BIIT-04 Testing Bushings With Two Taps Galera PPT

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

Suggested Test Procedure For

Bushings With Two taps

Offer by:
Reynaldo Galera
Doble Engineering
Brazil
Scope
• The objective of this paper is to
establish
t bli h a standard,
t d d safe f and
d
practical procedure to measure all
capacitances
it in
i a two
t tap
t bushing.
b hi
• Although this is a new procedure,
there are many manufactures that
have made this typey of bushing g at
least as far back as 1983.

BIIT- Test Procedure for Two Tap Bushing


Definition
• Potential, Capacitance
tap
– Definition per IEEE
C57.19.00 3.6 bushing g
voltage tap: A connection C1
to one of the conducting
layers of a capacitance-
capacitance
graded bushing, providing
a capacitance voltage
divider.

C2
BIIT- Test Procedure for Two Tap Bushing
Definition
• Test tap
– Definition per IEEE
C57.19.00.37
bushing test tap: A
connection to one of
the conducting layers
of a capacitance-
graded bushing for
measurement of
partial discharge, C1
power factor
factor, and
capacitance values.
C2

BIIT- Test Procedure for Two Tap Bushing


Two Taps
• A bushing with two taps is constructed
with one potential and one test tap.
• Resulting in a three capacitor model
– C1: Insulation system between center
conductor and tapped condenser layer closest
to center conductor
– C2: Insulation system between the two
tapped condenser layers
– C3:
C3 Outer
O ter most condenser la
layer
er to gro
ground
nd
flange

BIIT- Test Procedure for Two Tap Bushing


Two Taps

BIIT- Test Procedure for Two Tap Bushing


Tap Cover plays a roll
• In this bushing design the tap cover has and
electrical roll
– Grounds the tap
– Tap cover OFF or ON is significant

BIIT- Test Procedure for Two Tap Bushing


Haefely (France)
• Only C1 is provided on the Nameplate

BIIT- Test Procedure for Two Tap Bushing


Passoni Villa
• Nameplate provides C1 and C2

BIIT- Test Procedure for Two Tap Bushing


Bushing Company
• Nameplate C1, C2 and C3 provided

BIIT- Test Procedure for Two Tap Bushing


Preferred Approach
• Test smallest insulation specimen possible
– One
O section
ti att a time
ti

BIIT- Test Procedure for Two Tap Bushing


Keep track of what’s being energized

• C2||C3
– With cap on Potential Tap and Test Tap energized C3
is measured in parallel with C2

BIIT- Test Procedure for Two Tap Bushing


Keep track of what’s being energized
• Kirchoff’s Current Law
– Conservation of chargeg
– All current that leave the test instrument has to come
back

BIIT- Test Procedure for Two Tap Bushing


Keep track of what’s being energized

• Preferred approach for C3


– Allows one to keep the center conductor grounded

BIIT- Test Procedure for Two Tap Bushing


Multiple Options
• Preferred test mode is UST
– Less susceptible
p to electrostatic interference
– Safety, retain ground at the top terminal

BIIT- Test Procedure for Two Tap Bushing


Test Sequence

• Ground bushing center conductor


• Isolate apparatus from system
• Short-circuit all windings on Transformer application
• Clean bushings to minimize surface leakage
• Remove test tap cover only on bushing under test when
necessary
• Apply test leads
• Remove grounds on center conductor only when
necessary to perform tests
• P f
Perform measurementt
• Reapply grounds if removed, then remove test leads
• Replace bushing tap cover

BIIT- Test Procedure for Two Tap Bushing


C1 Measurement Procedure

• Assuming grounds applied and winding


electically short circuited if applicable
• Place the HV lead at the top of the
bushing
• R
Remove POTENTIAL TAP COVER
Make sure that the TAP is clean and dry
• Place a LV lead on the POTENTIAL TAP
• Keep TEST TAP COVER ON
• Remove ground from center conductor
• Make UST measurement at maximum
test voltage do not exceed L-G rating of
b hi
bushing

BIIT- Test Procedure for Two Tap Bushing


C1 Test Connect

BIIT- Test Procedure for Two Tap Bushing


C2 Measurement Procedure
• Remove cap on both TAPS
• Make sure that the TAPS are
clean and dry
• Place HV cable on
POTENTIAL TAP
• Place a LV on the TEST TAP
• Make UST measurement,
test voltage should not
exceeding L-G rating of
POTENTIAL TAP,, typically
yp y
2KV

BIIT- Test Procedure for Two Tap Bushing


C2 Test Connect

BIIT- Test Procedure for Two Tap Bushing


C3 Measurement Procedure
• Remove cap on both
TAPS
• Make sure that the
TAPS are clean and dry
• Place HV cable on the
TEST TAP
• Place a LV on the
POTENTIAL TAP
• Make GST Guard
measurement test
voltage should not
exceeding
di L L-G
G rating
ti off
TEST TAP, typically
500V

BIIT- Test Procedure for Two Tap Bushing


C3 Test Connection

BIIT- Test Procedure for Two Tap Bushing


Investigative Test: Inverted C1
• Place a LV lead on Center
Conductor then remove ground
• Remove POTENTIAL TAP
COVER. Make sure that the
TAP is clean and dry
dry. Do not
remove TEST TAP COVER
• Place HV cable on POTENTIAL
TAP
• Make UST measurement, test
voltage
g should not exceeding
g L-
G rating of POTENTIAL TAP,
typically 2KV

BIIT- Test Procedure for Two Tap Bushing


Investigative Test: Inverted C2
• Remove cap on both
TAPS
• Make sure that the
TAPS are clean and dry
• Place HV cable on the
TEST TAP
• Place a LV on the
POTENTIAL TAP
• Make UST
measurement test
voltage should not
exceeding L-G rating of
TEST TAP, typically
500V

BIIT- Test Procedure for Two Tap Bushing


Thank You

SPECIAL THANKS TO DOBLE


BRAZILIAN CLIENTS:

ELTRONORTE
PLENA TRANSMISSORA
CHESF
AREVA TRANSFORMERS

For g
givingg me pictures,
p , test
results, answering questions
and partnership.

BIIT- Test Procedure for Two Tap Bushing