Professional Documents
Culture Documents
H2 Safety Vent
H2 Safety Vent
By Thomas G Witte, CEO of Witte Engineered Gases, and Nick Barilo, Executive Director of Center for Hydrogen
Safety
Unfortunately, the configuration of hydrogen vent Improper designs that can cause vent system
systems may not be considered during the initial failure include:
design or not included in the process hazard • Incorrect supports
assessment (PHA). This can lead to vent stack • Incorrect piping expansion/contraction
damage or failure and hydrogen being discharged • Joints or vent system components with melting
to undesired locations. It is essential that vent points below the hydrogen flame temperatures
systems be designed by qualified engineers • Undersizing the vent system
or designers. Designers need to consider the • Incorrect vent stack termination
following:
• Process flow parameters (including maximum Failures include:
pressure, peak flow, maximum or minimum • Overpressurization
temperature, and composition) • Plugging the vent system
• Air ingress during a release 211/17, Hydrogen Vent Systems for Customer
• Interaction between flow streams Applications. Additionally, it is a best safety
• Liquid air or ice issues as a result of incorrect practice to design the pressure rating of the
installation piping at the highest rated pressure entering the
• A hydrogen release adversely affecting people vent system.
or property
2. Plugging/blocking the vent system
Clearly, many potential failures for a system can The vent system should be designed to avoid
be (and often are) overlooked in the design and freezing from the introduction of moisture or
PHA for a hydrogen system. other obstructions (such as insects or bird nests).
For either an LH2 or a GH2 vent stack, ensure
The Center for Hydrogen Safety (CHS), a global water cannot collect in the vent stack by using
membership organization dedicated to promoting a water barrier cap that will open only during
hydrogen safety and best practices worldwide, required hydrogen releases. If water can collect
has had extensive discussions among its in the vent system, such as in a cold LH2 stack
members and the Hydrogen Safety Panel about interaction with humid air, provide a monitored
vent design and other hydrogen safety practices. water collection chamber at least 0.6 m (2 ft)
As a result of these discussions, CHS has below the cold hydrogen inlet at the bottom
developed a list of the top 10 considerations for of the vent stack and ensure that it provides
designers to avoid the most common mistakes enough volume to collect water from the vent,
that can result in vent system failure. typically several gallons for small vent stacks.
All piping from any relief valve or valve outlet
1. Overpressurization should slope downward with no liquid collection
The system should be designed for a minimum points between the components and the vertical
pressure of 40 bar, as recommended by the vent stack. Signs should be placed near the
European Industrial Gas Association (EIGA) vent system directing the fire department not to
spray water on the vent stack outlet. Only helium 5. Incorrect temperature rating for joints or vent
should be used for LH2 systems if a purge gas system
is required, since it is the only gas that will not Ensure the melting point for the joints and vent
solidify at LH2 temperatures. system components is above the hydrogen flame
temperature during a release. This is especially
3. Incorrect supports a risk for plastic piping and copper-brazed
The design of supports for vent stacks should joints. Welded 304 or 316-type stainless steel is
consider reaction forces (especially from the recommended material for the vent system.
pressure safety relief valve activating), local Plastic, cast iron, ductile or malleable iron,
wind, and seismic forces, and ensure that the and high silicone should be avoided. Materials
supports are designed for vent system expansion/ with low melting points (i.e., aluminum, copper,
contraction due to temperature changes. The end brass, and bronze) are not recommended
of the vent stack must be supported such that the because of their reduced strength at high
reaction forces sum to zero. This is accomplished temperatures. Carbon steel and many polymers
by vertical flow upward or a tee stack that are not suitable materials for LH2 hydrogen
equalizes the flow through both opposing legs systems with operating temperatures below
of the tee. ‘L’ type or single-exit horizontal flow -29°C (-20°F).
direction vent stacks are discouraged due to the
large directional reaction forces. Even with tee 6. Air ingress during a release
stacks, harmonic motion can occur if the top vent Ensure there are no openings in the vent system
stack outlet supports are more than 0.5–0.6 m that can pull air into the vent stack during a flow
(1.5–2 ft) below the top of the vent stack. event (i.e., from a venturi effect), which may result
in a fire or deflagration in the vent stack.
4. Incorrect piping expansion/contraction
Consider pipe and fitting expansion/contraction 7. Undersizing the vent system
due to temperature changes. Make sure piping Vent systems should be designed for the
connected to the vent piping (such as conduit or maximum peak flow at the operating pressure of
propane for flaring) expands or contracts at the every stream that can flow simultaneously. The
same rate as the hydrogen piping or the attached design should address the distance and pressure
conduit/piping is designed to move independently drop of each flow stream.
of the hydrogen vent stack. Installation errors
have caused vent stack failures from changes 8. Interaction between flow streams
in flow direction (forces on elbows) and the use Ensure any interaction between the flow streams
of compression fittings on thick walls and/or is considered for all the design parameters. For
large-diameter tubing being incorrectly installed. example, combining multiple hydrogen streams
Changes in flow direction create reaction forces into one stack is common. Designers should
within the piping that can result in failures. ask whether a single vent stack is acceptable
Typically, vent systems are not pressure tested or if multiple vent stacks are needed. Operating
after installation; thus, incorrectly connected joints conditions should be evaluated in this instance.
may fail during the operation of the vent system. An In the case of two streams – e.g., one with a
example of this is swaged tubing on thick-walled pressure of 700 barg and the other at 12 barg –
or large-diameter piping. This type of connection two stacks are recommended. Another scenario
requires hydraulic machinery to ensure a correct may be combining GH2 at cold temperature (from
connection with good mechanical integrity. an LH2 source) with a stream of GH2 at ambient