General UT32A-D

Specifications Digital Indicating Controller


l
(Dual-loop, Panel Mounting Type) tiona
Func ment
nce
GS 05P08D31-01EN Enha

n Overview
The UT32A-D dual-loop digital indicating control-
lers employ an easy-to-read, 14-segment large color
LCD display, along with navigation keys, thus greatly
increasing the monitoring and operating capabilities.
A ladder sequence function is included as standard.
The short depth of the controller helps save instrument
panel space.
The UT32A-D has a DIN rail mounting type (with op-
tion code /MDL). For more details, please see General
Specification GS 05P08D81-01EN.
n Control Computation Function
n Features (1) Types of control
• Dual-loop control is available. • PID control
• A 14-segment, active (PV display color changing • ON/OFF control
function) color LCD display is employed. (2) Control Computation Function
Two five-digit, high-resolution displays are possible. (a) Target setting point and the number of PID param-
Alphabet letters can be displayed in an easy-to-read eter groups
manner. The guide display shows parameter names. Respectively, four sets of target setpoints, alarm
• Easy to operate setpoints, and PID parameters can be set.
Navigation keys (SET/ENTER and Up/Down/Left/Right (b) Selecting the PID parameter group
arrow keys) are employed to facilitate making settings. The following PID parameter groups can be selected.
• 65 mm depth • Target setpoint number (SPNO) (The PID number
The small depth enables the mounting in a thin and can be set arbitrarily.)
small instrumented panel. • Measured input zone PID
• Ladder sequence function is included as standard. • Target setpoint zone PID
This function allows for creating a simple sequence • Reached target setpoint zone PID
control. Dedicated LL50A Parameter Setting Software (c) Auto-tuning
(sold separatly) allows for performing programming • Tuning results can be selected from two options,
using a ladder language. Normal or Stable.
• Quick setting function • Tuning output limit can be set.
Setting only the minimum necessary parameters for (d) “Super” function: Overshoot-suppressing function
operation is possible. (e) “Super 2” function: Hunting-suppressing function
• Equipped with a multitude of functions (f) STOP preset output function
Universal I/O is included as standard. PID control, (g) Input ERROR preset output function
ON/OFF control, etc. are available. (h) MANUAL preset output function
• LL50A Parameter Setting Software (sold separately)
(3) Operation Mode Switching
The parameters and ladder programs of UTAdvanced
digital indicating controller can be built from a PC using AUTO/MANUAL and RUN/STOP switching
Operation mode
REMOTE/LOCAL switching (only model with
this software. It makes data management even easier. switching
communication option)
• Dust-proof and drip-proof
IP66 (for front panel) (Not applicable to side-by-side (4) Control Parameter Setting Range
close mounting.) Proportional band 0.1 to 999.9%
NEMA4 (Hose-down test only) Integral time 1 to 6000 sec. or OFF (using manual reset)
Derivative time 1 to 6000 sec. or OFF
n Functional Specifications ON/OFF control
Control Specifications hysteresis (one or two 0.0 to 100.0% of measured input range width
hysteresis points)
(1) Control Mode Preset output -5.0 to 105.0% (however, 0 mA or less cannot
Dual-loop control value be output)
(2) Control period High/low output -5.0 to 105.0%
limiter Low limit setpoint < high limit setpoint
200 ms
When manual control is carried out with 4 to
Tight shut
20 mA output, control output can be reduced to
Table of Number of Inputs and Outputs function
about 0 mA.
Rate-of-change
Number of Number Number Number of 0.1 to 100.0%/sec., OFF
Model and limiter of output
analog input of analog of contact contact
suffix code
points output points input points output points
UT32A
-Dx0 2 2 3 3

Yokogawa Electric Corporation GS 05P08D31-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan 2nd Edition Mar.14, 2016 (YK)
Tel.: 81-422-52-7179 Fax.: 81-422-52-6619
2
Alarm Functions (3) Sequence Device
• Types of Alarm (loop-1 and loop-2) Types of device Number of points
Input relay 3
Measured value PV (measured value) high/low limit alarm Digital I/O
Deviation high/low limit alarm Output relay 3
alarm
Deviation high and low limits alarm M relay (bit data) 256
Deviation alarm
Deviation within high and low limits alarm DAT register (data) 28
Rate-of-change Internal device
Analog input PV high/low limit alarm P register (parameter) 10
alarm PV rate-of-change alarm
K register (constant) 30
SP (setpoint) high/low limit alarm
Target SP high/low limit alarm Special device Special relay (bit data) 12
Setpoint alarm Target SP deviation high/low limit alarm Process data and process relay can be used besides
Target SP deviation high and low limits alarm
Target SP deviation within high and low limits alarm
the above-mentioned.
Output alarm
Control output high/low limit alarm (4) Program capacity
Cooling control output high/low limit alarm Max Program capacity: 300 steps *
Heater disconnection alarm (for /HA option) *: Available number of steps differs according to the
Other alarms Self-diagnosis alarm parameters and using command.
FAIL
(5) Ladder computation period
• Alarm Functions
Ladder computation period is the same as control
Alarm stand-by action
Alarm output
period.
Alarm latch (forced reset) function
action Alarm hysteresis
Alarm ON/OFF delay timer
Number of alarm
4
settings
Number of alarm
3
output points

Contact I/O Function


This function allows for allocating the input error condi-
tion, operation condition, alarm condition or other con-
ditions to the contact input and contact output. AUTO/
MAN, REMOTE/LOCAL, and STOP/START can be
switched individually or simultaneously both in loop-1
and loop-2.
AUTO/MANUAL switching
REMOTE/LOCAL switching (only model with
communication option)
STOP/START switching
Switching to AUTO
Switching to MANUAL
Switching to REMOTE (only model with
communication option)
Contact input
Switching to LOCAL (only model with
communication option)
AUTO-TUNING START/STOP switching
LCD backlight ON/OFF switching
Message interrupt displays 1 through 4
SP number specification
PID number specification
Manual preset output number specification
Alarms 1 through 4
Contact output
Status output

Ladder Sequence Function


(1) Number of I/O Points
Number of I/O
Digital input points 3
Digital output points 3

(2) Types of Command


Number of
Remark
commands
Number of basic Load, AND, OR, Timer,
13
command types Counter, etc.
Comparison, reverse, addition/
Number of applica- subtraction/multiplication/
73
tion command types division, logic operation, high/
low limiter, etc.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
3
Communication Function
Communication
Function Method Interface Targets Max connection
Data
PLC and others,
A standard industry protocol UT75A, UT55A,
Modbus allowing communications UT52A, UT35A,
between the controller and Slave RS-485 31 units
(RTU/ASCII) UT32A, UP55A,
devices such as PCs, PLCs, UP35A, UP32A,
and DCSs. UM33A (*1)
A protocol allowing multiple UT75A, UT55A, Read/Write: 4
controllers to send and RS-485 UT52A, UT35A, units
Peer to peer receive data between Multi-drop (2 wire UT32A, UP55A, Read only : 28
one another. The Ladder only) UP35A, UP32A units PV, SP, OUT,
Program is used.
A protocol to coordinate the UT75A, UT55A, ALM etc
Coordinated operation of two or more UT52A, UT35A, Master : 1 unit
Master/Slave RS-485
Communication instruments controlling the UT32A, UP55A, Slave : 31 units
same process. UP35A, UP32A(*1)
The proprietary Yokogawa PC and others,
protocol allowing UT75A, UT55A,
PC link communications to PCs, UT52A, UT35A,
PLCs and touch panels. Slave RS-485 31units
UT32A, UP55A,
A protocol to communicate UP35A, UP32A,
Ladder UM33A(*1)
to PLCs.
*1: UT digital indication controllers can be connected.
Physical Interface
RS-485 Standard : EIA RS-485
Communication method : Two-wire harf-duplex or four-wire harf-duplex, start-stop synchoronization,
and non-procedural
Baud rate : 600,1200,2400,4800,9600,19200 or 38400bps, Peer to peer communication is fixed at 19200bps
Maximum communication distance : 1200m
Terminating resistor : 220Ω (External)

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
4
n Hardware Specifications The accuracy is that in the standard operating condi-
tions: 23 ±2°C, 55 ±10%RH, and power frequency at
Display Specifications 50/60 Hz.
• PV display *1: ±0.3°C and ±1 digit in the range between 0 and 100°C
5-digit, 14-segment active color LCD (white/red) ±0.5°C ±1 digit in the range between -100 and 200°C
Character height: 13.0 mm *2: W-5% Re/W-26% Re (Hoskins Mfg.Co.), ASTM E988
• Data display • Applicable standards: JIS, IEC and DIN (ITS-90) for ther-
5-digit, 11-segment color LCD (orange) mocouples and resistance-temperature detectors (RTD)
• Bar graph display • Input sampling period: Synchronized to control period
12-segment color LCD (orange) • Burnout detection
Upscale and downscale of function, and OFF can
Universal Input Specifications (PV1, PV2)
be specified for the standard signal of thermocou-
• Number of input points: 2 ple and resistance-temperature detector (RTD).
• Types of input, instrument range, and measurement For integrated signal input, 0.1 V or 0.4 mA or less
accuracy (see the table below) is judged as a burnout.
Instrument range • Input bias current: 0.05 μA (for thermocouple and
Types of input Accuracy
°C °F resistance-temperature detector (RTD))
-270.0 to 1370.0°C -450.0 to 2500.0°F ±0.1% of instrument
range ±1 digit for 0°C
• Resistance-temperature detector (RTD) measured
K -270.0 to 1000.0°C -450.0 to 2300.0°F
-200.0 to 500.0°C -200.0 to 1000.0°F or more current: About 0.16 mA
J -200.0 to 1200.0°C -300.0 to 2300.0°F ±0.2% of instrument • Input resistance
-270.0 to 400.0°C -450.0 to 750.0°F range ±1 digit for less
than 0°C 1 MΩ or more for thermocouple/mV input
However, ±2% of About 1 MΩ for voltage input
instrument range
±1 digit for less than
About 250 Ω for current input (with built-in shunt
T
0.0 to 400.0°C -200.0 to 750.0°F -200°C of thermocouple resistance)
K ±1% of instrument
range ±1 digit for less
• Allowable signal source resistance
than -200°C of thermo- 250 Ω or less for thermocouple/mV input
couple T Effect of signal source resistance: 0.1 μV/Ω or less
±0.15% of instrument
range ±1 digit for 400°C 2 kΩ or less for DC voltage input
B 0.0 to 1800.0°C 32 to 3300°F
or more Effect of signal source resistance: about
±5% of instrument
range ±1 digit for less
0.01%/100 Ω
than 400°C • Allowable wiring resistance
S 0.0 to 1700.0°C 32 to 3100°F ±0.15% of instrument Up to 150 Ω per line for resistance-temperature
Thermocouple

R 0.0 to 1700.0°C 32 to 3100°F range ±1 digit


±0.1% of instrument detector (RTD) input (conductor resistance
range ±1 digit between the three lines shall be equal)
N -200.0 to 1300.0°C -300.0 to 2400.0°F ±0.25% of instrument
range ±1 digit for less
Effect of wiring resistance: ±0.1°C/10 Ω
than 0°C • Allowable input voltage/current
E -270.0 to 1000.0°C -450.0 to 1800.0°F ±0.1% of instrument
range ±1 digit for 0°C
±10 V DC for thermocouple/mV/mA or resistance-
L -200.0 to 900.0°C -300.0 to 1600.0°F
-200.0 to 400.0°C -300.0 to 750.0°F or more temperature detector (RTD) input
±0.2% of instrument ±20 V DC for V input
range ±1 digit for less
than 0°C ±40 mA DC for mA input
U
0.0 to 400.0°C -200.0 to 1000.0°F However, ±1.5% of • Noise reduction ratio
instrument range ±1 digit
for less than -200.0°C of
40 dB or more (at 50/60 Hz) in normal mode
thermocouple E 120 dB or more (at 50/60 Hz) in common mode
W (*2) 0.0 to 2300.0°C 32 to 4200°F
±0.2% of instrument • Reference junction compensation error
range ±1 digit
Platinel ±0.1% of instrument ±1.0°C (15 to 35°C)
0.0 to 1390.0°C 32.0 to 2500.0°F
2 range ±1 digit ±1.5°C (-10 to 5°C and 35 to 50°C)
±0.5% of instrument
range ±1 digit for 800°C Contact Input Specifications (DI)
PR20-40 0.0 to 1900.0°C 32 to 3400°F or more
Accuracy not guaran- • Number of points: 3 points (standard)
teed for less than 800°C • Input type: no-voltage contact input or transistor con-
W97
Re3-W75 0.0 to 2000.0°C 32 to 3600°F
±0.2% of instrument tact input
range ±1 digit
Re25 • Input contact capacity: 12 V DC, 10 mA or more
-200.0 to 500.0°C -300.0 to 1000.0°F
±0.1% of instrument
Be sure to use a contact with a minimum ON
detector (RTD) 3-wire
Resistance-temperature

range ±1 digit (*1)


JPt100
±0.1% of instrument current of 1 mA or less
-150.00 to 150.00°C -200.0 to 300.0°F
range ±1 digit • ON/OFF detection
-200.0 to 850.0°C -300.0 to 1560.0°F ±0.1% of instrument
-200.0 to 500.0°C -300.0 to 1000.0°F range ±1 digit (*1) For no-voltage contact input:
Contact resistance 1 kΩ or less in ON state
Pt100
±0.1% of instrument
Contact resistance 50 kΩ or more in OFF state
-150.00 to 150.00°C -200.0 to 300.0°F
range ±1 digit Transistor contact input:
2 V or less in ON state
0.400 to 2.0000 V - Leak current 100 μ A or less in OFF state
Standard
signal
1.000 to 5.000 V - • Status detection minimum hold time: control period
4.00 to 20.00 mA -
0.000 to 2.000 V -
±0.1% of instrument + 50 ms
DC voltage 0.00 to 10.00 V -
range ±1 digit • Application: SP switching, operation mode switching,
-10.00 to 20.00 mV - event input
DC current 0.00 to 20.00 mA -

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
5
Control Output Specifications (OUT, OUT2) • Heater current detection resolution: Within 1/250 of
• Number of points: 2 CT input range span
• Output functions: • Disconnection detection ON time: Minimum 200 ms.
Current output or voltage pulse output (for time proportional output)
• Current output: Safety and EMC Standards
4 to 20 mA DC or 0 to 20 mA DC/load resistance • Safety:
600 Ω or less Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-
• Current output accuracy: 2-201 (CE), IEC/EN 61010-2-030 (CE), approved by
±0.1% of span (however, ±5% of span for 1 mA CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL
or less) 61010-1.
The accuracy is that in the standard operating Installation category: II
conditions: 23 ±2°C, 55 ±10%RH, and power Pollution degree: 2
frequency at 50/60 Hz Measurement category: I (CAT I) (UL, CSA)
• Voltage pulse output O (Other) (CE)
Application: time proportional output Rated measurement input voltage: Max. 10 V DC
ON voltage: 12 V or more/load resistance of 600 Rated transient overvoltage: 1500 V (*)
Ω or more *: This is a reference safety standard value for measure-
OFF voltage: 0.1 V DC or less ment category I of CSA/UL 61010-1, and for measure-
Time resolution: 10 ms or 0.1% of output value, ment category O of IEC/EN 61010-2-030. This value is
whichever is larger not necessarily a guarantee of instrument performance.
Control Relay Contact Output Specifications • EMC standards:
(OUT, OUT2) Compliant with
CE marking
• Types of contact and number of points: 2 points, EN 61326-1 Class A, Table 2 (For use in industrial
1a-contact point (common is separated) locations),
• Contact rating EN 61326-2-3
1a-contact: 3 A at 240 V AC or 3 A at 30 V DC *: The instrument continues to operate at a measurement
(resistance load) accuracy of within ±20% of the range during testing.
*: The control output should always be used with a load EN 55011 Class A, Group 1
of 10 mA or more. EN 61000-3-2 Class A
• Application: time proportional output, ON/OFF output EN 61000-3-3
• Time resolution for control output: 10 ms or 0.1% of EMC Regulatory Arrangement in Australia and New Zealand
output value, whichever is larger EN 55011 Class A, Group 1
Alarm Relay Contact Output Specifications • KC marking: Electromagnetic wave interference
(ALM) prevention standard, electromagnetic wave protection
• Types of contact and number of points: 3 points, standard compliance
1a-contact points (common is separated) Power Supply Specifications and Isolation
• Contact rating
1a-contact: 1 A at 240 V AC or 1 A at 30 V DC • Power supply
(resistance load) Rated voltage: 100 to 240 V AC (+10%/-15%), 50/60 Hz
*: The alarm output should always be used with a load 24 V AC/DC (+10%/-15%) (When the
of 1 mA or more. /DC option is specified)
• Application: alarm output, FAIL output, etc. • Power consumption: 15 VA (For the /DC option,
24 V DC: 7 VA, 24 V AC: 11 VA)
Heater Break Alarm Specifications (for /HA Option) • Storage: Nonvolatile memory
• Function: Measures the heater current using an • Allowable power interruption time: 20 ms (at 100 V AC)
external current transformer (CT) and generates a • Withstanding voltage
heater break alarm when the measured value is less 2300 V AC for 1 minute between primary and
than the disconnection detection value. secondary terminals (UL, CSA)
• Number of input points: 2 points 3000 V AC for 1 minute between primary and
• Number of output points: 2 points (transistor contract secondary terminals (CE)
output) 1500 V AC for 1 minute between primary terminals
• CT input resistance: about 9.4 Ω 500 V AC for 1 minute between secondary
• CT input range: 0.0 to 0.1 Arms (0.12 Arms or more terminals
cannot be applied) (Primary terminals = Power (*) and relay output
• Heater current alarm setting range: OFF, 0.1 to 300.0 terminals, Secondary terminals = Analog I/O signal
Arms terminals, contact input terminals, communication
Heater current measured value display range: 0.0 to terminals, and functional grounding terminals.)
360.0 Arms *: Power terminals for 24 V AC/DC models are the
*: The CT ratio can be set. CT ratio setting range: 1 to 3300 secondary terminals.
• Recommended CT: CT from URD Co. Ltd. • Insulation resistance
CTL-6-S-H: CT ratio 800, measurable current Between power supply terminals and a grounding
range: 0.1 to 80.0 Arms terminal: 20 MΩ or more at 500 V DC
CTL-12L-30: CT ratio 3000, measurable current
range: 0.1 to 180.0 Arms
• Heater current measurement period: 200 ms
• Heater current measurement accuracy: ±5% of CT
input range span ±1 digit (CT error is not included)

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
6
• Isolation specifications Construction, Mounting, and Wiring
PV1 (universal) input terminal
• Dust-proof and drip-proof: IP66 (Front panel) (Except
for side-by-side close mounting)/NEMA4 *
PV2 (universal) input terminal *: Hose-down test only
Control (analog) output terminal (OUT, OUT2) • Material: Polycarbonate resin (Flame retardancy: UL94 V-0)
(not isolated between the analog output terminals)
• Case color: White (Light gray) or Black (Light Char-
Control relay (2 a-contact) output terminal (OUT, OUT2) coal gray)
Alarm-1 relay (a-contact) output terminal
Internal
circuits
Power
supply
• Weight: 0.5 kg or less
Alarm-2 relay (a-contact) output terminal
• External dimensions (mm):
48 (width) x 96 (height) x 65 (depth from the
Alarm-3 relay (a-contact) output terminal
panel surface)
Contact input terminal (3 points) • Mounting: DIN rail mounting type
RS485 communication terminal
• Panel cutout dimensions (mm):
Current transformer input terminal
45+0.6/0 (width) x 92+0.8/0 (height)
The circuits divided by lines are insulated mutually. • Mounting position: Up to 30 degrees above the hori-
zontal. No downward titling allowed.
Environmental Conditions • Wiring: M3 screw terminal with square washer (signal
Normal operating conditions wiring and power)
• Ambient temperature: -10 to 50°C (side-by-side
mounting: -10 to 40 °C)
• Ambient humidity: 20 to 90% RH (no condensation)
• Magnetic field: 400 A/m or less
• Continuous vibration (at 5 to 9 Hz) Half amplitude of
1.5 mm or less
(at 9 to 150 Hz) 4.9 m/s2 or less, 1 oct/min for 90 min-
utes each in the three axis directions
• Rapid vibration: 14.7 m/s2, 15 s or less
• Impact: 98 m/s2 or less, 11 msec.
• Installation altitude: 2,000 m or less above sea level
• Warm-up time: 30 minutes or more after the power is
turned on
• Start-up time within 10 s
Transportation and Storage Conditions
• Temperature: -25 to 70°C
• Temperature change rate: 20°C per hour or less
• Humidity: 5 to 95%RH (no condensation)

Effects of Operating Conditions


• Effect of ambient temperature
For voltage or TC input:
±1 μ V/°C or ±0.01% of F.S. (instrument
range)/°C, whichever is greater
For RTD input:
±0.05°C/°C (ambient temperature) or less
For current input:
±0.01% of F.S. (instrument range)/°C
For analog output:
±0.02% of F.S./°C or less
• Effect of power supply fluctuation:
For analog input: ±0.05% of F.S. (instrument range)
or less
For analog output: ±0.05% of F.S. or less
(Each within rated voltage range)

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
7
n Block Diagram
Loop-1 PV input Loop-2 PV input 接点入力

PV PV2 DI1 DI2 DI3

Input Type IN Input Type IN

Input unit UNIT Input unit UNIT

Input range/scale RH, RL SDP SH, SL Input range/scale RH, RL SDP SH, SL

Analog input bias A.BS Analog input bias A.BS

Analog input filter A.FL Analog input filter A.FL

Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software User’s Manual.

Loop-1
AUTO (ON)/MAN (OFF)
PV input bias BS PV input bias BS
switch
PV input filter FL PV input filter FL

Communication Communication Loop-1 and Loop-2


SPNO SP SPNO SP STOP (ON)/RUN (OFF)
RT RT
switch
Ratio bias computation RBS Target setpoints 1 to 4 Ratio bias computation RBS Target setpoints 1 to 4
REMOTE LOCAL REMOTE LOCAL
R/L R/L
Loop-2
AUTO (ON)/MAN (OFF)
SP limiter SPH, SPL SP limiter SPH, SPL switch
SP ramp rate UPR, DNR TMU SP ramp rate UPR, DNR TMU

PV display SP display PV display SP display


Loop-1 Loop-2
Control computation Control computation
CNT ALG CNT ALG

Output limiter OH, OL Output limiter OH, OL


Input error preset output EPO Input error preset output EPO
Normal Normal
When sensor burnout occurs When sensor burnout occurs
Manual preset output MPON Manual preset output MPON

Manual operation Manual operation


OH, OL OH, OL
Output limiter OLMT MAN AUTO Output limiter OLMT MAN AUTO
Loop-1 Loop-2
A/M A/M2
DI1 AUTO (ON)/MAN (OFF) DI3 AUTO (ON)/MAN (OFF)
switch switch
Preset output PO Preset output PO
STOP RUN STOP RUN
S/R Loop-2 S/R Loop-2
DI2 STOP (ON)/RUN (OFF) DI2 STOP (ON)/RUN (OFF)
switch switch
Output terminal assignment Output terminal assignment
OT OT

Alarm

Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.

For option code /HA


(PV high limit)

(PV high limit)


(PV low limit)

Heater break alarm


Loop-1 Loop-1
Alarm 2
Alarm 1

Alarm 3

Control Control
Output Output

OUT OUT OUT2 OUT2 AL1 AL2 AL3 HAL1 HAL2

Heater break Heater break


Relay Curren or voltage pulse Relay Curren or voltage pulse alarm 1 alarm 2

Terminal Parameter Function


Legend
Analog signal Contact signal Front panel key

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
8
n Terminal Arrangement
Terminal Arrangement for UT32A-D Dual Loop Controls
Loop-1 and Loop-2 control output Loop-2 PV input PV2 Loop-1 PV input PV1
Relay contact output Factory default: TC input RTD input Factory default: TC input RTD input
PV input type is PV input type is
OUT2 NO 101 undefined. A 301 undefined. A 201
+ 302 + 202
OUT NO 102 b 302 b 202
- 303 - 203
COM 103 B 303 B 203
Contact rating: 240 V AC, 3 A Current (mA) input Voltage (mV, V) input Current (mA) input Voltage (mV, V) input
30 V DC, 3 A (resistance load)
Factory default: Control output is relay.
- 303 + 302 - 203 + 202

Contact output ALM + 304 - 303 + 204 - 203

External contact output (relay)


Alarm-3 output UT
104
(PV high limit)
AL3
101 301 201 Loop-2 control output OUT2
-112 -312 -212
Common 105 Current/voltage pulse output
Control output is relay at factory default.
Alarm-2 output 101 301 201 Current output range can be changed.
(PV low limit) 106 + 205
AL2 102 302 202 0-20 mA DC,
4-20 mA DC,
Common 107 Voltage pulse (12 V)
103 303 203
Alarm-1 output - 206
(PV high limit) 108 104 304 204
AL1
Common 109 105 305 205

Relay contact rating: 240 V AC, 1 A 106 306 206 Loop-1 control output OUT
30 V DC, 1 A (resistance load)
107 307 207 Current/voltage pulse output
Control output is relay at factory default.
108 308 208 Current output range can be changed.
Power supply 0-20 mA DC,
+ 207
109 309 209 4-20 mA DC,
100-240 V AC power supply 24 V AC/DC power supply Voltage pulse (12 V)
110 310 210 - 208
N N
110 - 110
111 311 211
L L
111 + 111 112 312 212

112 112 Contact input DI


Allowable range: External contact input
100-240 V AC (+10%/-15%) (24 V AC/DC power supply: No-voltage UP +5V
UP Transistor contact
(free voltage) Option code /DC) contact
DI3
Loop-2 AUTO when DI3=ON
50/60 Hz shared
Loop-2 MAN when DI3=OFF
209 DI3 209
+5V
Loop-1 and Loop-2 STOP when DI2=ON DI2
210 DI2 210
RS-485 communication RS485 Heater break alarm HBA (Option code /HA) Loop-1 and Loop-2 RUN when DI2=OFF +5V
Loop-1 AUTO when DI1=ON
DI1
External contact output (transistor) Heater current detection input 211 DI1 211
RS-485 (Suffix code: Loop-1 MAN when DI1=OFF
UT COM
Type 2=1) Heater break alarm-1 HAL1 307 310
Common
212 COM 212
SDB(+) 307 output CT1
Heater break alarm-2
311 Contact rating: 12 V DC, 10 mA or more
SDA(-) 308
output
HAL2 308 CT2
Functions can be changed.
312
SG 309 Common COM 309 COM

RDB(+) 310 Transistor contact rating: 24 V DC, 50 mA

RDA(-) 311

n External Dimensions and Panel Cutout Dimensions


Unit: mm
11
48 65 Bracket Terminal cover (option)
20
105.2
91.6
94.6
96

Bracket
1 to 10 mm (panel thickness)
• General mounting • Side-by-side close mounting
70 min. [(N-1)×48+45] +0.6
0
+0.8
92 0

145
(53) min.
“N” stands for the number of controllers to be
installed.
92 +0.8
0
However, the measured value applies if N≥5.
Normal tolerance:
45+0.6
0 (25) ±(value of JIS B 0401-1998 tolerance class IT18)/2

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
9
n Model and Suffix Code
Model Suffix code Option code Description
Digital Indicating Controller (Power supply: 100-240 V AC)
UT32A
(provided with 3 DIs and 3 DOs)
Type 1:
-D Dual-loop type
Basic control
0 None
Type 2:Functions
1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire)
Type 3:Fixed code 0 None
-1 English (Default. Can be switched to other language by the setting.)
-2 German (Default. Can be switched to other language by the setting.)
Display language (*1)
-3 French (Default. Can be switched to other language by the setting.)
-4 Spanish (Default. Can be switched to other language by the setting.)
0 White (Light gray)
Case color
1 Black (Light charcoal gray)
Fixed code -00 Always "-00" (for Standard Code Model)
/HA Heater break alarm (*2)
/DC Power supply 24 V AC/DC
Option codes
/CT Coating (*3)
/CV Terminal cover
*1: English, German, French, and Spanish are available for the guide display.
*2: The /HA option can be specified when the Type 2 code is "0."
*3: When the /CT option is specified, the UT32A does not conform to the safety standards (UL and CSA) and CE marking (Prod-
ucts with /CT option are not intended for EEA-market).

n Items to be specified when ordering


Model and suffix codes, whether User’s Manual and QIC required.

n Standard accessories
Brackets (mounting hardware), Unit label, Operation Guide

n Special Order Items


Model code Suffix code Description
LL50A -00 Parameter Setting Software
X010 See the General Specifications (*) Resistance Module

*: Necessary to input current signal to voltage input terminal.


Name Model
Terminal cover UTAP002
User’s Manual (CD) UTAP003

User’s Manual
Product user’s manuals can be downloaded or viewed at the following URL. To view the user’s manual, you need to
use Adobe Reader 7 or later by Adobe Systems.
URL: http://www.yokogawa.com/ns/ut/im/

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 05P08D31-01EN Mar.14, 2016-00
Subject to change without notice.