1000 cfm 1000 cfm 1000 cfm 1000 cfm

15'
8000 cfm 6000 cfm 4000 cfm 2000 cfm

A B C D
45' 40' 40' 35' 15'

1000 cfm 1000 cfm 1000 cfm 1000 cfm

Equivalen
legnht of static Rectangul
Section Flow rate velocity friction Friction t Duct Remark
duct Pressure ar Duct
Diameter

(cfm) (fpm) (in wg/100ft) (ft) (in of wg) (in of wg) (inch) (inch)

A 8000 3000 0.556 45 0.25 22.1 24"x16" Main 22.995 0.22995


B 6000 2400 0.375 40 0.15 0.182 21.4 22"x16" Main
C 4000 1900 0.250 40 0.1 0.121 19.7 20"x16" Main
C 4000 1834 0.135
D 2000 1500 0.229 35 0.08 0.08 15.6 14x16 Main
Branch 1000 1300 0.200 15 0.03 0.03 11.9 12"x10" Branch
SP = R x {(V1/4000)2-(V2/4000)2}

SP = Static Pressure
V1 = Velocity at previous duct section
V2 = Velocity at current duct section
R = Recovery factor, depends on shape of fitting that changes velocity, 0,7 - 0,9