HIMACHAL PRADESH STATE ELECTRICITY BOARD LIMITED
(A State Government Undertaking)
Regd. Office :Vidyut Bhawan, HPSEBL, Shimla-171004 (H.P)
CIN U40109HP2009SGC031255
GST No. :HPSEBL 02AACCH4894EHZB
Telephone Number: 01972-221469 (Office), 221469 (FAX)
Website Address :www.hpseb.in
Email sedeshmr@hpseb.in &sedeshmr@gmail.com
No. HPSEBL/SEDES/SSD-478/KEL/2021-22- 0191-9S Dated:- 2C|o3 |20-
To
M/S Kanohar Electricals Ltd.,
Rithani, Delhi Road, Meerut (U.P.)-250103
E-mail-info@kanohar.com
Subject Design, Engineering, Manufacturing, Testing of Equipment, Delivery, Storage at Site,
Erection along with other Allied Works & Civil Works, Testing & Commissioning of
equipment at site on Turn Key Basis for Construction of 66/11 kV, 2x6.3 MVA Sub
Station Bithal (Chharota) By LILOing 66 kV S/C Nogli-Kumarsain Line at Bithal,
District Shimla (Himachal Pradesh)" against Tender Specification No. SSD-478/2021
- Approval of Cable Trench Layout, EKD & DSLP Plan thereof.

Reference: Your office letter No. KEL/EPC-034/Bithal-102/Elec./211 dated 16.03.2022.

Dear Sir,
This has reference to your office letter referred above, vide which the Cable Trench
Layout, Erection Key Diagram and Direct Stroke Lighting Protection Plan have been submitted for
approval. The drawings have been checked as per the tender specifications and relevant IS &
approved with as tabulated below

S. No Description Remarks
1 Erection Key Diagram Approved.
Note: The additional quantity of clamp &
connectors, if required shall be supplied
free of cost.
2 Cable Trench Layout | Approved.
(Outdoor & Indoor) Note: The channels of adequate capacity
shall be provided belowindoor panels.
3 Direct Stroke Lighting Approved.
Protection Plan &
Calculations
One set of approved drawings is enclosed herewith for your reference. Mere
approval of drawing shall not relieve the fim from discharging any obligations under the Contract.
Any discrepancy, error or omission that is found at later stage shall be rectified free of cost by your
firm.
Yours sincerely,

DA: As above. ronen


(Er. K.K. Bhardwaj),
Superintending Engineer (Design),
ES, HPSEBL, Hamirpur-177001
E-mail- sedeshmr@gmail.com
and
Copy of above a/w approved dráwings is forwarded to the following for information
necessary action please:
1. The Chief Engineer, Electrical System, HPSEBL, Hamirpur-177001.
-171011.
2. The Superintending Engineer, Electrical System Circle, HPSEBL, Shimla
3. The Additional Superintending Engineer (Civil) of this office.
Kotla (Jeori)-172101.
4. The Sr. Executive Engineer, Electrical System Division, HPSEBL,

Superintending Engineer (Design),


ES, HPSEBL, Hamirpur-177001
10
TO RTHMAT
EL/EPCO34/PE/E/DSLP/DRG/1006
10015-
ROD ELECTRODE

EHT OF xom FROM

soxten GI FLAT (TYP)


sOMmm GI FLAT

ROO ELECTRODE
TO EARIH

R177888 cONTROL ROOM BUILDINGLIGHTNING PROTECTION PLAN

50xBmm GlAT OI

R10950 CED ED
EHT OF m OMLa
R21450 5xbrum Gl ELAT(YPL

K7888

RODELEC RODELECTRODE
2on TREATED P
(TREATEDPITm
TO EARTTHMAT OARTHMAT
cONTROL ROOM BUILDINGLIGHTNING,PROTECTION ELEVATION

LEGENDS:

66*y/224v/1kY roWER TH PEAK

REFERENCE
1) ELECTRICAL LArUT PLAN, DRG NO: KEL/EPcO34/PE/E/ELPs/pRG/1002, REv-01
17888 (uGHTNING GM UGHTING MAST)
R21450 ) DSLP CALOULATION, DOC Na KEL/EPCO34/PE/E/DSP /DoC/1006A, REV-o

7/3.15MM GS EARTHIREE

a Bus Heg
wG

Egupmert Bn Hegt,

o 7sh=14475

so00200 000 1.5h-28950

1S25960

SECTION B-

FIRST SUBMISSIONN SKR DG. SRP. 16.03.2022


SE
REV. DESCRIPTION REP. CHKD.
DESCRIPTION
APPD. E

NOTE: HIMACHAL PRADESH STATE ELECTRICITY BOARD LTD.|


1) ALL DIMENSIONS ARE IN mm UNLESS oTHERISE SPECIFIED. CUSTOMER
ZONE-1 iGHT OF OBECT TO BE PROTECTED4300mm FROM FGL UOHTNINGOECON OF SUBSTANON SHALL BE FOLLOWED AS PER RAZEVIG METHOD. KANOHAR ELECTRICALS LTD.
FROM 17300mm (PLINTH+ TOWER+PEAK+S*IKE) HEG PEx OwEN ANSFORMER BAY De E Z ELDER,2/Y 1ANSFORMER BAY,
Approved cONTRACTORKANOHAR EPC DIVISION
(66kv LINE SIDE & 66/11kV TRANSFORMER SIDE EQUIPMENTS, ie. LA,CVI, TRANSTORMEK OI NO.
) 66kV UNE SIDE&RANSFORMER SDE EQUIPMENTS & 11kV UNE SIDE BPI CUM CABLE HPSEBL/SEDES/SsD-478(LOI)/2021-22-7972-79, DATED 29/12/2021
SUPPON e r D BY PEAK TOwER

ME SUNDER JACK BUS ARE PROTECTED BY 7/3.15MM GS


DESIGN ENGINEERING. MANUFACTURING, TESTING OF EQUIPMENT, DELIVERY.STORAGE AT
T NTHeLN+SPIKE) HEIGHT M. PROJECT G O N ALONG W E VL STDT
zONE T O F O8ECTTO BEPROECTED 2300mm FROM FGL 5). 11kV UNE MOUN TED LA's ARE PROTECTED BY 7/3.15MM GS EARTHMRE.
BECIESE ER. LT TRANSFORMER, DG SET ETC.) 66/11 Kv, 2x6.3 MVA SUB STATIONBITHAL (CHHAROTA) BY LILOing 66 V S/C
0. CONTROL ROOM B I N G LGHINING PROTECnON. SHMLA (HIMACHAL PRADESH)" AGANST
EPROIE .
0OkV JACK BUS&EOUPMENT
.
UNDER
eu e
JACK BUS
TENDER SPECIFICATN C s 78
IN ERECTIoN KEY DIAGRAM ORAWNG. 50x6MM GI FLAT QUANTY FOR BUILDING EARTHING
SHAL BE SBMIEDIN EARTHMAT LAYOUT DRAMNG. SUBSTATION 66/11kV, 2x6.3MVA SUB-STATION AT CHHAROTA (BITHAL)
HEGHT OF OBJECT TO BE PROTECTED= 9600 mm FROM FL
HUGHT LM, RG. TITLE LAYOUT PLAN& SECTION
N D KE)
. NO. pcO34 /E
(22*Y UNE SDE LA & ) . KEL/EPCO34/PE/E/0SLP/DRG/1006
SCALE JOB NO. SHEET 01 0F 01
CUSTOMER
HIMACHAL PRADESH STATE ELECTRICITYY
BOARDLTD.

PROJECT

DESIGN, ENGINEERING, MANUFACTURING, TESTING OF EQUIPMENT, DELIVERY,


STORAGE AT SITE, ERECTION ALONG WITH OTHER ALLIED WORKS & CIVIL WORKS,
TESTING & COMMISSIONING OF EQUIPMENT AT SITE ON TURN KEY BASIS FOR
CONSTRUCTION OF 66/11 KV, 2x6.3 MVA SUB - STATION BITHAL (CHHAROTA) BY
LILOing 66 kV S/C NoGLI-KUMARSAIN LINE AT BITHAL, DISTRICT SHIMILA (HIMACHAL
PRADESH" AGAINST TENDER SPECIFICATION NO. SD-478/2021.

NOA NO.
HPSEBL/SEDES/SSD-478(LON/2021-22-7972-79, DATED 29/12/2021

TITLE

Direct Stoke Lightning Protection Calculation

KANOHAR ELECTRICALS LIMITED


EPC DIVISION
KANOHAR F-395, SECTOR -63, NOIDA - 201301

REV. No. DESCRIPTION APPRD DATE DATE


PREPARED DG
16.03.2022

NO. OF
CHECKED SRP SHEETS
3

First Submission SRP 16-03-2022 REV. No.


APPROVED SRP
0
DOC. No. KEL/EPC034/PE/E/DSLP/DOC/1006A
DSLP CALCULATION FOR 66/11v,2x6.3MVASUB-STATION AT CHHAROTA(BITHAL)
DESIGN PHILOSOPHY FOR DIRECT STROKELIGHTNING PROTECTION
Single LightningMast
The radius of protection zone offered by a Lightning Mast with tip 'a' at height 'h' from the
be obtained with geometrical construction as shown in figure 1.0.
ground level, can

FIG-1

a h _

CROS S SECTION OF THE


PROTECTIVE zONE A T A HIGHT 'hx'.

The radius of protective zone, offered by an LM at height 'hx' from ground level, is 'Rx.
Geometrically it can be seen that,
forhy< 2/3 h -(1)
R 1.5 h1h
0.8h

and Rx
0.75h
The above mentioned criteria is applicablewhere h < 30m. Ifh> 30 m, then-
for h,> 2/3 h (2)

1.5h1h
0.8h h
for hy 2/3h (3)

and
0.75h 5 for h> 2/3 h -(4)

Lightning Protectionby RollingSphere for ParallelShieldWires Mathod


The cross section of the protective zone on a plane perpendicular to the ground wire is constructed
in the same way as for a lightning mast with the only difference that breadth of the zone at the
ground plane for a ground wire suspended at a height h « 30m equals 1.2h.
Half the breadth of the protective zone at a level hx > (2/3)h is determined as:

bx = 0.6h (1 hx /h) -(5)


At a level hx< (2/3)h, half the breadth ofthe protective zone is:
bx 1.2h ( 1 - hx /0.8h) -(6)
Internal Protection of two shield wires
If the distance between two ground wires S<4h the point situated midway between the ground wires
at a level of
h0 = h-(S/4) -(7)
will be protected from lightning strokes.

Approved

AEE/AE (ASEDesign)ES

KEUEPCO34/PEJE/DSLP/DOC/1006A
DIRECT STROKE LIGHTNING PROTECTION CALCULATION BY LIGHTNING MASSI
s6/11KV.2x6.3MVASUB-STATION ATCHHAROTA (BITHALL
Single Liahtning Mast Method:
Calculation for 66/22/11kV Switchyard Area: (Tower/LM Helaht above FGL+Spike) Mdway point Midway pont
Helght of LM Height of Live Tower Active above
Htof Tower Reference Co- efflclent Distar Protectlve radlus
prot ht.
prot Dlstistance
SILNo above FGL Part above FGL between Towers
FGL
Spike (Meters) (Meters)
(Meters) (Meters) (Meters)
(Meters) (Meters)
(P) (s) () (ho) (rox)
(hx) (ha)
(h) Protection Zone-1
66kV LAICVT Height Level (4.3Mtrs from FGL)
-

Peak Tower with 17.888


17.300 4.300 13.00
Spike
Protection Zone-2
I 22kV & 11kV Equipment Height Level (4Mtrs from FGL)-
LM 21.450
19.300 4.000 15.30
from FGL)- Protection Zone-3
22kV Feeder Bay Gantry Mounted LA Height Level (9.6Mtrs
LM 10.950
19.300 9.600 9.70

Approved

SE(Design)ES
EE/AE xen

KELEPCO34/PE/E/DSLP/DOC/1006A
66/11kV 2x6.3MVA SUB.STATION AT CHHAROTA(BTHALL
Lightning Protection byRelllng Sphere for ParallelShield Wires Method
A.
66kVFeeder,Buscoupler &Transformer Bay areaUnderJackBus
Height of Ground wire tied at top of Towers (h) 16.3 m

from Ground Level))

Distance between two Ground wire (S) 12 m

Maximum height below which all equipments will be protected


by Ground wire (Ho) h-S/4
13.3 m

Height to be protected (66KV Jack Bus Height) 12.3 m

The Zone of Protection is bounded by an are of a circle passingthrough three points namely HO =13.3m
and other two at a point where two ground wires are tied with Terminal Gantry Towers

Conclusion
66kV Jack Bus is protected by the Shleld Wire.
AccordinglyAll the live parts under the Jack Bus Area are protected by the Shleld Wire

B. 11k Feeder Bay Gantry mounted ILA


Height of Ground wire tied at top of Towers (h) 10.8 m
(from Ground Level)

Distance between two Ground wire (S) 4.5 m

Maximum height below which all equipments will be protected


by Ground wire (Ho) h-S/4
9.675 m

Height to be protected (11kV Gantry Mounted LA Height) 9.3 m

The Zone of Protection is bounded by an arc of a circle passing through three points namely H0 =9.675 m
and other two at a point where two ground wires are tied with Terminal Gantry Towers

Conclusion

11kV Feeder Bay GantryMounted LAis protected by the Shield Wire.

Approved
so
AEE/AE XepSE(Design)ES

KELIEPCO34/PE/E/DSLP/DOC/1006A