Professional Documents
Culture Documents
MAG500-6000 Installation & Fault Finding
MAG500-6000 Installation & Fault Finding
1
Sensor shipped with Sensor-Prom installed in junction Box.
2
Remove Sensor Prom before burying sensor.
3
Make sure Sensor-Prom details match details of Magflow Sensor, Cal Factor & Serial Number
4
Install Sensor-Prom into transmitter REMOTE junction box (as shown).
Sensors: MAG1100, MAG3100, MAG3100W, MAG5100W
Electrode Circuit (Terminals 82, 0 and 83) Must be a three core cable with overall screen to
BS5308.
Do not use a twin pair or multi core cable.
Coil Circuit (Terminals 85 and 86) Same three core cable can be utilized on this
connection. Additional un-used core is not a
Problem on the coil circuit.
Use a single cable run from flow sensor to signal converter. Avoid junction boxes and terminal rails in
panels.
Full cable specification is 3 core BS5308 Part 1 or Part 2 (Braided screen or foil screen) Type 1 flexible
cable or type 2 armored cable.
i.e. BS5308, Part 1, Type 1, 3 core, 1.5mm section
Our own engineers use a 1.5mm section for ease of handling. Manual states minimum 0.5mm section for
the coil circuit and 0.2mm section for the electrode circuit.
If armoured cable is used suitable glands to fit our PG 13.5 threaded cable entries will be required.
If the guidelines are not followed the flowmeter could give unstable readings due to electrical
interference. If the flowmeter works to a satisfactory standard, it will not pass the Verificator insulation
test. The Verificator will identify the following points and fail the system.
NOTE:
Current Output - “Time Constant” effects response time of unit, (Mag 6000/5000) not just the mA
output.
Time Constant can only be altered if mA is set to ON.
If the output terminals (31, 32) are not connected , Turn off mA output after adjusting “Time
Constant”, this will prevent P42 alarm. May require power re-cycle to clear alarm.
2. Insulation Tester (Megger) – Required to test resistance to earth for Coil Connections.
Fluke Insulation & DMM combined Fluke (1577 or 1587) (Recommendation only)
Fluke Insulation & DMM combined Fluke (1577 or 1587) (Recommendation only)
4. Verificator – May be required as a last resort. Will help identify wiring inadequacies
that other instrument can not detect. Talk to Siemens.
The converter system is equipped with an error and status log system with 4 groups of information.
1. Information without a functional error involved
2. Warnings which may cause malfunction in the application. The cause of the error may
disappear on its own.
3. Permanent errors which may cause malfunction in the application. The error requires an
operator intervention.
4. Fatal error which is essential for the operation of the flowmeter
2 menus are available in service and operator menus for registration of information and errors
1. Error pending
2. Status log
A replacement can easily be done as all settings are stored in and downloaded from the SENSORPROM. unit
- no extra settings need to be made. If no spare transmitter is available - then check transmitter according to
check table.
5. Using Moving coil meter. Check resistance between 82 & 0, then 83 & 0. At this stage the pipe needs
to be full because the resistance of the material / fluid in the pipe is being measured. The recorded
values should be between 5 and 50K but should be within 2K of each other. Any deviation would
indicate a wiring problem with regards to electrode circuit, connections 82,0,83.
6. Always repeat tests at sensor end with all remote connections removed. This will establish if the Mag
sensor is faulty, or if poor / incorrect remote connections are causing inaccuracies.
7. If all the above tests have proved successful and there are still inaccuracies or unstable readings then
the Siemens Verificator could be use to highlight any more sensitive errors.
If possible try a signal converter compact mounted in order to eliminate cable problems. From our experience
incorrect cable installation is the main cause of Insulation failure when using the Verificator.