1195.2
1193.7
and power electrical systems.
ftoledo2@azc.uam.mx
VI. BIBLIOGRAPHY