Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

TT-1617 12/13

INSTALLATION INSTRUCTIONS

Original Issue Date: 12/13


Model: 5/7.5/10EKD and 4/6/8EFKD
Market: Marine
Subject: Seawater Flow Switch Kit GM90489
Introduction Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
Installation of this kit involves adding a seawater flow generator set or connected equipment, disable the generator
switch and replacing/relocating the seawater pressure set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
switch with a new switch that provides enhanced (3) Remove the battery cables, negative (--) lead first.
protection for loss or low seawater flow. Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
Required Tools generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
The following tools and supplies are needed: computer.
D Electrical tape
D Teflon tape WARNING
D LoctiteR 565 general purpose pipe sealant paste
D Drill and 3/16 in. drill bit
D 5/16 in. socket, 1/4 in. drive
D 10 mm socket, 1/4 in. drive
D 15 mm open end wrench Hazardous voltage. Moving parts.
Can cause severe injury or death.
D 13 mm open end wrench
D 3/8 in. open end wrench Operate the generator set only when
D 7/16 in. open end wrench all guards and electrical enclosures
are in place.
D 3 in. Phillips screwdriver
D 1/4 in. socket
Testing live electrical circuits. Hazardous voltage or
D 1/4 in. drive ratchet current can cause severe injury or death. Have trained and
D Hose cutter knife qualified personnel take diagnostic measurements of live
D Wire cutter circuits. Use adequately rated test equipment with electrically
insulated probes and follow the instructions of the test
D Rags
equipment manufacturer when performing voltage tests.
Observe the following precautions when performing voltage
Safety Precautions tests: (1) Remove all jewelry. (2) Stand on a dry, approved
Observe the following safety precautions while electrically insulated mat. (3) Do not touch the enclosure or
components inside the enclosure. (4) Be prepared for the
performing this procedure. system to operate automatically.
(600 volts and under)
WARNING

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Procedure Engine-End View
1
1. Remove the generator set from service.
1.1 Push the generator set power button OFF.

1.2 Disconnect power to the battery charger, if


equipped.

1.3 Disconnect the generator set engine starting


battery, negative (--) lead first.
GM55219C

2. Remove the sound shield, if equipped. 1. 5/16 in. x 1.75 in. bolt

2.1 Remove the three 5/16 in. x 2.5 in. bolts from the Figure 3 Engine-End Door Removal
sound shield roof. See Figure 1.
2.4 Remove the 5/16 in. x 1.75 in. bolts to remove the
exhaust panel and the generator-end door. See
1 Top View Figure 4.

Generator-End View
1
2

GM55219C
1. 5/16 in. x 2.5 in. bolts (qty. 3)

Figure 1 Roof Bolt Removal GM55219C

1. 5/16 in. x 1.75 in. bolt on exhaust panel


2.2 Release the two latches on the service side door 2. 5/16 in. x 1.75 in. bolt on generator-end door
to remove the service-side door. See Figure 2.
Figure 4 Exhaust Panel and Generator-End Door
Removal
Service-Side View
1 2.5 Remove the two 5/16 in. x 0.625 in. bolts on the
nonservice-side door. After these bolts are
removed, remove the roof and remaining panels.

Nonservice-Side View

GM55219C
1. Latches (qty. 2)

Figure 2 Service-Side Door Removal

2.3 Remove the 5/16 in. x 1.75 in. bolt to remove the 1
engine end door. See Figure 3. GM55219C

1. 5/16 in. x 0.625 in. bolts (qty. 2)

Figure 5 Nonservice-Side Door Removal


2 TT-1617 12/13
3. Remove the high exhaust temperature Top View of Exhaust Manifold
switch.
3.1 Cut lead #37 from the existing high exhaust
temperature switch. See Figure 6 for location of
the switch. Tape the end of the lead with electrical
tape and tuck the lead into the split loom of the
wiring harness.

1
2
1 GM53065-B

1. Seawater pressure switch

Figure 7 Current Location of Seawater Pressure


Switch

4.3 Use a 3/8 in. open end wrench to remove the pipe
plug and install the new seawater pressure switch
(GM54744) using a 7/16 in. open end wrench at
the location shown in Figure 8. Save the pipe plug.
GM58164-B
Note: Use LoctiteR 565 on the threads of the new
1. High exhaust temperature switch (249872) and hex cap bolt
seawater pressure switch and the existing
(X-6238-2)
2. Catalyst pipe plug.

Figure 6 Exhaust Temperature Switch Location 4.4 Install the pipe plug (removed in step 4.3) at the
former location of the seawater pressure switch.
3.2 Use a 15 mm open end wrench to remove the hex See Figure 8.
cap bolt and temperature switch and save the
temperature switch for the possible return to
Side View of Exhaust Manifold
Kohler Power Systems. Discard the hex cap bolt
(X-6238-2).

4. Remove, replace, and relocate the


seawater pressure switch.
4.1 Disconnect leads N5 and 87 from the seawater
pressure switch.
2
Note: Place rags underneath the seawater
pressure switch to absorb a small amount GM53065-
of water. 1
1. Seawater pressure switch (GM54744)
2. Pipe plug (X-75-4)
4.2 Use a 13 mm open end wrench to remove the
seawater pressure switch and 45_ fitting and save Figure 8 New Location of Seawater Pressure
for the possible return to Kohler Power Systems. Switch and Pipe Plug

5. Install the wiring harness.


Note: For Sound Shielded Units: Ensure that
the sound shield panel that contains the
ADC II controller is loosened enough to
route the new wiring harness (GM90471).
The 5/16 in. x 1.75 in. bolt may need to be
removed and the controller harness may
need to be disconnected for ease of
access.

LoctiteR is a registered trademark of Loctite Corporation.

TT-1617 12/13 3
5.1 Route the relay end of the wiring harness
Nonservice Side 7
(GM90471) behind the fuel pump, behind the
sound shield ADC II panel (if equipped), and up
into the bottom of the junction box. See Figure 9.

Note: If routing the harness as outlined in


Step 5.1 does not work, pull the harness
through from the inside of the junction box
and leave the relay base end of the
harness inside the junction box.

5.2 Route the flow switch connector (P5) and leads 5 6


87A and N5 of the new harness (GM90471) on the Service Side
right side of the fuel pump, over the top the stator 1 2
shell, and underneath the catalyst to the
nonservice side. See Figure 9.

5.3 Connect leads 87A and N5 from the new wiring


harness (GM90471) to the new seawater
pressures switch (GM54744) on the nonservice
side.

5.4 On the service side, disconnect the blue


connectors from the lift pump and the existing
wiring harness (containing leads F4B/N4 that
connect to leads F4C/N3). See Figure 9 for the lift
pump location.

5.5 The connector containing leads F4 and N (from


the new wiring harness) connects to the lift pump’s
connector. 4 3

5.6 The connector containing leads F4B and N (from 1. Relay end of wiring harness (route into junction box)
2. Seawater flow switch connector and leads 87A and N5
the new wiring harness) connects to the existing (route to nonservice side)
wiring harness. 3. Fuel pump
4. Lift pump
5.7 The leads that were disconnected from the old 5. Seawater pressure switch (GM54744)
6. Terminal ends of leads 87A and N5
seawater pressure switch now connect to the new
7. Seawater flow switch connector
wiring harness leads 87 and N5.
Figure 9 Wiring Harness (GM90471) Routing

Connects to new relay in junction box.

Connects to existing
harness on the service side.

Connects to new seawater flow switch


on the nonservice side.

Connects to new seawater Connects to old seawater Connects to existing lift


pressure switch on the pressure switch leads on pump on the service side.
nonservice side. the service side.
Figure 10 Wiring Harness (GM90471)

4 TT-1617 12/13
6. Install the relay in the junction box. 1
6.1 Use a 5/16 in. socket, 1/4 in. drive to remove the
junction box cover.

6.2 Place a rag inside the junction box to catch any


filings.

6.3 Drill a 3/16 in. hole at the location shown in


Figure 11.

6.4 Remove the rag and any drill filings from inside of
the junction box.

6.5 Mount the relay (GM49746) at the location shown


in Figure 12 using a screw (X-50-1) and nut
(X-70-3).

6.6 Connect the relay-connector end of the new wiring


harness (GM90471) to the new relay (GM49746).

6.7 Use a 5/16 in socket, 1/4 in. drive to reinstall the


junction box cover.
GM40265-D

1 1. Relay (GM49746), screw (X-50-1), and nut (X-70-3)

Figure 12 Relay Location (Inside Junction Box)

1
inch

GM40265-D

1. 3/16 in. hole


(1 in. down from top edge and 1 in. over from pem stud)

Figure 11 Hole Location for Relay (Inside Junction


Box)

TT-1617 12/13 5
7. Install the flow switch. 7.2 For Units With a Siphon Break:

7.1 For Units Without a Siphon Break: 7.2.1 Remove the hose located between the
heat exchanger end cap and the hose
Note: Proceed to Section 7.2 for units with a connector. See Figure 14.
siphon break.
7.2.2 Cut this hose into a 4-inch piece and a
7.1.1 Remove the molded hose located 5-inch piece.
between the heat exchanger end cap and
catalyst. See Figure 13. Save the molded
hose for re-use.

1
GM60007-A

1. Remove this hose.


GM58158-L
Figure 14 Hose Location (Units With Siphon Break)
1. Remove this hose.
7.2.3 Reuse the hose (cut to 4 inches in
Figure 13 Hose Location (Units Without Siphon Step 7.2.2) as shown in Figure 15, item 4.
Break) Install the flow switch (GM90436), and
hose fittings (GM90472 qty. 2) as shown in
7.1.2 Install a new hose (X-312-42), flow switch Figure 15.
(GM90436), and hose fittings (GM90472
qty. 2) as shown in Figure 15. Note: Units equipped with a siphon break
will not use the new hose X-312-42
Note: Use Teflon tape on the threads of supplied in the kit.
the flow switch fittings. Wrap the
tape around at least 3 times. Note: Use Teflon tape on the threads of
the flow switch fittings. Wrap the
Note: Avoid any kinks in hoses that tape around at least 3 times.
connect to the flow switch.
Note: Avoid any kinks in hoses that
7.1.3 Reuse the molded hose (removed in connect to the flow switch.
Step 7.1.1) but spin the hose 180_ from its
original position. See Figure 15, item 1. 7.2.4 Reuse the hose cut to 5 inches in
Step 7.2.2) as shown in Figure 15, item 2.
7.1.4 Secure the hoses using hose clamps
(X-426-12 qty. 2) and existing hose 7.2.5 Secure the hoses using hose clamps
clamps. (X-426-12 qty. 2) and existing hose
clamps.
7.1.5 Connect the flow switch connector to the
new wiring harness connector that was 7.2.6 Connect the flow switch connector to the
routed to the nonservice side in Step 5.2. new wiring harness connector that was
routed to the nonservice side in Step 5.2.

6 TT-1617 12/13
1 test validates the seawater flow switch
2
operation and wiring.

8.2.4 Reset the controller. See the operation


manual for reset procedure.

8.2.5 Reconnect the wire to the seawater


OUT pressure switch that was removed in
IN Step 8.2.1.

8.3 Seawater Pressure Switch Validation Test

8.3.1 Pull the newly installed relay (P26) from its


base.
4 3 GM58158-M

8.3.2 Start the generator set and run for


1. Units without a siphon break: Existing molded hose
45 seconds.
routed to catalyst and flow switch.
2. Units with a siphon break: Existing hose cut to a 5-inch
piece routed to siphon break connector and flow switch. 8.3.3 Close the seacock. Verify that the
3. Flow switch (GM90436) and hose fittings (GM90472 qty. 2) generator set shuts down on “Coolant
4. Units without a siphon break: Hose (X-312-42) or loss” after the applicable time delay. This
Units with a siphon break: Existing hose cut to a 4-inch
piece.
test validates the low seawater pressure
switch operation and wiring.
Figure 15 Flow Switch Installation
8.3.4 Reset the controller. See the operation
manual for reset procedure.
8. Run and test the generator set
Note: After installing kit GM90489 and before 8.3.5 Reinstall the relay (P26) to its base.
reinstalling all sound shield panels/doors,
If either one of these validation tests do not yield the
if equipped, perform the following
desired results, verify proper wiring. If the wiring is
validation tests.
correct, replace the part that is failing the validation test.
8.1 Check For Any Water Leaks
8.4 If the seawater pressure switch and seawater flow
8.1.1 Reconnect the engine starting battery, switch pass the validation tests, replace the sound
negative (--) lead last. shield panels/doors, if equipped, using the
reverse procedure as outlined in Section 2.
8.1.2 Reconnect power to the battery charger, if
equipped. 8.5 After sound shield panels/doors are reinstalled,
start and run the generator set for 5 minutes. While
8.1.3 Start and run the generator set for applying boat load verify proper operation of the
5 minutes to verify that there are no water generator set. If the generator set does not
leaks from the newly installed seawater operate correctly, determine the root cause and
flow switch and new/relocated seawater correct. If the generator set operates properly,
pressure switch. return the generator set to service.

8.1.4 Shut down the generator set. Note: See Section 9 for seawater flow switch
maintenance.
8.2 Seawater Flow Switch Validation Test
Note: Leave the maintenance procedure
8.2.1 Remove one lead from the seawater (Section 9), service schedule (Section 10),
pressure switch. and wiring diagrams (Section 11) with the
owner for proper maintenance.
8.2.2 Restart the generator set and run for
45 seconds.

8.2.3 Create a low seawater pressure condition


by closing the seacock. Verify that the
generator set shuts down on “Coolant
loss” after the applicable time delay. This

TT-1617 12/13 7
9. Procedure to Clean Seawater Flow 1
Switch
Check and clean the seawater flow switch according to
the Service Schedule in Section 10. 2

9.1 Push the generator set power button OFF. 4 3

9.2 Disconnect power to the battery charger, if


6
equipped.
5
9.3 Disconnect the generator set engine starting 7
battery, negative (--) lead first.

9.4 Firmly grasp the housing and turn the bonnet


assembly 45_ counterclockwise (as indicated on
the top of the bonnet) to unlock the mating tabs on 1. Bonnet assembly
the two parts. See Figure 16. 2. Stem
3. Spring
4. Shuttle
9.5 Pull the bonnet assembly out of the housing. Be 5. Retaining clip
careful not to pull on the lead wires. 6. O-ring
7. Housing
9.6 Clean the shuttle, stem, spring, retaining clip, and
inside of the housing by lightly scraping and/or Figure 16 Flow Switch Assembly
wiping away any debris or buildup.
Parts List
9.7 Check the O-ring, bonnet assembly, shuttle, and Kit: GM90489
spring for any damage. Replace the flow switch, if
Qty. Description Part Number
necessary.
1 Relay, 12 V GM49746
9.8 Reassemble by ensuring the spring is set within 1 Switch, seawater pressure
(2.0 psi ± 0.5) GM54744
the clips on the shuttle cap.
1 Switch, flow GM90436
9.9 Reposition the O-ring in the counter-bored 1 Harness GM90471
shoulder of the housing. 2 Fittings, hose GM90472
1 Hose (0.63 ID x 5.0 in.) X-312-42
9.10 Insert the bonnet assembly into the housing,
2 Clamp, hose (0.69--1.25 in.) X-426-12
allowing the tabs on the bonnet to clear the mating
lugs on the housing. Ensure bonnet stem end 1 Screw (#10-32 x 0.5 in.) X-50-1
aligns with centering feature in the housing. 1 Nut (10-32) X-70-3

9.11 Lock the bonnet assembly by firmly grasping the


housing and turning the bonnet 45_ clockwise as
indicated on the top of the bonnet. This engages
the mating tabs on the two parts.

9.12 Reconnect the engine starting battery, negative


(--) lead last.

9.13 Reconnect power to the battery charger, if


equipped.

8 TT-1617 12/13
10. Service Schedule
After Every Every Every
Before 50 Hr or 100 Hr or 300 Hr or 500 Hr or
Perform Service at Intervals Indicated (X) Starting 1 Month 3 Months 6 Months Yearly
Fuel System
Check the fuel level and fill as necessary X
Check fuel lines and replace as necessary *[ X
Replace the fuel filter *[ X
Lubrication System
Check crankcase oil level and add as necessary X
Replace the oil in crankcase * X (200 hr)
Replace the lube oil filter element * X (200 hr)
Cooling System
Check coolant level and fill as necessary * X
X (during
Check seawater outlet and clean as necessary [
operation)
Check function of siphon break, if equipped X
Check and clean seawater flow switch * X
Replace seawater pump impeller *[ X X
(check)
Adjust seawater pump tension *[ X (200 hr) X
Check heat exchanger anticorrosion zinc X
condition *
Replace heat exchanger anticorrosion zinc * X
X (1000 hr/
Flush cooling system *[
2 years)
Ignition System
Check spark plugs condition and gap * X
Replace spark plugs * X (250 hr)
Intake/Exhaust System
Inspect exhaust system components *[ X
X (during
Check the exhaust gas condition
operation)
Service backfire flame arrestor * X
Check and/or replace the catalyst assembly *[ X
X (every
Replace the CO sensor module *[ 2 years)
Check the crankcase breather pipe for obstructions *[ X
Inspect the complete exhaust system *** X
Electrical System
Keep battery charged and in good condition  X
Check and tighten electrical connections * X
Clean battery cables [ X (200 hr)
Engine And Mounting
Check for water, fuel, coolant, and oil leakage *[] X
Retighten all nuts and bolts * X
Check tightness of mounting bolts/vibromounts * X (200 hr)
Remote Control System
X (break-in
Check remote control operation X
period)
Generator
Test run generator set X (weekly)
Blow dust out of generator *[ X
Clean slip rings and inspect brushes *[ X (1000 hr.)
* Requires removal of sound shield, if installed. *** Should be performed by your local distributor/dealer.
[ Consult your local distributor/dealer for service.  Consult battery manufacturer’s instructions.
] Read WARNING found at the beginning of manual regarding moving parts.

TT-1617 12/13 9
11. Wiring Diagrams

GM90655A--

Figure 17 Point-to-Point Wiring Diagram (Sheet 1 of 2)

10 TT-1617 12/13
GM90655B--

Figure 18 Point-to-Point Wiring Diagram (Sheet 2 of 2)

TT-1617 12/13 11
ADV8631A--

Figure 19 Schematic Wiring Diagram (Sheet 1 of 1)

12 TT-1617 12/13
Notes

TT-1617 12/13 13
Notes

14 TT-1617 12/13
Notes

TT-1617 12/13 15
KOHLER CO., Kohler, Wisconsin 53044 USA Kohler Power Systems
Phone 920-457-4441, Fax 920-459-1646 Asia Pacific Headquarters
For the nearest sales and service outlet in the 7 Jurong Pier Road
US and Canada, phone 1-800-544-2444 Singapore 619159
KOHLERPower.com Phone (65) 6264-6422, Fax (65) 6264-6455

Availability is subject to change without notice. Kohler Co. reserves the


right to change the design or specifications without notice and without any
obligation or liability whatsoever. Contact your local Kohlerr generator
set distributor for availability.
 2013 by Kohler Co. All rights reserved.

16 TT-1617 12/13

You might also like