Project: PROJEK1
Variant: New simulation variant
Standalone system with batteries
System power: 107 kWp
Semarang - Indonesia
Author
Project: PROJEK1
Variant: New simulation variant
PVsyst V7.4.0
VC0, Simulation date:
01/09/23 10:59
with v7.4.0
Project summary
Geographical Site Situation Project settings
Semarang Latitude -6.99 °S Albedo 0.20
Indonesia Longitude 110.42 °E
Altitude 16 m
Time zone UTC+7
Meteo data
Semarang
Meteonorm 8.1 (2016-2021), Sat=100% - Synthetic
System summary
Standalone system Standalone system with batteries
System information
PV Array Battery pack
Nb. of modules 288 units Technology Lead-acid, vented, vehicle starting
Pnom total 107 kWp Nb. of units 24378 units
Voltage 1224 V
Capacity 23900 Ah
Results summary
Useful energy from solar 147545 kWh/year Specific production 1385 kWh/kWp/year Perf. Ratio PR 70.86 %
Missing Energy 0 kWh/year Available solar energy 167587 kWh/year Solar Fraction SF 100.00 %
Excess (unused) 4 kWh/year
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Detailed User's needs 4
Main results 5
Loss diagram 6
Predef. graphs 7
PVsyst V7.4.0
VC0, Simulation date:
01/09/23 10:59
with v7.4.0
General parameters
Standalone system Standalone system with batteries
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 10 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
User's needs
Daily household consumers
Constant over the year
Average 404 kWh/Day
PV Array Characteristics
PV module Battery
Manufacturer Generic Manufacturer Electrona
Model Mono 370 Wp Twin 120 half-cells Model Dural SC
(Original PVsyst database) Technology Lead-acid, vented, vehicle starting
Unit Nom. Power 370 Wp Nb. of units 239 in parallel x 102 in series
Number of PV modules 288 units Discharging min. SOC 20.0 %
Nominal (STC) 107 kWp Stored energy 23402.9 kWh
Modules 24 Strings x 12 In series Battery Pack Characteristics
At operating cond. (50°C) Voltage 1224 V
Pmpp 96.8 kWp Nominal Capacity 23900 Ah (C10)
U mpp 371 V Temperature Fixed 20 °C
I mpp 261 A
Total PV power
Nominal (STC) 107 kWp
Total 288 modules
Module area 538 m²
Cell area 477 m²
Array losses
Thermal Loss factor DC wiring losses Serie Diode Loss
Module temperature according to irradiance Global array res. 24 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC Loss Fraction 0.2 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.4.0
VC0, Simulation date:
01/09/23 10:59
with v7.4.0
PVsyst V7.4.0
VC0, Simulation date:
01/09/23 10:59
with v7.4.0
Main results
System Production
Useful energy from solar 147545 kWh/year Perf. Ratio PR 70.86 %
Available solar energy 167587 kWh/year Solar Fraction SF 100.00 %
Excess (unused) 4 kWh/year
Loss of Load Battery aging (State of Wear)
Time Fraction 0.0 % Cycles SOW 99.8 %
Missing Energy 0 kWh/year Static SOW 90.0 %
Legends
GlobHor Global horizontal irradiation E_User Energy supplied to the user
GlobEff Effective Global, corr. for IAM and shadings E_Load Energy need of the user (Load)
E_Avail Available Solar Energy SolFrac Solar fraction (EUsed / ELoad)
EUnused Unused energy (battery full)
E_Miss Missing energy
PVsyst V7.4.0
VC0, Simulation date:
01/09/23 10:59
with v7.4.0
Loss diagram
1922 kWh/m² Global horizontal irradiation
+1.6% Global incident in coll. plane
energy
0.00% -1.75% Battery efficiency loss
0.0 kWh -1.79% Charge/Disch. Current Efficiency Loss
PVsyst V7.4.0
VC0, Simulation date:
01/09/23 10:59
with v7.4.0
Predef. graphs
Daily Input/Output diagram