ST-1 & 2
CLASS A SYSTEM
Case-1 ; Considering only leakage through the Door at the ST-1 area
a) To calculate pressure required in stairwell to exhaust 1.815 m3/s to atmosphere via fire floor
Area of single leaf door=2.2X1.1=2.42 sq.m
Area of exhaust vent = 1.815/2.5 =0.726 sq.m
A.E = (1/A1^2+1/A2^2)^-0.5
= (1/2.42^2+1/0.726^2)^-0.5
= 0.70 sq.m
P1=(Q/(0.83XA.E))^2
= (1.815/(0.83X0.7))^2
= 9.75890283533939 Pa
This is more than covered by 50 Pa
54
Fittings
SAT(sound attonuator) 0 70
VAV 0 0
Flexible duct 0 0.3inch/100ft 0.00
sub total 89.14
Friction loss
Total
pa/m inch/100ft Friction
Loss(Pa)
0.57 0.07 5.740
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 2.296
0.57 0.07 5.740
0.57 0.07 4.592
TOTAL 78.064
Calculation for Stair case pressurization System . ST-3 to 7
CLASS A SYSTEM
Case-1 ; Considering only leakage through the single Door at the ST-3 area
Double Door area ( only at Ground floor)
Height-H/(m) = 2.2 m
Width-D/(m) = 2.2 m
Total No of Door = 1 Nos
Total Area = 4.84 m2
Leakage factor for Double Door is , K 0.03
Air Flow rate Q , as per BS 5588
Q=0.83xAxP^0.5
Q1 =0.83X(1X0.03)X50^0.5
Q1 0.18 m3/s
Single Door Area (all the floor apart from Ground Floor )
Height-H/(m) = 2.2 m
Width-D/(m) = 1.1 m
Total No of Door = 6 Nos
Total Area = 14.52 m2
Leakage factor for single Door is , K 0.01
Air Flow rate Q , as per BS 5588
Q=0.83xAxP^0.5
Q2=0.83X(4X0.01)X50^0.5
Q2= 0.35 m3/s
Total Air Flow rate for ST-01
Q3 = Q1+Q2
Q3 = 0.18+0.35 m3/s
0.53 m3/s
1,119.56 cfm
Increase by 50% 0.79 m3/s
1,679.34 cfm
Case-2 ; Considering one single door is opened (Class A system)
a) To calculate pressure required in stairwell to exhaust 1.815 m3/s to atmosphere via fire floor
Area of single leaf door=2.2X1.1=2.42 sq.m
Area of exhaust vent = 1.815/2.5 =0.726 sq.m
A.E = (1/A1^2+1/A2^2)^-0.5
= (1/2.42^2+1/0.726^2)^-0.5
= 0.70 sq.m
P1=(Q/(0.83XA.E))^2
= (1.815/(0.83X0.7))^2
= 9.75890283533939 Pa
This is more than covered by 50 Pa
Friction loss
Volume flow Eq. Total
Rate/(cfm) Diameter(De) pa/m inch/100ft Friction
Width/(mm) Height/(mm) Length(m) m Loss(Pa)
750 650 6,356.00 10 0.763 0.57 0.07 5.740
650 650 5,448.00 4 0.711 0.57 0.07 2.296
650 550 4,540.00 4 0.653 0.57 0.07 2.296
550 550 3,632.00 4 0.601 0.57 0.07 2.296
450 550 2,724.00 4 0.543 0.57 0.07 2.296
350 550 1,816.00 4 0.477 0.57 0.07 2.296
350 350 908.00 4 0.383 0.57 0.07 2.296
34 TOTAL 19.516
Fittings
SAT(sound attonuator) 0 70
VAV 0 0
Flexible duct 0 0.3inch/100ft 0.00
sub total 73.96