TPIL NRL
Originator / Document
This document is copyright and shall not be reproduced without Asset Code Discipline Sequence Number
Contractor Type Revision
permission of NRL
TP 1ZZZA EL DAT 0020 D2
NUMALIGARH REFINERY
LIMITED
Project : Numaligarh Refinery Expansion Project NRL PO Number : 4300062833-AMA/16.06.2020
Unit : Non Specific LV VARIABLE FREQUENCY DRIVE SYSTEM Rev.
1 GENERAL
2 Item : As per SR Quantity : As per SR
3 General specification: NR-0ZZZZ-EL-SPE-0018 Standards, codes: As per Specification
4 Supplier: Manufacturer:
5 ENVIRONMENTAL CONDITIONS
6 Installation (indoor/outdoor) / Environment type Indoor Corrosive Industrial environment / Mounting location
Extreme moisture inside the Panel
7 Maximum ambient temperature 38 °C VLT®
8 Minimum ambient temperature 5 °C Automation Drive
9 Design ambient temperature 40 °C FC 360 is
designed to
operate at 45-
50°C ambient
temperature at
full load and
55°C with
derating. This
means there is
no need to install
extra cooling
equipment or
oversize the
drive, resulting in
cost savings
10 Altitude/Maximum relative Humidity 90m above MSL 85 % @ 35°C 5-95% (IEC
60721-3-3; Class
3K3 (non-
condensing)
during operation
11 Hazardous area classification As per requirement Noted
12 Seismic Zone Code IS-1893 Zone-V/Site spectra whichever is governing) As per IS 1893,Seismic factor Noted
= 0.36
13 GENERAL SPECIFICATION
14 Drive type / Application Induction motor Noted and Agreed
15 System Voltage/Frequency/Phases 415 ± 6% V 50 ± 3% Hz No: 3 Noted and Agreed
16 System 3 phases fault level 50 / 65 kA for 1 Sec Noted
TO BE COMPLETED BY PURCHASER
Originator/ Asset Code Sequence DATA SHEET FOR MV TECHNIP INDIA LIMITED Page2 of 3
Contractor Disc. Code Doc. Type No. Rev.
VARIABLE FREQUENCY
TP 1ZZZA EL DAT 0020 D2 DRIVE SYSTEM 082176C-ZZZ-SP-1693-0001_D2
NUMALIGARH REFINERY
LIMITED
Project : Numaligarh Refinery Expansion Project NRL PO Number : 4300062833-AMA/16.06.2020
Unit : Non Specific MV VARIABLE FREQUENCY DRIVE SYSTEM Rev.
100
101 VFD ENCLOSURE
102 Degree of protection IP-42 for fan cooled enclosures & IP-52 for self-ventilated enclosures Noted
103 Cable glands type Double compression Noted
104 Cable entry / cable type / cable section Bottom Al, XLPE Insul, PVC, Armoured, FRLS Sq.mm Noted
105 Access Front Noted
106 Back to back possibility Noted
107 Painting (Mfr standard,... / color) As per Painting specification / Colour : Light Grey (RAL 7035) Noted
108 Noise level at full load 75 db (A) at 1 m (refer specification) Noted
109
110 CONVERTER MANUFACTURER DATA
111 Converter type / model no. VLT FC 360
112 Converter rating 22 KW
113 Type of cooling / Number of fans or pumps Refer Design
Guide
114 Heat losses Refer Design
Guide
115 Losses at full load Refer Design
Guide
116 Overload capability (125%, 150%) min sec. Refer Design
Guide
117 Efficiency of VFDS with motor 4/4 % 2/4 % Refer Design
Guide
118 Power factor of VFDS with motor 4/4 2/4 Refer Design
Guide
119 Feedback for speed control Refer Design
Guide
120 Rated output frequency Refer Design
Guide
121 Rated output Voltage / Current Refer Design
TO BE COMPLETED BY MANUFACTURER
Guide
122 Motor protection by built-in electronic device Yes No Refer Design
Guide
123 Motor protection by motor thermocouple/ thermistor Yes No Refer Design
Guide
124 Maximum pulsating torque / current Refer Design
Guide
125 Starting torque / Reacceleration torque Refer Design
Guide
126 Critical speed in the speed range Refer Design
Guide
127 Length / Width / Height Refer Design
Guide
128 Weight Refer Design
Guide
129
130 MOTOR/CONVERTER CABLE SPECIFICATION:
131 Derating factor
132 Minimum section
133 Maxiumum length
134 Earthing cable requirement
NOTES:
1 Combined testing of VFD along with motor for hazardous area application as per specification shall be carried out by vendor .
The interface with remote control room DCS shall be either through hardwired connection (with potential free contacts and transducers) or through
2 serial communication link as required and detailed in the DCS I/O list
Interface/control requirement between VFD / LCS / switchboards/DCS/ECS shall be finalized as per process/operational requirement during detail
3
engineering.
4 VFD shall have required interface with ECS as per the ECS I/O list.
5 Bypass for VFD shall be provided only if the drive shall continue to run in case of VFD failure as required by the process.
6 pulse system can be accepted for the MV VFDs with suitable mitigation measures to achieve the THD requirement of IEEE-519 w.r.to input side D2
6 harmonic level .
Originator/ Sequence
Asset Code Disc. Code Doc. Type No. Rev. DATA SHEET FOR MV TECHNIP INDIA LIMITED
Contractor
VARIABLE FREQUENCY Page 3 of 3
TP 1ZZZA EL DAT 0020 D2 DRIVE SYSTEM 082176C-ZZZ-SP-1693-0001_D2