Professional Documents
Culture Documents
Oi Awt210-En I
Oi Awt210-En I
A B B M E A S U R E M E N T & A N A LY T I C S | O P E R AT I N G I N S T R U C T I O N | O I/AW T 2 1 0 - E N R E V. I
AWT210
2-wire conductivity, pH/ORP pION transmitter
The AWT210 transmitter is available with a AWT210 transmitter – Data Sheet DS/AWT210
AWT210 transmitter –
SI/AWT210
Safety Instruction
2 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
Contents
1 Health and safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 6 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . 17
Document symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Terminal connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Safety precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ground connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Potential safety hazards. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Gland entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
AWT210 transmitter – electrical damage to the Communication module connections. . . . . . . . . . . . . . . 18
equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 HART module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Safety standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FOUNDATION Fieldbus module . . . . . . . . . . . . . . . . 18
Product symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Profibus PA module . . . . . . . . . . . . . . . . . . . . . . . . . . 18
End-of-life battery disposal . . . . . . . . . . . . . . . . . . . . 5 pH/ORP/pION sensor module connections. . . . . . . . . . 19
Information on ROHS Directive 2011/65/EU (RoHS II). 5 Standard sensors without diagnostic functions19
Standard sensors with diagnostic functions . . . 19
2 Cybersecurity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Conductivity sensor module connections. . . . . . . . . . . 20
2-electrode sensors . . . . . . . . . . . . . . . . . . . . . . . . . 20
3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 4-electrode sensors . . . . . . . . . . . . . . . . . . . . . . . . . 20
Name plate/certification label . . . . . . . . . . . . . . . . . . . . . . 6 Toroidal sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Transmitters without hazardous area approval . . 6 Gland entries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Transmitters with cFMus approval and ATEX, Fitting the EZLink modules . . . . . . . . . . . . . . . . . . . . . . . . 21
IECEx & UKEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Connecting the EZLink sensors. . . . . . . . . . . . . . . . . . . . 22
Long cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4 Hazardous area considerations . . . . . . . . . . . . . . 7 Hot plug-in (EZLink sensors only). . . . . . . . . . . . . . . . . . . 22
Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Sensor addition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CE & UKEX Marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Sensor replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Ignition protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Replacing the sensor with a sensor of the same
Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Interconnection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 To use sensor setup parameters from the new
Power supply for intrinsically safe applications . 7 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Service and repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Risk of electrostatic discharge . . . . . . . . . . . . . . . . . 7 Operator Page – normal conditions. . . . . . . . . . . . . . . . . 23
Hazardous area relevant information. . . . . . . . . . . . . . . . 8 Operator Page – alarm conditions. . . . . . . . . . . . . . . . . . 24
cFMus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Operator menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ATEX, IECEx & UKEX . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Signals View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Specific conditions of use . . . . . . . . . . . . . . . . . . . . . . . . . 12 Standard sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
EZLink sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5 Mechanical installation . . . . . . . . . . . . . . . . . . . . . 13
Sensor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8 Diagnostic alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Transmitter installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Transmitter dimensions . . . . . . . . . . . . . . . . . . . . . . 13 9 Password security and Access Level . . . . . . . . . 28
Fitting communication modules . . . . . . . . . . . . . . 13 Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Write protect switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Optional installation accessories . . . . . . . . . . . . . . 13 Setting passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Password recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Panel mounting (optional) . . . . . . . . . . . . . . . . . . . . 15 Advanced level password recovery . . . . . . . . . . . 29
Pipe mounting (optional) . . . . . . . . . . . . . . . . . . . . . 16 Service level password recovery . . . . . . . . . . . . . . 29
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 3
12 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
pH sensor calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Auto Buffer Cal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
1-point manual calibration . . . . . . . . . . . . . . . . . . . 52
2-point manual calibration . . . . . . . . . . . . . . . . . . . 52
2-electrode conductivity sensor calibration. . . . . . . . . 53
4-electrode conductivity sensor calibration. . . . . . . . . 54
Toroidal conductivity sensor calibration. . . . . . . . . . . . 54
PV Zero calibration . . . . . . . . . . . . . . . . . . . . . . . . . . 54
PV Span calibration . . . . . . . . . . . . . . . . . . . . . . . . . . 55
13 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
DANGER WARNING
The signal word ‘DANGER’ indicates an imminent danger. Bodily injury.
Failure to observe this information will result in death or
To ensure safe use when operating this equipment, the
severe injury.
following points must be observed:
2 Cybersecurity
Product recycling and disposal This product is designed to be connected to and to
communicate information and data via a digital communication
(Europe only) interface. It is your sole responsibility to provide and
continuously ensure a secure connection between the product
ABB is committed to ensuring that the risk of any and your network or any other network (as the case may be).
environmental damage or pollution caused by any of You shall establish and maintain any appropriate measures
its products is minimized as far as possible. The (such as but not limited to the application of authentication
European Waste Electrical and Electronic Equipment measures etc.) to protect the product, the network, its system
(WEEE) Directive that initially came into force on and the interface against any kind of security breaches,
August 13 2005 aims to reduce the waste arising from unauthorized access, interference, intrusion, leakage and/or
electrical and electronic equipment; and improve the theft of data or information.
environmental performance of all those involved in
the life cycle of electrical and electronic equipment. ABB Ltd and its affiliates are not liable for damages and/or
In conformity with European local and national losses related to such security breaches, any unauthorized
regulations, electrical equipment marked with the access, interference, intrusion, leakage and/or theft of data
above symbol may not be disposed of in European or information.
public disposal systems after 12 August 2005.
NOTICE
For return for recycling, please contact the equipment
manufacturer or supplier for instructions on how to return
end-of-life equipment for proper disposal.
3 Overview
Name plate/certification label
The following name plates are examples only. The name
plates attached to the transmitter may be different.
Wall mounting
bracket* Transmitters without hazardous area approval
ABB Ltd. St Neots, PE19 8EU, UK
Display
ABB Ltd. Stonehouse, GL10 3TA, UK (Manf.)
AWT210 2 Wire Transmitter
AWT200050 1725 2809
Serial No.: 3K210000000000
Supply:
Transmitter HART 14-30VDC, 4-20mA
Keypad door lock FF/PA 9-24VDC, 15mA
DATE OF MANUFACTURE: MM/YYYY
Tamper-evident seal
attachment point
Factory reset Write protect II 1 G Ex ia IIC T4 Ga IS: Class I, Div 1 Gps ABCD T4
FM18ATEX0017X / IECEx FME 18.0001X Class II, Div 1 Gps EFG T4
ON switch
switch FM22UKEX0046X C US Class I, Zone 2 AEx/Ex ic IIC T4 Gc
OFF Installation Dwg. AWT200034
II 3 G Ex ic IIC T4 Gc
APPROVED -25 C ≤ Ta ≤ +60 C
Exia
FM21ATEX0011X / IECEx FME 18.0001X NI: Class I, Div 2 Gps ABCD
FM22UKEX0047X Class II/III, Div 2 Gps FG
Installation Dwg. AWT200035 -25 C ≤ Ta ≤ +60 C
Sensor Module Fitted
-20 C ≤ Ta ≤ +60 C / IP66 FM18US0040X / FM18CA0019X
Toroidal Conductivity Module: Installation Dwg.
Communications Module Fitted AWT210xxC1xxxxxxxxxx USA: AWT200030 & AWT200031
HART Module: 2-Electrode Conductivity Module: Canada: AWT200032 & AWT200033
AWT210xxxxH1xxxxxxxx AWT210xxC2xxxxxxxxxx
Fieldbus Module: 4-Electrode Conductivity Module: WARNING: SUBSTITUTION OF
AWT210xxxxF1xxxxxxxx AWT210xxC4xxxxxxxxxx COMPONENTS MAY IMPAIR INTRINSIC
Profibus Module: Digital EZLink Module: SAFETY.
AWT210xxxxP1xxxxxxxx AWT210xxD1xxxxxxxxxx AVERTISSEMENT: LA SUBSTITUTION
pH/ORP Module: DE COMPOSANTS PEUT NUIRE À LA
AWT210xxP1xxxxxxxxxx SÉCURITÉ INTRINSÈQUE.
Communications module Sensor module Transmitters with cFMus approval and ATEX, IECEx & UKEX
Plastic enclosure
*Panel- and pipe-mount options are also available – see page 13 II 1 G Ex ia IIC T4 Ga IS: Class I, Div 1 Gps ABCD T4
FM18ATEX0017X / IECEx FME 18.0001X
FM22UKEX0046X
FM Class II, Div 1 Gps EFG T4
Class I, Zone 2 AEx/Ex ic IIC T4 Gc
Figure 1 AWT210 transmitter – main components Installation Dwg. AWT200034 -25 C ≤ Ta ≤ +60 C
II 3 G Ex ic IIC T4 Gc Exia
FM21ATEX0011X / IECEx FME 18.0001X FM18US0040X / FM18CA0019X
FM22UKEX0047X Installation Dwg.
Installation Dwg. AWT200035
NOTICE
Sensor Module Fitted USA: AWT200030
-20 C ≤ Ta ≤ +60 C / IP66 Canada: AWT200032
Toroidal Conductivity Module:
Communications Module Fitted AWT210xxC1xxxxxxxxxx
HART Module: 2-Electrode Conductivity Module:
After commissioning, the factory reset switch must be set AWT210xxxxH1xxxxxxxx AWT210xxC2xxxxxxxxxx
Fieldbus Module: 4-Electrode Conductivity Module: WARNING: SUBSTITUTION OF
to the OFF position. This will ensure the device does not AWT210xxxxF1xxxxxxxx AWT210xxC4xxxxxxxxxx COMPONENTS MAY IMPAIR INTRINSIC
Profibus Module: Digital EZLink Module: SAFETY.
lose configuration settings in the event of a power loss. AWT210xxxxP1xxxxxxxx AWT210xxD1xxxxxxxxxx AVERTISSEMENT: LA SUBSTITUTION
pH/ORP Module: DE COMPOSANTS PEUT NUIRE À LA
AWT210xxP1xxxxxxxxxx SÉCURITÉ INTRINSÈQUE.
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 7
Table 3 Input parameters of AWT210 transmitter: Profibus Table 4 Output parameters of sensor:
CLASS I, DIV 1 GROUPS A, B, C, D; T4 4-electrode, 2-electrode, toroidal, pH
CLASS II, DIV 1 GROUPS E, F, G; T4 CLASS I, DIV 1 GROUPS A, B, C, D; T4
Entity model (linear) CLASS II, DIV 1 GROUPS E, F, G; T4
Maximum voltage Ui = 24 V CLASS I, ZONE 2 AEx/Ex ic IIC T4 Gc
174 Maximum open circuit voltage Uo = 11.8 V
Maximum input current li =
mA Maximum short-circuit current lo = 11.8 mA
Maximum power Pi = 1.2 W Maximum output power Po = 36 mW
0.0 Internal inductance Lo = 1H
Internal inductance Li =
mH
Internal capacitance Co = 1.5 μF
Internal capacitance Ci = 1.1 nF
FISCO field device
Maximum voltage Ui = 17.5 V Table 5 Output parameters of sensor: EZLink
360 CLASS I, DIV 1 GROUPS A, B, C, D; T4
Maximum input current li = CLASS II, DIV 1 GROUPS E, F, G; T4
mA
2.52 CLASS I, ZONE 2 AEx/Ex ic IIC T4 Gc
Maximum power Pi =
W Maximum open circuit voltage Uo = 5.21 V
0.0 Maximum short-circuit current lo = 98.2 mA
Internal inductance Li =
mH Maximum output power Po = 127.9 mW
Internal capacitance Ci = 1.1 nF Internal inductance Lo = 43 mH
CLASS I, ZONE 2 AEx/Ex ic IIC T4 Gc Internal capacitance Co = 60 μF
Entity model (linear)
Maximum voltage Ui = 24 V
250
Maximum input current li =
mA
Maximum power Pi = 1.2 W
0.0
Internal inductance Li =
mH
Internal capacitance Ci = 1.1 nF
FISCO field device
Maximum voltage Ui = 14.0 V 15.0 V 16.0 V 17.0 V 17.5 V
274 199 154 121 112
Maximum input current li =
mA mA mA mA mA
2.52
Maximum power Pi =
W
0.0
Internal inductance Li =
mH
Internal capacitance Ci = 1.1 nF
10 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
CLASS II/III, DIV 2, GROUP F,G T4 Maximum open circuit voltage Uo = 11.8 V
Maximum short-circuit current lo = 11.8 mA
Maximum output power Po = 36 mW
Ingress protection classification
Internal inductance Lo = 1H
4X*/IP66
Internal capacitance Co = 1.5 μF
NOTICE
To download the cFMus non-incendive safety control drawing Parameters apply to entire system inclusive of cables.
for Canada, click here or scan this code:
Each specified electrical parameter must be applied
individually and in combination. Do not exceed the
maximum values when applying the electrical parameters
individually or in combination.
5 Mechanical installation
Sensor installation
Location
Refer to the sensor’s Operating Instruction for installation
For general location requirements refer to Figure 4. Select a
procedures.
location away from strong electrical and magnetic fields. If this
is not possible, particularly in applications where mobile
Transmitter installation communications equipment is expected to be used, screened
cables within flexible, earthed metal conduit must be used.
Transmitter dimensions
Dimensions in mm (in)
Install in a clean, dry, well ventilated and vibration-free location
99 ( (3.89) providing easy access. Avoid rooms containing corrosive gases
144 (5.67) 73 ( (2.87) or vapors, for example, chlorination equipment or chlorine gas
cylinders.
16
(0.63) 55
10 (2.16)
(0.39)
Humidity
COMMUNICATION SENSOR
MODULE MODULE
…5 Mechanical installation
…Transmitter installation
Wall mounting
Referring to Figure 5:
1 Position the left- and right-hand mounting brackets A into
NOTICE
the recesses on the rear of the transmitter as shown and If the optional weathershield D is used, position it between
secure with the bracket securing screws. Ensure the plastic the transmitter and wall and pass 2 screws C through
washers remain in the positions fitted. fixing holes (both sides) in weathershield.
Dimensions in mm (in)
62
A (2.44)
B
152 (5.98)
C
Screws not
Weathershield dimensions supplied
200
(7.87)
Optional weathershield
Dimensions in mm (in)
138 +1.0
–0.0
25.5
+0.04
(5.43 –0.0 ) (1.00)
73 (2.87)
138 +1.0
A –0.0
(5.43 +0.04
–0.0 )
30 (1.2)
30
(1.2)
A
Gasket
B
Mounting panel –
E
D G max. thickness
6 (0.24)
C
F
…5 Mechanical installation
…Transmitter installation
Dimensions in mm (in)
Weathershield
(see page 14 for dimensions)
B
Pipe-mount kit
C Vertical
pipe A
C Horizontal
pipe Pipe diameters:
max. 62 (2.44)/min. 45 (1.77)
B
E
E
6 Electrical installation
Terminal connections
Power Ammeter
GUARD
SHIELD
+ – + –
SENSE
RTD 1
RTD 2
RTD 3
REF
1 2 3 4 5
1 2 3 4 5 6 7 8
FOUNDATION Fieldbus and 2-electrode conductivity modules
Profibus PA modules
DRIVE +
DRIVE –
SHIELD
A B A B
RTD 1
RTD 2
RTD 3
1 2 3 4 5
1 2 3 4 5 6 7 8
4-electrode conductivity modules
SENSE +
SENSE –
DRIVE +
DRIVE –
SHIELD
RTD 1
RTD 2
RTD 3
1 2 3 4 5 6 7 8
Toroidal conductivity modules
SENSE +
SENSE –
DRIVE +
DRIVE –
SHIELD
RTD 1
RTD 2
RTD 3
1 2 3 4 5 6 7 8
…6 Electrical installation
Ground connection Communication module connections
Normal grounding practice is to terminate all grounds at the HART module
control room side, in which case the field side of the screen Power Ammeter
should be adequately protected to avoid contact with metallic
+ – + –
objects. The transmitter case should be grounded.
1 2 3 4 5
WARNING
Bodily injury Safe area installations
14 to 42 V DC
If conduit hubs are used, they will not provide a bonding of
the enclosure or system. Hazardous area
installations
14 V DC to Ui
Functional earth
Referring to Figure 9, ground connections are provided:
Ammeter connection for loop current test
internally A and externally B.
A B A B
1 2 3 4 5
For IS systems the grounding should be at the safety barrier Hazardous area
earth connection. For bus-powered systems the grounding of installations
9 V DC to Ui
the screen should be close to the power supply unit. The
specific noise immunity and emitted interference are only Functional earth
guaranteed when bus screening is fully effective – for example,
ensuring that screening is maintained through any existing
junction boxes. Appropriate equipotential bonding must be PROFIBUS PA module
provided to avoid differences in potential among the individual
Connected internally
plant components.
NOTICE
Safe area installations
HART, PROFIBUS, and Fieldbus protocols are not secure. 9 to 32 V DC
Therefore, the intended application should be assessed
before implementation to ensure these protocols are Hazardous area
suitable. installations
9 V DC to Ui
Functional earth
Gland entries
For hazardous area installations, suitable Ex glands and
blanking elements must be used to seal the entry holes.
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 19
NOTICE
ORP (Redox) and Antimony pH sensors do not feature
temperature compensation therefore do not have
temperature sensors or related wiring.
NOTICE
Ensure sensor diagnostics are Off when using standard
sensors without diagnostic functions.
NOTICE
Ensure sensor diagnostics are On when using standard
sensors with diagnostic functions.
NOTICE
AWT210 pH sensor modules are supplied standardized to
theoretical sensor characteristics. Following installation,
but before use, a process calibration should be performed
to ensure optimum accuracy. For pH sensor calibration
procedures see page 50.
20 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…6 Electrical installation
Conductivity sensor module connections
2-electrode sensors
NOTICE
AWT210 2-electrode conductivity sensor modules are supplied
standardized to theoretical sensor characteristics. Following
installation, but before use, a process calibration should be
performed to ensure optimum accuracy. For 2-electrode
conductivity sensor calibration procedures see page 53.
4-electrode sensors
NOTICE
AWT210 4-electrode conductivity sensor modules are supplied
standardized to theoretical sensor characteristics. Following
installation, but before use, a process calibration should be
performed to ensure optimum accuracy. For 4-electrode
conductivity sensor calibration procedures see page 54.
Toroidal sensors
NOTICE
AWT210 toroidal conductivity sensor modules are supplied
standardized to theoretical sensor characteristics. Following
installation, but before use, a process calibration should be
performed to ensure optimum accuracy. For toroidal
conductivity sensor calibration procedures see page 54.
Gland entries
For hazardous area installations, suitable Ex glands and
blanking elements must be used to seal the entry holes.
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 21
2 Put the EZLink bulkhead connector cable through the anti- 10 Plug connector block cradle C into the EZLink module A.
rotation washer B. Make sure that the alignment tab is in
the correct orientation.
C
B
D
Figure 10 Fitting the bulkhead connector
A
C
To retain existing sensor setup parameters
Press the key to access the Operator menu.
B From the operator menu use the keys to highlight
Download Config / Transmitter→Sensor and press the key to
download the existing sensor setup parameters from the
transmitter to the new sensor.
Figure 12 Connecting the sensor EZLink connector -
AWT210 can only accept one EZLink in the position shown To use sensor setup parameters from the new sensor
Press the key to access the operator menu.
From the operator menu use the keys to highlight Upload
Config / Sensor→Transmitter and press the key to upload the
sensor setup parameters from the new sensor to the transmitter.
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 23
7 Operation
Operator Page – normal conditions
HART Tag (HART devices) or Tag Descriptor (FF and PA devices)
Advanced
Service
Write Protected
PV + temperature
Operator Calibration
menu page
PV + temperature + PV %
PV + temperature + OP
(HART devices only
Note.
When the instrument starts, the ABB Initializing splash screen
may show twice, or once, depending on the software version.
Firstly, it shows when power is applied to the instrument, then
it shows again when all subsystems have initialized. In some
software versions, these actions are performed in a single
operation.
…7 Operation
Operator Page – alarm conditions
If any of the diagnostic alarms are active the NAMUR status of the device is indicated by displaying the class
and category of the highest priority active alarm.
Alarm class
Check Function
Process
Off Specification
Maintenance Required
Operator Calibration
menu page
Operator menu
From the Operator menu, use the keys to highlight the required menu and press the key to select:
Operator Menu
Download Config
Upload Config
Diagnostics
Configuration
Hold Output
Release Output
Operator Page 1
Operator Page 2
Autoscroll
Signals view
Back Select
Signals View
Signals View
PV 7.33 pH
SV 25.0 °pH
TV 37 KW
QV 1.06 mV
PV% 12.4 %
Back Exit
Standard sensors
Sensor type
2-electrode conductivity Sensor type
Sensor type
4-electrode conductivity pH (EZLink) Sensor type
Signal pH
Toroidal conductivity
PV pH, ORP, Ion Conc or pION Conductivity or concentration Conductivity or concentration Conductivity or Concentration
SV Temperature Temperature Temperature Temperature
Conductivity without Conductivity without Conductivity without
TV Reference impedance
temperature compensation temperature compensation temperature compensation
QV Cell output (mV) Conductivity Conductivity Conductivity
Primary variable percentage Primary variable percentage Primary variable percentage Primary variable percentage
PV%
of engineering range of engineering range of engineering range of engineering range
Current output Current output Current output Current output
O/P
(HART versions only) (HART versions only) (HART versions only) (HART versions only)
EZLink sensors
Signal Sensor type Sensor type
pH Redox
PV pH Redox/ORP
SV Temperature —
TV — —
QV Cell output (mV) Conductivity
PV% Primary variable percentage of engineering range Primary variable percentage of engineering range
O/P Current output (HART versions only) Current output (HART versions only)
26 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
8 Diagnostic alarms
Note.
Alarms are listed in alarm priority order (high number = high priority alarm).
Configuration DATA
--C098.041-- SIMULATION
Enable loop current
Configuration CURRENT OUTPUT
mode. Disable loop test/
--C097.030-- FIXED trim & PV cal.
Process
SENSOR IS DIRTY Clean sensor
--M082.005--
Check terminals
Electronics DIAGNOSTIC
Check sensor wiring
--M081.006-- INPUT READ ERROR Check electrode
Check terminals
Electronics LOW ELECTRODE
Check sensor wiring
--M080.039-- IMPEDANCE Check electrode
Access Level
The Access Level is entered via the Operator/Enter Configuration menu option. Use the keys to highlight the required level
and press to enter the level.
Access Level
Read Only
Calibrate
Advanced
Service
Back Select
Enter Password
When this switch is in the OFF position, all access levels are
available (Read Only, Calibrate, Advanced and Service).
Setting passwords
Passwords can be set to enable secure access at 2 levels:
Calibrate and Advanced. The Service Level is password
protected at the factory and reserved for factory use only.
Passwords can contain up to 6 characters and are set, changed
or restored to their default settings at the Device Setup/
Security Setup parameter – see page 47.
Password recovery
Advanced level password recovery
To recover the Advanced level password, move the Write
Protect switch to the OFF position (see page 6). Select the
Service Access level and enter the Service level password to
gain access. From the Service level, the Device Setup menu can
be accessed to reset the Advanced level password.
10 Menu overview
pH menus
Level pH
Menu Language
Measurement Type
• pH Sensor Type
Easy Setup
– Isopotential Point
– Asymmetric Potential
• PV Unit
• Valence
• Magnitude
Exit Select • End Magnitude
• End mV
See page 36
Temperature Units
Temp. Comp. Type
• Manual Temperature
• Solution Coefficient
Operator page 1
Exit Select
Operator Page 1
Menu
Operator Page 2
Contrast
Display
Language
Exit Select
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 31
Level pH
Exit Select
PA version:
Slave Address
Device Tag
Ident No. Selector
Manuf. ID
Device Type
PA Profile
Exit Select
32 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
Menu Language
Measurement Type
Cell Constant
Easy Setup
• Concentration Units
• Concentration Curve Name
Temperature Units
Operator page 1
Exit Select
See page 37
Exit Select
See page 41
Exit Select
Operator Page 1
Menu
Operator Page 2
Contrast
Display
Language
Exit Select
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 33
Exit Select
PA version:
Slave Address
Device Tag
Ident No. Selector
Manuf. ID
Device Type
PA Profile
Exit Select
34 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
See page 30
Menu Sensor Diagnostics
• Conductivity Calibration Diagnostic Status
Menu
• Concentration Calibration Diagnostics
Calibrate Temperature Calibration
Hold Output (HART only)
Edit Calibration
Restore Defaults
Exit Select
Exit Select
See page 33
Menu HART version:
Device Address
Menu Measurement Type Communication HART Tag
Sensor Group HART Description
• Concentration Units Message
Sensor Setup
• Conductivity Units Manuf. ID
• Concentration Curve Name Last Command
– Concentration Curve Table HART Revision
Exit Select
Temperature Units Resp. Preamble
Temperature Compensation Type Loop Current Mode
Exit Select • Manual Temperature
• Auto Temperature Compensation PA version:
See page 37 Option
Slave Address
– Temperature Compensation
Device Tag
Coefficient
Ident No. Selector
– User Defined Temperature
Compensation Curve Manuf. ID
Reference Temperature Device Type
Temperature Sensor Type PA Profile
Detect Temperature Sensor
Foundation Fieldbus version
Node Address
Menu Security Setup Device Tag
PDM Compatibility (HART only) Manuf. ID
Device Setup Reset to defaults Device Type
Device Revision
Simulation
Operator Page 1
Menu
Operator Page 2
Contrast
Display
Language
Exit Select
Exit Select
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 35
See page 31
Menu Sensor Diagnostics
PV Zero Calibration Diagnostic Status
Menu
PV Span Calibration Diagnostics
Calibrate Temperature Calibration
Hold Output (HART only)
Edit Calibration
Restore Defaults
Exit Select
Exit Select
See page 34
Menu HART version:
Device Address
Menu Measurement Type Communication HART Tag
• Concentration Solution HART Description
• Concentration Units Message
Sensor Setup
• Conductivity Units Manuf. ID
• Concentration Curve Name Last Command
– Concentration Curve Table HART Revision
Exit Select
Temperature Units Resp. Preamble
Temperature Compensation Type Loop Current Mode
Exit Select • Manual Temperature
• Auto Temperature Compensation PA version:
See page 38 Option
Slave Address
– Temperature Compensation
Device Tag
Coefficient
Ident No. Selector
– User Defined Temperature
Compensation Curve Manuf. ID
Reference Temperature Device Type
Temperature Sensor Type PA Profile
Detect Temperature Sensor
Foundation Fieldbus version
Node Address
Menu Security Setup Device Tag
PDM Compatibility (HART only) Manuf. ID
Device Setup Reset to defaults Device Type
Device Revision
Simulation
Operator Page 1
Menu
Operator Page 2
Contrast
Display
Language
Exit Select
Exit Select
36 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
11 Configuration
Easy Setup
pH
Easy Setup Note. Easy Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to pH sensor types.
Exit Select
Eng Range Low Set the Process value engineering range minimum value. EZLink sensors only
mV Soln. Coeff. Enabled only if Measurement Type = pH and Temp. Comp. Type = Auto.
Low Slope Limit A pH probe degrades over time. As this happens the slope calculated by a calibration procedure EZLink sensors only
gradually decreases. Set the slope value below which a calibration fails. The low slope warning
diagnostic is activated if the calibration calculates a slope less than 20 % above this value.
Operator Page 1 Selects range of values displayed on Operator Page 1 – see page 56 for examples of character formats/sizes.
PV/PV + Temperature/PV + Temp + PV%/PV + Temp + O/P
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 37
2-electrode conductivity
Easy Setup Note. Easy Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to 2-electrode conductivity sensor types.
Exit Select
Temp. Unit Temperature unit displayed and applied to all temperature parameters/values.
Not enabled if Temperature Compensation Type = Manual.
°F/°C
Operator Page 1 Selects range of values displayed on Operator Page 1 – see page 56 for examples of character formats/sizes.
PV/PV + Temperature/PV + Temp + PV%/PV + Temp + O/P
38 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…11 Configuration
… Easy Setup
4-electrode conductivity
Easy Setup Note. Easy Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to 4-electrode conductivity sensor types.
Exit Select
Temp. Unit Temperature unit displayed and applied to all temperature parameters/values.
Not enabled if Temperature Compensation Type = Manual.
°F/°C
Operator Page 1 Selects range of values displayed on Operator Page 1 – see page 56 for examples of character formats/sizes.
PV/PV + Temperature/PV + Temp + PV%/PV + Temp + O/P
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 39
Toroidal conductivity
Easy Setup Note. Easy Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to toroidal conductivity sensor types.
Exit Select
Temp. Unit Temperature unit displayed and applied to all temperature parameters/values.
Not enabled if Temperature Compensation Type = Manual.
°F/°C
Operator Page 1 Selects range of values displayed on Operator Page 1 – see page 56 for examples of character formats/sizes.
PV/PV + Temperature/PV + Temp + PV%/PV + Temp + O/P
40 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…11 Configuration
Calibrate
pH
Calibrate Note. Calibrate menus are sensor-specific – the menus in this section are applicable to
transmitters connected to pH sensor types.
Access to the Calibrate menu is permitted via the Calibrate and Advanced levels or directly from
an Operator page using the Cal button.
Exit Select
PV Manual Cal
1 Point Cal
2 Point Cal
Temperature Cal
Hold Output HART versions only. Not available if HART in Multidrop or Fixed Output mode.
Disabled/Enabled.
When Enabled: output is held automatically at the beginning of a PV calibration and released automatically at the end.
When Disabled: output remains active throughout any PV calibration.
Auto Buffer Setup
Buffer Type User Def/ABB/NIST/DIN 19266/MERCK/US Tech.
(MERCK Not available for EZLink sensors.)
Buffer 1 Value Enabled only if Buffer Type = User Def.
Available selections based on Buffer Type:
ABB 4.01 pH/ABB 7.00 pH/ABB 9.18 pH/MERCK 4.00 pH/MERCK 7.00 pH/MERCK 9.00 pH/MERCK 10.00
pH/DIN 1.68 pH/DIN 4.01 pH/DIN 6.86 pH/DIN 9.18 pH/US TECH 4.01 pH/US TECH 7.00 pH/US TECH
10.01 pH/NIST 4.01 pH/NIST 6.86 pH/NIST 9.18 pH
PV Slope
PV Offset
Temp Slope
Temp Offset
Restore Defaults
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 41
2-electrode conductivity
Calibrate Note. Calibrate menus are sensor-specific – the menus in this section are applicable to
transmitters connected to 2-electrode conductivity sensor types.
Access to the Calibrate menu is permitted via the Calibrate and Advanced levels or directly from
an Operator page using the Cal button.
Exit Select
Temperature Cal
Hold Output HART versions only. Not available if HART in Multidrop or Fixed Output mode.
Disabled/Enabled.
When Enabled: output is held automatically at the beginning of a PV calibration and released automatically at the end.
When Disabled: output remains active throughout any PV calibration.
Edit Cal
PV Slope
PV Offset
Temp Slope
Temp Offset
Restore Defaults
4-electrode conductivity
Calibrate Note. Calibrate menus are sensor-specific – the menus in this section are applicable to
transmitters connected to 4-electrode conductivity sensor types.
Access to the Calibrate menu is permitted via the Calibrate and Advanced levels or directly from
an Operator page using the Cal button.
Exit Select
Temperature Cal
Hold Output HART versions only. Not available if HART in Multidrop or Fixed Output mode.
Disabled/Enabled.
When Enabled: output is held automatically at the beginning of a PV calibration and released automatically at the end.
When Disabled: output remains active throughout any PV calibration.
Edit Cal
PV Slope
PV Offset
Temp Slope
Temp Offset
Restore Defaults
42 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…11 Configuration
… Calibrate
Toroidal conductivity
Calibrate Note. Calibrate menus are sensor-specific – the menus in this section are applicable to
transmitters connected to toroidal conductivity sensor types.
Access to the Calibrate menu is permitted via the Calibrate and Advanced levels or directly from
an Operator page using the Cal button.
Exit Select
PV Zero Cal
PV Span Cal
Temperature Cal
Hold Output HART versions only. Not available if HART in Multidrop or Fixed Output mode.
Disabled/Enabled.
When Enabled: output is held automatically at the beginning of a PV calibration and released automatically at the end.
When Disabled: output remains active throughout any PV calibration.
Edit Cal
PV Slope
PV Offset
Temp Slope
Temp Offset
Restore Defaults
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 43
Sensor Setup
pH
Sensor Setup Note. Sensor Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to pH sensor types.
Exit Select
mV Soln. Coeff. Enabled only if Measurement Type ≠ pH and Temp. Comp. Type = Auto.
Reset Configuration Select to reset all Sensor Setup parameters to their default values.
(EZLink sensors only.)
44 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…11 Configuration
… Sensor Setup
2-electrode conductivity
Sensor Setup Note. Sensor Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to 2-electrode conductivity sensor types.
Exit Select
Pure H2O Type Enabled only if Temp. Comp. Type = Auto and Auto TC Option = Pure H2O.
Neutral/Acid./Base
User Def. TC Curve Enabled only if Temp. Comp. Type = Auto and Auto TC Option = User Def. TC.
X1 Temp/Y1 K/Kref/X2 Temp/Y2 K/Kref/X3 Temp/Y3 K/Kref/
X4 Temp/Y4 K/Kref/X5 Temp/Y5 K/Kref/X6 Temp/Y6 K/Kref/Table Error
None
Not Saved
Reference Temp.
4-electrode conductivity
Sensor Setup Note. Sensor Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to 4-electrode conductivity sensor types.
Exit Select
User Def. TC Curve Enabled only if Temp. Comp. Type = Auto and Auto TC Option = User Def. TC.
X1 Temp/Y1 K/Kref/X2 Temp/Y2 K/Kref/X3 Temp/Y3 K/Kref/
X4 Temp/Y4 K/Kref/X5 Temp/Y5 K/Kref/X6 Temp/Y6 K/Kref/Table Error
None
Not Saved
Reference Temp.
…11 Configuration
… Sensor Setup
Toroidal conductivity
Sensor Setup Note. Sensor Setup menus are sensor-specific – the menus in this section are applicable to
transmitters connected to toroidal conductivity sensor types.
Exit Select
User Def. TC Curve Enabled only if Temp. Comp. Type = Auto and Auto TC Option = User Def. TC.
X1 Temp/Y1 K/Kref/X2 Temp/Y2 K/Kref/X3 Temp/Y3 K/Kref/
X4 Temp/Y4 K/Kref/X5 Temp/Y5 K/Kref/X6 Temp/Y6 K/Kref/Table Error
None
Not Saved
Reference Temp.
Device Setup
Menu Used to setup security parameters, set PDM compatibility (for HART-enable transmitters) and to
reset default (factory-set) parameters.
Device Setup
Exit Select
Display
Menu Used to setup Operator pages (1, 2), select the display language and set the display contrast.
Display
Exit Select
…11 Configuration
Input/Output
Menu Used to configure input/output values.
Input/Output
Exit Select
Diagnostics
Menu See page 26 for all diagnostic messages/actions.
Diagnostics
Exit Select
Communication
Menu Communication level menus are enabled only if an optional communications module is fitted.
Refer to the communications supplementary manuals for full details of Profibus, MODBUS and
Communication
HART connections and configuration together with tables detailing Profibus slot/indexes and
MODBUS coils and registers.
Exit Select
Device Info
Menu Displays read-only factory-set details for the transmitter software and connected sensor(s).
Device Info
Exit Select
12 Calibration
pH sensor calibration
Auto Buffer Cal
Performs a 2 point calibration using 2 pre-defined buffer solutions – see Auto Buffer Setup, page 40.
Exit
52 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…12 Calibration
…pH sensor calibration
1-point manual calibration 2-point manual calibration
Performs a manual calibration (Offset adjustment) at a single Performs a 2-point calibration using 2 pre-defined buffer
reference point. solutions.
1 Wait for stable reading – 1 Point Manual––– 1 Buffer temperature – 2 Point Manual –––
Monitor the process value and The temperature of the buffer
continue ( ) to the next step once PV 7.00 pH solutions is displayed. The Buffer Temperature
the value has stabilized. temperature can be edited by
Continue When Stable
pressing the key. When the 25.0 °C
Exit
Exit
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 53
Exit
54 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…12 Calibration
4-electrode conductivity sensor calibration Toroidal conductivity sensor calibration
4-electrode conductivity may require wet calibration for the Toroidal conductivity may require wet calibration for the
greatest accuracy. greatest accuracy.
<1 µS/cm the PV Offset is recalculated. the next step once the value has Abort Continue
• If the calibration is performed at a conductivity value stabilized.
≥1 µS/cm the PV Slope is recalculated.
2 Sampling – PV Zero Cal ––––
For Group B sensors The procedure moves automatically
• If the calibration is performed at a conductivity value to the next stage once the PV has PV 1.2 uS/cm
<5 µS/cm the PV Offset is recalculated. been sampled.
• If the calibration is performed at a conductivity value
≥ 5µS/cm the PV Slope is recalculated. Abort
Exit
Exit
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 55
PV Span calibration
Apply span and wait for – –––
1 PV Zero Cal
stable reading
Ensure that a span solution is PV 752 uS/cm
present at the sensor, monitor the
Continue When Stable
process value and continue ( ) to
the next step once the value has Abort Continue
stabilized.
Abort
Exit
Exit
56 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
13 Specifications
Operation Password protection
Display/LCD (W x H) Access to configuration levels is enabled only after the
75 x 65 mm (3.0 x 2.55 in) user has entered a password:
Language • Calibrate level: user-assigned password
English, German, French, Spanish, Italian, Portuguese, • Advanced level: user-assigned password
Russian, Turkish, Chinese, Polish • Service level: factory set password
Input
Keypad
pH/ORP/plon sensor types
4 tactile membrane keys
pH: Glass, Antimony (Sb)
ORP: (Redox): Platinum (Pt), Gold (Au)
Mechanical data pION: Custom user-programmable
Protection
IP66/NEMA 4X Input impedance
>1x1013Ω
Dimensions
Height: 144 mm (5.76 in) min. (excluding glands) pH/ORP/plon measurement range and resolution
Width: 144 mm (5.76 in) door closed – min.
Display Accuracy
Depth – 99 mm (3.9 in) door closed – min. Type Range
resolution repeatability
(excluding fixing brackets)
0 to 14 pH
Weight: aluminum enclosure 1.15 kg (2.53 lb) pH 0.01 pH ±0.01 pH
(–2 to 16 over range)
Weight: polycarbonate enclosure 0.75 kg (1.65 lb) ORP –1500 to 1500 mV 1 mV ±1 mV
pION –1500 to 1500 mV 1 mV ±1 mV
Panel dimensions
Cut-out height: 138 +1.0 –0.0 mm (5.43 +0.04 –0.0 in)
Dynamic response
Cut-out width: 138 +1.0 –0.0 mm (5.43 +0.04 –0.0 in)
<1 second for 90 % step change at 0 seconds damping
Thickness: 35 mm (1.38 in) Max.
Depth behind panel: 67 mm (2.7 in) min.
Damping
Distance between cut-outs: 40 mm (1.57 in) min.
Configurable: 0 to 99.9 seconds
Materials of construction
Conductivity sensor types
Aluminum enclosure: LM20 aluminum
AWT210: ABB 2-electrode conductivity sensors
Polycarbonate enclosure: LEXAN 505RU
AWT210: ABB 4-electrode conductivity sensors
10 % GF polycarbonate
AWT210: ABB toroidal conductivity sensors
Cable entries
Conductivity measurement range and resolution
Aluminum enclosure: 2 holes to accept M20 or ½ in cable
AWT210 2-electrode conductivity transmitter:
glands or conduit hubs and 2 holes to accept M16 cable
glands or conduit hubs Cell Conductivity Display Accuracy
Polycarbonate enclosure: 5 holes to accept M20 or ½ in constant range resolution repeatability
cable glands or conduit hubs and 2 holes to accept M16 0.01 0 to 200 µS/cm 0.001 µS/cm ±1.0 % of
measurement
cable glands or conduit hubs 0.1 0 to 2000 µS/cm 0.01 µS/cm
range per
Transmitters are supplied with blanking plugs for all of 1 0 to 20000 µS/cm 0.1 µS/cm decade
the cable entry holes
…Conductivity measurement range and
Optional cable gland packs are available
resolution
AWT210 4-electrode conductivity transmitter:
Terminal connections
AWG 26 to 14 (0.14 to 2.5 mm2) Sensor Conductivity Display Accuracy
group range resolution repeatability
Configuration security A 0 to 2000 mS/cm 0.1 µS/cm ±0.5 % of
Hardware switch configuration measurement
Access to configuration is enabled only after a hardware B 0 to 2000 µS/cm 0.01 µS/cm range per decade
switch has been set. This switch is situated behind a
tamper-evident seal.
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 57
AWT210 toroidal conductivity transmitter: Power supply (FF models and PA models)
Sensor Conductivity Display Accuracy
Supply voltage
range resolution repeatability 9 to 32 V DC (General purpose installations)
±0.5 % of 9 to 24V DC (Intrinsically Safe Ex ia)
ABB
0 to 2000 mS/cm 1.0 µS/cm measurement
toroidal
range per decade
Quiescent current
15 mA quiescent current consumption
ORP
250
pION
Supply
voltage
Conductivity temperature compensation modes 10 20 30 40 (V DC)
19.5 V
Temperature AWT210 AWT210 AWT210
Ex ia installations 14 to 30 V
element 2-electrode 4-electrode toroidal
0 to 15 % NaOH General installations 14 to 42 V
0 to 20 % NaCI
0 to 18 % HCl With 250 Ω resistor for HART communication min. supply
0 to 20 % H2SO4 voltage = 19.5 V DC
Pure water neutral salt
Pure water trace base
Pure water trace acid
User-defined
58 AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I
…13 Specifications
Output (HART models) Approvals, certification and safety
Configured range
4 to 20 mA, user-programmable across measurement range. Factory Mutual (cFMus) Intrinsic Safety
Linear and non-linear. Available with polycarbonate & aluminum enclosures
EMC
Storage temperature
Emissions and immunity
–40 to 70 °C (–40 to 158 °F)
Meets requirements of IEC61326 for an industrial
environment.
Vibration
IEC 60068-2-6 Test FC: vibration, sinusoidal
*4X Hosedown self-assessed not approved by 3rd party.
DS/AWT210-EN Rev. G
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 59
Appendix B – Upgrading/Reloading
Factory reset switch
When this switch is set to the ON position and the instrument is
powered up, the instrument is reset to the factory default
values.
NOTICE
Resetting to factory default values resets all of the
instrument configuration parameters including passwords.
AW T 2 1 0 | 2 - W I R E C O N D U C T I V I T Y, P H/O R P, P I O N T R A N S M I T T E R | O I/A W T 2 1 0 - E N R E V. I 61
Wall-mount kit
Main case assemblies Part number Description
Acknowledgements
• EZLink is a trademark of ABB Limited
• Fieldbus is a registered trademark of the Fieldbus Foundation
• HART is a registered trademark of the FieldComm Group
• LEXAN is a trademark of SABIC Global Technologies B.V.
• Modbus is a registered trademark of Schneider Electric USA Inc.
• PROFIBUS is a registered trademark of PROFIBUS organization
Notes
—
ABB Measurement & Analytics
—
We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained
therein. Any reproduction, disclosure to third parties or utilization of its contents – in
whole or in parts – is forbidden without prior written consent of ABB.
© ABB 2023