VARIABLE FREQUENCY STARTER
www.rxpe.com
VFS VARIABLE FREQUENCY STARTER
Rong xin
Rongxin Power Electronic Corp., Ltd. RXPE has manufactured many high-power
Power
(Shorted for RXPE) is a high-tech
enterprise specialized in R&D, designing,
equipments with voltage classes of 380V,
660V, 1140V, 3kV, 6kV, 10kV, 27.5kV and
Electronic
engineering and manufacturing of HV
power electronic equipment
35kV. The total installed capacity is over
3,000,000KVA. Products of RXPE have
Co.,Ltd .
(www.rxpe.com). been widely used in over 200 steel and
RXPE is the first public company in power metallurgy enterprises, over 200 coal mines,
electronic industry in China. (Rongxin dozens of power substations, industrial
Shares for short, Stock code 002123) substations and electric-railway traction
RXPE is located in Anshan Economic substations. Products of RXPE are used for
Development Zone, the floor area is 60000 power transmission and distribution, electric
㎡, and the building areas is 35000㎡. drive, control optimization, and energy
RXPE possesses the modern office conservation.
building, standard plant, production line, RXPE has become the leader in the power
66kV substation, full-load testing center for and electronic industry in China and
HV frequency converter and soft starter, cooperate with famous institutions & electric
HV full-load test center for SVC, and etc.. co operations worldwide is willing to offer
RXPE passes the certification of ISO9001, better products and hope to benefit more to
the quality of the product can satisfy the the economic of the World
requirements of international standards.
VFS VARIABLE FREQUENCY STARTER
Characteristic of VFS
VFS (Variable Frequency Starter) adopts the patent of RXPE, which realize
the step frequency conversion and stepless voltage regulation through the
control to the thyrister. It can output 12.5 Hz, 25Hz and 50Hz frequencies, and
through controlling the voltage/ frequency ratio to realize small starting current
and big starting torque characteristics. At the same time, it can realize voltage
slope starting, constant current starting, soft stop, brake stop and other
start/stop controlling method. This technology is newly developed, and
become one of the best motor starting technologies in the world.
◆ With small Starting current and big starting torque; through adopting the frequency
conversion function, the starting current could be controlled within acceptable current
with the starting effort of 80-90% the rated torque.
◆ A more flexible starting mode; we could select different starting frequency
combination according to the on-spot loading and grid condition, and realize voltage
slope starting and current limit starting under different starting frequencies.
◆ A more available motor starting control: could realize starting both of forward and
reverse directions, with free stop, soft stop and brake stop and other stop methods
optional.
VARIABLE FREQUENCY STARTER
Characteristic of VFS
◆ With adjustable Starting time and starting torque; starting time and torque could
be adjusted according to the on-spot requirement.
◆ With full motor protection
◆ Adopting digital control mode, with MODBUS, PROFIBUS and RS 485
communication interface
◆ centrifuge
◆ mixer
◆ compressor(e.g. screw type, plunger type,
centrifugal type and turbo type, etc.)
◆ cold compressor
◆ HVAC system
◆ pulverizer
◆ conveyor
◆ main power plant
◆ propeller
◆ anchorage winch
◆ bilge pump
VFS VARIABLE FREQUENCY STARTER
Two step VFS: through the control of the thyrister’s firing angle to control the
output voltage and output frequency, thus the output frequency could be
12.5Hz or 50Hz. via change the motor voltage/ frequency ratio, to obtain the
starting current and starting torque an optimum adjustment.
Besides, VFS offers a soft stop function. It simulates the motor starting process,
and the working voltage will smoothly reduce. In this way, it could avoid the
driving sudden stop which will benefit the water pump driving( avoiding the
water hammer effect) or the conveyor belt. VFS offers step stop function. Three
step VFS the frequency changes: 50Hz—25Hz— 12.5Hz (two step VFS
frequency changes only 50 Hz— 12.5Hz). The motor voltage accordingly
reduced, with a good brake character, and realize fleetly stop.
VARIABLE FREQUENCY STARTER
◆ To determine the initial starting torque of the motor (the torque is proportional to the
square of the voltage). Setting range: 10-50%Vr. (could be expanded to 80%Vr.)
◆ This adjustment also determines the surge current and the mechanical shock. If the
setting is too high, it will cause a high initial mechanical shock and high surge
current( even if the current limit is very low, the initial voltage setting override the
current limit setting)
Current limit
◆ To determine the motor highest current during starting. Setting range 100
400% of nominal current Ir (could be expanded to 500% Ir).
◆ If the setting is too high, that will causes greater current drawn from the busbar
and faster acceleration. While if too low may prevent the motor from completing
the starting process and reaching the full speed.
◆ Current limit is not operating during Run and soft stop.
Acceleration time
◆ To determine the motor voltage ramp-up time
from initial to full voltage.
◆ Setting range 1-30 sec. (could be expand
to90 sec.)
◆ It is recommended to set acceleration time to the
minimum acceptable value (about 5sec)
Note :
◆ Since current limit overides acceleration time,
when current limit is set low, starting time will be
longer than the preset acceleration time.
◆ If motor reach full speed before voltage reach
nominal voltage, acceleration time setting is
overridden and cause the voltage to ramp-up quickly
to nominal.
VARIABLE FREQUENCY STARTER
VFS follows IP32 standard to install and operate its cubical unit, the design of which is
suitable to harsh conditions. The whole system includes:
◆ Digital VFS controller
◆ High power sector, bypass contactor
◆ Low voltage controller
Using site bus PROFIBUS, MODBUS and RS485 to realize:
◆ Remote control ( start, stop etc.)
◆ Remote supervision
VFS VARIABLE FREQUENCY STARTER
Operating Panel
VFS operating panel is very convenient, which offers an immediate and continuously
supervision. It owns an eligible menu with easy maintainace function. All the key data are set
before ex-works. The users could set a proper parameters due to their own requirement
easily.
Rong xin
Power
Electronic
Co.,Ltd.
VFS Medium/low
power type
工作原理
Ambient temperature 1. 0-40℃, max. 60℃, when above 40℃, capacity reducing 10% every 5℃
1.during operation 2. -10℃ -- +50℃
2.during transmission 3. -25℃--+70℃
3.storage
Altitude Max. 1000 m, when above 1000 m, VFS capacity
reduction appears refer to curves below
Max. humidity 95%, no condensation
VFS VARIABLE FREQUENCY STARTER
Selection manual
VARIABLE FREQUENCY STARTER
Note:
1. The difference between I type and II type are the starting torques, we
recommend to select II type for start heavy loading.
2. The nominal currents in the table are the rated current of motor to be
started.
3. Please consult us upon special request.
4. 6kV equals 6.6kV; 10kV equals 11kV in the table.