Error messages Status display

F.xxx Fatal error. The door drive no longer operates. STOP Stop
Cover buttons flash quickly.
_Ec_ CLOSE limit position
E.xxx Minor error. The door drive now only operates
in dead-man mode (possibly dependent upon
direction). Cover buttons flash slowly. ≡Ec≡ CLOSE limit position locked electrically

I.xxx Information. Individual door functions are ZUF@ Closing active


disrupted, e.g., if parameterisation is missing or
maintenance is due ZUF@ Closing active (flashes)

x.xxx. Active error. When this has been corrected, it �Eo� OPEN limit position
must be acknowledged by pressing and holding
the rotary-push button. ≡Eo≡ OPEN limit position locked electrically

x.xxx Active error. When this has been corrected, it Opening active
@AUF
does not have to be acknowledged
@AUF Opening active (flashes)
xxxx. Corrected error. It must be acknowledged
F.000 Door position outside movement range �E1� Partial opening position reached
F.185 Confirmation after restart of the control unit Smoke/heat ventilation (RWA) intermediate
≡rA≡
F.211 NA1 EMERGENCY STOP triggered stop position locked electrically
F.212 NA2 EMERGENCY STOP triggered ≡E1≡ Partial opening position locked electrically
F.214 Wicket door open
≡SE≡ Safety edge activated
F.216 Door lock bolt does not unlock
≡Lb≡ Light barrier activated
F.217 Wicket door lock bolt does not unlock
F.330 Slack rope/overload switch triggered
≡S1≡ Pull-in safety device activated

F.336 Negative result for electromagnetic test of ≡S2≡ Pull-in safety device activated
wicket door switch
≡S3≡ Pull-in safety device activated
F.700 OPEN and CLOSE limit switches simultaneously
engaged NOTF Emergency operation

F.701 Partial opening and close limit switches simulta- Hd.cL Closing in dead-man mode (membrane but-
neously engaged ton: CLOSE)
F.750 Absolute value encoder protocol error in Hd.oP Opening in dead-man mode (membrane but-
transmission ton: OPEN)
F.752 Error in transmission to the drive’s absolute Hd.Ec CLOSE limit position reached
value encoder
Hd.Eo OPEN limit position reached
F.850 Collective input fault
‘Hd’ Manual
F.922 Emergency stop transistor defective
HD.ru Inching mode
F.927 Hardware testing of the open, close or safety
transistors failed E.I.C.H. Safety edge (SKS) functional test (in dead-
man mode) possible, the direction of rotation
F.931 Internal control unit error during ROM test is set, automatic switch after travelling a short
F.932 Internal control unit error during RAM test distance in calibration of CLOSE limit position

F.970 Internal access error on non-volatile memory


E.I.E.c. Calibration of the CLOSE limit position
(EEPROM) required (in dead-man mode or reverse, if the
decimal points are flashing)
E.020 Running time exceeded in close direction
E.I.E.o. Calibration of the OPEN limit position required
E.021 Running time exceeded in open direction (in dead-man mode or reverse, if the decimal
E.031 Direction of rotation of the drive different to points are flashing)
expected rotation direction E.I.E.I. Calibration of the partial opening E1 (in dead-
E.080 Maintenance is necessary man mode)

E.115 Stop command engaged for too long


E.I.E.S. Calibration of the safety edge (SKS) pre-limit
switch position (in maintained operation,
E.117 Travel command "Open" engaged for too long if safety edge is o.k., otherwise dead-man
mode)
E.320 Obstacle blocking travel
E.335 Wicket door switching uneven
E.341 Pull-in safety device Open 1 triggered Operator level

E.342 Pull-in safety device Open 2 triggered Calling up parameterisation mode:


Press the rotary-push button (DDT) together with the
E.343 Pull-in safety device Close triggered OPEN button until P.000 appears on the display.
E.350 Safety edge SE1 is connected in the OPEN limit Leaving parameterisation mode:
position or in the PARTIALLY OPEN limit position Press the rotary-push button (DDT) for 5 seconds.
E.352 Negative test of input SE1 000 Door cycle counter
E.360 Safety edge SE2 is connected in the OPEN limit 005 Maintenance counter
position or in the PARTIALLY OPEN limit position
010 Stay open time 1
E.362 Negative test of input SE2
011 Stay open time 2
E.364 No switching impulse from the safety edge in
the lower limit position - testing failed (DW) 014 Switch-off delay for outdoor light

E.374 Safety edge testing pre-limit switch set too high 920 Error history

E.408 Communication error with expansion module 925 Software version

E.801 Negative test from light barrier 1


E.802 Negative test from light barrier 2 Diagnostic mode
E.803 Negative test from pull-in safety device Open 1 n Cycle display open
E.804 Negative test from pull-in safety device Open 2 u Maintenance cycle display
E.805 Negative test from pull-in safety device Close Sx.xx Software version display
E.806 Negative test from safety edge SE1 HiSt Error report history
E.807 Negative test from safety edge SE2 SEy.x Safety input y has status x (x=0..1)
E.810 Radio edge could not be activated. Γy.x Input y has status x (x=0..1) Example Γ01.1
input FE1 is active
E.851 Collective input fault

Information messages
I.043 Fault in the pre-limit switch for the light barrier
I.081 Maintenance interval has elapsed
I.111 Wireless push-button channel 1 engaged for
too long
I.112 Wireless push-button channel 2 engaged for
too long
I.113 Wireless push-button channel 3 engaged for
too long
I.114 Wireless push-button channel 4 engaged for
too long
I.116 Travel command "Close" engaged for too long
I.118 Travel command sequence button engaged for
too long
I.119 Travel command sequence button engaged for
too long
I.220 RWA input triggered
I.351 Safety edge SE1 has triggered on 5 consecu-
tive closing movements
I.361 Safety edge SE2 has triggered on 5 consecu-
tive closing movements
I.852 Collective input fault
I.905 Keypad on cover is not attached properly
en Information sheet for BDC-E800R/S
Position of the terminals and complete connecting diagram: P991: 3
Drive
3~230 V
3~230 V

3~400 V 3~230 V

3 2 1 8 7 9 6 1011 4 5

RADIO
PLUG-IN MODULE
X4

ON

Selection switch automatic closing


Travel command sequence
OPEN/STOP/CLOSE
Selection switch partial opening

Travel command OPEN


Relay / contactor
2.5 AT Travel command CLOSE
X2
Travel command STOP

EMERGENCY STOP

Light barrier
1 AT

Power output
24 V DC max. 0.5 A

Slack rope overload

X3

X1

Door Door OSE


closed open green = SE1 / FE1
OSE 1 white = 0 V
Potential-free relay outputs
Power brown = 12 V
output
5
3 x 400 V AC / 50 - 60 Hz

Position of the terminals and complete connecting diagram: P991: 5


Drive with mechanical limit switching

S1F Safety limit switch OPEN


S2F Safety limit switch CLOSE
Drive
S3F Safety limit switch emergency operation
S3F S1F S4F Thermoswitch
S5 S6 S7 S8 S5 Operational limit switch OPEN
S4F S2F S6 Operational limit switch CLOSE
S7 Pre-limit switch (VES)
PE 1 2 3 4 5 6 7 8 9 10 11 S8 Functional limit switch ½ door height

12

3 2 1 7 6 8 5 11 9 4 10

RADIO
PLUG-IN MODULE
X4

ON

Travel command OPEN


Relay / contactor
2. 5 AT Travel command CLOSE
X2
Travel command STOP

EMERGENCY STOP

Light barrier
1 AT

Power output
24 V DC max. 0.5 A

Slack rope overload

X3

X1

Door Door OSE


closed open green = SE1 / FE1
OSE 1 white = 0 V
Potential-free relay outputs
Power brown = 12 V
output
5
3 x 400 V AC / 50 - 60 Hz

Butzbach GmbH Service Center:


Industrietore Phone +49 (0) 8337/901-111
Fax +49 (0) 8337/901-102
Weiherstrasse 16
89293 Kellmünz, Germany After Sales Service:
Phone +49 (0) 8337/901-444
Fax +49 (0) 8337/901-459
E-mail service-center@butzbach.com
4041 630 119 0 04.14 5420.5643A Internet www.butzbach.com