1VCE015876T0001

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN.

REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

CUSTOMER : AIC

B B

ORDER : 8170001311 ITEM : 10000

PROJECT : Impianto Centro America


C C

SWITCHGEAR NAME : Quadro QMT

D D

SWITCHGEAR TYPE : UniSec 17.5 kV - 60 Hz - 630 A - 25 kA x 1 s

E
DOCUMENT : General Arrangement Drawings E

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved COVER SHEET Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en A01 A03
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

INDEX OF SHEETS STANDARD REFERENCES


SHEET DESCRIPTION REVISION
A THIS DRAWING IS IN COMPLIANCE WITH THE FOLLOWING INTERNATIONAL STANDARDS: A
A01 COVER SHEET A - IEC 60617: GRAPHICAL SYMBOLS FOR DIAGRAMS
A03 INDEX OF SHEETS A - IEC 61082: PREPARATION OF DOCUMENTS USED IN ELECTROTECHNOLOGY
A05 REVISION LIST A - IEC 81346: STRUCTURING PRINCIPLES AND REFERENCE DESIGNATIONS

C01 GENERAL CHARACTERISTICS A THE DIAGRAM INDICATES COMPONENTS HAVING A MOVABLE PART IN THE FOLLOWING POSITION OR
D01 SINGLE LINE DIAGRAM A OPERATIONAL STATE (IEC 61082-1 7.4.4.1):
D02 SINGLE LINE DIAGRAM A - C.BREAKER OR CONTACTOR IN OPEN (OFF) AND SERVICE POSITION
- DISCONNECTORS AND EARTHING SWITCH IN OPEN POSITION
E01 KEY INTERLOCKING A
- WITHDRAWABLE VOLTAGE TRANSFORMERS IN CONNECTED POSITION
B E02 KEY INTERLOCKING A B
- CLOSING SPRINGS OF C.BREAKER IN DISCHARGED POSITION
F01 FRONT VIEW DRAWING A - CONNECTOR OF C.BREAKER AUXILIARY CIRCUITS IN CONNECTED POSITION
H01 FOUNDATION FRAMES DRAWING A - CIRCUITS IN DE-ENERGIZED STATE
J01 FOUNDATION FRAME DRAWINGS WITH DETAILS A - RELAYS IN NON-ACTUATED STATE
- GAS PRESSURE AT RATED SERVICE VALUE
L01 SECTION VIEW A
- FUSES NOT OPERATED
L02 SECTION VIEW A - DOORS AND PRESSURE RELIEF FLAPS IN CLOSED POSITION
Q01 INTERCONNECTION DIAGRAM A

C C

D D

E E

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved INDEX OF SHEETS Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en A03 A05
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

INDEX REVISION LIST


A A
REV

DESCRIPTION DATE PREPARED APPROVED

A FIRST ISSUE 30/03/2017 TASCA LOCATELLI

C
D

B E B
F

I
L

C C

D D

E E

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved REVISION LIST Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en A05 C01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

CHARACTERISTICS NOTES
A (IN COMPLIANCE WITH STANDARD IEC 62271-200) A
SWITCHGEAR VERSION = COMPLETE COLOUR OF FRONT DOORS = RAL 7035

RATED VOLTAGE (Un) = 17.5 kV SIDEWALLS PAINTED = NO SIDES = L+R

OPERATING VOLTAGE = 13.8 kV

RATED FREQUENCY (fr) = 60 Hz

RATED LIGHTNING IMPULSE WITHSTAND VOLTAGE (Up) = 95 kV


B
RATED POWER FREQUENCY WITHSTAND VOLTAGE (Ud) = 38 kV SUPPLIED IMPLEMENTS B

RATED CURRENT OF MAIN BUSBARS (Ir) = 630 A MIMIC DIAGRAM

RATED SHORT-TIME WITHSTAND CURRENT (Ik) = 25 kA COUPLE OF SIDES CLOSING

RATED PEAK WITHSTAND CURRENT (Ip) = 65 kA BOTTOM CLOSURE

RATED DURATION OF SHORT CIRCUIT (tk) = 1s ISOLATOR OPERATING LEVER

INTERNAL ARC CLASSIFICATION (IAC) = AF

C AMBIENT CONDITION = NORMAL C

AMBIENT AIR TEMPERATURE = -5°C...+40°C

DEGREE OF PROTECTION (OPERATION SEATS EXCLUDED) = IP3X

DEGREE OF PROTECTION WITH OPEN DOORS = IP2X

RATED SUPPLY VOLTAGE OF CONTROL AND SIGNALLING CIRCUITS (Ua) = 230VAC


IDENTIFICATION OF CONDUCTORS
RATED SUPPLY VOLTAGE OF SPRING CHARGING MOTOR (Ua) = 230VAC

D RATED SUPPLY VOLTAGE OF LIGHTING AND HEATING CIRCUITS (Ua) = 230VAC D


TYPE OF CABLE FOR LOW VOLTAGE CONDUCTORS = 450/750V
FOR IDENTIFICATION OF CONDUCTORS THE "LOCAL END CONNECTION LABELLING" SYSTEM IS USED,
TYPE OF CABLE FOR LOW VOLTAGE CONDUCTORS = PVC IN COMPLIANCE WITH STANDARD IEC 62491 PARAGRAPH 6.2. THIS SYSTEM FORESEES THAT THE
MARKING OF A CONDUCTOR END SHOWS THE DESIGNATION OF THE TERMINAL TO WHICH IT IS
CROSS-SECTION OF CONDUCTORS FOR CURRENT CIRCUITS = 4 mm² CONNECTED. IN COMPLIANCE WITH STANDARD IEC 61666 EACH CONDUCTOR IS IDENTIFIED WITH THE
REFERENCE DESIGNATION OF THE CONNECTED ELECTRICAL COMPONENT FOLLOWED BY SIGN ":"
CROSS-SECTION OF CONDUCTORS FOR VOLTAGE CIRCUITS = 1.5 mm² (COLON), FOLLOWED BY THE TERMINAL DESIGNATION. FOR EXAMPLE THE CONDUCTOR CONNECTED
TO TERMINAL "10" OF THE COMPONENT WITH DESIGNATION "-XA" HAS THE MARKING "-XA:10". THE
CROSS-SECTION OF CONDUCTORS FOR MOTORS = 2.5 mm² CONDUCTOR MARKING IS PLACED IN SUCH A WAY TO READ IT ALWAYS FROM THE TERMINAL
TOWARDS THE CONDUCTOR, AS SHOWN BELOW
CROSS-SECTION OF OTHER CONDUCTORS (CONTROL AND SIGNALLING CIRCUITS) = 1 mm²
E E
CROSS-SECTION OF CONDUCTORS FOR INTERCONNECTIONS = 2.5 mm²

CROSS-SECTION OF CONDUCTORS FOR INTERCONNECTIONS OF SUPPLY VOLTAGE = 4 mm² -XDA


COMMUNICATION CABLE = - 9
-XDA:10
10 -XDA:10
11

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved GENERAL CHARACTERISTICS Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en C01 D01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

3 AC 13.8kV 60Hz, 630A, 25kA for 1Sec


A -BB1 BB1 A
/
D02.1A

B B
-QAB -QAB -QAB -QAB
HD4/P HD4/P HD4/P HD4/P
17.5kV 17.5kV 17.5kV 17.5kV
630A 630A 630A 630A
25kA 25kA 25kA 25kA

P1 -PFV1 P1 -PFV1 P1 -PFV1 P1 -PFV1


-BCT1 REF615 -BCT1 REF615 -BCT1 REF615 -BCT1 REF615
-BCT2 -AA -BCT2 -AA -BCT2 -AA -BCT2 -AA
-BCT3 P2 -BCT3 P2 -BCT3 P2 -BCT3 P2
200-400/1A 200-400/1A 200-400/1A 200-400/1A
5VA 5VA 5VA 5VA
C cl.5P10 cl.5P10 cl.5P10 cl.5P10 C

-BAT1
-QCE -BAT2 -QCE -QCE -QCE
-BAT3
13.8/V3kV
0,1/V3kV-70VA-cl.1
0,1/3kV-70VA-cl.6P

D D

-BCN -BCN -BCN


100/1A 100/1A 100/1A
-BCN 0.5VA-cl.3 0.5VA-cl.3 0.5VA-cl.3
100/1A
0.5VA-cl.3

E E
Panel H01 H02 H03 H04
Panel Name WBC WBC WBC WBC

Description Incoming Outgoing 1 Outgoing 2 Outgoing 3

Rated Current 630A 630A 630A 630A


Max. Cable Size 3x1x300mm² 3x1x300mm² 3x1x300mm² 3x1x300mm²
Circuit Diagram 1VCE015876T0100 1VCE015876T0101 1VCE015876T0101 1VCE015876T0101

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved SINGLE LINE DIAGRAM Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05 &EFA
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en D01 D02
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A BB1 -BB1 A
/
D01.8A

B B
-QAB
HD4/P
17.5kV
630A
25kA

P1 -PFV1
-BCT1 REF615
-BCT2 -AA
-BCT3 P2
200-400/1A
5VA
C cl.5P10 C

-QCE

D D

-BCN
100/1A
0.5VA-cl.3

E E
Panel H05
Panel Name WBC

Description Outgoing 4

Rated Current 630A


Max. Cable Size 3x1x300mm²
Circuit Diagram 1VCE015876T0101

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved SINGLE LINE DIAGRAM Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05 &EFA
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en D02 E01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

TAKING OUT OF SERVICE


OPENING CIRCUIT BREAKER
TO DRAW THE WITHDRAWABLE PART OUT OF CIRCUIT BREAKER KEY MATRIX
OPENING DOOR COMPARTIMENT OF CIRCUIT BREAKER
RACK THE CIRCUIT-BREAKER
INSERT KEY IN THE EARTH OPERATING SEAT OF EARTING SWITCH -QCE ...5
B CLOSING EARTHING SWITCH B
-QAB REMOVE THE KEY -QCE ...6
OPENING DOOR CABLES COMPARTIMENT OF MEDIUM VOLTAGE

COMMISSIONING
REPEAT THE OPERATION OF "PUTTING OUT OF SERVICE" IN OPPOSITE SEQUENCE
C C

-PFV1
5 6

-QCE

D D

E E

Panel = H01 = KEY FREE WITH APPARATUS IN OPEN OR TEST POSITION

= KEY FREE WITH APPARATUS IN CLOSED POSITION


F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved KEY INTERLOCKING Ref. designation DCC


AIC LOCATELLI H01 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en E01 E02
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

TAKING OUT OF SERVICE


OPENING CIRCUIT BREAKER
TO DRAW THE WITHDRAWABLE PART OUT OF CIRCUIT BREAKER KEY MATRIX
OPENING DOOR COMPARTIMENT OF CIRCUIT BREAKER
RACK THE CIRCUIT-BREAKER
INSERT KEY IN THE EARTH OPERATING SEAT OF EARTING SWITCH -QCE ...5
B CLOSING EARTHING SWITCH B
-QAB REMOVE THE KEY -QCE ...6
OPENING DOOR CABLES COMPARTIMENT OF MEDIUM VOLTAGE

COMMISSIONING
REPEAT THE OPERATION OF "PUTTING OUT OF SERVICE" IN OPPOSITE SEQUENCE
C C

-PFV1
5 6

-QCE

D D

E E

Panel = H02,H03,H04,H05 = KEY FREE WITH APPARATUS IN OPEN OR TEST POSITION

= KEY FREE WITH APPARATUS IN CLOSED POSITION


F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved KEY INTERLOCKING Ref. designation DCC


AIC LOCATELLI H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en E02 F01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

FRONT VIEW

B B

C C

D D

27 600 600 600 600 600 27

3054

E E
Panel H01 H02 H03 H04 H05

Panel Type WBC WBC WBC WBC WBC

Description Incoming Outgoing 1 Outgoing 2 Outgoing 3 Outgoing 4

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id
1:20
Customer Approved FRONT VIEW DRAWING Ref. designation DCC
AIC LOCATELLI H01,H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en F01 H01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

FOUNDATION FRAMES

B B

C C

D D

600 600 600 600 600


3055

E E
Panel H01 H02 H03 H04 H05

Panel Type WBC WBC WBC WBC WBC

Description Incoming Outgoing 1 Outgoing 2 Outgoing 3 Outgoing 4

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id
1:20
Customer Approved FOUNDATION FRAMES DRAWING Ref. designation DCC
AIC LOCATELLI H01,H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en H01 J01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

FOUNDATION FRAMES DETAILS

B B

43,5 513 43,5 43,5 513 43,5

ø ø
12 12
,5 ,5
(4 (4
x) x)

98,5

98,5
236,5

236,5
C C
230

230
800

800
1200

1200
700,5

700,5
10 10 10 10
268,5

268,5
92 101

92 101
30 30 30 30
43 154

43 154
D D
33

33
82 436 82 82 436 82

600 600

PANELS: H01 PANELS: H02, H03, H04, H05


E E

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id
1:20
Customer Approved FOUNDATION FRAME DRAWINGS WITH DETAILS Ref. designation DCC
AIC LOCATELLI H01,H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en J01 L01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

SECTION VIEW

B B

230 230 DISTANCE BETWEEN THE CABLE CONNECTION POINT AND


-
THE FLOOR = 600mm
14 1 LVC
1
2 EARTHING SWITCH

3 MEDIUM VOLTAGE CABLES


C C
6 CURRENT TRANSFORMER

9 CIRCUIT BREAKER

2000
9 14 INTERPANEL WIRING PASSAGE
6 15 VOLTAGE TRANSFORMER

3
2
D D

15

S0i
Si
0
3
7.5
1
Si
0
4
3
1
3

1200

1270

E E
Panel : H01

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id
1:20
Customer Approved SECTION VIEW Ref. designation DCC
AIC LOCATELLI H01 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en L01 L02
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8

A A

SECTION VIEW

B B

230 230 DISTANCE BETWEEN THE CABLE CONNECTION POINT AND


-
THE FLOOR = 600mm
14 1 LVC
1
2 EARTHING SWITCH

3 MEDIUM VOLTAGE CABLES


C C
6 CURRENT TRANSFORMER

9 CIRCUIT BREAKER

2000
9 14 INTERPANEL WIRING PASSAGE
6

3
2
D D

S0i
Si
0
3
7.5
1
Si
0
4
3
1
3

1200

1270

E E
Panel : H02, H03, H04, H05

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id
1:20
Customer Approved SECTION VIEW Ref. designation DCC
AIC LOCATELLI H02,H03,H04,H05 &ELH
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en L02 Q01
1 2 3 4 5 6 7 8
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPRODUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPESS AUTHORITY IS STRICTLY FORBIDDEN 1 2 3 4 5 6 7 8
COLOUR
CROSS H01 H02 H03 H04 H05
SECTION
[ mm² ]

A -XDI1 -XDI1 -XDI1 -XDI1 -XDI1 A


bk 4 1 2 1 2 1 2 1 2 1 2

AUXILIARY POWER SUPPLY


230VAC AUXILIARY CIRCUITS
bk 4 3 4 3 4 3 4 3 4 3 4

-XDI2 -XDI2 -XDI2 -XDI2 -XDI2


1 2 1 2 1 2 1 2 1 2
bk 4
AUXILIARY POWER SUPPLY 230VAC
CIRCUIT BREAKER SPRING CHARGING MOTOR
3 4 3 4 3 4 3 4 3 4
B bk 4 B

-XDI4 -XDI4 -XDI4 -XDI4 -XDI4


1 2 1 2 1 2 1 2 1 2
bk 4
C C
AUXILIARY POWER SUPPLY
230VAC HEATING AND LIGHTING
3 4 3 4 3 4 3 4 3 4
bk 4

D D

E E

F F
Scale Based on Created on TASCA 30/03/2017 TITLE External doc. id

Customer Approved INTERCONNECTION DIAGRAM Ref. designation DCC


AIC LOCATELLI H01,H02,H03,H04,H05
Project no Project name Work order id Resp. (division/department) Document kind Document id Revision Lang Page Cont
Impianto Centro America 8170001311 ABB SpA EPMV General Arrangement Drawings 1VCE015876T0001 A en Q01
=H01&CD/A01
1 2 3 4 5 6 7 8

You might also like