Professional Documents
Culture Documents
Albadi 2019
Albadi 2019
Abstract
Power flow, or load flow, is widely used in power system operation and
planning. The power flow model of a power system is built using the relevant
network, load, and generation data. Outputs of the power flow model include
voltages at different buses, line flows in the network, and system losses. These
outputs are obtained by solving nodal power balance equations. Since these
equations are nonlinear, iterative techniques such as the Newton-Raphson, the
Gauss-Seidel, and the fast-decoupled methods are commonly used to solve this
problem. The problem is simplified as a linear problem in the DC power flow
technique. This chapter will provide an overview of different techniques used to
solve the power flow problem.
1. Problem formulation
1
Computational Models in Engineering
Table 1.
Type of buses in the power flow problem.
The values of diagonal elements (Y ii ) are equal to the sum of the admittances
connected to bus i. The off-diagonal elements (Y ij ) are equal to the negative of the
admittance connecting the two buses i and j. It is worth noting that with large
systems, Y-bus is a sparse matrix.
n
Y ii ¼ ∑ yij (2)
j¼0
j 6¼ i
Y ij ¼ Y ji ¼ yij (3)
The net injected power at any bus can be calculated using the bus voltage (V i ),
neighboring bus voltages (V j ), and admittances between the bus and its
neighboring buses (yij ) as shown in Figure 1.
Ii ¼ V i yi0 þ ðV i V 1 Þyi1 þ ðV i V 2 Þyi2 þ … þ V i V j yij
Ii ¼ V i ∑ yij ∑ yij V j ¼ V i Y ii þ ∑ Y ij V j
j¼0 j¼1 j¼1
j 6¼ i j 6¼ i j 6¼ i
Si ¼ Pi þ jQ i ¼ V i Ii ∗
2
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
Figure 1.
Net injected power.
Or
Si ∗ ¼ Pi jQ i ¼ V i ∗ Ii
Real and reactive power can be calculated from the following equations:
8 0 19 8 0 19
>
> >
> >
> >
>
< B C= < B C=
∗B C ∗ B C
Pi ¼ Re V i @V i ∑ yij ∑ yij V j A ¼ Re V i @V i Y ii þ ∑ Y ij V j A
>
> >
> >
> >
>
: j¼0 j¼1
; : j¼1
;
j 6¼ i j 6¼ i j 6¼ i
8 0 19 8 0 19
>
> >
> >
> >
>
< B C = < B C=
Q i ¼ Im V i @V i ∑ yij ∑ yij V j C
∗B
A> ¼ Im V i
∗ BV i Y ii þ ∑ Y ij V j C
@ A>
>
> > >
> >
: j¼0 j¼1
; : j¼1
;
j 6¼ i j 6¼ i j 6¼ i
Or
n
Pi ¼ ∑ jV i jV j Y ij cos θij δi þ δj (4)
j¼1
n
Q i ¼ ∑ jV i jV j Y ij sin θij δi þ δj (5)
j¼1
And the current (Ii) can be written as a function of the power as follows:
Pi jQ i
¼ V i ∑ yij ∑ yij V j ¼ V i Y ii þ ∑ Y ij V j (6)
Vi∗ j¼0 j¼1 j¼1
j 6¼ i j 6¼ i j 6¼ i
3
Computational Models in Engineering
Figure 2.
Impedance diagram.
Figure 3.
Admittance diagram.
3. Gauss-Seidel technique
The Gauss-Seidel (GS) method, also known as the method of successive dis-
placement, is the simplest iterative technique used to solve power flow problems. In
general, GS method follows the following iterative steps to reach the solution for the
function f ðxÞ ¼ 0:
• Rearrange the function into the form x ¼ g ðxÞ to calculate the unknown
variable.
4
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
• Calculate the value g x½0 based on initial estimates x½0 .
• Calculate the improved value x½1 ¼ g x½0 .
• Continue
½kþ1solving for improved values until the solution is within acceptable
limits x ½k
x ≤ ϵ.
In the context of a power flow problem, the unknown variables are voltages at
all buses, but the slack. Both voltage magnitudes and angles are unknown for
load buses, whereas voltage angles are unknown for regulated/generation buses.
The voltage V i at bus i can be calculated using either equations:
!
1 Pi sch jQ i sch
Vi ¼ þ ∑ yij V j (8)
∑ j ¼ 1 yij Vi∗ j
j 6¼ i
0 1
1 B BP i
sch
jQ i sch C
Vi ¼ ∑ Y ij V j C (9)
Y ii @ Vi∗ j¼1
A
j 6¼ i
where yij is the admittance between buses i and j, Y ij is the Y-bus element, Pi sch
the net scheduled injected real power, Q i sch is the net scheduled injected reactive
power, and V i ∗ is the conjugate of V i . The net injected quantities are the sum of the
generation minus load. Typically, the initial estimates of V i ¼ 1 ∠ 0° .
The iterative voltage equation is as follows:
!
½kþ1 1 Pi sch jQ i sch ½k or kþ1
Vi ¼ ∑j 6¼ i Y ij V j (10)
Y ii V i ∗ ½k
Or
!
1 Pi sch jQ i sch
V i ½kþ1 ¼ þ ∑ yij V j ½k or kþ1 (11)
∑j ¼ 0 yij Vi∗ j 6¼ i
Both real and reactive powers are scheduled for the load buses, and Eq. 6 is used
to determine both voltage magnitudes and angles (jV i j ∠ δ) for every iteration
(V i ½kþ1 ).
For regulated buses, only real power is scheduled. Therefore, net injected
reactive power is calculated based on the iterative voltages (V i ½kþ1 ) using either
equations:
8 0 19
>
> >
>
< B n n C=
½kþ1 ∗ ½k B ½k ½k or kþ1 C
Qi ¼ Im V i @V i ∑ yij ∑ yij V j A> (12)
>
> >
: j¼0 j¼1
;
j 6¼ i
5
Computational Models in Engineering
n ½k or kþ1
Q i ½kþ1 ¼ ∑ jV i j½k V j Y ij sin θij δi ½k þ δj ½k (13)
j¼1
where jV i j and V j are the magnitudes of the voltage at buses i and j, respec-
tively. δi and δj are the associated angles. yij is the admittance between buses i and j.
Y ij is the magnitude of the Y-bus element between the two buses; and θij is the
corresponding angle.
Since the voltage magnitude (jV i j) is specified at regulated/PV buses, Eqs. (8) or
(9) will be used to determine the voltage angles only. To achieve this, two options
can be used:
1. When using the polar form (jV i j ∠ δi ), discard the iterative voltage magnitude
and keep the iterative angle.
2. When using the rectangular form (Rei þ j Imi ), discard the real part (Rei ) and
keep the imaginary part (Imi ) of the iterative voltage. The new real part
(Rei new ) can be calculated from the specified magnitude (jV i j) and the iterative
imaginary part.
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
Rei new
¼ jV i j2 Imi 2 (14)
The iterative process stops when the voltage improvement reaches acceptable
limits: V i ½kþ1 V i ½k ≤ ϵ.
Example 2: Gauss-Seidel power flow solution.
Figure 4 below shows a 3-bus system. Perform 2 iterations to obtain the voltage
magnitude and angles at buses 2 and 3. Impedances are given on 100 MVA base.
Solution:
The admittance values of the transmission network and the injected power in
per unit at buses 2 and 3 are calculated as shown in Figure 5. Note that net injected
power at the load bus is negative while that of the PV bus is positive. Per units
values are obtained by diving actual values (MW and MVAR) by the base (100
MVA).
Iteration #1: assume V 2 ½0 ¼ 1:00 ∠ 0° and V 3 ½0 ¼ 1:03 ∠ 0° .
!
½1 1 P2 sch jQ 2 sch ½0
V2 ¼ ∗ þ y21 V 1 þ y23 V 3
y21 þ y23 V 2 ½0
1 2 þ j0:5
¼ þ ð5 j15Þ1:02 ∠ 0° þ ð15 j50Þ1:00 ∠ 0°
ð5 j15Þ þ ð15 j50Þ 1:00 ∠ 0°
V 2 ½1 ¼ 1:0120 j0:0260 ¼ 1:0123 ∠ 1:4717°
6
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
Figure 4.
3-Bus power system.
Figure 5.
Power flow input data.
Q 3 ½1 ¼ Im 1:03 ∠ 0° 1:03 ∠ 0° ð10 j40 þ 15 j50 Þ ð10 j40Þ1:02 ∠ 0°
þð15 j50Þð1:0120 j0:0260ÞÞg
¼ Imf1:7201 j0:9373g ¼ 0:9373 pu
Since the magnitude of V 3 is specified, we retain the imaginary part of V 3 ½1 and
calculate the real part using Eq. (14).
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
Rei new ¼ 1:032 0:00222 ¼ 1:03 pu
7
Computational Models in Engineering
Therefore,
Iteration #2: considering V 2 ½1 ¼ 1:0120 j0:0260 and V 3 ½1 ¼ 1:03 j0:0022.
!
1 P2 sch jQ 2 sch
V 2 ½2 ¼ ∗ þ y21 V 1 þ y23 V 3 ½1
y21 þ y23 V 2 ½1
1 2 þ j0:5
¼ þ ð5 j15Þ1:02 ∠ 0° þ ð15 j50Þð1:03 j0:0022Þ V 2 ½2
ð5 j15Þ þ ð15 j50Þ 1:0120 j0:0260
¼ 1:0115 j 0:0270 ¼ 1:0119 ∠ 1:5273°
Only imaginary value of the calculated V 3 ½2 is retained and the real part is
calculated based on the retained imaginary values and the scheduled jV 3 j:
pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
Rei new ¼ 1:032 0:00302 ¼ 1:03 pu
Therefore,
Table 2.
Gauss-Seidel iterative solution.
8
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
4. Newton-Raphson technique
Based on x½0 , the deviation from the correct solution can be iteratively
calculated.
c f x½0 Δf x½0
Δx½0 ¼ ¼ (18)
f 0 ðx½0 Þ f 0 ðx½0 Þ
n ½k or kþ1
Pi ½kþ1 ¼ ∑ jV i j½k V j Y ij cos θij δi ½k þ δj ½k (21)
j¼1
9
Computational Models in Engineering
When more variables are used, the derivative f 0 is replaced by partial derivatives
with respect to different variables. The partial derivative matrix is called the Jaco-
bian matrix.
2 3
∂Pi ∂Pi " #
6 ∂δi ∂jV i j 7 J J PjV j
f0 ¼ 6
4 ∂Q
7 ¼ Pδ
5 (22)
i ∂Q i J Qδ J Q jV j
∂δi ∂jV i j
Therefore, the Newton-Raphson power flow formulation can be solved using the
below equation:
To solve for the deviation, the inverse of the Jacobian matrix is required for
every iteration.
" # " #1 " #
Δδ½k J Pδ ½k J PjV j ½k ΔPi ½k
¼ (24)
ΔjV i j½k J Qδ ½k J Q jV j ½k ΔQ i ½k
Since the unknown variables are δ2 , δ3 , and jV 2 j; the scheduled quantities are
P2 sch , P3 sch , and Q 2 sch , the following problem formulation can be written.
10
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
2 3
2 3 2 3 ∂P2 ½k ∂P2 ½k ∂P2 ½k 2 3
½ k
P2 sch
6 P2 ∂δ2 ∂δ3 ∂jV 2 j 7 Δδ2 ½k
6 sch 7 6 ½k 7 6 ∂P3 ½k ∂P3 ½k ∂P3 ½k 76
7
½k 7
4 P3 5 4 P3 5 6
¼ 6 ∂δ2 ∂δ3 ∂jV 2 j 74 Δδ3 5
4 5 ½k
Q 2 sch Q 2 ½ k ∂Q 2 ½k ∂Q 2 ½k ∂Q 2 ½k Δ j V 2 j
∂δ2 ∂δ3 ∂jV 2 j
n
P2 ¼ ∑ jV 2 jV j Y 2j cos θ2j δ2 þ δj
j¼1
¼ jV 2 jjV 1 jjY 21 j cos ðθ21 δ2 þ δ1 Þ þ jV 2 j2 jY 22 j cos ðθ22 Þ þ jV 2 jjV 3 jjY 23 j cos ðθ23 δ2 þ δ3 Þ
∂P2
¼ jV 2 jjV 1 jjY 21 j sin ðθ21 δ2 þ δ1 Þ þ jV 2 jjV 3 jjY 23 j sin ðθ23 δ2 þ δ3 Þ
∂δ2
∂P2
¼ jV 2 jjV 3 jjY 23 j sin ðθ23 δ2 þ δ3 Þ
∂δ3
∂P2
¼ jV 1 jjY 21 j cos ðθ21 δ2 þ δ1 Þ þ 2jV 2 jjY 22 j cos ðθ22 Þ þ jV 3 jjY 23 j cos ðθ23 δ2 þ δ3 Þ
∂jV 2 j
n
P3 ¼ ∑ jV 3 jV j Y 3j cos θ3j δ3 þ δj
j¼1
¼ jV 3 jjV 1 jjY 31 j cos ðθ31 δ3 þ δ1 Þ þ jV 3 jjV 2 jjY 32 j cos ðθ32 δ3 þ δ2 Þ þ jV 3 j2 jY 33 j cos ðθ33 Þ
∂P3
¼ jV 2 jjV 3 jjY 32 j sin ðθ32 δ3 þ δ2 Þ
∂δ2
∂P3
¼ jV 3 jjV 1 jjY 31 j sin ðθ31 δ3 þ δ1 Þ þ jV 3 jjV 2 jjY 32 j sin ðθ32 δ3 þ δ2 Þ
∂δ3
∂P3
¼ jV 3 jjY 32 j cos ðθ32 δ3 þ δ2 Þ
∂jV 2 j
n
Q 2 ¼ ∑ jV 2 jV j Y 2j sin θ2j δ2 þ δj
j¼1
¼ jV 2 jjV 1 jjY 21 j sin ðθ21 δ2 þ δ1 Þ jV 2 j2 jY 22 j sin ðθ22 Þ jV 2 jjV 3 jjY 23 j sin ðθ23 δ2 þ δ3 Þ
∂Q 3
¼ jV 2 jjV 1 jjY 21 j cos ðθ21 δ2 þ δ1 Þ þ jV 2 jjV 3 jjY 23 j cos ðθ23 δ2 þ δ3 Þ
∂δ2
∂Q 3
¼ jV 2 jjV 3 jjY 23 j cos ðθ23 δ2 þ δ3 Þ
∂δ3
∂Q 3
¼ jV 1 jjY 21 j sin ðθ21 δ2 þ δ1 Þ 2jV 2 jjY 22 j sin ðθ22 Þ jV 3 jjY 23 j sin ðθ23 δ2 þ δ3 Þ
∂jV 2 j
11
Computational Models in Engineering
2 33 2 2 3 2 3
ΔP2 ½12 0:5500 1:4500
6 7 6 7 6 7 6 7
The mismatch power matrix:4 ΔP3 ½1 5 ¼ 4 1:5 5 4 0:5665 5 ¼ 4 0:9335 5
ΔQ 2 ½1 0:5 1:8000 1:3000
The Jacobian matrix (J) elements for iteration # 1 are as follows:
2 3
66:8 51:5 19:45
6 7
J ¼ 4 51:5 93:52 15:45 5
20:55 15:45 63:2
Iteration #2: Consider V 2 ½1 ¼ 1:0123 ∠ 1:5986° and V 3 ½1 ¼ 1:03 ∠ 0:1891° .
2 ½ 2 3 2 3
P2 2:0109
6 7 6 7
The calculated quantities: 4 P3 ½2 5 ¼ 4 1:5202 5
Q 2 ½ 2 0:4621
2 3 2 3 2 3 2 3
ΔP2 ½2 2 2:0109 0:0109
6 7 6 7 6 7 6 7
The mismatch power matrix: 4 ΔP3 ½2 5 ¼ 4 1:5 5 4 1:5202 5 ¼ 4 0:0202 5
ΔQ 2 ½2 0:5 0:4621 0:0379
The Jacobian matrix elements are calculated as follows:
2 3
67:07 51:74 18:26
6 7
J ¼ 4 52:50 94:49 14:18 5
22:51 16:91
65:34
2 3 2 31 2 3
Δδ2 ½2 67:07 51:74 18:26 0:0109
6 7 6 7 6 7
4 Δδ3 ½2 5 ¼ 4 52:50 94:49 14:18 5 4 0:0202 5
ΔjV 2 j½2 22:51 16:91 65:34 0:0379
2 3 2 3
Δδ2 ½2 0:1272 103 rad
6 ½2 7 ¼ 6 7
4 Δδ3 5 4 0:2154 103 rad 5
ΔjV 2 j½2 0:4810 103 pu
12
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
2 3 2 3 2 3
δ2 ½2 δ2 ½1 Δδ2 ½2
6 ½2 7 6 ½1 7 6 7
4 δ3 5 ¼ 4 δ3 5 þ 4 Δδ3 ½2 5
jV 2 j½2 jV 2 j½1 ΔjV 2 j½2
2 ½2 3 2 3 2 3
δ2 0:0279 rad 0:1272 103 rad
6 ½2 7 6 7 6 7
4 δ3 5 ¼ 4 0:0033 rad 5 þ 4 0:2154 103 rad 5
jV 2 j½2 1:0123 pu 0:4810 103 pu
2 ½2 3 2 3 2 3
δ2 0:0277 rad 1:5871°
6 ½ 2 7 6 7 6 7
4 δ3 5 ¼¼ 4 0:0035 rad 5 ¼ 4 0:2005° 5
jV 2 j½2 1:0118pu 1:0118 pu
It is worth noting that the mismatch between calculated and scheduled quanti-
ties diminishes very quickly.
2 3 2 3 2 3 2 3
ΔP2 ½1 1:4500 ΔP2 ½2 0:0109
6 7 6 7 6 7 6 7
4 ΔP3 ½1 5 ¼ 4 0:9335 5and4 ΔP3 ½2 5 ¼ 4 0:0202 5
ΔQ 2 ½1 1:3000 ΔQ 2 ½2 0:0379
The iterative solution is presented in Table 3.
Table 3.
Newton-Raphson iterative solution.
5. Fast-decoupled technique
In high voltage transmission systems, the voltage angles between adjacent buses
are relatively small. In addition, X=R ratio is high. These two properties result in a
strong coupling between real power and voltage angle and between reactive power
and voltage magnitude. In contrary, the coupling between real power and voltage
magnitude, as well as reactive power and voltage angle, is weak. Considering adja-
cent buses, real power flows from the bus with a higher voltage angle to the bus
with a lower voltage angle. Similarly, reactive power flows from the bus with a
higher voltage magnitude to the bus with a lower voltage magnitude.
Fast-decoupled power flow technique includes two steps: (1) decoupling real
and reactive power calculations; (2) obtaining of the Jacobian matrix elements
directly from the Y-bus.
" #
ΔP J Pδ 0 Δδ
¼ (26)
ΔQ 0 J Q jV j ΔjV j
or
13
Computational Models in Engineering
h i
½ΔQ ¼ J Q jV j ½ΔjV j (28)
Since the unknown voltage angles are δ2 and δ3 , elements for ½B0 are obtained
from the Y-bus (intersection of columns numbers 2 & 3 and rows numbers 2 & 3)
as follows:
0 65 50
½B ¼
50 90
00
Since the unknown voltage magnitude is jV 2 j at bus 2, B contains one element
only (intersection of the column and the row number 2):
½B0 ¼ ½65
14
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
2 3
ΔP2 ½k
" # 6 ½k1 7 h i h i
Δδ2 ½k 1 6 jV 2 j 7 1 ΔQ 2 ½k
¼ ½B0 6 6
7 and ΔjV 2 j½k ¼ B00
½k 7
Δδ3 ½k jV 2 j½k1
4 ΔP3 5
jV 3 j½k1
Iteration #1: assume V 2 ½0 ¼ 1:00 ∠ 0° and V 3 ½0 ¼ 1:03 ∠ 0° .
The calculated quantities:
2 3 2 3
P2 ½1 0:5500
6 ½1 7 6 7
4 P3 5 ¼ 4 0:5665 5
Q 2 ½1 1:8000
Calculation of δ2 and δ3 :
2 3
ΔP2 ½1 2 3
" # 6 7 " #1 1:4500
Δδ2 ½1
6 jV 2 j½0 7
0 1 6
65 50 6 1:00 7
¼ ½B 6 7¼ 6 7
7 4 0:9335 5
Δδ3 ½1 4 ΔP3 ½1 5 50 90
jV 3 j½0 1:03
" # " #
0:0254 rad 1:4569 °
¼ ¼
0:0041 rad 0:2324°
" # " # " # " # " #
δ2 ½1 δ2 ½0 Δδ2 ½1 0 1:4569° 1:4569°
¼ þ ¼ þ ¼
δ3 ½1 δ3 ½0 Δδ3 ½1 0 0:2324° 0:2324°
Calculation of jV 2 j:
h i
½1 1 1:3
ΔjV 2 j ¼ ½65 ¼ 0:0200
1:00
h i
ΔjV 2 j½1 ¼ jV 2 j½0 þ ΔjV 2 j½1 ¼ 1:00 þ 0:0200 ¼ 1:020 pu
Iteration #2: considering V 2 ½1 ¼ 1:020 ∠ 1:4569° and V 3 ½0 ¼ 1:03 ∠ 0:2324° .
The calculated quantities:
2 3 2 3
P2 ½2 1:6671
6 ½2 7 6 7
4 P3 5 ¼ 4 1:2133 5
Q 2 ½2 0:0239
15
Computational Models in Engineering
Calculation of δ2 and δ3 :
2 3
ΔP2 ½2 2 3
" # 6 ½1 7 1 0:3329
Δδ2 ½2 6
0 1 6 jV 2 j 7
7 65 50 6 1:02 7
¼ ½B 6 ¼ 6 7
½2 7 4 0:2867 5
Δδ3 ½2 4 ΔP3 5 50 90
jV 3 j½1 1:03
" # " #
Δδ2 ½2 0:0046 rad 0:0300°
¼ ¼
Δδ3 ½2 0:0005 rad 0:0286°
" # " # " # " # " # " #
δ2 ½2 δ2 ½1 Δδ2 ½2 1:4569° 0:0300° 1:7213°
¼ þ ¼ þ ¼
δ3 ½2 δ3 ½1 Δδ3 ½2 0:2324° 0:0286° 0:2021°
Calculation of jV 2 j:
h i
½ 2 1 0:4761
ΔjV 2 j ¼ ½65 ¼ 0:0072
1:02
h i
jV 2 j½2 ¼ jV 2 j½1 þ ΔjV 2 j½2 ¼ 1:02 0:0072 ¼ 1:0128 pu
The remaining five iterations are shown in Table 4. It shows that this method
converges slower than Newton-Raphson method.
Table 4.
Fast-decoupled iterative solution.
Or
16
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
Solution:
The first step in DC power flow technique is obtaining ½B from the Y-bus.
2 3
15 j55 5 þ j15 10 þ j40
6 7
Y ¼ 4 5 þ j15 20 j65 15 þ j50 5
10 þ j40 15 þ j50 25 j90
For this problem, Since the unknown voltage angles are δ2 and δ3 , elements for
½B are obtained from the Y-bus as follows:
65 50
½B ¼
50 90
" # " #1 " # " #1 " #
δ2 65 50 P2 65 50 2
¼ ¼
δ3 50 90 P3 50 90 1:5
" # " #
0:0313 rad 1:7958 °
¼ ¼
0:0007 rad 0:0428°
Specific branch losses are calculated using branch power flow. For example, the
losses in the line i – j are the algebraic sum of the power flow.
The current between buses Iij is a function of the voltages and the admittance
between V i and V j . It is worth noting that Iji ¼ Iij
Iij ¼ V i V j yij (38)
17
Computational Models in Engineering
Solution:
The polar form of the Y-bus is used.
2 3
57:01 ∠ 74:74° 15:81 ∠ 108:43° 41:23 ∠ 104:04°
6 7
Y ¼ 4 15:81 ∠ 108:43° 68:01 ∠ 72:90° 52:20 ∠ 106:70° 5
41:23 ∠ 104:04° 52:20 ∠ 106:70° 93:41 ∠ 74:48°
¼ jV 1 j2 jY 11 j cos ðθ11 Þ þ jV 1 jjV 2 jjY 12 j cos ðθ12 δ1 þ δ2 Þ þ jV 1 jjV 3 jjY 13 j cos ðθ13 δ1 þ δ3 Þ
¼ 0:5195 pu
n
Q 1 ¼ ∑ jV 1 jV j Y 1j sin θ1j δ1 þ δj
j¼1
¼ jV 1 j2 jY 11 j sin ðθ11 Þ jV 1 jjV 2 jjY 12 j cos ðθ12 δ1 þ δ2 Þ jV 1 jjV 3 jjY 13 j sin ðθ13 δ1 þ δ3 Þ
¼ 0:4572 pu
The total real power losses can be calculated using the total net injected real a
power at all buses:
PL ¼ P1 þ P2 þ P3
PL ¼ P1 þ P2 þ P3 ¼ 0:5195 2 þ 1:5 ¼ 0:0195 pu
QL ¼ Q1 þ Q2 þ Q3
However, Q 3 is unknown and can be calculated based on the given bus voltages:
n
Q 3 ¼ ∑ jV 3 jV j Y 3j sin θ3j δ3 þ δj
j¼1
¼ jV 3 jjV 1 jjY 31 j sin ðθ31 δ3 þ δ1 Þ jV 3 jjV 2 jjY 32 j sin ðθ32 δ3 þ δ2 Þ jV 3 j2 jY 33 j sin ðθ33 Þ
¼ 1:0220 pu
18
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
Figure 6.
Power flow results.
c. Branch losses
To calculate the losses in line 1–2, SL 12 is calculated by summing S12 and S21 .
These flows are calculated as follows: S12 ¼ V 1 I12 ∗ and S21 ¼ V 2 I21 ∗
I12 ¼ ðV 1 V 2 Þy12 ¼ 1:02 ∠ 0° 1:0118 ∠ 1:5871° ð5 þ j15Þ ¼ 0:4635 þ j0:0121 pu
I21 ¼ ðV 2 V 1 Þy21 ¼ I12 ¼ 0:4635 j0:0121 pu
S12 ¼ V 1 I12 ∗ ¼ 1:02 ∠ 0° ð0:4635 j0:0121Þ ¼ 0:4728 j 0:0123 pu
S21 ¼ V 2 I21 ∗ ¼ 1:0118 ∠ 1:5871° ð0:4635 þ j0:0121Þ ¼ 0:4685 þ j0:0252 pu
SL 12 ¼ S12 þ S12 ¼ ð0:4728 j 0:0123 Þ þ ð0:4685 þ j0:0252Þ ¼ 0:0043 þ j0:0129pu
Line 2–3:
Total losses:
SL ¼ SL 13 þ SL 23 þ SL 12 ¼ 0:0195 þ j0:0648 pu
8. Conclusions
Power flow analysis, or load flow analysis, has a wide range of applications in
power systems operation and planning. This chapter presents an overview of the
power flow problem, its formulation as well as different solution methods. The
19
Computational Models in Engineering
power flow model of a power system can be built using the relevant network, load,
and generation data. Outputs of the power flow model include voltages (magnitude
and angles) at different buses. Once nodal voltages are calculated, real and reactive
power flows in different network branches can be calculated. The calculation of
branch power flows enables technical loss calculation in different network
branches, as well as the total system technical losses.
Power flow analysis is performed by solving nodal power balance equations.
Since these equations are nonlinear, iterative techniques such as the Gauss-Seidel,
the Newton-Raphson, and the fast-decoupled power flow methods are commonly
used to solve this problem. In general, the Gauss-Seidel method is simple but
converges slower than the Newton-Raphson method. However, the latter method
required the Jacobian matrix formation of at every iteration. The fast-decoupled
power flow method is a simplified version of the Newton-Raphson method. This
simplification is achieved in two steps: 1) decoupling real and reactive power cal-
culations; 2) obtaining of the Jacobian matrix elements directly from the Y-bus
matrix. The DC power method is an extension to the fast-decoupled power flow
formulation. In DC power flow method, the voltage is assumed constant at all buses
and the problem becomes linear.
Acknowledgements
The author would like to acknowledge the financial support and thank the Rural
Area Electricity Company and Sultan Qaboos University for sponsoring the publi-
cation of this chapter under project number CR/ENG/ECED/16/02.
Author details
Mohammed Albadi
Sultan Qaboos University, Muscat, Oman
© 2019 The Author(s). Licensee IntechOpen. This chapter is distributed under the terms
of the Creative Commons Attribution License (http://creativecommons.org/licenses/
by/3.0), which permits unrestricted use, distribution, and reproduction in any medium,
provided the original work is properly cited.
20
Power Flow Analysis
DOI: http://dx.doi.org/10.5772/intechopen.83374
References
21