This document contains specifications for two surge arresters used in power distribution systems. The arresters have nominal voltages of 9kV and 24kV and are designed for outdoor use mounted on brackets. They have rated discharge currents of 10kA and belong to Class 1 per IEC 99-1 standards. The document lists technical characteristics including maximum residual voltages under different impulse currents, electric strength of the housing, and absence of digital counters or leakage current meters.
This document contains specifications for two surge arresters used in power distribution systems. The arresters have nominal voltages of 9kV and 24kV and are designed for outdoor use mounted on brackets. They have rated discharge currents of 10kA and belong to Class 1 per IEC 99-1 standards. The document lists technical characteristics including maximum residual voltages under different impulse currents, electric strength of the housing, and absence of digital counters or leakage current meters.
This document contains specifications for two surge arresters used in power distribution systems. The arresters have nominal voltages of 9kV and 24kV and are designed for outdoor use mounted on brackets. They have rated discharge currents of 10kA and belong to Class 1 per IEC 99-1 standards. The document lists technical characteristics including maximum residual voltages under different impulse currents, electric strength of the housing, and absence of digital counters or leakage current meters.
- Lighting impulse (wave 8/20 us) - - 5 kA kVp 27.6 22 - 10 kA kVp 29.7 23.5 - 20 kA kVp 33.3 26.4 - Steep current impulse (front time 1 us) - 10 kA kVp 31.8 26.6 - Switching impulse (front time 30 us) - 1000 A kVp 22.9 @ 500A 20.2 @ 500A
11 Electric strength of housing (at sea level)
- Power frequency withstand voltage, dy kVrms 63 60 - Power frequency withstand voltage, wet kVrms 65 65 - Impulse withstand voltage (wave 1.2/50 us) kVp 150 150
12 Digital counter per phase - - -
13 Leakage current meter per phase - - -
SURGE ARRESTER - INZP 2410 No DESCRIPTION UNIT DATA-1 DATA-2
1 Manufacturer - INAEL - SPAIN VLA - HUBBEL
2 Type of designation - Outdoor Outdoor
3 Type of mounting - Bracket Bracket
4 Nominal voltage kV 24 24
5 Highest system voltage kV - -
6 Class of arrester to IEC 99-1 - 1 1
7 Frequency Hz 50 50
8 Rated nominal discharge current kA 10 10
9 Ratio influence voltage measured at
1.1 times Us/V3 uV - -
10 Maximum residual voltage
- Lighting impulse (wave 8/20 us) - - 5 kA kVp 73.6 56.1 - 10 kA kVp 79.2 60 - 20 kA kVp 88.8 67.3 - Steep current impulse (front time 1 us) - 10 kA kVp 84.8 67.8 - Switching impulse (front time 30 us) - 1000 A kVp 61.2 @ 500A 51.4 @ 500A
11 Electric strength of housing (at sea level)
- Power frequency withstand voltage, dy kVrms 85 85 - Power frequency withstand voltage, wet kVrms 90 90 - Impulse withstand voltage (wave 1.2/50 us) kVp 190 190