NRL VFD Datasheet Format

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

NUMALIGARH REFINERY LIMITED Total pages: 3

NRL EXPANSION PROJECT

DATA SHEET FOR


LV VARIABLE FREQUENCY DRIVE SYSTEM

D2 06/09/2021 Approved For Design MAS AKM SVM


D1 29/03/2021 Approved For Design MN AKM SVM
Rev Date Reason for Issue Prepared By Checked By Approved By Prepared By Reviewed By Reviewed By
Com.Rep.
Disc. Eng. Disc. Lead Contr. Rep Disc. Eng. Proj. Eng
Dept. Head

TPIL NRL

Category Code Description


TECHNIP INDIA LIMITED Facility Area Code 1Z NR & MT Non Specific

NRL’s PO NO:4300062833AMA/16.06.2020 Document Type DAT Data Sheet

System Number 00 General


TP DOC REF: 082176C-ZZZ-SP-1693-0001_D2
Life Cycle 02 Disk Ref.:

Originator / Document
This document is copyright and shall not be reproduced without Asset Code Discipline Sequence Number
Contractor Type Revision
permission of NRL
TP 1ZZZA EL DAT 0020 D2
NUMALIGARH REFINERY
LIMITED
Project : Numaligarh Refinery Expansion Project NRL PO Number : 4300062833-AMA/16.06.2020
Unit : Non Specific LV VARIABLE FREQUENCY DRIVE SYSTEM Rev.
1 GENERAL
2 Item : As per SR Quantity : As per SR
3 General specification: NR-0ZZZZ-EL-SPE-0018 Standards, codes: As per Specification
4 Supplier: Manufacturer:
5 ENVIRONMENTAL CONDITIONS
6 Installation (indoor/outdoor) / Environment type Indoor Corrosive Industrial environment / Mounting location
Extreme moisture inside the Panel
7 Maximum ambient temperature 38 °C VLT®
8 Minimum ambient temperature 5 °C Automation Drive
9 Design ambient temperature 40 °C FC 360 is
designed to
operate at 45-
50°C ambient
temperature at
full load and
55°C with
derating. This
means there is
no need to install
extra cooling
equipment or
oversize the
drive, resulting in
cost savings
10 Altitude/Maximum relative Humidity 90m above MSL 85 % @ 35°C 5-95% (IEC
60721-3-3; Class
3K3 (non-
condensing)
during operation
11 Hazardous area classification As per requirement Noted
12 Seismic Zone Code IS-1893 Zone-V/Site spectra whichever is governing) As per IS 1893,Seismic factor Noted
= 0.36
13 GENERAL SPECIFICATION
14 Drive type / Application Induction motor Noted and Agreed
15 System Voltage/Frequency/Phases 415 ± 6% V 50 ± 3% Hz No: 3 Noted and Agreed
16 System 3 phases fault level 50 / 65 kA for 1 Sec Noted
TO BE COMPLETED BY PURCHASER

17 System neutral earthing Solidly Grounded Noted


18 Upstream protection (supplied by others) ACB/ MCCB Noted
19 Converter transformer type Dry Noted
20 Input side isolating device (switch, breaker) ACB/MCCB Noted
21 Input side isolating device rating /type As required Noted
22 Ouput side isolating device (switch, breaker) MCCB N/A
23 Output side isolating device rating /type As required Noted
24 Earth bus material / size Copper 30 x 6 mm min. N/A
25 Earthing switch Yes No N/A
26 Auxiliary supply voltage (Internal/ External) 240 V AC To be derived internally Noted
27 Control supply voltage (Internal/ External) 110VDC External N/A
28 Reacceleration / Restarting Yes No / Yes No
29 GENERAL CHARACTERISTICS
30 Execution By Vendor No of pulse: 12 Pulse (Note - 6) D2
31 Type of control (speed, torque, power) As per requirement Noted
32 Speed range / Power range As per Process requirement Noted
33 Output current limitation Yes No Yes
34 Voltage dips tolerated for reacceleration / restarting 20% Noted
35 Operating speed if loss of speed signal As per specification Noted
36 Speed limitation before tripping As per specification Noted
37 Harmonic currents at full load 5th level / 7th level / 11th level / / 25th level : Vendor to specify Meets EN
61000-3-12
38 THD of Voltage and current at inverter output As per IEC 61800-4 Noted
39 Harmonic voltage distortion at min. fault level As per IEEE519 Noted
40 Immunity class / Radiofrequency interference class As per standard Noted
41 Bypass feature As required (see Note 5) Noted
42 REMOTE CONTROL - FIELD MOUNTED LCS / CONTROL ROOM
43 Speed, frequency or power control Yes No Yes
44 Normal Start/ Stop Yes No Yes
45 Emergency shut down stop / Load shed signal Yes No Yes No Yes
46 Local - Remote selector switch Yes No Yes
47 Direction of rotation reversal selector Yes No Yes
48 Forward-Reverse Yes No Yes
49 Auto/Manual mode Yes No Yes
50 Start/Stop for Bypass starter Yes No Yes
51 Trip-Remote breaker Yes No Yes
52 CONVERTER CUBICLE CONTROL
53 Normal Start /Stop Yes No Yes
54 Fault reset Yes No Yes
55 Emergency shut down push button Yes No Yes
56 Speed, frequency or power control Yes No Yes
57 Forward-Reverse Yes No Yes
58 Auto/Manual mode Yes No No
59 Local - Remote Yes No Yes
60 Start/Stop for Bypass starter Yes No Yes
61 Trip-Remote breaker Yes No Yes
62 REMOTE MONITORING AND SIGNALLING
63 Ready for operation / Running Yes No Yes No Yes
64 Converter alarm / Converter trip Yes No Yes No Yes
65 Transformer alarm / Transformer trip Yes No Yes No No
66 Supply CB trip Yes No NO
67 CONVERTER CUBICLE MONITORING AND SIGNALLING (in addition to the ones specified in specification cl.5.6.5 & 5.6.6)
68 Output current Yes No Yes
69 Output frequency Yes No Yes
70 Output voltage Yes No Yes
71 Lamp Test Yes No NO
72 Ready for operation / Running Yes No Yes No Yes
73 Converter alarm / Converter trip Yes No Yes No Yes
74 Transformer alarm / Transformer trip Yes No Yes No No
75 Supply CB trip Yes No NO

Originator/ Asset Code Sequence DATA SHEET FOR MV TECHNIP INDIA LIMITED Page2 of 3
Contractor Disc. Code Doc. Type No. Rev.
VARIABLE FREQUENCY
TP 1ZZZA EL DAT 0020 D2 DRIVE SYSTEM 082176C-ZZZ-SP-1693-0001_D2
NUMALIGARH REFINERY
LIMITED
Project : Numaligarh Refinery Expansion Project NRL PO Number : 4300062833-AMA/16.06.2020
Unit : Non Specific MV VARIABLE FREQUENCY DRIVE SYSTEM Rev.

76 CONVERTER CUBICLE FAULT (ALARM AND/OR TRIP + DISPLAY)


77 Motor
78 Short-circuit Yes No Yes
79 Motor protection Yes No Yes
80 Earth fault in the stator windings Yes No Yes
81 Stator overtemperature Yes No Yes
82 Bearing temperature, lube oil flow, vibration Yes No NO

83 Transformer alarm / Transformer trip Yes No NO

84 Converter Yes No Yes


85 Undervoltage (Input side) Yes No Yes
TO BE COMPLETED BY PURCHASER

86 Internal short circuit Yes No Yes


87 DC overvoltage Yes No Yes
88 Loss of control voltage Yes No Yes
89 Earth fault main circuit Yes No Yes
90 Over temperature power electronics Yes No Yes
91 Auxiliaries failure Yes No NO

92 One-phase interruption motor side Yes No Yes


93 Motor current protection Yes No Yes
94 Converter current protection (rectifier/ inverter) Yes No NO

95 5% measured value deviation for the setpoint Yes No NO

96 U/f ratio incorrect Yes No Yes


97 105% Overspeed Yes No Yes
98 95% Underspeed Yes No Yes
99 Motor stalled Yes No NO

100
101 VFD ENCLOSURE
102 Degree of protection IP-42 for fan cooled enclosures & IP-52 for self-ventilated enclosures Noted
103 Cable glands type Double compression Noted
104 Cable entry / cable type / cable section Bottom Al, XLPE Insul, PVC, Armoured, FRLS Sq.mm Noted
105 Access Front Noted
106 Back to back possibility Noted
107 Painting (Mfr standard,... / color) As per Painting specification / Colour : Light Grey (RAL 7035) Noted
108 Noise level at full load 75 db (A) at 1 m (refer specification) Noted
109
110 CONVERTER MANUFACTURER DATA
111 Converter type / model no. VLT FC 360
112 Converter rating 22 KW
113 Type of cooling / Number of fans or pumps Refer Design
Guide
114 Heat losses Refer Design
Guide
115 Losses at full load Refer Design
Guide
116 Overload capability (125%, 150%) min sec. Refer Design
Guide
117 Efficiency of VFDS with motor 4/4 % 2/4 % Refer Design
Guide
118 Power factor of VFDS with motor 4/4 2/4 Refer Design
Guide
119 Feedback for speed control Refer Design
Guide
120 Rated output frequency Refer Design
Guide
121 Rated output Voltage / Current Refer Design
TO BE COMPLETED BY MANUFACTURER

Guide
122 Motor protection by built-in electronic device Yes No Refer Design
Guide
123 Motor protection by motor thermocouple/ thermistor Yes No Refer Design
Guide
124 Maximum pulsating torque / current Refer Design
Guide
125 Starting torque / Reacceleration torque Refer Design
Guide
126 Critical speed in the speed range Refer Design
Guide
127 Length / Width / Height Refer Design
Guide
128 Weight Refer Design
Guide
129
130 MOTOR/CONVERTER CABLE SPECIFICATION:
131 Derating factor
132 Minimum section
133 Maxiumum length
134 Earthing cable requirement

NOTES:
1 Combined testing of VFD along with motor for hazardous area application as per specification shall be carried out by vendor .
The interface with remote control room DCS shall be either through hardwired connection (with potential free contacts and transducers) or through
2 serial communication link as required and detailed in the DCS I/O list
Interface/control requirement between VFD / LCS / switchboards/DCS/ECS shall be finalized as per process/operational requirement during detail
3
engineering.

4 VFD shall have required interface with ECS as per the ECS I/O list.
5 Bypass for VFD shall be provided only if the drive shall continue to run in case of VFD failure as required by the process.
6 pulse system can be accepted for the MV VFDs with suitable mitigation measures to achieve the THD requirement of IEEE-519 w.r.to input side D2
6 harmonic level .

Originator/ Sequence
Asset Code Disc. Code Doc. Type No. Rev. DATA SHEET FOR MV TECHNIP INDIA LIMITED
Contractor
VARIABLE FREQUENCY Page 3 of 3
TP 1ZZZA EL DAT 0020 D2 DRIVE SYSTEM 082176C-ZZZ-SP-1693-0001_D2