KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.
A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

12
4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB
LEVELS UNLESS OTHERWISE INDICATED.

P.T SLAB
5- THIS DRAWING TO BE READ IN CONJUNCTION WITH

Z03-B03-300X1000
Z03-B03-300X1000
10 THIK. 350mm

Z02-B03-300X1000
F'c=35MPa 11
600
RELEVANT STRUCTURAL , ARCHITECTURAL ,

Z01-B04-300X800
Z02-B03-300X1000
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &

600
AA Z03-B04-01-300X950 Z03-B04-01-300X950
SPECIFICATIONS . THE CONTRACTOR SHALL
BA COORDINATE THESE DRAWINGS AND DOCUMENTS

Z02-B03-300X1000
AND REPORT IF ANY DISCREPANCY FOR

Z03-B03-300X1000
18 CLARIFICATION BEFORE PROCEEDING WITH THE
Z03-B05-01-400X800

WORK INVOLVED .

Z01-B03A-3-400X1450
Z02-B03-300X1000
8

Z01-B04-300X800
P.T SLAB
THIK. 350mm
F'c=35MPa
Z0
3-
B0
5-
01

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


-4
00
X8
00

BB FOOTINGS .
00
X7
00
1-4

Z03-B03-300X1000
-0
06
3-B

AB
Z0 16 Z01-B04 Z01-B04
7- DESIGN FOUNDATION IS BASED ON ASSUMED NET

Z01-B03A-2-400X1450
700

BEARING CAPACITY AS PER SOIL REPORT.

Z02-B03-300X1000

Z01-B04-300X800
0X

Z02-B03-300X1000
-40

P.T SLAB
2
6-0

P.T SLAB THIK. 350mm


-B0

P.T SLAB
THIK. 350mm
Z03

Z03-B05-01-400X800 P.T SLAB P.T SLAB F'c=35MPa THIK. 350mm


20 THIK. 350mm F'c=35MPa
THIK. 350mm
F'c=35MPa F'c=35MPa
Z01-B04 Z01-B04 F'c=35MPa
COLUMN LEGEND:
700
-400X

CB-03
BC
06-02
Z03-B

Z01-B03A-1-400X1450
15
AC CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

Z01-B04-300X800
Z01-B06-300X1620

Z02-B03-300X1000

Z01-B06A-300X1620
Z01-B07-300X1620

Z01-B07-300X1620
Z0
3-B
06
-04
00 -40
0X
X8 70
00 0 Z01-B06-300X1620
1-4

Z0
3-
B 05
- 0
REINFORCEMENT LEGEND:
Z03-B05A-01-400X800

Z02-B03-300X1000
P.T SLAB 950 950 950 950 950
THIK. 350mm Z01-B01-300X900
Z01-B01-300X900 Z01-B01-300X900 Z01-B01-300X900 Z01-B01-300X900
BD
F'c=35MPa TOP REINFORCEMENT

9
Location of stair starter is BOTTOM REINFORCEMENT
19
not matching with Arch.

AD

Z01-B03-500X1000/1500
P.T SLAB

Z02-B03-300X1000
Z03-B03-01-300X950 Z03-B03-02-300X950 Z03-B03-01-300X950 Z03-B03-01-300X950 Z03-B03-02-300X950 Z03-B03-02-300X950 Z03-B03-03-300X950 Z03-B03-01-300X950 Z03-B03-02-300X950 Z03-B03-03-300X950

Z01-B02-400X900/1500
BE

Z01-B02-400X900/1500
THIK. 350mm

Z01-B02-400X900/1500

Z01-B02-400X900/1500

Z01-B02-400X900/1500
F'c=35MPa
600

600

600

600
AE

Z03-B01A-400X1250

Z02-B03-300X1000
Z03-B01-850X1250
Z03-B02-400X1250

Z03-B02-400X1250

Z03-B02-400X1250

Z03-B02-400X1250

Z03-B01-850X1250
Z03-B01-850X1250

Z03-B01-850X1250

Z03-B01-850X1250

Z03-B01-850X1250

Z03-B01-850X1250

Z03-B01-850X1250

13
14

A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

01 REVISED AS CLOUDED 2023-11-19


00 ISSUED FOR COORDINATION 2023-10-19
Revision No. Description Date
Revisions
Client

Design Consultant (logo)


GROUND FLOOR GENERAL ARRANGEMENT LAYOUT PLAN
01 MASTER PLAN

Programme / Programme Management Consultant

Main Contractor

ARABIAN CONSULTING ENGINEERING SERVICES


RegistrationNo.248
P.O.Box146,Riyadh Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859
info@esolution-pt.com
A Approved www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title
B Approved as Noted BANK ALJAZIRA
RIYADH
C Resubmitted As Noted Drawing Title

D Disapproved
-These drawings must be stamped by Esolution Company
before construction, and this approval is considered F No Action Taken
ineffective without Esolution Company’s stamp GROUND FLOOR
-All levels and dimensions should be coordinated with Signature Date GENERAL ARRANGEMENT LAYOUT PLAN
Hassan Al Mawaldi 20/11/2023
ARCH before the constructions. MASTER PLAN
-All openings should be coordinated with ARCH & MEP This drawing has been reviewed for design and general arrangement only.
before the constructions. The action indicated does not relieve the contractor from responsibility for Approved Seal Date
full compliance with the Contract Documents and other working drawings.
Contractor shall indicate on his submittal any deviation, if any, from
Designed Drawn Checked
Contract Documents.
The action indicated shall not vary the Contract Sum. M.K M.S M.A
Scale A1 (594x841) Revision No

1-300 00
Drawing No

ES-PL-FP-GF-GA-M
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.
P.T SLAB
Z03-B03-300X1000

10 THIK. 350mm 2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


Z02-B03-300X1000

F'c=35MPa 11 ATTENTION OF THE ARCHITECT / ENGINEERS.

Z01-B04-300X800
Z02-B03-300X1000
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.

Z03-B04-01-300X950 4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

BA 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
Z02-B03-300X1000
Z03-B03-300X1000

MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &


SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE

Z01-B03A-3-400X1450
Z02-B03-300X1000
8

Z01-B04-300X800
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.
BB
COLUMN LEGEND:
Z03-B03-300X1000

Z01-B04 Z01-B04
CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

Z01-B03A-2-400X1450
Z02-B03-300X1000

Z01-B04-300X800
Z02-B03-300X1000

P.T SLAB
THIK. 350mm REINFORCEMENT LEGEND:
P.T SLAB
F'c=35MPa THIK. 350mm TOP REINFORCEMENT
Z01-B04 Z01-B04 F'c=35MPa
BOTTOM REINFORCEMENT

CB-03
BC

Z01-B03A-1-400X1450
Z01-B04-300X800

Z01-B06-300X1620
Z02-B03-300X1000

Z01-B06A-300X1620
Z01-B07-300X1620

Z01-B07-300X1620
Z01-B06-300X1620

01 REVISED AS CLOUDED 2023-11-19


00 ISSUED FOR COORDINATION 2023-10-19
Z02-B03-300X1000

P.T SLAB 950 950 950 950 950 Revision No. Description Date
THIK. 350mm Z01-B01-300X900
Z01-B01-300X900 Z01-B01-300X900 Z01-B01-300X900 Z01-B01-300X900
BD Revisions
F'c=35MPa Client

9
Location of stair starter is
not matching with Arch.

Design Consultant (logo)

Z01-B03-500X1000/1500
P.T SLAB
Z02-B03-300X1000

Z03-B03-03-300X950
Z01-B02-400X900/1500

BE
Z01-B02-400X900/1500

THIK. 350mm
Z01-B02-400X900/1500

Z01-B02-400X900/1500

Z01-B02-400X900/1500
F'c=35MPa

Programme / Programme Management Consultant


Z03-B01A-400X1250

Z02-B03-300X1000

ARABIAN CONSULTING ENGINEERING SERVICES Main Contractor

RegistrationNo.248
P.O.Box146,Riyadh
Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,

A Approved Riyadh , Saudi Arabia


Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7 info@esolution-pt.com


www.esolution-pt.com
esolution construction & Engineering

B Approved as Noted precast & Post tension concrete specialists

Project Title

BANK ALJAZIRA
C Resubmitted As Noted
RIYADH
D Disapproved Drawing Title

-These drawings must be stamped by Esolution Company GROUND FLOOR GENERAL ARRANGEMENT LAYOUT PLAN
01 ( ZOON-01 ) F No Action Taken
before construction, and this approval is considered
ineffective without Esolution Company’s stamp Signature Date GROUND FLOOR
-All levels and dimensions should be coordinated with Hassan Al Mawaldi 20/11/2023
GENERAL ARRANGEMENT LAYOUT PLAN
ARCH before the constructions. ( ZONE-01 )
This drawing has been reviewed for design and general arrangement only.
-All openings should be coordinated with ARCH & MEP The action indicated does not relieve the contractor from responsibility for
before the constructions. full compliance with the Contract Documents and other working drawings.
Approved Seal Date
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents.
The action indicated shall not vary the Contract Sum. Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-125 00
Drawing No

ES-PL-FP-GF-GA-Z1
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12'


General Notes
12 1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN
DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

Z03-B03-300X1000
Z03-B03-300X1000
2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE

Z02-B03-300X1000
ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS

600
ARE IN METERS UNLESS OTHERWISE INDICATED.

Z03-B04-01-300X950 Z03-B04-01-300X950 4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,

Z02-B03-300X1000
Z03-B03-300X1000
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

Z03-B03-300X1000
16
CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

Z02-B03-300X1000
P.T SLAB REINFORCEMENT LEGEND:
P.T SLAB THIK. 350mm
TOP REINFORCEMENT
THIK. 350mm F'c=35MPa
F'c=35MPa BOTTOM REINFORCEMENT

15

01 REVISED AS CLOUDED 2023-11-19


00 ISSUED FOR COORDINATION 2023-10-19

Z02-B03-300X1000
Revision No. Description Date
Revisions
Client

Design Consultant (logo)

Z03-B03-01-300X950 Z03-B03-02-300X950 Z03-B03-02-300X950 Z03-B03-03-300X950 Z03-B03-01-300X950 Z03-B03-02-300X950 Z03-B03-03-300X950


600

600

600
Programme / Programme Management Consultant

Z03-B01A-400X1250

Z02-B03-300X1000
Z03-B01-850X1250
Z03-B02-400X1250

Z03-B02-400X1250

Z03-B02-400X1250

Z03-B02-400X1250

Z03-B01-850X1250
Z03-B01-850X1250

Z03-B01-850X1250

Z03-B01-850X1250

Main Contractor

13
ARABIAN CONSULTING ENGINEERING SERVICES Posttension Contractor
14 Bahrain Tower,

RegistrationNo.248 King Fahed St , Olaia,


Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858

P.O.Box146,Riyadh Fax: +966 (11) 201 9859

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' info@esolution-pt.com


www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

A Approved BANK ALJAZIRA


RIYADH
B Approved as Noted Drawing Title

GROUND FLOOR GENERAL ARRANGEMENT LAYOUT PLAN


01 ( ZOON-02 ) C Resubmitted As Noted

D Disapproved
GROUND FLOOR
-These drawings must be stamped by Esolution Company GENERAL ARRANGEMENT LAYOUT PLAN
F No Action Taken
before construction, and this approval is considered ( ZONE-02 )
ineffective without Esolution Company’s stamp Signature Date
-All levels and dimensions should be coordinated with Hassan Al Mawaldi 20/11/2023
Approved Seal Date

ARCH before the constructions.


This drawing has been reviewed for design and general arrangement only.
-All openings should be coordinated with ARCH & MEP The action indicated does not relieve the contractor from responsibility for
Designed Drawn Checked

full compliance with the Contract Documents and other working drawings. M.K M.S M.A
before the constructions. Contractor shall indicate on his submittal any deviation, if any, from Scale A1 (594x841) Revision No

Contract Documents. 1-125 00


The action indicated shall not vary the Contract Sum. Drawing No

ES-PL-FP-GF-GA-Z2
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A1 A2 A3 A4 A5 A5'
General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.
600
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.

AA 4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
18
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR

Z03-B05-01-400X800
CLARIFICATION BEFORE PROCEEDING WITH THE
P.T SLAB WORK INVOLVED .
THIK. 350mm
F'c=35MPa

Z0
6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .

3-
B0
5-
FOOTINGS .

01
-4
00
X8
00
7- DESIGN FOUNDATION IS BASED ON ASSUMED NET
BEARING CAPACITY AS PER SOIL REPORT.

70
0 COLUMN LEGEND:
00X
1-4
06-0
3- B
Z0
AB CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

700
0X
2 -40
6-0
REINFORCEMENT LEGEND:

-B0
Z03
Z03-B05-01-400X800 P.T SLAB TOP REINFORCEMENT
20
THIK. 350mm
BOTTOM REINFORCEMENT
F'c=35MPa

0
0X70 -40
3 -B 06-02
0
AC

Z
Z0
3-B
06
-04
00 -40
8 0X
0X 70
0
-40
- 01
5
- B0
3
Z0 00 ISSUED FOR COORDINATION 2023-10-19

Z03-B05A-01-400X800
Revision No. Description Date
Revisions
Client

19

Design Consultant (logo)

AD Z03-B03-01-300X950 Z03-B03-02-300X950 Z03-B03-01-300X950 Z03-B03-01-300X950

600

600
AE Programme / Programme Management Consultant
ARABIAN CONSULTING ENGINEERING SERVICES
RegistrationNo.248

Z03-B02-400X1250

Z03-B02-400X1250
Z03-B01-850X1250

Z03-B01-850X1250

Z03-B01-850X1250
P.O.Box146,Riyadh
Main Contractor

A Approved
Posttension Contractor
Bahrain Tower,
B Approved as Noted King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A1 A2 A3 A4 A5 A5' C Resubmitted As Noted


info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title
D Disapproved BANK ALJAZIRA
RIYADH
F No Action Taken Drawing Title

GROUND FLOOR GENERAL ARRANGEMENT LAYOUT PLAN Signature Date


01 ( ZOON-03 ) Hassan Al Mawaldi 20/11/2023

-These drawings must be stamped by Esolution Company This drawing has been reviewed for design and general arrangement only. GROUND FLOOR
The action indicated does not relieve the contractor from responsibility for
before construction, and this approval is considered full compliance with the Contract Documents and other working drawings. GENERAL ARRANGEMENT LAYOUT PLAN
ineffective without Esolution Company’s stamp Contractor shall indicate on his submittal any deviation, if any, from ( ZONE-03 )
Contract Documents.
-All levels and dimensions should be coordinated with The action indicated shall not vary the Contract Sum.
ARCH before the constructions. Approved Seal Date

-All openings should be coordinated with ARCH & MEP


Designed Drawn Checked
before the constructions. M.K M.S M.A
Scale A1 (594x841) Revision No

1-125 00
Drawing No

ES-PL-FP-GF-GA-Z3
KEY PLAN

B6
BD BA A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

LWC Slab 300mm Slab


LWC Slab 300mm Slab SSL -400 Tower Ground Floor
LWC Slab 300mm Slab SSL -400
PT Slab 350mm Slab SSL -1,000 -100 SSL
Tower Ground Floor Tower Ground Floor
-100 SSL -100 SSL PT Slab 350mm Slab General Notes
SSL -1,000
SSL -1,500 SSL -1,670 1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN
PT Slab 350mm Slab
DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
Beam (300x1620) PT Slab 350mm Slab Beam (300x1620) W1-300mm W1-300mm DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
PT Slab 350mm Slab PT Slab 350mm Slab Beam (300x950) COMMENCEMENT OF WORKS OR MANUFACTURING OF
Beam (300x1450) COMPONENT.
PT Slab 350mm Slab
2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT / ENGINEERS.
Section 08
8 1 : 50 Section 09 3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS

9 Section 10 ARE IN METERS UNLESS OTHERWISE INDICATED.

1 : 50 10 1 : 50
4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB
LEVELS UNLESS OTHERWISE INDICATED.

B6 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
AD AE MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
AA
Section 11 is not matching SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR

with plan CLARIFICATION BEFORE PROCEEDING WITH THE


WORK INVOLVED .
Tower Ground Floor PT Slab 350mm Slab LWC Ramp
6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .
-100 SSL Parking Ground Floor Parking Ground Floor FOOTINGS .
SSL -1,000 -400 SSL 10% SSL -1,000 -400 SSL
PT Slab 350mm Slab SSL -1,000 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET
Beam (300x950)
BEARING CAPACITY AS PER SOIL REPORT.
SSL -1,500 PT Slab 350mm Slab Beam (300x950)
COLUMN LEGEND:
RW-400mm RW-400mm
PT Slab 350mm Slab Beam (300x850) PT Slab 350mm Slab PT Slab 350mm Slab

W1-300mm CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:
Section 11
11 Section 12 TOP REINFORCEMENT

1 : 50 12 1 : 50 Section 13
BOTTOM REINFORCEMENT

AD AE
13 1 : 50
A8 A9 A9'
RC Ramp 300 mm THK

PT Slab 350mm Slab


Parking Ground Floor
DP 500mm Slab PT Slab 350mm Slab -400 SSL
C06 Parking Ground Floor
PT Slab 350mm Slab DP 500mm Slab
SSL -1,000 -400 SSL Beam (400x800)
PT Slab 350mm Slab C06 Parking Ground Floor C07 Parking Ground Floor PT Slab 350mm Slab
Beam (300x950) -400 SSL -400 SSL
00 ISSUED FOR COORDINATION 2023-10-19
Revision No. Description Date

Section 18 Client
Revisions

18 1 : 50
C16 PT Beam (700x1000)
C6-1 RW-400mm

Section 15 Design Consultant (logo)

15 Section 16
Section 14 1 : 50 16 1 : 50
14 1 : 50
A2 Programme / Programme Management Consultant

RC Ramp 300 mm THK

C06 C06 ARABIAN CONSULTING ENGINEERING SERVICES Main Contractor


Parking Ground Floor Parking 1st Floor
-400 SSL 2600 SSL RegistrationNo.248
RC UPSTAND 1500 mm HEIGHT
250 mm THK
RC UPSTAND 1500 mm HEIGHT
250 mm THK
P.O.Box146,Riyadh
Beam (400x800) WITH RAMP WITH RAMP PT Slab 350mm Slab
Posttension Contractor
PT Slab 350mm Slab RC Ramp 300 mm THK Bahrain Tower,
King Fahed St , Olaia,

A Approved Riyadh , Saudi Arabia


Tel: +966 (11) 201 9858

Section 19 Fax: +966 (11) 201 9859


info@esolution-pt.com

19 1 : 50 PT Slab 350mm Slab B Approved as Noted


www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

Beam (400x800) C Resubmitted As Noted BANK ALJAZIRA


Parking Ground Floor RIYADH
SSL -1,000 With Ramp -400 SSL
PT Slab 350mm Slab D Disapproved Drawing Title

RC UPSTAND 1500 mm HEIGHT RC UPSTAND 1500 mm HEIGHT


-These drawings must be stamped by Esolution Company F No Action Taken
before construction, and this approval is considered
250 mm THK
WITH RAMP

RC Ramp 300 mm THK


250 mm THK
WITH RAMP

Signature Date
General Details
ineffective without Esolution Company’s stamp Hassan Al Mawaldi 20/11/2023
-All levels and dimensions should be coordinated with
ARCH before the constructions. This drawing has been reviewed for design and general arrangement only.
The action indicated does not relieve the contractor from responsibility for
-All openings should be coordinated with ARCH & MEP full compliance with the Contract Documents and other working drawings.
Beam (400x800) Contractor shall indicate on his submittal any deviation, if any, from
before the constructions. With Ramp Contract Documents.
Approved Seal Date

The action indicated shall not vary the Contract Sum. Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-125 00
Section 20 Drawing No
ES-PL-FP-GF-GD
20 1 : 50
KEY PLAN
TOP BARS
Beam Label SPAN Width Depth BOTT BARS
MID SUPPORT SIDE BARS STIRRUPS
END SUPPORT MID SPAN A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN

RIGHT SUPPORT Zone A Zone B Zone C


UP

LEFT SUPPORT BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

Bar F Bar G Bar A Bar B Bar C1 Bar D1 Bar C2 Bar D2 Bar E BD

BE
BD

AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

Z01 B01 01 300 900 950 4-20 - 5-20 - 6-20 - 6-20 - 4-20E T12@200 T10@200 T10@200 T10@200
ARABIAN CONSULTING ENGINEERING SERVICES
02 300 900 950 4-20 - - - 6-20 - 6-20 - 4-20E T12@200 T10@200 T10@200 T10@200
RegistrationNo.248
03 300 900 950 4-20 - - - 6-20 - 6-20 - 4-20E T12@200 T10@200 T10@200 T10@200

04 300 900 950 4-20 - 5-20 - - - - - 4-20E T12@200 T10@200 T10@200 T10@200
P.O.Box146,Riyadh
General Notes
Z01 B02 01 400 900/1500 4-20 2T20
- 7-20 - - - - - 4-20E T10@100-4L T10@200-4L T10@100-4L
1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN
Z01 B03 01 500 1000/1500 4-25 4-25 5-20 3-20 - - 4-20 4-20 4-25E T12@200 T10@200-4L T10@200-4L T10@200-4L DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
A Approved DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
Z01 B03A 01 400 1450 4-20 3-20 4-20 3-20 - - 4-20 4-20 4-20E T12@200 T10@200 T10@200 T10@200
COMMENCEMENT OF WORKS OR MANUFACTURING OF
02 400 1450 4-20 3-20 4-20 3-20 4-20 4-20 4-20 4-20 4-20E T12@200 T10@200 T10@200 T10@200 COMPONENT.
B Approved as Noted
03 400 1450 4-20 3-20 4-20 3-20 4-20 4-20 - - 4-20E T12@200 T10@200 T10@200 T10@200 2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT / ENGINEERS.
Z01 B04 01 300 800 4-20 4-20 - - - - - 2-20E - T10@200 T10@200 T10@200
C Resubmitted As Noted
Z01 B05 01 300 800 3-20 - 3-20 - 4-20 4-20 - - 2-16E - T10@200 T10@200 T10@200 3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.
02 300 800 3-20 - 3-20 - 4-20 4-20 - - 2-16E - T10@200 T10@200 T10@200 D Disapproved
4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB
Z01 B06 01 300 1620 4-20 3T20 4-20 - - - - - 2-20E T12@200 T10@200 T10@200 T10@200 LEVELS UNLESS OTHERWISE INDICATED.
Z01 B06A 01 300 1620 4-20 3-20 4-20 3-20 - - - - 2-20E T12@200 T10@200 T10@200 T10@200 F No Action Taken 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH
Z01 B06 01 300 1620 4-25 3-25 4-25 3-25 - - - - 2-20E T12@100 T12@100 T12@100 T12@100 RELEVANT STRUCTURAL , ARCHITECTURAL ,
Signature Date MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
TOP BARS Hassan Al Mawaldi 20/11/2023 COORDINATE THESE DRAWINGS AND DOCUMENTS
Beam Label SPAN Width Depth AND REPORT IF ANY DISCREPANCY FOR
MID SUPPORT SIDE BARS STIRRUPS
MID SPAN CLARIFICATION BEFORE PROCEEDING WITH THE
This drawing has been reviewed for design and general arrangement only. WORK INVOLVED .
BOTT BARS END SUPPORT LEFT SUPPORT RIGHT SUPPORT Bar E Zone A Zone B Zone C The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings. 6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .
Bar F Bar G Bar A Bar B Bar C1 Bar D1 Bar C2 Bar D2 FOOTINGS .
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents. 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET
Z03 B01 01 850 1250 SEE BEAM ELEVATION should be submitted The action indicated shall not vary the Contract Sum. BEARING CAPACITY AS PER SOIL REPORT.
Z03 B02 01 400 1250 SEE BEAM ELEVATION should be submitted COLUMN LEGEND:
Z03 B03 01 300 1000 4-20 - 4-20 - - - - - 2-20E - T10@200 T10@200 T10@200

Z03 B04 01 300 950 4-20 - 4-20 - - - 4-20 - 2-16E - T10@200 T10@200 T10@200 CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

02 300 950 4-20 - 4-20 - 4-20 - - - 2-16E - T10@200 T10@200 T10@200

Z03 B05 01 400 800 4-25 - 4-25 - - - - - 4-25E T12@200 T10@200 T10@200 T10@200
REINFORCEMENT LEGEND:
Z03 B05A 01 400 800 4-25 4-25 4-25 - - - - - 4-25E T12@200 T10@200 T10@200 T10@200
TOP REINFORCEMENT

Z03 B06 01 400 700 4-25 - 4-25 - 4-20 - - - 2-20E T10@200 T10@200 T10@200 T10@200 BOTTOM REINFORCEMENT

02 400 700 4-25 - - - 4-20 - 4-20 - 2-20E T10@200 T10@200 T10@200 T10@200

04 400 700 4-25 - 4-25 - - - 4-20 - 2-20E T10@200 T10@200 T10@200 T10@200

-These drawings must be stamped by Esolution Company


TOP BARS
Beam Label SPAN Width Depth
SIDE BARS STIRRUPS
before construction, and this approval is considered
MID SUPPORT
MID SPAN
ineffective without Esolution Company’s stamp
BOTT BARS END SUPPORT LEFT SUPPORT RIGHT SUPPORT Bar E Zone A Zone B Zone C
-All levels and dimensions should be coordinated with 02
01
UPDATED AS COMMENTED
UPDATED AS COMMENTED
2023-11-19
2023-11-07
Bar F Bar G Bar A Bar B Bar C1 Bar D1 Bar C2 Bar D2
ARCH before the constructions. 00
Revision No.
ISSUED FOR COORDINATION
Description
2023-10-19
Date

Z02 B03 01 300 1000 5-25 - 5-25 - - - - - 3-25E - T10@100 T10@100 T10@100 -All openings should be coordinated with ARCH & MEP Client
Revisions

Z02 B03 02 300 1000 5-25 - - 5-25 - 5-25 - 3-25E - T10@100 T10@100 T10@100 before the constructions.

Design Consultant (logo)

Programme / Programme Management Consultant


Ln1 Ln2 LnN

0.25Ln1 0.3Ln1 or 0.3Ln2 (Larger) 0.3Ln1 or 0.3Ln2 (Larger) 0.3Ln2 or 0.3LnN (Larger) 0.3Ln2 or 0.3LnN (Larger) 0.25LnN

BEAM HEIGHT BEAM HEIGHT BEAM HEIGHT


0.2Ln1 0.2Ln1 or 0.2Ln2 (Larger) 0.2Ln1 or 0.2Ln2 (Larger) 0.2Ln2 or 0.2LnN (Larger) 0.2Ln2 or 0.2LnN (Larger) 0.2LnN
B A E D1 C1 E D2 C2 E A B
Main Contractor
d
d

d
h
h

h
F G F G F G Posttension Contractor
Bahrain Tower,
0.125Ln1 0.125Ln2 0.125Ln2 0.125LnN King Fahed St , Olaia,
Riyadh , Saudi Arabia
ZONE A ZONE B ZONE C ZONE D ZONE E ZONE A ZONE B ZONE C ZONE D ZONE E ZONE A ZONE B ZONE C ZONE D ZONE E Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859
info@esolution-pt.com
www.esolution-pt.com
NOTES:
esolution construction & Engineering
1. SEE BEAM SCHEDULE FOR STIRRUP TYPE AND SPACING.
precast & Post tension concrete specialists
2. CONTINUOUS BOTTOM BAR 'G' SHALL BE SPLICED AT THE SUPPORT AS NEEDED.

Project Title

BANK ALJAZIRA
RIYADH
Drawing Title

Ln
Ln1 Ln2

0.25Ln 0.25Ln
Z03-BEAMS REINFORCEMENT
0.25Ln1 0.3Ln1 or 0.3Ln2 (Larger) 0.3Ln1 or 0.3Ln2 (Larger) 0.25Ln2

0.2Ln
BEAM HEIGHT
0.2Ln BEAM HEIGHT BEAM HEIGHT
DETAILS
0.2Ln1 0.2Ln1 or 0.2Ln2 (Larger) 0.2Ln1 or 0.2Ln2 (Larger) 0.2Ln2
B A E C D
B A E D C E A B
d

d
h

F G F G F G
Approved Seal Date
0.125Ln1 0.125Ln2

ZONE A ZONE B ZONE C ZONE D ZONE E ZONE A ZONE B ZONE C ZONE D ZONE E
ZONE A ZONE B ZONE C Designed Drawn Checked

NOTES: M.K M.S M.A


NOTES: 1. SEE BEAM SCHEDULE FOR STIRRUP TYPE AND SPACING.
1. SEE BEAM SCHEDULE FOR STIRRUP TYPE AND SPACING. 2. CONTINUOUS BOTTOM BAR 'F' SHALL BE SPLICED AT THE SUPPORT AS NEEDED. Scale A1 (594x841) Revision No

1-125 00
Drawing No
ES-PL-FP-GF-GD
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.
A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


600
RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &

600
AA
SPECIFICATIONS . THE CONTRACTOR SHALL
BA COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


BB FOOTINGS .

AB 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:
BC
AC CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:
BD
TOP REINFORCEMENT

BOTTOM REINFORCEMENT

AD
BE
600

600

600

600
AE

A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

00 ISSUED FOR COORDINATION 2023-10-19

ARABIAN CONSULTING ENGINEERING SERVICES Revision No. Description Date


Revisions
RegistrationNo.248 Client

P.O.Box146,Riyadh

Design Consultant (logo)


GROUND FLOOR HORIZONTAL TENDONS LAYOUT A Approved
01 MASTER PLAN
B Approved as Noted
Programme / Programme Management Consultant
C Resubmitted As Noted

D Disapproved
Main Contractor

F No Action Taken

Signature Date
Hassan Al Mawaldi 20/11/2023 Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
*℄ Fax: +966 (11) 201 9859
This drawing has been reviewed for design and general arrangement only. info@esolution-pt.com
www.esolution-pt.com

The action indicated does not relieve the contractor from responsibility for esolution construction & Engineering
precast & Post tension concrete specialists
full compliance with the Contract Documents and other working drawings.
Project Title
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents. BANK ALJAZIRA
The action indicated shall not vary the Contract Sum. RIYADH
Drawing Title

-These drawings must be stamped by Esolution Company


before construction, and this approval is considered
ineffective without Esolution Company’s stamp GROUND FLOOR
-All levels and dimensions should be coordinated with HORIZONTAL TENDONS LAYOUT
ARCH before the constructions. MASTER PLAN
-All openings should be coordinated with ARCH & MEP
before the constructions. Approved Seal Date

Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-300 00
Drawing No

ES-PL-FP-GF-HZ-M
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

BA 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.
BB
COLUMN LEGEND:

CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

BC

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
BD Revisions
Client

Design Consultant (logo)

BE

Programme / Programme Management Consultant

Main Contractor

Posttension Contractor
ARABIAN CONSULTING ENGINEERING SERVICES Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
RegistrationNo.248 Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A12 A12' B1' B1 B2 B3 B4 B5 B6 P.O.Box146,Riyadh B7


info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

BANK ALJAZIRA
A Approved RIYADH
Drawing Title
B Approved as Noted
GROUND FLOOR HORIZONTAL TENDONS LAYOUT
01 ( ZOON-01 ) C Resubmitted As Noted

*℄ D Disapproved GROUND FLOOR


HORIZONTAL TENDONS LAYOUT
℄ -These drawings must be stamped by Esolution Company F No Action Taken ( ZOON-01 )
before construction, and this approval is considered
Signature Date
ineffective without Esolution Company’s stamp Hassan Al Mawaldi 20/11/2023 Approved Seal Date
-All levels and dimensions should be coordinated with
ARCH before the constructions. This drawing has been reviewed for design and general arrangement only. Designed Drawn Checked

The action indicated does not relieve the contractor from responsibility for
-All openings should be coordinated with ARCH & MEP full compliance with the Contract Documents and other working drawings.
M.K
Scale A1 (594x841)
M.S M.A
Revision No
before the constructions. Contractor shall indicate on his submittal any deviation, if any, from 1-125 00
Contract Documents.
Drawing No
The action indicated shall not vary the Contract Sum.
ES-PL-FP-GF-HZ-Z1
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12'


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS

600
ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
Revisions
Client

Design Consultant (logo)


600

600

600
Programme / Programme Management Consultant

Main Contractor

ARABIAN CONSULTING ENGINEERING SERVICES Posttension Contractor


Bahrain Tower,
King Fahed St , Olaia,
RegistrationNo.248 Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 P.O.Box146,Riyadh


A12' info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

A Approved BANK ALJAZIRA


RIYADH
B Approved as Noted Drawing Title

GROUND FLOOR HORIZONTAL TENDONS LAYOUT


01 ( ZOON-02 ) C Resubmitted As Noted

D Disapproved GROUND FLOOR


*℄
HORIZONTAL TENDONS LAYOUT
℄ -These drawings must be stamped by Esolution Company F No Action Taken
( ZOON-02 )
before construction, and this approval is considered
Signature Date
ineffective without Esolution Company’s stamp Hassan Al Mawaldi 20/11/2023 Approved Seal Date
-All levels and dimensions should be coordinated with
ARCH before the constructions. This drawing has been reviewed for design and general arrangement only. Designed Drawn Checked
The action indicated does not relieve the contractor from responsibility for
-All openings should be coordinated with ARCH & MEP full compliance with the Contract Documents and other working drawings.
M.K M.S M.A
Scale A1 (594x841) Revision No
before the constructions. Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents. 1-125 00
The action indicated shall not vary the Contract Sum. Drawing No

ES-PL-FP-GF-HZ-Z2
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A1 A2 A3 A4 A5 A5'
General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.
600
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.

AA 4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

AB CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

AC

00 ISSUED FOR COORDINATION 2023-10-19


ARABIAN CONSULTING ENGINEERING SERVICES Revision No. Description Date
Revisions
RegistrationNo.248 Client

P.O.Box146,Riyadh

A Approved Design Consultant (logo)

AD
B Approved as Noted
600

600
AE C Resubmitted As Noted Programme / Programme Management Consultant

D Disapproved
Main Contractor

F No Action Taken

Signature Date
Hassan Al Mawaldi 20/11/2023 Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
This drawing has been reviewed for design and general arrangement only. Fax: +966 (11) 201 9859

A1 A2 A3 A4 A5 A5' The action indicated does not relieve the contractor from responsibility for
info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
full compliance with the Contract Documents and other working drawings. precast & Post tension concrete specialists

Contractor shall indicate on his submittal any deviation, if any, from Project Title
Contract Documents. BANK ALJAZIRA
The action indicated shall not vary the Contract Sum. RIYADH
Drawing Title

GROUND FLOOR HORIZONTAL TENDONS LAYOUT


01 ( ZOON-03 )
-These drawings must be stamped by Esolution Company
*℄ before construction, and this approval is considered GROUND FLOOR
ineffective without Esolution Company’s stamp HORIZONTAL TENDONS LAYOUT

-All levels and dimensions should be coordinated with ( ZOON-03 )
ARCH before the constructions.
-All openings should be coordinated with ARCH & MEP Approved Seal Date

before the constructions. Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-125 00
Drawing No

ES-PL-FP-GF-HZ-Z3
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.
A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


600
RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &

600
AA
SPECIFICATIONS . THE CONTRACTOR SHALL
BA COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


BB FOOTINGS .

AB 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:
BC
AC CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:
BD
TOP REINFORCEMENT

BOTTOM REINFORCEMENT

AD
BE
600

600

600

600
AE

A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
Revisions
Client

L.L=5.00 KN/m2
Design Consultant (logo)
GROUND FLOOR LOADING LAYOUT D.L=10.00 KN/m2
MASTER PLAN
ARABIAN CONSULTING ENGINEERING SERVICES
01 L.L=5.00 KN/m2
RegistrationNo.248 D.L=8.00 KN/m2 Programme / Programme Management Consultant
P.O.Box146,Riyadh L.L=5.00 KN/m2
D.L=2.00 KN/m2
A Approved L.L=5.00 KN/m2 Main Contractor

D.L=20.00 KN/m2
B Approved as Noted L.L=5.00 KN/m2
Posttension Contractor
C Resubmitted As Noted D.L=6.00 KN/m2 Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
L.L=5.00 KN/m2 Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

D Disapproved info@esolution-pt.com

D.L=12.00 KN/m2
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

F No Action Taken L.L=5.00 KN/m2 Project Title

BANK ALJAZIRA
Signature
RIYADH
Date LINE LOAD = 15 KN/M
Drawing Title
Hassan Al Mawaldi 20/11/2023

This drawing has been reviewed for design and general arrangement only.
The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings.
This drawing was previously approved
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents.
( code B) on 06/11/2023 GROUND FLOOR
LOADING LAYOUT
The action indicated shall not vary the Contract Sum.
MASTER PLAN

Approved Seal Date

Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-300 00
Drawing No

ES-PL-FP-GF-LD-M
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

BA 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.
BB
COLUMN LEGEND:

CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

BC

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
BD Revisions
Client

Design Consultant (logo)

BE

Programme / Programme Management Consultant

Main Contractor

ARABIAN CONSULTING ENGINEERING SERVICES Posttension Contractor


Bahrain Tower,
King Fahed St , Olaia,
RegistrationNo.248 Riyadh , Saudi Arabia

D.L=30.00 KN/m2 Tel: +966 (11) 201 9858


Fax: +966 (11) 201 9859
P.O.Box146,Riyadh info@esolution-pt.com

L.L=5.00 KN/m2 www.esolution-pt.com


esolution construction & Engineering
precast & Post tension concrete specialists

D.L=10.00 KN/m2 Project Title

BANK ALJAZIRA
A Approved
L.L=5.00 KN/m2 RIYADH
B Approved as Noted D.L=8.00 KN/m2 Drawing Title

GROUND FLOOR LOADING LAYOUT L.L=5.00 KN/m2


C Resubmitted As Noted 01 ( ZOON-01 )
D.L=2.00 KN/m2
D Disapproved L.L=5.00 KN/m2 GROUND FLOOR
D.L=20.00 KN/m2 LOADING LAYOUT
F No Action Taken
L.L=5.00 KN/m2 ( ZONE-01 )
Signature Date D.L=6.00 KN/m2
Hassan Al Mawaldi 20/11/2023
L.L=5.00 KN/m2 Approved Seal Date

This drawing has been reviewed for design and general arrangement only. D.L=12.00 KN/m2
The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings.
This drawing was previously approved L.L=5.00 KN/m2
Designed

M.K
Drawn

M.S
Checked

M.A

Contractor shall indicate on his submittal any deviation, if any, from


Contract Documents.
( code B) on 06/11/2023 LINE LOAD = 15 KN/M
Scale A1 (594x841)

1-125
Revision No

00
The action indicated shall not vary the Contract Sum. Drawing No

ES-PL-FP-GF-LD-Z1
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12'


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
D.L=30.00 KN/m2 COMPONENT.

L.L=5.00 KN/m2 2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

D.L=10.00 KN/m2 3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS

600
L.L=5.00 KN/m2 ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


D.L=8.00 KN/m2 LEVELS UNLESS OTHERWISE INDICATED.

L.L=5.00 KN/m2 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
D.L=2.00 KN/m2 MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
L.L=5.00 KN/m2 COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
D.L=20.00 KN/m2 CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .
L.L=5.00 KN/m2 6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .
FOOTINGS .
D.L=6.00 KN/m2
L.L=5.00 KN/m2 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET
BEARING CAPACITY AS PER SOIL REPORT.

D.L=12.00 KN/m2 COLUMN LEGEND:

L.L=5.00 KN/m2 CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

LINE LOAD = 15 KN/M


REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

ARABIAN CONSULTING ENGINEERING SERVICES


RegistrationNo.248
P.O.Box146,Riyadh

A Approved 00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
Revisions

B Approved as Noted Client

C Resubmitted As Noted

D Disapproved Design Consultant (logo)

F No Action Taken
600

600

600
Programme / Programme Management Consultant
Signature Date
Hassan Al Mawaldi 20/11/2023

This drawing has been reviewed for design and general arrangement only. Main Contractor
The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings.
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents.
The action indicated shall not vary the Contract Sum. Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' info@esolution-pt.com


www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

BANK ALJAZIRA
RIYADH
Drawing Title

GROUND FLOOR LOADING LAYOUT


01 ( ZOON-02 )

GROUND FLOOR
LOADING LAYOUT
( ZONE-02 )

This drawing was previously approved Approved Seal Date

( code B) on 06/11/2023 Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-125 00
Drawing No

ES-PL-FP-GF-LD-Z2
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A1 A2 A3 A4 A5 A5'
General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
D.L=30.00 KN/m2 COMPONENT.

L.L=5.00 KN/m2 2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.
600
D.L=10.00 KN/m2 3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
L.L=5.00 KN/m2 ARE IN METERS UNLESS OTHERWISE INDICATED.

AA 4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


D.L=8.00 KN/m2 LEVELS UNLESS OTHERWISE INDICATED.

L.L=5.00 KN/m2 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
D.L=2.00 KN/m2 MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
L.L=5.00 KN/m2 COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
D.L=20.00 KN/m2 CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .
L.L=5.00 KN/m2 6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .
FOOTINGS .
D.L=6.00 KN/m2
L.L=5.00 KN/m2 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET
BEARING CAPACITY AS PER SOIL REPORT.

D.L=12.00 KN/m2 COLUMN LEGEND:

L.L=5.00 KN/m2
AB CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

LINE LOAD = 15 KN/M


REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

AC
ARABIAN CONSULTING ENGINEERING SERVICES
RegistrationNo.248
P.O.Box146,Riyadh

00 ISSUED FOR COORDINATION 2023-10-19


A Approved Revision No. Description Date
Revisions
Client
B Approved as Noted

C Resubmitted As Noted
Design Consultant (logo)

AD D Disapproved

600

600
F No Action Taken
AE Programme / Programme Management Consultant
Signature Date
Hassan Al Mawaldi 20/11/2023

Main Contractor
This drawing has been reviewed for design and general arrangement only.
The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings.
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents.
Posttension Contractor
The action indicated shall not vary the Contract Sum. Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A1 A2 A3 A4 A5 A5' info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

BANK ALJAZIRA
RIYADH
Drawing Title

GROUND FLOOR LOADING LAYOUT


01 ( ZOON-03 ) This drawing was previously approved
( code B) on 06/11/2023 GROUND FLOOR
LOADING LAYOUT
( ZONE-03 )

Approved Seal Date

Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-125 00
Drawing No

ES-PL-FP-GF-LD-Z3
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

General Notes

A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7 1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN
DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.
600

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE

600
AA ATTENTION OF THE ARCHITECT / ENGINEERS.
PS2 PS2 PS2 PS3

BA
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.
PS3

PS2

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.
BB
5- THIS DRAWING TO BE READ IN CONJUNCTION WITH
PS4
RELEVANT STRUCTURAL , ARCHITECTURAL ,
AB
PS2 PS2 PS2 PS2 PS2 PS3 MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
PS2
AND REPORT IF ANY DISCREPANCY FOR
BC CLARIFICATION BEFORE PROCEEDING WITH THE
PS3

AC WORK INVOLVED .
PS2 PS2 PS2 PS2 PS2 PS6

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

BD 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


PS3
BEARING CAPACITY AS PER SOIL REPORT.
PS2 Location of stair starter is
not matching with Arch.

COLUMN LEGEND:
AD
PS4
BE
600

600

600

600
AE PS5 CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT
A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

Location of stair starter is


not matching with Arch.

GROUND FLOOR REINFORCEMENT PLAN 00 ISSUED FOR COORDINATION 2023-10-19


01 MASTER PLAN Revision No. Description Date
Revisions
Client

Design Consultant (logo)

ROWS

SETS

Programme / Programme Management Consultant

TYP.
90
ROWS

(TYPICAL SPACE OF STIRRUPS PERIMETER)


FOR EDGE COLUMN

S
SETS ROWS

S
Main Contractor

S
S
S

TYP.
90
SETS

TYP.
90
Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
(TYPICAL SPACE OF STIRRUPS PERIMETER)
FOR INTERIOR COLUMN (TYPICAL SPACE OF STIRRUPS PERIMETER) Riyadh , Saudi Arabia
FOR CORNER COLUMN Tel: +966 (11) 201 9858
A A Fax: +966 (11) 201 9859
info@esolution-pt.com
SLAB THK

SLAB THK
PUNCHING REINFORCEMENT SCHEDULE www.esolution-pt.com

AS/PLAN
esolution construction & Engineering
50Ø 50Ø SHORT precast & Post tension concrete specialists
LONG DIRECTION
PUNCHING DIRECTION
ARABIANCONSULTINGENGINEERINGSERVICES MARK BAR SPACING NO. OF NO. OF BAR SPACING NO. OF NO. OF Project Title
SIZE (S) ROWS SETS SIZE (S) ROWS SETS
RegistrationNo.248 PS1 12 230 175 10 15 10 12 230 175 10 15 10 BANK ALJAZIRA
P.O.Box146,Riyadh AS SHOWN ON PLAN PS2 12 230 175 8 12 7 12 230 175 8 12 7
RIYADH
PS3 14 305 175 10 15 5 14 305 175 10 15 5

PS4 14 305 175 8 12 3 14 305 175 8 12 3


Drawing Title
PS5 14 330 175 14 21 5 14 330 175 14 21 5
A Approved
PS6 14 330 175 12 18 7 14 330 175 12 18 7

B Approved as Noted

C Resubmitted As Noted
-These drawings must be stamped by Esolution Company
D Disapproved
before construction, and this approval is considered GROUND FLOOR
ineffective without Esolution Company’s stamp REINFORCEMENT PLAN
F No Action Taken
-All levels and dimensions should be coordinated with MASTER PLAN
Signature Date
Hassan Al Mawaldi 20/11/2023 ARCH before the constructions.
This drawing has been reviewed for design and general arrangement only.
-All openings should be coordinated with ARCH & MEP Approved Seal Date

The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings. before the constructions.
Contractor shall indicate on his submittal any deviation, if any, from Designed Drawn Checked
Contract Documents.
M.K M.S M.A
The action indicated shall not vary the Contract Sum.
Scale A1 (594x841) Revision No

1-300 00
Drawing No

ES-PL-FP-GF-RE-M
KEY PLAN

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7 A1 A2 A3 A4 A5


A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
PS3 DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.
BA
2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT / ENGINEERS.
PS3
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
BB SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
PS4
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .
PS3
6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .
FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

BC CONTINUD COLUMN STOP COLUMN PLANTED COLUMN


PS3

PS6
REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

BD
PS3

Location of stair starter is


not matching with Arch.

00 ISSUED FOR COORDINATION 2023-10-19

PS4
BE Revision No. Description Date
Revisions
Client
PS5

Design Consultant (logo)

ARABIANCONSULTINGENGINEERINGSERVICES
RegistrationNo.248
P.O.Box146,Riyadh
-These drawings must be stamped by Esolution Company
Location of stair starter is before construction, and this approval is considered Programme / Programme Management Consultant

A Approved not matching with Arch. ineffective without Esolution Company’s stamp
A12 A12' B Approved as Noted B1' B1 B2 B3 B4 B5 B6 -All levels and dimensions
B7 should be coordinated with
Main Contractor

C Resubmitted As Noted
ARCH before the constructions.
D Disapproved
-All openings should be coordinated with ARCH & MEP
GROUND FLOOR REINFORCEMENT PLAN
01 ( ZOON-01 ) before the constructions.
F No Action Taken Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Signature Date Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Hassan Al Mawaldi 20/11/2023 ROWS
Fax: +966 (11) 201 9859
info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
This drawing has been reviewed for design and general arrangement only. precast & Post tension concrete specialists
The action indicated does not relieve the contractor from responsibility for SETS

full compliance with the Contract Documents and other working drawings. Project Title
Contractor shall indicate on his submittal any deviation, if any, from BANK ALJAZIRA

TYP.
90
Contract Documents.
The action indicated shall not vary the Contract Sum. RIYADH
ROWS

(TYPICAL SPACE OF STIRRUPS PERIMETER) Drawing Title


FOR EDGE COLUMN

S
SETS ROWS

S
S
S
S

TYP.
90
SETS

TYP.
90
GROUND FLOOR
(TYPICAL SPACE OF STIRRUPS PERIMETER)
(TYPICAL SPACE OF STIRRUPS PERIMETER)
REINFORCEMENT PLAN
FOR INTERIOR COLUMN
FOR CORNER COLUMN
A A ( ZOON-01 )
SLAB THK

SLAB THK

PUNCHING REINFORCEMENT SCHEDULE


AS/PLAN

50Ø 50Ø SHORT


LONG DIRECTION
PUNCHING DIRECTION
MARK BAR SPACING NO. OF NO. OF BAR SPACING NO. OF NO. OF Approved Seal Date
SIZE (S) ROWS SETS SIZE (S) ROWS SETS
PS1 12 230 175 10 15 10 12 230 175 10 15 10
AS SHOWN ON PLAN PS2 12 230 175 8 12 7 12 230 175 8 12 7

PS3 14 305 175 10 15 5 14 305 175 10 15 5


Designed Drawn Checked
PS4 14 305 175 8 12 3 14 305 175 8 12 3
M.K M.S M.A
PS5 14 330 175 14 21 5 14 330 175 14 21 5

14
Scale A1 (594x841) Revision No
PS6 330 175 12 18 7 14 330 175 12 18 7

1-125 00
Drawing No

ES-PL-FP-GF-RE-Z1
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

AA AA

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12'


BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING

600
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
PS2 PS2 COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


PS2 PS2 PS2 PS2
FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

ARABIANCONSULTINGENGINEERINGSERVICES
RegistrationNo.248 CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

P.O.Box146,Riyadh

REINFORCEMENT LEGEND:
PS2
A Approved
PS2 PS2 PS2 TOP REINFORCEMENT

BOTTOM REINFORCEMENT
B Approved as Noted

C Resubmitted As Noted

D Disapproved

F No Action Taken

Signature Date
Hassan Al Mawaldi 20/11/2023

This drawing has been reviewed for design and general arrangement only.
The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings.
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents. 00 ISSUED FOR COORDINATION 2023-10-19
The action indicated shall not vary the Contract Sum. Revision No. Description Date
Revisions
Client
600

600

600
-These drawings must be stampedDesign
byConsultant
Esolution (logo)
Company
before construction, and this approval is considered
ineffective without Esolution Company’s stamp
-All levels and dimensions shouldProgramme
be coordinated with
/ Programme Management Consultant
ARCH before the constructions.
-All openings should be coordinated with ARCH & MEP
before the constructions. Main Contractor

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12'

GROUND FLOOR REINFORCEMENT PLAN


01 ( ZOON-02 ) Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
ROWS
Fax: +966 (11) 201 9859
info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists
SETS
Project Title

BANK ALJAZIRA

TYP.
90
RIYADH
ROWS

(TYPICAL SPACE OF STIRRUPS PERIMETER) Drawing Title


FOR EDGE COLUMN

S
SETS ROWS

S
S
S
S

TYP.
90
SETS

TYP.
90
GROUND FLOOR
(TYPICAL SPACE OF STIRRUPS PERIMETER)
(TYPICAL SPACE OF STIRRUPS PERIMETER)
REINFORCEMENT PLAN
FOR INTERIOR COLUMN
FOR CORNER COLUMN
A A ( ZOON-02 )
SLAB THK

SLAB THK

PUNCHING REINFORCEMENT SCHEDULE


AS/PLAN

50Ø 50Ø SHORT


LONG DIRECTION
PUNCHING DIRECTION
MARK BAR SPACING NO. OF NO. OF BAR SPACING NO. OF NO. OF Approved Seal Date
SIZE (S) ROWS SETS SIZE (S) ROWS SETS
PS1 12 230 175 10 15 10 12 230 175 10 15 10
AS SHOWN ON PLAN PS2 12 230 175 8 12 7 12 230 175 8 12 7

PS3 14 305 175 10 15 5 14 305 175 10 15 5


Designed Drawn Checked
PS4 14 305 175 8 12 3 14 305 175 8 12 3
M.K M.S M.A
PS5 14 330 175 14 21 5 14 330 175 14 21 5

PS6 14 330 175 12 18 7 330 175 12 18 7


Scale A1 (594x841) Revision No
14

1-125 00
Drawing No

ES-PL-FP-GF-RE-Z2
KEY PLAN

A1 A2 A3 A4 A5 A5'
A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

600 ARABIANCONSULTINGENGINEERINGSERVICES General Notes


RegistrationNo.248
1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN
P.O.Box146,Riyadh
DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
AA DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
PS2 COMMENCEMENT OF WORKS OR MANUFACTURING OF
A Approved COMPONENT.

B Approved as Noted 2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.
C Resubmitted As Noted
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
D Disapproved ARE IN METERS UNLESS OTHERWISE INDICATED.
PS2
4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB
F No Action Taken LEVELS UNLESS OTHERWISE INDICATED.
Signature Date 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH
Hassan Al Mawaldi 20/11/2023 RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
This drawing has been reviewed for design and general arrangement only. SPECIFICATIONS . THE CONTRACTOR SHALL
The action indicated does not relieve the contractor from responsibility for COORDINATE THESE DRAWINGS AND DOCUMENTS
full compliance with the Contract Documents and other working drawings.
AND REPORT IF ANY DISCREPANCY FOR
Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents. CLARIFICATION BEFORE PROCEEDING WITH THE
The action indicated shall not vary the Contract Sum. WORK INVOLVED .
AB
PS2 6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .
FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:
PS2

CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

AC -These drawings must be stamped by Esolution Company REINFORCEMENT LEGEND:


PS2
before construction, and this approval is considered TOP REINFORCEMENT

ineffective without Esolution Company’s stamp BOTTOM REINFORCEMENT

-All levels and dimensions should be coordinated with


ARCH before the constructions.
-All openings should be coordinated with ARCH & MEP
before the constructions.
PS2

00 ISSUED FOR COORDINATION 2023-10-19


AD Revision No. Description Date
Revisions
Client

600

600
AE

Design Consultant (logo)

Programme / Programme Management Consultant

A1 A2 A3 A4 A5 A5' Main Contractor

GROUND FLOOR REINFORCEMENT PLAN


01 ( ZOON-03 ) Posttension Contractor
Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
ROWS
Fax: +966 (11) 201 9859
info@esolution-pt.com
www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists
SETS

Project Title

BANK ALJAZIRA

TYP.
90
RIYADH
ROWS

(TYPICAL SPACE OF STIRRUPS PERIMETER) Drawing Title


FOR EDGE COLUMN

S
SETS ROWS

S
S
S
S

TYP.
90
SETS

TYP.
90
GROUND FLOOR
(TYPICAL SPACE OF STIRRUPS PERIMETER)
(TYPICAL SPACE OF STIRRUPS PERIMETER)
REINFORCEMENT PLAN
FOR INTERIOR COLUMN
FOR CORNER COLUMN
A A ( ZOON-03 )
SLAB THK

SLAB THK

PUNCHING REINFORCEMENT SCHEDULE


AS/PLAN

50Ø 50Ø SHORT


LONG DIRECTION
PUNCHING DIRECTION
MARK BAR SPACING NO. OF NO. OF BAR SPACING NO. OF NO. OF Approved Seal Date
SIZE (S) ROWS SETS SIZE (S) ROWS SETS
PS1 12 230 175 10 15 10 12 230 175 10 15 10
AS SHOWN ON PLAN PS2 12 230 175 8 12 7 12 230 175 8 12 7

PS3 14 305 175 10 15 5 14 305 175 10 15 5


Designed Drawn Checked
PS4 14 305 175 8 12 3 14 305 175 8 12 3
M.K M.S M.A
PS5 14 330 175 14 21 5 14 330 175 14 21 5

14
Scale A1 (594x841) Revision No
PS6 330 175 12 18 7 14 330 175 12 18 7

1-125 00
Drawing No

ES-PL-FP-GF-RE-Z3
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.
A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


600
RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &

600
AA
SPECIFICATIONS . THE CONTRACTOR SHALL
BA COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


BB FOOTINGS .

AB 7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:
BC
AC CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:
BD
TOP REINFORCEMENT

BOTTOM REINFORCEMENT

AD
BE
600

600

600

600
AE

A1 A2 A3 A4 A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' B1' B1 B2 B3 B4 B5 B6 B7

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
Revisions
Client

Design Consultant (logo)


GROUND FLOOR VERTICAL TENDONS LAYOUT
01 MASTER PLAN

Programme / Programme Management Consultant

ARABIAN CONSULTING ENGINEERING SERVICES


RegistrationNo.248
Main Contractor
P.O.Box146,Riyadh

A Approved Posttension Contractor


Bahrain Tower,
King Fahed St , Olaia,
*℄ Riyadh , Saudi Arabia

B Approved as Noted Tel: +966 (11) 201 9858


Fax: +966 (11) 201 9859
info@esolution-pt.com
℄ www.esolution-pt.com
esolution construction & Engineering

C Resubmitted As Noted precast & Post tension concrete specialists

Project Title

BANK ALJAZIRA
D Disapproved
RIYADH
-These drawings must be stamped by Esolution Company F No Action Taken
Drawing Title

before construction, and this approval is considered


ineffective without Esolution Company’s stamp Signature Date
Hassan Al Mawaldi 20/11/2023
-All levels and dimensions should be coordinated with
GROUND FLOOR
ARCH before the constructions. This drawing has been reviewed for design and general arrangement only.
VERTICAL TENDONS LAYOUT
-All openings should be coordinated with ARCH & MEP The action indicated does not relieve the contractor from responsibility for
full compliance with the Contract Documents and other working drawings. MASTER PLAN
before the constructions. Contractor shall indicate on his submittal any deviation, if any, from
Contract Documents.
The action indicated shall not vary the Contract Sum. Approved Seal Date

Designed Drawn Checked

M.K M.S M.A


Scale A1 (594x841) Revision No

1-300 00
Drawing No

ES-PL-FP-GF-VR-M
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS


ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

BA 5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.
BB
COLUMN LEGEND:

CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

BC

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
BD Revisions
Client

Design Consultant (logo)

BE

Programme / Programme Management Consultant

Main Contractor

ARABIAN CONSULTING ENGINEERING SERVICES


Posttension Contractor
RegistrationNo.248 Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
P.O.Box146,Riyadh Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A12 A12' B1' B1 B2 B3 B4 B5 B6 B7 info@esolution-pt.com


www.esolution-pt.com
esolution construction & Engineering
precast & Post tension concrete specialists

Project Title
A Approved
BANK ALJAZIRA
RIYADH
B Approved as Noted
Drawing Title

GROUND FLOOR VERTICAL TENDONS LAYOUT C Resubmitted As Noted


01 ( ZOON-01 )
D Disapproved
-These drawings must be stamped by Esolution Company
*℄
GROUND FLOOR
before construction, and this approval is considered F No Action Taken
℄ VERTICAL TENDONS LAYOUT
ineffective without Esolution Company’s stamp ( ZOON-01 )
-All levels and dimensions should be coordinated with Signature Date
Hassan Al Mawaldi 20/11/2023
ARCH before the constructions. Approved Seal Date
-All openings should be coordinated with ARCH & MEP This drawing has been reviewed for design and general arrangement only.
before the constructions. The action indicated does not relieve the contractor from responsibility for Designed Drawn Checked
full compliance with the Contract Documents and other working drawings.
M.K M.S M.A
Contractor shall indicate on his submittal any deviation, if any, from
Scale A1 (594x841) Revision No
Contract Documents.
The action indicated shall not vary the Contract Sum. 1-125 00
Drawing No

ES-PL-FP-GF-VR-Z1
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'
B1 B2 B3 B4 B5 B6 B7

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12'


General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.

3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS

600
ARE IN METERS UNLESS OTHERWISE INDICATED.

4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
Revisions
Client

Design Consultant (logo)


600

600

600
Programme / Programme Management Consultant

Main Contractor

Posttension Contractor
Bahrain Tower,
ARABIAN CONSULTING ENGINEERING SERVICES King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
RegistrationNo.248 Fax: +966 (11) 201 9859

A5 A5' A6 A7 A8 A9 A9' A10 A11 A12 A12' info@esolution-pt.com


www.esolution-pt.com
P.O.Box146,Riyadh esolution construction & Engineering
precast & Post tension concrete specialists

Project Title

BANK ALJAZIRA
A Approved RIYADH
Drawing Title

GROUND FLOOR VERTICAL TENDONS LAYOUT B Approved as Noted


01 ( ZOON-02 )
C Resubmitted As Noted

Disapproved
GROUND FLOOR
D
*℄ -These drawings must be stamped by Esolution Company VERTICAL TENDONS LAYOUT

before construction, and this approval is considered F No Action Taken ( ZOON-02 )
ineffective without Esolution Company’s stamp
Signature Date
-All levels and dimensions should be coordinated with Hassan Al Mawaldi 20/11/2023
Approved Seal Date

ARCH before the constructions.


Designed Drawn Checked
-All openings should be coordinated with ARCH & MEP This drawing has been reviewed for design and general arrangement only.
M.K M.S M.A
The action indicated does not relieve the contractor from responsibility for
before the constructions. full compliance with the Contract Documents and other working drawings.
Scale A1 (594x841) Revision No

Contractor shall indicate on his submittal any deviation, if any, from 1-125 00
Contract Documents. Drawing No

The action indicated shall not vary the Contract Sum. ES-PL-FP-GF-VR-Z2
KEY PLAN

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

AA AA

BA BA

DN
UP

BB BB

ZONE 1
AB AB

AC
ZONE 3 ZONE 2 BC
AC
BC

BD BD

BE
AD AD BE
AE AE

A1 A2 A3 A4 A5
A5' A6 A7 A8 A9
A9' A10 A11 A12
A12' B1'B1 B2 B3 B4 B5 B6 B7

A1 A2 A3 A4 A5 A5'
General Notes

1- DO NOT SCALE FROM THIS DRAWING ONLY WRITTEN


DIMENSIONS SHOULD BE FOLLOWED . ALL EXISTING
DIMENSIONS TO BE CHECKED AT SITE PRIOR TO
COMMENCEMENT OF WORKS OR MANUFACTURING OF
COMPONENT.

2- ANY DISCREPANCIES , IF ANY TO BE BROUGHT TO THE


ATTENTION OF THE ARCHITECT / ENGINEERS.
600
3- ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
ARE IN METERS UNLESS OTHERWISE INDICATED.

AA 4- ALL LEVELS INDICATED ARE STRUCTURAL SLAB


LEVELS UNLESS OTHERWISE INDICATED.

5- THIS DRAWING TO BE READ IN CONJUNCTION WITH


RELEVANT STRUCTURAL , ARCHITECTURAL ,
MECHANICAL & ELECTRICAL DRAWINGS , DETAILS &
SPECIFICATIONS . THE CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND DOCUMENTS
AND REPORT IF ANY DISCREPANCY FOR
CLARIFICATION BEFORE PROCEEDING WITH THE
WORK INVOLVED .

6- FOUNDATION LEVEL ( BOTTOM LEVEL OF RC .


FOOTINGS .

7- DESIGN FOUNDATION IS BASED ON ASSUMED NET


BEARING CAPACITY AS PER SOIL REPORT.

COLUMN LEGEND:

AB CONTINUD COLUMN STOP COLUMN PLANTED COLUMN

REINFORCEMENT LEGEND:

TOP REINFORCEMENT

BOTTOM REINFORCEMENT

AC

00 ISSUED FOR COORDINATION 2023-10-19


Revision No. Description Date
Revisions
Client

ARABIAN CONSULTING ENGINEERING SERVICES


RegistrationNo.248
Design Consultant (logo)

AD P.O.Box146,Riyadh

600

600
AE A Approved Programme / Programme Management Consultant

B Approved as Noted

Main Contractor
C Resubmitted As Noted

D Disapproved
Posttension Contractor
F No Action Taken Bahrain Tower,
King Fahed St , Olaia,
Riyadh , Saudi Arabia
Tel: +966 (11) 201 9858
Fax: +966 (11) 201 9859

A1 A2 A3 A4 A5 A5' Signature Date info@esolution-pt.com


www.esolution-pt.com

Hassan Al Mawaldi 20/11/2023 esolution construction & Engineering


precast & Post tension concrete specialists

Project Title

This drawing has been reviewed for design and general arrangement only. BANK ALJAZIRA
The action indicated does not relieve the contractor from responsibility for RIYADH
full compliance with the Contract Documents and other working drawings. Drawing Title
Contractor shall indicate on his submittal any deviation, if any, from
GROUND FLOOR VERTICAL TENDONS LAYOUT Contract Documents.
( ZOON-03 ) The action indicated shall not vary the Contract Sum.
01

*℄ GROUND FLOOR

-These drawings must be stamped by Esolution Company VERTICAL TENDONS LAYOUT
before construction, and this approval is considered ( ZOON-03 )
ineffective without Esolution Company’s stamp
-All levels and dimensions should be coordinated with Approved Seal Date

ARCH before the constructions.


-All openings should be coordinated with ARCH & MEP Designed Drawn Checked

M.K M.S M.A


before the constructions. Scale A1 (594x841) Revision No

1-125 00
Drawing No

ES-PL-FP-GF-VR-Z3