LEGEND:
SYMBOL DESCRIPTION
A A
50 INSTANTANEOUS OVER CURRENT PROTECTION
BUS SECTION-1 BUS COUPLER-1 BUS SECTION-2 BUS COUPLER-2 BUS SECTION-3 50N INSTANTANEOUS EARTH FAULT PROTECTION
CT CURRENT TRANSFORMER
CL CLASS
630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
LBS 2 SF6 SF6 LBS 1 LBS SF6 SF6 LBS 2 SF6 SF6 LBS 1 LBS SF6 SF6 LBS 2 SF6 SF6 LBS 1
TTB TEST TERMINAL BLOCK
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM R Y B PHASE INDICATING LAMPS
100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A
5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA
5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA
POTENTIAL TRANSFORMER
F INVERTER TRANSFORMER-4
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-3 INVERTER TRANSFORMER-2
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-1 INVERTER TRANSFORMER-10
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-9 INVERTER TRANSFORMER-8
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-7 INVERTER TRANSFORMER-18
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-17
LINE SWITCH WITH F
3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, EARTH SWITCH
ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC,
+/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH
CURRENT TRANSFORMER
TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB
BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63
WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT
OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT
VACUUM CIRCUIT BREAKER
Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel FIXED TYPE.
100kVA 100kVA 100kVA 100kVA 100kVA
Aux.Trafo. Aux.Trafo. Aux.Trafo. Aux.Trafo. Aux.Trafo.
LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel
CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT MB MARSHALLING BOX
1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA
G G
63 BUCHHOLZ RELAY(GOR)
H 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR WTI(49WT) TRAFO. WINDING TEMP. INDICATOR H
F1 F2 F3 F4 F1 F2 F3 F1 F2 F3 F4 F1 F2 F3 F1 F2 F3
MOG MAGNETIC OIL GUAGE (TRAFO.) WITH LOW OIL LEVEL, ALARM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
NOTES:
1. ALL NUMERICAL RELAYS PROVIDED SHALL BE PROVIDED WITH AN INBUILT TRIP
100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A
CIRCUIT MONITORING AND MASTER TRIP FUNCTIOS.
5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA
5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA
2. ALL RELAYS & MFM METERS SHALL BE COMMUNICABLE TYPE & COMPATIBLE
WITH SCADA SYSTEM.
3. THE INVERTER STATION AUXILIARY TRANSFORMER AND MAIN AUXILIARY
1Runx3Cx300Sq.mm,18/30kV,
1Runx3Cx300Sq.mm,18/30kV,
XLPE,AL Conductor Cable.
1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV,
1Runx3Cx300Sq.mm,18/30kV,
XLPE,AL Conductor Cable.
1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV, TRANSFORMER RATINGS SHALL BE DECIDED DURING DETAILED ENGINEERING
I INVERTER TRANSFORMER-19
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-20
INVERTER TRANSFORMER-6
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-5 INVERTER TRANSFORMER-14
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-13 INVERTER TRANSFORMER-12
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-11 INVERTER TRANSFORMER-16
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-15 BASED ON ACTUAL LOADS. I
3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA,
1500KVA,
ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC,
ONAN,22/0.6kV,OCTC,
+/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH
+/- 5% IN,STEPS OF 2.5% EACH
Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel
CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT 6 GMS RK JS UPDATED ACC. TO CUSTOMER COMMENTS 24-09-2018
J 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA J
5 GMS RK JS UPDATED ACC. TO CUSTOMER COMMENTS 17-09-2018
Inv - 02 Inv - 01 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01
Container - 19 Container - 20 Container - 6 Container - 5 Container - 14 Container - 13 Container - 12 Container - 11 Container - 16 Container - 15 4 GMS RK JS UPDATED ACCORDING TO CUSTOMER COMMENTS 28-08-2018
3 YG RK RK UPDATED ACCORDING TO CUSTOMER COMMENTS 28-06-2018
2 YG RK RK UPDATED ACCORDING TO CUSTOMER COMMENTS 08-06-2018
1 YG RK RK FOR APPROVAL 16-05-2018
0 YG RK RK FOR APPROVAL 28-04-2018
AC SINGLE LINE DIAGRAM REV DRAWN
DRAWING TITLE:
REVIEWED APPROVED CHANGE
DRAWING NUMBER:
DATE
COMPANY (EETC)
3. CH-BB-CNS-EL-03
4. Benban - Annexure 1 (IS-Reactor) SCALE:
NTS
FORMAT:
DIN A1
SHEET:
1/1