Professional Documents
Culture Documents
General Pump Curves
General Pump Curves
Duity Values
Assume D 497.2 mm 734 Q
C 150 75.5 H
v 1.050126064 m/s OK
HL 0.001572872 m/m
Static Head 70 m
v velocity m/s
C constant
D diameter in mm
hL headloss per unit length m/m
HL total headloss in m
A area in sq.m
Table
Q (m3/hr) H (m) H (m)
m
0 70.0 120 1
56 70.0 110 2
100 70.1 100 3
150 70.3 80 4
180 70.4 60 5
200 70.5 40 6
250 70.7 0 7
300 71.0 8
350 71.4 9
400 71.8 10
Pump Curves
Head H (m)
140
120
100
80
60
40
20
0
0 50 100 150 200 250 300
Discharge Q (m3/hr)
A 0.216475369 0.070685835 m2
k 6.655387287 0.822503875
A 0.1941566 0.19415658 0.1941566 0.194156584 0.194156584 0.194156584 0.194156584 0.194156584 0.194156584 0.194156584
(D/4)0.63 0.2688542 0.26885419 0.2688542 0.268854191 0.268854191 0.268854191 0.268854191 0.268854191 0.268854191 0.268854191
Pipe Length 3500 3500 3500 3500 3500 3500 3500 3500 3500 3500
Head Loss 0 0.04691396 0.1372842 0.290881116 0.40770634 0.495545525 0.749111641 1.04997385 1.39686366 1.788737096
Static Head 70 70 70 70 70 70 70 70 70 70
System Head 70 70.046914 70.137284 70.29088112 70.40770634 70.49554553 70.74911164 71.04997385 71.39686366 71.7887371