PRODUCED BY AN AUTODESK STUDENT VERSION

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

LEGEND:
SYMBOL DESCRIPTION
A A
50 INSTANTANEOUS OVER CURRENT PROTECTION

51 IDMT OVER CURRENT PROTECTION

BUS SECTION-1 BUS COUPLER-1 BUS SECTION-2 BUS COUPLER-2 BUS SECTION-3 50N INSTANTANEOUS EARTH FAULT PROTECTION

51N IDMT EARTH FAULT PROTECTION

86 HIGH SPEED TRIPPING RELAY (MASTER TRIP/LOCKOUT RELAY)


B B
TCM TRIP CIRCUIT MONITORING

87L LINE/CABLE DIFFERENTIAL PROTECTION

59 OVER VOLTAGE(O/V) PROTECTION

27 UNDER VOLTAGE(U/V) PROTECTION


67 DIRECTIONAL OVER CURRENT PROTECTION

C 67N DIRECTIONAL EARTH FAULT OVER CURRENT PROTECTION C


52 CIRCUIT BREAKER

VCB VACUUM CIRCUIT BREAKER

CT CURRENT TRANSFORMER

CL CLASS

TP THREE POLE / TRIPLE POLE


D D
CU COPPER
2Runx3Cx300Sq.mm,18/30kV, 3Runx1Cx630Sq.mm Cu. Conductor Cable. 2Runx3Cx300Sq.mm,18/30kV, 3Runx1Cx630Sq.mm Cu. Conductor Cable. 2Runx3Cx300Sq.mm,18/30kV, 3Runx1Cx630Sq.mm Cu. Conductor Cable.
XLPE,AL Conductor Cable. XLPE,AL Conductor Cable. XLPE,AL Conductor Cable.
I/C IN COMER

TRI VECTOR METER 0.2 CLASS WITH RS485 PORT


TVM
(A,V,PF,KW,KVAR,KWH,KVARH)-IMP/EXP
TO REFER AUX.SLD (CH-BB-SLD-EL-03) TO REFER AUX.SLD (CH-BB-SLD-EL-03)
22kV RMU PANEL 22kV RMU PANEL 22kV RMU PANEL 22kV RMU PANEL 22kV RMU PANEL MULTI FUNCTION METER 0.2CLASS WITH RS485 PORT
BLOCK - 2 BLOCK 1 BLOCK - 5 BLOCK - 4 BLOCK - 9
MFM
(A,V,PF,KW,KVAR,KWH,KVARH)
22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR
E F1 F2 F3 F4 F1 F2 F3 F1 F2 F3 F4 F1 F2 F3 F1 F2 F3 F4
E
SA SURGE ARRESTOR

PRODUCED BY AN AUTODESK STUDENT VERSION


PRODUCED BY AN AUTODESK STUDENT VERSION

630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
LBS 2 SF6 SF6 LBS 1 LBS SF6 SF6 LBS 2 SF6 SF6 LBS 1 LBS SF6 SF6 LBS 2 SF6 SF6 LBS 1
TTB TEST TERMINAL BLOCK
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM R Y B PHASE INDICATING LAMPS

100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A
5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA
5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA
POTENTIAL TRANSFORMER

FAULT CURRENT LIMITING REACTOR


1Runx3Cx300Sq.mm,18/30kV,XLPE,AL Conductor Cable. 1Runx3Cx300Sq.mm,18/30kV,XLPE,AL Conductor Cable.
1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV,

F INVERTER TRANSFORMER-4
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-3 INVERTER TRANSFORMER-2
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-1 INVERTER TRANSFORMER-10
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-9 INVERTER TRANSFORMER-8
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-7 INVERTER TRANSFORMER-18
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-17
LINE SWITCH WITH F
3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, EARTH SWITCH
ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC,
+/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH
CURRENT TRANSFORMER
TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB
BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63 BR-63
WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT
OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT
VACUUM CIRCUIT BREAKER
Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel FIXED TYPE.
100kVA 100kVA 100kVA 100kVA 100kVA
Aux.Trafo. Aux.Trafo. Aux.Trafo. Aux.Trafo. Aux.Trafo.

LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel

CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT MB MARSHALLING BOX
1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA
G G

IT IS PROHIBITED TO REPRODUCE IT FOR OTHER PURPOSES WITHOUT AUTHORIZATION IN WRITING.


Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 50BF BREAKER FAILURE PROTECTION
Container - 4 Container - 3 Container - 2 Container - 1 Container - 10 Container - 9 Container - 8 Container - 7 Container - 18 Container - 17
TRANSFORMER PROTECTION RELAY SHALL COVERS BELOW

63 BUCHHOLZ RELAY(GOR)

1Runx3Cx300Sq.mm,18/30kV,XLPE,AL Conductor Cable. OTI(49OT) TRAFO. OIL TEMP. INDICATOR.

22kV RMU PANEL


BLOCK - 10
22kV RMU PANEL
BLOCK - 3
22kV RMU PANEL
BLOCK - 7
22kV RMU PANEL
BLOCK - 6
22kV RMU PANEL
BLOCK - 8
PRD PRESSURE RELIEF DEVICE

H 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR 22kV, 630A, TP, 20kA/1 SEC, 'CU' BUS BAR WTI(49WT) TRAFO. WINDING TEMP. INDICATOR H
F1 F2 F3 F4 F1 F2 F3 F1 F2 F3 F4 F1 F2 F3 F1 F2 F3

MOG MAGNETIC OIL GUAGE (TRAFO.) WITH LOW OIL LEVEL, ALARM

THIS DOCUMENT IS THE PROPERTY OF JUWI


630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
LBS 2 SF6 SF6 LBS 1 LBS SF6 SF6 LBS 2 SF6 SF6 LBS 1 LBS SF6 SF6 LBS SF6 SF6

50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
50 51 86
50N 51N TCM
NOTES:
1. ALL NUMERICAL RELAYS PROVIDED SHALL BE PROVIDED WITH AN INBUILT TRIP
100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A 100/1A
CIRCUIT MONITORING AND MASTER TRIP FUNCTIOS.
5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA 5P20-5VA
5P10-5VA 5P10-5VA 5P10-5VA 5P10-5VA
2. ALL RELAYS & MFM METERS SHALL BE COMMUNICABLE TYPE & COMPATIBLE
WITH SCADA SYSTEM.
3. THE INVERTER STATION AUXILIARY TRANSFORMER AND MAIN AUXILIARY
1Runx3Cx300Sq.mm,18/30kV,
1Runx3Cx300Sq.mm,18/30kV,
XLPE,AL Conductor Cable.
1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV,
1Runx3Cx300Sq.mm,18/30kV,
XLPE,AL Conductor Cable.
1Runx3Cx300Sq.mm,18/30kV, 1Runx3Cx300Sq.mm,18/30kV, TRANSFORMER RATINGS SHALL BE DECIDED DURING DETAILED ENGINEERING
I INVERTER TRANSFORMER-19
XLPE,AL Conductor Cable.

INVERTER TRANSFORMER-20
INVERTER TRANSFORMER-6
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-5 INVERTER TRANSFORMER-14
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-13 INVERTER TRANSFORMER-12
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-11 INVERTER TRANSFORMER-16
XLPE,AL Conductor Cable.
INVERTER TRANSFORMER-15 BASED ON ACTUAL LOADS. I
3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA, 3000/1500-1500KVA,
1500KVA,
ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC, ONAN,22/0.6-0.6kV,OCTC,
ONAN,22/0.6kV,OCTC,
+/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH +/- 5% IN,STEPS OF 2.5% EACH
+/- 5% IN,STEPS OF 2.5% EACH

TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB TRFO-MB


BR-63 TRFO-MB BR-63 BR-63 BR-63 BR-63
BR-63 BR-63 BR-63 BR-63
WTI-49WT BR-63 WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT WTI-49WT
OTI-49OT WTI-49WT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT OTI-49OT
OTI-49OT

Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel Aux. LT Panel

100kVA 100kVA 100kVA 100kVA 100kVA


Aux.Trafo. Aux.Trafo. Aux.Trafo. Aux.Trafo. Aux.Trafo.

LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel LT Panel


LT Panel

CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT CHINT 6 GMS RK JS UPDATED ACC. TO CUSTOMER COMMENTS 24-09-2018
J 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA 1500KVA J
5 GMS RK JS UPDATED ACC. TO CUSTOMER COMMENTS 17-09-2018
Inv - 02 Inv - 01 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01 Inv - 02 Inv - 01
Container - 19 Container - 20 Container - 6 Container - 5 Container - 14 Container - 13 Container - 12 Container - 11 Container - 16 Container - 15 4 GMS RK JS UPDATED ACCORDING TO CUSTOMER COMMENTS 28-08-2018
3 YG RK RK UPDATED ACCORDING TO CUSTOMER COMMENTS 28-06-2018
2 YG RK RK UPDATED ACCORDING TO CUSTOMER COMMENTS 08-06-2018
1 YG RK RK FOR APPROVAL 16-05-2018
0 YG RK RK FOR APPROVAL 28-04-2018
AC SINGLE LINE DIAGRAM REV DRAWN

DRAWING TITLE:
REVIEWED APPROVED CHANGE

DRAWING NUMBER:
DATE

MV DESIGN PACKAGE SINGLE LINE DIAGRAM CH-BB-SLD-EL-01

K PROJECT NAME & ADDRESS: CUSTOMER: PROJECT NUMBER


K
ACWA BENBAN FOR ENERGY (58.5MW)
Technical Reference Documnets and Drawings: ASWAN ACWA POWER 43-4
1. EETC Technical Specifications of the Delivery Point for the PV Power EPC: OFFTAKER: STATUS:

Plant Projects at Benban Site May 2017


EGYPT ELECTRICITY TRANSMISSION
2. CH-BB-DET-EL-29 FOR APPROVAL
A1 - ( 841 x 594 )mm

COMPANY (EETC)

3. CH-BB-CNS-EL-03
4. Benban - Annexure 1 (IS-Reactor) SCALE:

NTS
FORMAT:

DIN A1
SHEET:

1/1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PRODUCED BY AN AUTODESK STUDENT VERSION