COMPUTATION OF LOADS

I. TOTAL LOAD
500 m² ( 2 VA/ m²) = 1000 VA
A. GENERAL LIGHTING AND CONVENIENCE RECEPTACLE LOAD
22 LIGHTING OUTLETS
5 CONVENIENCE OUTLETS
· PROVIDE 3, 15 AMPERE CIRCUIT BREAKER FOR LIGHTING OUTLET
· PROVIDE 1, 20 AMPERE CIRCUIT BREAKER FOR CONVENIENCE OUTLET

APPLICATION OF DEMAND FACTOR


DEMAND FACTOR IS 100% FOR 1000 VA = 1000 VA
B. OTHER LOADS
1 - 1 HP AIR CONDITIONING UNIT
8 A (230V) = 1840 VA
· PROVIDE 1, 20 AMPERE CIRCUIT BREAKER FOR AIR CONDITIONING UNIT

II. CIRCUIT REQUIREMENT


· USE: 3, 15 AMPERE CIRCUIT BREAKER
2, 20 AMPERE CIRCUIT BREAKER

4 III. SERVICE ENTRANCE CONDUCTOR


1000 VA + 125%(1840 VA)
230 V = 14.25 A

· PROVIDE 8.0 mm2, 2 WIRE THHN FOR SERVICE ENTRANCE CONDUCTOR

5 ACU
IV. SERVICE EQUIPMENT
1000 VA + 250%(1840 VA)
230 V = 24.35 A
· PROVIDE 40 AMPERE CIRCUIT BREAKER FOR SERVICE EQUIPMENT PROTECTION,
INVERSE TIME CIRCUIT BREAKER

POWER LAYOUT
SCALE 1:100

DESIGNED BY CHECKED BY PROJECT TITLE OWNER SCHOOL SHEET NO.


BIKE PARTS WAREHOUSE
KRISTAN GLEN D. PULIDO ENGR. JEMIMAH P. NATIVIDAD

LOCATION:
(500 m²)
ADDRESS:
ANN D. LIM NUEVA VIZCAYA STATE
UNIVERSITY - BAMBANG 3
BSEE - 4A DATE:FEBRUARY 07, 2023
BAYOMBONG, NUEVA VIZCAYA SOLANO, NUEVA VIZCAYA
CAMPUS