Description.................................. 2
Specifications.............................. 3
Installation................................... 3
Constant level
Water
Afriso Ema AB
Kilvägen 2 • SE-232 37 Arlöv
Sweden
T +46-(0)40-92 20 50
F +46-(0)40-19 33 58 2460
www.afriso.se
ES 3
Manual
Description
System components The unit may be configured either as a type
Electronic unit ES3 is a universal control unit ES31 for ”cold products” (-25°C to +50°C
to be connected to type approved thermistor e.g. petrol or diesel), or as type ES32 for ”hot
probes. The version ES3K has a built-in products” (+20°C to +80°C e.g. crude oil).
muteable audible alarm. The selection of the ”cold” or ”warm” ranges
is achieved via links on the PCB. The cold
Description: range (-25°C - +50°C) is selected by linking
The electronic unit ES31 is designed for wall pins 1 and 2 on connector block J1.The warm
mounting. When the unit is connected to a range (+20°C to +50°C) is selected by linking
thermistor it may be configured to either a pins 2 and 3 on connector block J1.
high level alarm (e.g as an overfill preven-
tion) or a low level alarm (e.g as a tank leak 1 2 3
indication). J1
Function:
The sensor output is intrinsically safe.The unit
is fitted with a link on the PCB (inaccessible
from the outside) for changing between high
level and low level signals.
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • info@afriso.se • www.afriso.se
2
ES 3
Manual
Specifications
Supply 230 V, 50 Hz
Housing IP 40
Mounting example
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • info@afriso.se • www.afriso.se
3
ES 3
Manual
Mounting ES 334
Generally: Check that the correct alarm level has been
The ES3 units’s housing has a protection selected. For high level alarms pins 1 and
rating of IP40 and must only be mounted in 2 on connector J2 on the PCB must
dry rooms. If moisture is present, the be linked, and for low level alarms pins 2
unit must be mounted in an weatherproof and 3 must be linked.
enclosure with a protection rating of at least
IP 55. Carefully plug the ES3 unit into the base
ensuring that the PCB edge connector
The unit has 2 fixing holes for mounting makes correct contact with and does not
directly onto the wall with screws. damage any of the terminals.
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • info@afriso.se • www.afriso.se
4
ES 3
Manual
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • info@afriso.se • www.afriso.se
5
ES 3
Manual
L N
1 2 7 8 9 10 11 12
Blue or Mains 230 V
2-marked
Brown or 1-marked
L N
1 2 7 8 9 10 11 12
Blue or Mains 230 V
2-marked
Brown or 1-marked
AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • info@afriso.se • www.afriso.se
6
EU Declaration of Conformity
This declaration certifies that the below mentioned apparatus conforms to the essential requirement of the
EMC directive 2014/30/EU, Low-Voltage directive (LVD) 2014/35/EU and ATEX directive 2014/34/EU.
Description of the apparatus : Level Surveillance Equipment type ES31, ES32 and ES33.
EMC:
LVD:
ATEX:
Notified Body DNV GL Nemko Presafe AS; Notified body number 2460
Date: 2018-08-06
Signed:
Urban Nilsson
Position: Technical Manager
Afriso Ema AB
Kilvägen 2 • 232 37 Arlöv • Sweden
T +46-(0)40-92 20 50 • F +46-(0)40-19 33 58
www.afriso.se