Professional Documents
Culture Documents
Project Name & Address: Drawing Title: Client: Consultant: Checked By: Approved By: Prepared by
Project Name & Address: Drawing Title: Client: Consultant: Checked By: Approved By: Prepared by
Project Name & Address: Drawing Title: Client: Consultant: Checked By: Approved By: Prepared by
18"
18"
18"
6"
6"
6"
6"
12" 12" 12" 12"
11'-6"
INSPECTION ROOM JACQUARD SECTION JACQUARD SECTION WASHING ZONE
Floor Level
Section of X-X
SINGLE STORIED
BOILER BUILDING
6"
ETP OM L1:OM:81 12"
18"
L1:MPS:77
P
11'-3"
13'-0"
11'-6" 22'-7" 11'-6"
F BOILER ROOM
S
L1:HD:78
P F F
Control room L1:HD:80 L1:HD:79
L1:MCP:82
SECTION-A-A'
Y
OM For Ex-Fan Washing
FEMALE TOILET Sym Description
Section of Y-Y
Floor Level
OM For Fire Door.
L1:IM:87
L1:IM:86
L1:MD:76 Smoke Detector
L1:IM:72
L1:IM:71
L1:MPS:83
IM IM L1:MD:75
UP Toilet Toilet P Multi Detector
11'-6" STAIR-3 IM IM
11'-1"
JACQUARD SECTION
"
'-3 '
14
P 15 15
'-6
"
L1:SD:88 NAC1:HS:05 L1:MD:74
DEVICE INSTALLATION BASED ON NFPA 72.
S
S
P OM P P P P P P P · ALL FIRE ALARM MANUAL STATIONS SHALL BE MOUNTED NOT
L1:MD:65 L1:SD:67 L1:SD:68 L1:SD:69 L1:SD:70 L1:SD:73 LESS THAN 1.10 METERS & NOT MORE THAN 1.40 METERS FROM
Toilet
L1:SD:66
MALE TOILET
10'-3"
L1:MPS:85 L1:OM:84
THE FINISH FLOOR WITH REFERENCE TO THE BOTTOM OF
THE EQUIPMENT.
P · FIRE ALARM CONTROL PANEL SHALL BE MOUNTED NOT LESS
L1:SD:89 THAN 1.40 METERS FROM THE BOTTOM TO FINISHED FLOOR LEVEL.
· ALL FIRE ALARM CABLES SHALL BE FPLR TYPE.
12"
18" 2 X1C X 1.5mm2 FIRE ALARM DETECTORS,
MANUAL STATIONS, MODULE.
6"
15 2 X 1C X 2.5mm2 - POWER CABLE FOR 24V DC POWER.
10'-2"
'-1 · ALL AUDIO & VISUAL FIRE ALARM DEVICES SHALL BE
0" MOUNTED NOT LESS THAN 2.40 METERS ABOVE THE FINISH FLOOR
LINE & OR WITH A MINIMUM CLEARANCE OF 0.30 METERS BELOW
CEILING LINE.
P P P P P P P P
L1:SD:90 L1:SD:64 L1:SD:63 L1:SD:62 L1:SD:61 L1:SD:60 L1:SD:59 L1:SD:58 L1:MD:57 1. All Fire Panel,Detector,I/O Module,MPS,
10'-2"
Sounder Are UL Listed.
Washing
2. All Cable Are Fire Resistance Cable.
JACQUARD SECTION 3. Loop Circuit Wire Size 2X1.5 rm
11'-6" DISTRIBUTION JACQUARD SECTION 4. NAC Circuit Wire Size 2X2.5rm
5.Exhaust Fan & Lift Are Interfaced With O/M Module.
ROOM 6. All Sounder Circuit IN Build On NAC.
P
10'-5"
JACQUARD SECTION
L1:SD:54
11'-7" 10'-5" 10'-10" 10'-7" 10'-6" 10'-10" 10'-8" 10'-6" 11'-1" 10'-5" 10'-7" 10'-9" 10'-9" 10'-11"
L1:SD:01 L1:HD:02 L1:OM:03
P P P P P P P Chmical room Serial no Serial no Serial no
L1:SD:91 L1:SD:48 L1:SD:49 L1:SD:50 L1:SD:51 L1:SD:52 L1:SD:53 11'-1" 11'-3" Smoke Detector Heat Detector Output Module
10'-1"
L1:MD:55 L1:MD:56 L1:MPS:04 L1:MD:05 L1:IM:06
Serial no Serial no Serial no
6"
10'-2"
INSPECTION NAC1:HS:04
ROOM
X
P P P P P P P
X
L1:SD:92 L1:SD:44 L1:SD:42 L1:SD:41
L1:SD:46 L1:SD:45 L1:SD:43 L1:MD:40
LEGEND
10'-8"
L1:MPS:47
SL NO.SYMBOLSYMBOL DESCRIPTION QTY
ALL EXHAUST FAN INTERFACE WITH FIRE DOOR OUT PUT MODULE
11'-6" P
WASHING
Fire Alarm Control Panel
ZONE
01 FACP 01 Nos
4 Loop Addressable.
JACQUARD SECTION
9'-11"
NAC1:HS:02
02 RPTR Fire Alarm Repeater Panel 01 Nos
L1:SD:93
11'-7" 10'-5" 10'-10" 10'-7" 10'-6" 10'-10" 10'-8" 10'-6" 11'-1" 10'-5" 10'-7" 10'-9" 10'-9" 10'-11" 11'-1" 11'-3"
03 P
Addressable Smoke Detector 65 Nos
P P P P P P P
L1:SD:33 L1:SD:34 L1:SD:35 L1:SD:36 L1:SD:37 L1:SD:38 L1:MD:39 04 Addressable Heat Detector 6 Nos
10'-6"
F
INSPECTION 05 Addressable Multi Sensor Detector 9 Nos
ROOM JACQUARD SECTION JACQUARD SECTION
06 P Manual Pull Station 06 Nos
12"
9'-11"
08
ROOM Horn with Strobe (HNR)
OM For Fire Door. 09 02 Nos
P P P P P P P 10 EOLR(End Of Line Resistor) 00 Nos
L1:SD:94 L1:SD:32 L1:SD:31 L1:SD:30 L1:SD:29 L1:SD:28 L1:SD:27 L1:MD:261
" 5'- SLC Loop-1 (Circuit Pathway AS
10'-5"
'-11 2" 11 Class-A)(2-Core-1.5mm² Cable)
15 REQUIRED
SLC Loop-4 (Circuit Pathway AS
11'-6" 12 Class-A)(2-Core-1.5mm² Cable)
OM For Fire Door. REQUIRED
NAC Line (Circuit Pathway AS
6"
6"
13
12" 12"
L1:OM:25 OM STAIR-2 Class-B)2-Core 2.5mm2 Cable REQUIRED
JACQUARD SECTION
12"
12"
L1:OM:13
10'-3"
Fire Rated Door(Double)
L1:MPS:24
OM NAC1:HS:01 14 S S
06 Nos
L1:SD:20
C:\Users\Lenovo\Downloads\FireRated Elevator Curtain.jpg
L1:IM:23
L1:IM:22
P P P P P P PP
SECTION-A-A'
L1:SD:16 L1:SD:18 L1:SD:19
SECURITY BUILDING 1ST FLOOR L1:MPS:12
" L1:SD:14 L1:SD:15 L1:SD:17
10'-11"
UP Fire Curtain for lift '-7 WALL SYMBOL DESCRIPTON
"
12'-1
IM IM
15
S
S
IM IM IM
STAIR-1 P NAC1:HS:03 P
L1:IM:11
L1:IM:10
L1:IM:09
S
L1:SD:21
6"
6"
L1:SD:08
12" 12"
12"
12"
Y
2 hour fire rated Door
10'
L1:MPS:02
SUB STATION ROOM 13'-6"
12'-2"
1"
P
UP
'-1
A'
15
A'
EF
S
SECURITY BUILDING 1st floor
P
engineering store
engineering store
P P 18"
L1:OM:03
0' 10' 20' 40'
12"
'-3
L4:SD:148 L4:SD:147
5 STORIED (PARTIALLY 6 STORIED)BUILDING
"
BUILDING
2-STORIED
2-STORIED
P
FLOOR AREA = 29,045 SFT N
5'-9"
L4:SD:146 9"
11'-
3' WIDE CORRIDOR
3' WIDE CORRIDOR
P
CEILING DETAILS
Engineer room
Engineer room
L4:SD:149
L1:HD:04
L4:SD:145
P F CEILING HEIGHT 11'-6''
P L1:MPS:05 NAC4:HN:02
L4:MCP:150 FACP 6"
P SLAB THICKNESS 0'-6''
14'-3"
NAC4:HS:01
18"
12"
P FIRE
CONTROL NOTIFICATION APPLIANCE CIRCUIT :4 Nos
13'-6"
L4:SD:151 12
METRE
ROOM
GENERATOR ROOM
GAS
L1:SD:07
P L4:MPS:143
BATH
BATH
F
OM 13
9'-4"
'-6
SECURITY
F P
L1:HD:152 L4:SD:142 Loop-4 Come From L1:OM:06 "
SPACE
OPEN
A'
PROJECT NAME & ADDRESS: DRAWING TITLE: CLIENT: CONSULTANT: PREPARED BY: CHECKED BY: APPROVED BY:
DISHANG SWEATERS LTD. SAFETY SOURCE LTD. ENG. MD.SHAHADAT HOSSAIN ENG. MD.ABDUR RAHMAN DATE: 07-11-2023
MOUZA : DIAKHALI, VILLAGE- DHONAYEED, P.O- DISHANG SWEATERS LTD B. Sc IN EEE, AMIEB-A18050 B. Sc IN ETE.
ZIRABO, U.P- YEARPUR, P.S- ASULIA, SAVAR-DHAKA.
House # 27, Road # 01, Sector # 06, Fire safety Engineer
Fire safety Engineer
Uttara, Dhaka- 1230, Bangladesh. PAPER SIZE: A2
Cell # 01730791994, 01711195266.
Issue for Approval Email:info@safteysource.com.bd PAGE NO: 09