IT S811 Soft Starter, N and R - Instructions
IT S811 Soft Starter, N and R - Instructions
IT S811 Soft Starter, N and R - Instructions
50785
4. For 2-wire control, jumper P and Input 1 together. Table 3: Control Wiring
5. After an Overload Trip, the S811 Soft Starter cannot be Number of Torque
Wire Size Conductors Req.
restarted until the prescribed cool-down time
has elapsed. Cycling power does not reset the timer. 22 – 14 AWG (0.33 – 2.5 mm2) 2 3.5 Lb-in
(0.4 N•m)
If 24V DC power is removed, the soft starter will remember 12 AWG (4.0 mm2) 1
the remaining time and will resume the cool-down timing Table 4: Short Circuit Ratings
when power is again reapplied.
Three-Phase Short Circuit Rating
Soft Starter
6. When the S811 goes into bypass, a sound similar to Frame Size 240V 480V 600V
contactor chatter can be heard. This sound is the result of
multiple contactors closing one after the other in a very N 10 kA 10 kA 10 kA
short period. It is normal operation intended to reduce the R 10 kA 10 kA 10 kA
surge current requirements of your power supply.
Table 5: MOV Kit Options
Catalog
Initial Configuration Number Description
1. Before applying the Line voltage, apply 24V DC to the EMS38 600V (max) MOV for S811N and S811R Soft Start (side mounted)
+ and - connections of the S811’s terminal block. “ Eaton
Cutler-Hammer” will be displayed by the DIM while the Table 6: 24V Power Supply Kits
S811 is powering up. When power-up is complete the DIM Catalog Steady State Inrush Input
Number Wattage Wattage Voltage
should be displaying “3 ø Line Currents”.
PSS55A 55W 250W 115V AC
2. Using the DIM, review the parameter settings in the PSS55B 55W 250W 230V AC
“Configuration” and “Protections” menus. The following PSS55C 55W 250W 360 – 480V AC
setup procedures will use the factory default settings Table 7: Control Circuit Fuseholder Kit
unless changed by you. Catalog
3. In the Configuration menu set the Overld Trip FLA Number Fuse Type
parameter to the motor’s nameplate rated current. This C320FBR Class CC
setting assumes the motor has a 1.15 Service Factor.
4. Set Ovrld Trip Class parameter for the desired overload trip
characteristic (curve).