CE 323
Prob 1.
Determine the design moment strengths of the sections shown. Use fy = 414 MPa, f’c =27.6 MPa. Check
if the section is ductile.
Prob. 2
Determine the area of reinforcing steel required for T-beam shown if f’c = 21 MPa, fy = 414 MPa, Mu =
542 kN-m, L = 8.40 m and the clear distance between flanges is 900 mm.
Prob. 3
Select the tensile reinforcement needed for the T-beam if the reinforced concrete is assumed to weigh
23.5 kN/m3 and if a live floor load 7 kN/m2 is to be supported. Assume 12.0 m simple spans and fy = 414,
f’c = 27.6 MPa.