Relays

Name/Type Settings Frame/Model TC


DUAL 87T1 51P1P, (0.5-16 x CTR) 4.7 (282A) SEL-787 300/5 Relevador Transformador 1 devanado alta tension
Electronic U3, Very Inverse 2.5

DUAL 87T1-X 51P1P, (0.5-16 x CTR) 5.5 (1650A) SEL-787 1500/5 Relevador Transformador 1 devanado baja tension X
Electronic U3, Very Inverse 2
50P1P, (0.5-96 x CTR) 60 (18000A)

DUAL 87T1-Y 51P1P, (0.5-16 x CTR) 5.5 (1650A) SEL-787 1500/5 Relevador Transformador 1 devanado baja tension Y
Electronic U3, Very Inverse 2
50P1P, (0.5-96 x CTR) 60 (18000A)

DUAL 87T2 51P1P, (0.5-16 x CTR) 4.7 (282A) SEL-787 300/5 Relevador Transformador 2 devanado alta tension
Electronic U3, Very Inverse 2.5

DUAL 87T2-X 51P1P, (0.5-16 x CTR) 5.5 (1650A) SEL-787 1500/5 Relevador Transformador 2 devanado baja tension X
Electronic U3, Very Inverse 2
50P1P, (0.5-96 x CTR) 60 (18000A)

DUAL 87T2Y 51P1P, (0.5-16 x CTR) 5.5 (1650A) SEL-787 1500/5 Relevador Transformador 2 devanado baja tension Y
Electronic U3, Very Inverse 2
50P1P, (0.5-96 x CTR) 60 (18000A)

DUAL DER1 Phase SEL751A Relevador Interruptor derivado 1


Electronic 51P1P, (0.5-16 x CTR) 4.7 (282A) 300/5
U3, Very Inverse 3.0
GROUND
51N1P, (0.5-16 x CTR) 2 (120A) 300/5
U3, Very Inverse 1.1
50N1P, (0.5-100 x CTR) 70 (4200A)

DUAL DER2 Phase SEL751A Relevador Interruptor derivado 2


Electronic 51P1P, (0.5-16 x CTR) 4.7 (282A) 300/5
U3, Very Inverse 3.0
GROUND
51N1P, (0.5-16 x CTR) 2 (120A) 300/5
U3, Very Inverse 1.1
50N1P, (0.5-100 x CTR) 70 (4200A)

DUAL PPAL Phase SEL751A Relevador Interruptor Principal de celda Switchgear


Electronic 51P1P, (0.5-16 x CTR) 9 (540A) 300/5
U3, Very Inverse 3.0
GROUND
51N1P, (0.5-16 x CTR) 2 (120A) 300/5
U3, Very Inverse 1.5
50N1P, (0.5-100 x CTR) 80 (4800A)

TR2-DUAL TRACK Phase 735 Relevador Interruptor Principal de Subestacion 1


Electronic Pickup(Lo) 90 % (540A)
ANSI Very Inverse 1; 4 (S;M)
Instantaneous 8.0 (4800A)
Ground
Pickup(Lo) 20 % (120A)
ANSI Very Inverse 1; 2 (S;M)
Instantaneous 16.0 (9600A)

Ajustes para Proteccion Diferencial


DUAL 87T1 Pickup 0.3 multiplos tap
Electronic SLP1: 25%
SLP2: 60%
IRS1: 4 multiplos tap
U87P: 10 multiplo tap
PCT2: 15%
PCT4: 15%
PCT5: 30%