EP-51658-P-CAE-0201 (00) Phase A TG CE

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

EXPRO PRODUCTION

FOR

IN AMENAS ON DEMAND COMPRESSION

Document Title: TIGUENTOURINE CAUSE & EFFECT


Fast Track

Expro Document No: EP-51658-P-C&E-0201

00 05-Dec-23 Issued for Construction IB HA MT


DD 23-Mar-23 RE-ISSUED FOR APPROVAL (Fast Track) HA IB -
CC 09-Mar-23 ISSUED FOR APPROVAL (Fast Track) HA TK
BB 30-Nov-22 ISSUED FOR HAZOP HA - -
AA 16-Aug-22 ISSUED FOR REVIEW CZ TK -
REV DATE DESCRIPTION BY CHECKED APPROVED

PROJECT DOCUMENTS ARE CONTROLLED DOCUMENTS.


REVISIONS ARE DENOTED  IN RIGHT MARGIN

COMPANY:
Sonatrach
CONTRACTOR: CONTRACTOR REF:
Expro EP-51658
EXPRO P&IDs USED FOR THE GENERATION OF THIS REVISION OF THE CAUSE & EFFECT

P&ID Number P&ID Description Revision

EP-51658-P-PID-0203 P&ID INLET HP SEPARATOR GG

EP-51658-P-PID-0204 P&ID HP COMPRESSOR & FUEL GAS PACKAGE GG

EP-51658-P-PID-0210 P&ID UTILITIES FF

EP-51658-P-PID-0211 P&ID FIRE & GAS DETECTION FF

EP-51658-P-PID-0220 P&ID COMPRESSOR PACKAGE ZZ

EP-51658-P-PID-0221 P&ID FUEL GAS SKID ZZ

LIST OF ABBREVIATIONS

X - Input gives output in column shown


A - Activate
CL - Close
D - Control System input/alarm only
DA - Direct Acting (no output action required)
ESD 1 - Emergency Shutdown without Blowdown
ESD 0 - Emergency Shutdown with Blowdown
I/L NO. - Interlock Numbering
MO - Maintenance override
NZS - Drive
OP - Open
P - Permissive
PSD - Process Shutdown
SB - Startup bypass
SD - Shut Down
SP - Stop
ST - Start
T - Time delay of 120 seconds, associated with Action
USD - Unit Shut Down

EXPRO DOC. No.: EP-51658-P-C&E-0201 CAUSE AND EFFECT DIAGRAM SHEET 2 OF 3


EXPRO Notes

1,3

1
P&ID No. :

PID-0203

PID-0204

TBC

-
HP SEPARATOR INLET EMERGENCY

ESD 0 SHUTDOWN COMMAND TO

ESD 1 SHUTDOWN COMMAND TO


GAS EXPORT SHUTDOWN VALVE

GAS EXPORT SHUTDOWN VALVE


EMERGENCY SHUTDOWN WITH
In-Amenas Tiguentourine CAUSE AND EFFECT DIAGRAM

EFFECT

EMERGENCY SHUTDOWN
Description
Rev 00 Fast Track

SHUTDOWN VALVE

HP COMPRESSOR

HP COMPRESSOR
BLOWDOWN
Action

CL

CL

CL

A
-

ESDV 5004 / SDV-001


ESDV 5000

ESDV 5003

XA-XXXX

XA-XXXX
Tag No

ESD 0

ESD 1
CAUSE INITIATING DEVICE

SD I/L
Rev EXPRO P&ID No. Description Set Point Unit Voting TAG No D SB MO 1 2 3 5 8 9 10 11
LEVEL NO.

- - ESD 0 - EMERGENCY SHUTDOWN WITH BLOWDOWN - ESD 0 ESD 0 X X X X X


- - ESD 1 - EMERGENCY SHUTDOWN - ESD 1 ESD 1 X X X X X
GG PID-0203 HP INLET PRESSURE TRANSMITTER HIGH HIGH 16 Barg HH PIT-1001 USD X X X X
GG PID-0203 HP INLET PRESSURE TRANSMITTER LOW LOW 2 Barg LL PIT-1001 USD X X X X
FF PID-0204 HP COMPRESSORS DISCHARGE PRESSURE TRANSMITTER HIGH HIGH 39 Barg HH PIT-5003 USD X X X X X X
FF PID-0204 HP COMPRESSORS DISCHARGE PRESSURE TRANSMITTER LOW LOW 2 Barg LL PIT-5003 USD X X X X X X
- - DELETED - -
- - ESD 1 SHUTDOWN SIGNAL FROM HP COMPRESSOR (Note 1) - - XA-XXXX ESD 1 X X X
FF PID-0203 CLOSED LIMIT SWITCH FOR ESDV 5000 - - ZSC-5000 ALARM X
FF PID-0203 OPEN LIMIT SWITCH FOR ESDV 5000 - - ZSC-5000 ALARM X
EE PID-0204 CLOSED LIMIT SWITCH FOR ESDV 5003 - - ZSC-5003 ALARM X
EE PID-0204 OPEN LIMIT SWITCH FOR ESDV 5003 - - ZSO-5003 ALARM X
FF PID-0211 FUEL GAS SKID GAS DETECTOR - 1ooN GD-2009 ESD1 X X X
FF PID-0211 COMPRESSOR SKID GAS DETECTOR - 1ooN GD-2000 ESD1 X X X
FF PID-0211 COMPRESSOR SKID GAS DETECTOR - 1ooN GD-2001 ESD1 X X X
FF PID-0211 COMPRESSOR SKID GAS DETECTOR - 1ooN GD-2002 ESD1 X X X
FF PID-0211 FUEL GAS SKID FLAME DETECTOR - 1ooN FD-2008 ESD 0 X X X
FF PID-0211 COMPRESSOR SKID FLAME DETECTOR - 1ooN FD-2000 ESD 0 X X X
FF PID-0211 COMPRESSOR SKID FLAME DETECTOR - 1ooN FD-2001 ESD 0 X X X
FF PID-0211 PIPERACK FLAME DETECTOR - 1ooN FD-2009 ESD 0 X X X
FF PID-0211 CONTROL ROOM ESD PUSH BUTTON - - ESD-2000 ESD 0 X
FF DELETED - -

FF PID-0211 SAFE AREA ESD PUSH BUTTON - - ESD-2003 ESD 0 X


FIBRE OPTIC CABLE (FUTURE SCOPE) - HOLD 2
TBC CLOSED LIMIT SWITCH FOR ESDV 5004/SDV-0001 (HOLD 1,3) - - ZSC-5004/0001 ALARM X
TBC OPEN LIMIT SWITCH FOR ESDV 5004/SDV-0001 (HOLD 1,3) - - ZSO-5004/0001 ALARM X
NOTES: HOLDS:

1. FOR COMPRESSOR CAUSE & EFFECT - REFER TO DOCUMENT (EP-51658-P-CAE-0202 (ZZ)) 1. TAG NUMBERS TO BE CONFIRMED
2. FOR FUEL GAS SKID CAUSE & EFFECT - REFER TO DOCUMENT (EP-51658-P-CAE-0203 (ZZ)) 2. FIBRE OPTIC CABLE SHALL BE INSTALLED AFTER FAST TRACK PHASE
3. 1 OUT OF N FIRE AND/OR 1 OUT OF N (40% LEL) GAS DETECTION SHALL INITIATE AN ESD SHUTDOWN AND IT IS CONSIDERED CONFIRMED (FIRE OR GAS DETECTION) 3. SDV REQUIREMENT DURING FAST TRACK PHASE (PLC TO BE CONFIGURED
WITH PROVISION TO OVER-RIDE THE ACTION INCLUDING LIMIT SWITCHES)

EXPRO DOC. No.: EP-51658-P-C&E-0201 CAUSE AND EFFECT DIAGRAM