31145

6300
12420 1028 4244 1028 12420

ANCHOR BOLTS (76x2 BOLTS)


(1) JAULA DE PERNOS (76x2 PERNOS) (1)
NOTES
HA-30/F/20/XC2 HA-50/F/20/XC2 NATURAL GROUND LEVEL

210

100
COTA NATURAL DEL TERRENO INPUT DATA
2% 2% Foundation load document:

620

3120
3120

3010

2500
(2) MATERIALS USED FOR THE CALCULATION AND THEIR MAIN CHARACTERISTICS
1 1 (2)

300
(1)
1 1 CONCRETE:Foundation's slab is made of concrete HA-30/F/20/XC2 (fck=30 MPa).
(1)
Foundation's pedestal is made of concrete HA-50/F/20/XC2 (fck=50 MPa).

300
300
The minimum cover considered in the design is equal to 50 mm.
STEEL: Foundation is made of steel B500SD (fyk=500 MPa).
BLINDING CONCRETE h=100mm

100
6300

500 24400 100 SOIL CHARACTERISTICS


Main geotechnical features are the following:
SECTION A-A'
Minimum soil bearing capacity: 135 kPa
Minimum soil static elastic modulus: 45MPa
SCALE 1/60
ESCALA 1/60
Poisson ratio: 0,35

(2)
Excavation slope: 1H:1V
Buoyancy: NO
Seismic hazard risk: NO
Soil aggressiveness: NO

TOWER INTERFACE GEOMETRY


The anchor bolt cage interface geometry has been considered.

(1)
In the detailed design it will be checked that the quality of slab and pedestal concrete are suitable.
(2)
The slope inclination must be adapted to the particular conditions of the terrain according to the nature of the material encountered on site.
(3)
Current geometry is valid when considering a 2% slope at the stuffed material.
(4)
Refill geometry must be as shown in this drawing during its whole lifetime.
(5)
In the detail and constructive design, the tubes and the distribution of medium voltage electrical wiring and optical fiber according to the
3D VIEW specifications of the wind turbine manufacturer must be considered, as well as the pedestal for support of the access ladder to the wind turbine.
VISTA 3D

NOTAS
DATOS INICIALES
Foundation_Load_Drawing_6.1-158_50Hz_121mHH_PRD123_EN_r03
Foundation_Load_Drawing_6.1-158_50Hz_121mHH_PRD123_EN_r03

(1)
HA-30/F/20/XC2 (fck=30 MPa).
(1)
HA-50/F/20/XC2 MPa (fck=50 MPa).

A A'
Coeficiente de Poisson: 0,35

(2)

(1)

(2)

(3)

(4)

(5)
En el de detalle y constructivo considerarse el paso de tubos y para el paso del cableado de media
y fibra de acuerdo a las especificaciones del fabricante de aerogeneradores, como el pedestal para apoyo de la escalera de acceso al
aerogenerador.

PEDESTAL CONCRETE HA-50/F/20/XC2(1) (fck=50MPa)(1)


(1)
18
(fck=50MPa)(1)

SLAB CONCRETE HA-30/F/20/XC2(1) (fck=30 MPa)(1)


(1)
605
(fck=30 MPa)(1)
01 16/05/2022 MFJ SOB AHA

48 00 13/04/2022 ATR SOB AHA

DATE DRAFTED CHECKED APPROVED DESCRIPTION


(6) REV.
STEEL REINFORCEMENT B-500-SD (kg) FECHA DIBUJADO REVISADO APROBADO
(6)
77500
ACERO CORRUGADO B-500-SD (kg)
CLIENT/CLIENTE AUTHOR/AUTOR
MS Enertech S.L.
1926
Tel. +(34) 947 041 052
Tel. +(34) 947 218 542
www.ms-enertech.com
1229

PROJECT/PROYECTO
GROUT VOLUME (fck=90MPa)(1)
(1)
1,89
VOLUMEN DE GROUT (fck=90MPa)
GE 6.1-158 HH121m IEC Class S
(6)
124.4 FILE NAME/NOMBRE DEL ARCHIVO SCALE/ESCALA DATE/FECHA
(6)
A1 SPECIFIED/INDICADAS
E-Aragon_GE_6.1_158_HH121m-CIM-B-P-EI-R01.dwg
MAY 2022
(1)
In the detailed design it will be checked that the quality of slab and pedestal MAYO 2022
concrete and grout are suitable.
PLAN VIEW (1)
REV.
PLANTA
SCALE 1/60
ESCALA 1/60
(6)
The exact steel reinforcement quantity shall be calculated in a the detailed design.
(6)
01 01
01 OF/DE ___
SHEET/HOJA ___ 01