NAVKOM + EMERGENCY SOURCE OF ELECTRICAL POWER (ESEP) - Kelompok B
NAVKOM + EMERGENCY SOURCE OF ELECTRICAL POWER (ESEP) - Kelompok B
6. all ships of 300 gross tonnage and upwards engaged on international voyages and cargo
ships of 500 gross tonnage and upwards not engaged on international voyages and passenger
ships irrespective of size shall be fitted with an automatic identification system (AIS)
7. rudder, propeller, thrust, pitch and operational mode indicators, or other means, to determine
and display rudder angle, propeller revolutions, the force and direction of thrust (Rudder Angle
Indicator)
Navigation
Shipborne Navigational Sys. and Equipment - SOLAS Ch V, Regulation 19
General
8. a properly adjusted standard magnetic compass, or other means, independent of any power
supply, to determine the ship's heading and display the reading at the main steering
position(Magnetic compas)
11. a gyro-compass, or other means, to determine and display their heading by shipborne non-
magnetic means, being clearly readable by the helmsman at the main steering position. (Gyro
Compas)
Navigation
Shipborne Navigational Sys. and Equipment - SOLAS Ch V, Regulation 19
Navigation
NK Rules for Navigation Bridge Systems or Guidance - Safety Equipment
EMERGENCY SOURCE
OF
ELECTRICAL POWER
Emergency Source of Electrical Power
ESEP in Cargo Ships - SOLAS Ch II-1, Part D, Regulation 43
Emergency Lighting
2.1. For Period of 3 hour, Emergency lighting at every muster and embarkation station and over the sides
2.2. For Period of 18 hour:
● in all service and accommodation alleyways, stairways and exits, personnel lift cars and personnel lift
trunks
● in the machinery spaces and main generating stations including their control positions
● in all control stations, machinery control rooms, and at each main and emergency switchboard
● at all stowage positions for firemen’s outfits
● at the steering gear
● at the fire pump referred to in paragraph 2.5, at the sprinkler pump, if any, and at the emergency bilge pump,
if any, and at the starting positions of their motors
● in all cargo pump-rooms of tankers constructed on or after 1 July 2002
Emergency Source of Electrical Power
ESEP in Cargo Ships - SOLAS Ch II-1, Part D, Regulation 43
Communication and Navigation Eq.
2.3 For a period of 18 h:
● the navigation lights and other lights required by the International Regulations for Preventing Collisions at Sea
in force
● VHF radio; MF radio; the ship earth station (Inmarsat C); MF/HF radio installation required
2.4 For a period of 18 h:
● all internal communication equipment as required in an emergency
● the shipborne navigational equipment as required by regulation V/12;* where such provision is unreasonable
or impracticable the Administration may waive this requirement for ships of less than 5,000 gross tonnage
● intermittent operation of the daylight signalling lamp, the ship’s whistle, the manually operated call points and
all internal signals that are required in an emergency;
FireFighter Eq.
● (2.4) Fire detection and fire alarm system
● (2.5) For a period of 18 h one of the fire pumps required, if dependent upon the emergency generator for its
source of power
Emergency Source of Electrical Power
BKI Vol IV, Sec. 3-C Emergency Electrical Power Supply
Emergency Source of Electrical Power
BKI Vol IV, Sec. 3-C Emergency Electrical Power Supply
Emergency Source of Electrical Power
BKI Vol IV, Sec. 3-C Emergency Electrical Power Supply
ESEP
-
BATTERY
Beban DC di kapal Untuk Baterai
1. Communication
Name of Equipment Merk Power (W) Operating Voltage
Fire Alarm Crouse Hinds XB4 33.6 17 571.2 220 VDC 24 VDC
source: relionbattery.com/products/lithium/application/marine
Spesifikasi Baterai (2)
source: www.victronenergy.com
Spesifikasi Baterai (3)
source: www.rollsbattery.com
Pemilihan Spesifikasi Baterai
Voltase Sistem : 24 V Total Kebutuhan Energi : 68718.96 Wh
Kebutuhan Kapasitas : 2863.29 Ah
Manufacture Relion Battery Victron Energy Rolls Battery
Amount of Battery 29 15 16
Spesifikasi Baterai Terpilih
Manufacture Victron Energy
Voltage 25.6 V
Amount of Battery 15
Charger Requirement
BKI Vol IV, Sec. 20 Electrical Equipment
Charger Specification
BKI Vol IV, Sec. 20 Electrical Equipment
Voltase Battery : Charger Max. Time (0%-80%) : 10 jam
25.6 V Charger Current Needs : 240 A
Kapasitas Baterai Terpilih : 3000 Ah Amount of Charger : 3 pcs
Kapasitas Baterai (80%) : 2400 Ah
Victron Energy
Skylla - TG 24/100-G
Drawing
Drawing
Victron Energy
Recommendation Connection
ESEP
-
EMERGENCY GENERATOR
Emergency Generator
Emergency Generator Set is one type of Emergency Source of Electrical Power.
There are some rules & regulations about this equipment in
● ESEP shall be located above the uppermost continuous deck and shall be
readily accessible from the open deck.
● Where the ESEP is generator, it shall be driven by a suitable prime mover with
an independent supply of fuel, having a flashpoint of not less than 43°C.
● started automatically upon failure of the electrical supply from the main
source of electrical power and shall be automatically connected to the
emergency switchboard
● provided with a transitional source of emergency electrical power
● automatically started and supplying the required load as quickly as is safe
and practicable subject to a maximum of 45 s.
Requirement Generator by Class
Emergency electrical power supply on cargo ship, BKI Class Vol IV 2019 Edition,
Rules for Electrical Installation, Section 3-7
Emergency Generator
Emergency Generator must be can supply electrical power for equipment below:
Fire Alarm Crouse Hinds XB4 33.6 17 571.2 220 VDC 24 VDC
Brand : SILI
Type : 100CLZ-6
Capacity : 80m3/h
Head : 80 m
RPM : 2900
Freq : 50 Hz
Voltage : 380 Volt
Power : 37 kW
Beban AC di kapal Untuk Generator
6. Steering Gear
65.724 Kw
Pemilihan Emergency Generator
Merk Yanmar
Type 6HAL2-WHT
RPM 1500
Freq 50 Hz
Power 200 kW
Length 2574 mm
Width 1164 mm
Height 1804 mm
Emergency Generator Location