VFD PANEL REMOTE WASH CONTROL PANEL

(Duty Fan)

POWER ON

RUN FAULT OFF

HAND AUTO

UNIT REPLACE PRE REPLACE BAG FILTRATION


ON/OFF FILTER FILTER MODE

X3
X3
1
VFD PANEL 1 WASH WASH CYCLE NOTE 19
(Standby Fan) NOTE 5 MODE START 2
2
3
3 NOTE 20
NOTE 6 4
4
RUN FAULT OFF 5
5 NOTE 21
HAND AUTO NOTE 7 6
6 MUTE
BUZZER BUZZER 7
7 NOTE 22
NOTE 8 X1 8
8
L1 9
NOTE 1 NOTE 23
N 10
1 11
X1 L1 L2 L3 N X2 1 2 3 4 5 6 7 8 NOTE 2 NOTE 24
X3 2 12
OFF
1 3 13
NOTE 5 NOTE 3 HAND AUTO NOTE 25
2 NOTE 1 4 14

NOTE 3

NOTE 4
NOTE 2
3 5 15
NOTE 6 NOTE 4 NOTE 26
4 6 16
5
NOTE 7
6 X2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
7
NOTE 8
8

NOTE 11
NOTE 10

NOTE 12
NOTE 13
NOTE 14
NOTE 15
NOTE 16

NOTE 17

NOTE 18
NOTE 5

NOTE 6

NOTE 7

NOTE 8

NOTE 9
X1 L1 L2 L3 N X2 1 2 3 4 5 6 7 8

1
NOTE 1

NOTE 3

NOTE 4
NOTE 2

2
3 2
(DP MONITOR 1 1
CABINET MOUNTED
ON THE 2 (DP SWITCH
FILTER SECTION) (DP SWITCH MOUNTED ON
MOUNTED ON THE STAND BY
THE DUTY FAN)
FAN)

BROKEN LINES INDICATE THE WIRING TO BE DONE BY 46 Elmar Circle, Royersford,


ELECTRICAL CONTRACTOR Pennsylvania 19468 USA FIELD WIRING TYPICAL FOR ALL
REMOTE WASH CONTROL PANEL DIMENSION: 700 mm HIGH - 600 mm WIDE - 200 mm DEEP Phone: 1-610-792-1275 (3) UNITS
Fax: 1-610-792-4824
DRAWN BY: FR
PROJECT: MMC Hospital, Qatar
CREATED BY: FR
APPROVED BY: FR
DATE: May 2022 DRAWING NO :- 5 / 2022
Rev- 0
SCALE: NTS PAGE NO - 1/2
GENERAL NOTE
VFD PANEL NOTES
ALL EXTERNAL CONTROL WIRING SHALL BE 14GA, MINIMUM OR AS PER APPLICABLE CODES
1. TERMINAL X1 - L1, L2, L3 & N : INCOMING POWER SUPPLY TO THE VFD PANEL (415 V AC, 3 P, 50 HZ)

2. TERMINAL X2 - 1 & 2 : EXTERNAL INTERLOCK (VOLT FREE)


REMOTE WASH CONTROL PANEL NOTES
3. TERMINAL X2 - 3 & 4 : ON/OFF COMMAND FROM REMOTE WASH CONTROL PANEL (VOLT FREE)
4. TERMINAL X2 - 5 & 6 : SPEED SIGNAL FROM BMS (0-10 V, DC)
1. TERMINAL X1 - (L1 & N) : INCOMING POWER SUPPLY TO THE PANEL (230 V AC, 1 PHASE, 50 HZ)
5. TERMINAL X2 - 7 & 8 : SPEED FEED BACK SIGNAL TO BMS (0-10 V, DC)
2. TERMINAL X1 - 1 & 2 : POWER SUPPLY TO THE ESP (230 V AC, 1 PHASE, 50 HZ)
3. TERMINAL X1 - 3 & 4 : POWER SUPPLY TO DETERGENT SOLENOID VALVE (230 V AC, 1 PHASE, 50 HZ) 6. TERMINAL X3 - 1 & 2 : VFD RUN STATUS TO BMS (VOLT FREE)
4. TERMINAL X1 - 5 & 6 : POWER SUPPLY TO HOT WATER SOLENOID VALVE (230 V AC, 1 PHASE, 50 HZ) 7. TERMINAL X3 - 3 & 4 : VFD FAULT STATUS TO BMS (VOLT FREE)
8. TERMINAL X3 - 5 & 6 : AUTO STATUS TO BMS (VOLT FREE)
5. TERMINAL X2 - 1 & 2 : UNIT ON/OFF COMMAND FROM BMS (VOLT FREE) 9. TERMINAL X3 - 7 & 8 : SPARE (VOLT FREE)
6. TERMINAL X2 - 3 & 4 : ON/OFF COMMAND TO THE DUTY FAN VFD PANEL (VOLT FREE)
7. TERMINAL X2 - 5 & 6 : ON/OFF COMMAND TO THE STAND BY FAN VFD PANEL (VOLT FREE)
8. TERMINAL X2 - 7 & 8 : WASH CYCLE START COMMAND FROM BMS (VOLT FREE)
9. TERMINAL X2 - 9 & 10 : EXTERNAL INTERLOCK (VOLT FREE)
10. TERMINAL X2 - 11 : POWER SUPPLY TO THE DP SWITCHES IN THE AIR MONITOR CABINET (24 V AC)
11. TERMINAL X2 - 12 : SIGNAL FROM THE PRE FILTER DP SWITCH (24 V AC)
12. TERMINAL X2 - 13 : SIGNAL FROM THE BAG FILTER DP SWITCH (24 VAC)
13. TERMINAL X2 - 14 : POWER SUPPLY TO THE DUTY FAN DP SWITCH (24 V AC)
14. TERMINAL X2 - 15 : SIGNAL FROM THE DUTY FAN DP SWITCH (24 VAC)
15. TERMINAL X2 - 16 : POWER SUPPLY TO THE STAND BY FAN DP SWITCH (24 V AC)
16. TERMINAL X2 - 17 : SIGNAL FROM THE STAND BY FAN DP SWITCH (24 VAC)
17. TERMINAL X2 - 18 & 19 : POWER SUPPLY TO THE EXTERNAL BUZZER (24 V AC)
18. TERMINAL X2 - 20 & 21 : EXTERNAL FIRE ALARM INTERLOCK FROM BFA SYSTEM (VOLT FREE)

19. TERMINAL X3 - 1 & 2 : H-O-A SWITCH AUTO POSITION STATUS TO BMS (VOLT FREE)
20. TERMINAL X3 - 3 & 4 : UNIT ON STATUS TO BMS ( VOLT FREE )
21. TERMINAL X3 - 5 & 6 : PRE FILTER STATUS TO BMS (VOLT FREE)
22. TERMINAL X3 - 7 & 8 : BAG FILTER STATUS TO BMS ( VOLT FREE )
23. TERMINAL X3 - 9 & 10 : ESP FILTRATION MODE STATUS TO BMS (VOLT FREE)
24. TERMINAL X3 - 11 & 12 : ESP WASH MODE STATUS TO BMS (VOLT FREE)
25. TERMINAL X3 - 13 & 14 : DUTY FAN TRIP ALARM SIGNAL TO BMS (VOLT FREE)
26. TERMINAL X3 - 15 & 16 : STAND BY FAN TRIP ALARM SIGNAL TO BMS (VOLT FREE)

46 Elmar Circle, Royersford,


Pennsylvania 19468 USA FIELD WIRING TYPICAL FOR ALL
Phone: 1-610-792-1275 (3) UNITS
Fax: 1-610-792-4824
DRAWN BY: FR
PROJECT: MMC Hospital, Qatar
CREATED BY: FR
APPROVED BY: FR
DATE: May 2022 DRAWING NO :- 5 / 2022
Rev- 0
SCALE: NTS PAGE NO - 2/2