FILE NAME : 1007-KUR-PC-PID-1001_REVD3

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

FOR HOGPL CITY GAS PIPELINE SYSTEM FOR KURUKSHETRA

K PROCESS PARAMETERS DESIGN PARAMETERS K

FLUID NATURAL GAS DESIGN CLASS 300#

FLOW RATE 20 SCMH (MIN.) / 18000 SCMH (MAX.) DESIGN PRESSURE 49 kg/cm²g

INLET PRESSURE 19 kg/cm²g (MIN.) / 44 kg/cm²g DESIGN TEMPERATURE -29 / 65°C

OUTLET PRESSURE 16 kg/cm²g (MIN.) / 41 kg/cm²g (MAX.) LOCATION CLASS


OPERATING
0°C (MIN.) / 45°C (MAX.) PIPELINE CLASS 4
TEMPERATURE

J J

SHARMA PETROL PUMP


(TYPICAL DETAIL)
I NOTE-2 I
PG VENT
1053

3/4"
OLS 15HLT
2"x3/4" 3/4" 30HLT
FOR CNG STATION
NC
1007
NC
3/4" 30HLT
U/G A/G 2" 30HC H
4"
H 4"-P-30HC-1024

RB
INSULATING
JOINT 2"

TO CNG COMPRESSOR

G
G

TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL 4" TYPICAL TYPICAL TYPICAL 4"
DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 DETAIL-1 4" DETAIL-1 4" DETAIL-1

FROM CGS TO MODEL TOWN


8"-P-30HC-1023 8"x8"
1007-AMB-PC-PID-1001 1007-KUR-PC-PID-1001
SHT_6 OF 6 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" SHT_2 OF 4
FB FB FB FB FB FB FB FB FB FB FB
SV STATION-16 SV STATION-17 SV STATION-18 SV STATION-19 SV STATION-20 SV STATION-21 SV STATION-22 SV STATION-23 SV STATION-24 SV STATION-25 8" SV STATION-26
TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 F
F AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE PROVISION FOR AT A CHAINAGE
UP TO ~ 36.50 KM CONNECTIONS UP TO ~ 45.50 KM
UP TO ~ 15.50 KM UP TO ~ 18.50 KM UP TO ~ 21.50 KM UP TO ~ 24.50 KM UP TO ~ 27.50 KM UP TO ~ 30.50 KM UP TO ~ 33.50 KM UP TO ~ 39.50 KM UP TO ~ 42.50 KM
D3 D3 D3 D3 D3 D3 D3 D3 D3 D3 TO ADHOYA D3
VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT

E
E

SECTIONALISING VALVE (TYPICAL DETAIL - 1)

D
D
PG
(TYPICAL DETAIL)

PG

INSTRUMENTATION
PIPING
8" 3/4"
C
C 2"x3/4"

2"
3" 3"
3"

3/4"
B
B

GENERAL NOTES:- REFERENCE DRAWINGS CLIENT: PROJECT:


1. ALL LINE NUMBERING AND EQUIPMENT TAG NUMBERING SHALL BE PRE-FIXED WITH PROJECT & AREA CODE AS "1007-KUR". DRAWING TITLE DRAWING NUMBER HOGPL GAS PRIVATE LIMITED CGD PROJECT OF AMBALA -
2. ALL INSTRUMENT TAG NUMBER SHALL BE PRE-FIXED WITH PROJECT AREA CODE AS "1007-KUR " AND P & ID NUMBER. KURUKSHETRA & KOLHAPUR DISTRICT
(HOGPL)
NOTES:- TITLE:
PIPING & INSTRUMENTATION DIAGRAM
1. ALL INSTRUMENT SIGNALS SHALL BE INTERFACED TO STATION RTU.
2. VENT SHALL BE PROVIDED WITH FLAME ARRESTOR GOOSE NECK / RAIN HOOD WITH BIRD SCREEN. PMC: FOR FACILITIES AT CHAINAGE ~ 46.00 KM
3. ALL VENTS SHALL BE PROVIDED MIN. 3M HIGH FROM NEAREST HIGHEST OPERATING PLATFORM OR NEARBY D3 19.09.19 RE-ISSUED FOR CLIENT APPROVAL SKU BND AD
M/s. VCS QUALITY SERVICES PVT. LTD. SCALE: N.T.S TOTAL NO. OF SHTS: A
STRUCTURE WITHIN 15M WHICHEVER IS HIGHER. NON SPARKING MATERIAL (BRASS) SHALL BE USED FOR 1 OF 3
A D2 22.05.19 RE-ISSUED FOR CLIENT APPROVAL SKU BND AD B-10 SECOND FLOOR, BAJAJ BHAWAN
FLAPPER TYPE VENT CONNECTION
D1 12.03.19 ISSUED FOR CLIENT APPROVAL SKU BND AD SECTOR 3, NOIDA - 201301 SIZE JOB NO. DRAWING NUMBER REV.

REV. DATE DESCRIPTION PREP. CHKD. APPD. A1 1007 1007-KUR-PC-PID-1001 D3

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
FILE NAME : 1007-KUR-PC-PID-1001_REVD3

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

FOR HOGPL CITY GAS PIPELINE SYSTEM FOR KURUKSHETRA

PROCESS PARAMETERS DESIGN PARAMETERS


K K
FLUID NATURAL GAS DESIGN CLASS 300#

FLOW RATE 20 SCMH (MIN.) / 14160 SCMH (MAX.) DESIGN PRESSURE 49 kg/cm²g

INLET PRESSURE 19 kg/cm²g (MIN.) / 44 kg/cm²g DESIGN TEMPERATURE -29 / 65°C

OUTLET PRESSURE 16 kg/cm²g (MIN.) / 41kg/cm²g (MAX.) LOCATION CLASS - 4


OPERATING
0°C (MIN.) / 45°C (MAX.) PIPELINE CLASS 4
TEMPERATURE

J J

NEW BUS STAND

(TYPICAL DETAIL)
NOTE-2
PG
VENT

I OLD BUS STAND I


3/4" (TYPICAL DETAIL)
NOTE-2
15HLT 2"x3/4" OLS PG VENT
30HLT 3/4"
FOR CNG STATION 1053
NC
1008
NC
30HLT 3/4" 2" OLS
30HC 4" AG UG 3/4"
4"-P-30HC-1027 FOR CNG STATION
15HLT FOR FUTURE PROVISION
1009 2"x3/4" 3/4"
TO KURUKSHETRA SECTOR-2 30HLT
RB NC
INSULATING H
H 2" JOINT NC
4" 3/4" 30HLT
U/G A/G 4" 2" 30HC
4"-P-30HC-1029

4"-P-30HC-1025
KURUKSHETRA UNIVERSITY
RB
INSULATING 4"-P-30HC-1031
JOINT 2" A/G 4"
FOR DRS-1009
STATION
RB
INSULATING
4"-P-30HC-1028 TO CNG COMPRESSOR JOINT
4" AG UG G
FOR DRS-1007
G
PIPLI CHOWK STATION
INSULATING
TYPICAL TYPICAL TYPICAL JOINT TYPICAL TYPICAL TYPICAL
DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4" DETAIL-1 4"
4" 4"
FROM CGS 8"x6" TO MODEL TOWN
8"-P-30HC-1023 8"-P-30HC-1026 8"-P-30HC-1025 6"-P-30HC-1032
1007-KUR-PC-PID-1001 1007-KUR-PC-PID-1001
SHT_2 OF 3 8" 8"x4" 8" 8"x4" 8" 8"x4" 8" 8"x4" 8"x4" 8" 8"x4" 8" 8"x4" 8"x4" 6" 6" 6"x4" 6"x4" SHT_3 OF 3
FB FB FB FB FB FB
SV STATION-27 SV STATION-28 SV STATION-29 AT A CHAINAGE SV STATION-30 SV STATION-31 AT A CHAINAGE SV STATION-32 AT A CHAINAGE
TYP. - 1 TYP. - 1 TYP. - 1 UP TO ~ 56.58 TYP. - 1 TYP. - 1 UP TO ~ 62.00 KM TYP. - 1 UP TO ~ 65.40 KM
D3 D3 F
AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE VALVE PIT AT A CHAINAGE AT A CHAINAGE VALVE PIT AT A CHAINAGE
F VALVE PIT
UP TO ~ 48.50 KM UP TO ~ 51.50 KM UP TO ~ 54.40 KM UP TO ~ 57.40 KM UP TO ~ 60.40 KM UP TO ~ 63.40 KM
D3 D3 D3 D3 D3 D3 D3
VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT

FOR FUTURE PROVISION

E
E

SECTIONALISING VALVE (TYPICAL DETAIL - 1)

8"

D
D
PG
(TYPICAL DETAIL)

3" 3"
PG
3"

INSTRUMENTATION 3/4"
PIPING
3/4" 6"

C
C 2"x3/4"

2"
2" 2"
2"

3/4"

B
B

GENERAL NOTES:- REFERENCE DRAWINGS CLIENT: PROJECT:


DRAWING TITLE DRAWING NUMBER HOGPL GAS PRIVATE LIMITED CGD PROJECT OF AMBALA -
1. ALL LINE NUMBERING AND EQUIPMENT TAG NUMBERING SHALL BE PRE-FIXED WITH PROJECT & AREA CODE AS "1007-KUR".
2. ALL INSTRUMENT TAG NUMBER SHALL BE PRE-FIXED WITH PROJECT AREA CODE AS "1007-KUR" AND P & ID NUMBER. KURUKSHETRA & KOLHAPUR DISTRICT
(HOGPL)
NOTES:- TITLE:
PIPING & INSTRUMENTATION DIAGRAM FOR
1. ALL INSTRUMENT SIGNALS SHALL BE INTERFACED TO STATION RTU.
2. VENT SHALL BE PROVIDED WITH FLAME ARRESTOR GOOSE NECK / RAIN HOOD WITH BIRD SCREEN. PMC: FACILITIES UP TO AT CHAINAGE 65.00 KM
3. ALL VENTS SHALL BE PROVIDED MIN. 3M HIGH FROM NEAREST HIGHEST OPERATING PLATFORM OR NEARBY D3 19.09.19 RE-ISSUED FOR CLIENT APPROVAL SKU BND AD
M/s. VCS QUALITY SERVICES PVT. LTD. SCALE: N.T.S TOTAL NO. OF SHTS: A
STRUCTURE WITHIN 15M WHICHEVER IS HIGHER. NON SPARKING MATERIAL (BRASS) SHALL BE USED FOR 2 OF 3
A D2 22.05.19 RE-ISSUED FOR CLIENT APPROVAL SKU BND AD B-10 SECOND FLOOR, BAJAJ BHAWAN
FLAPPER TYPE VENT CONNECTION
D1 12.03.19 ISSUED FOR CLIENT APPROVAL SKU BND AD SECTOR 3, NOIDA - 201301 SIZE JOB NO. DRAWING NUMBER REV.

REV. DATE DESCRIPTION PREP. CHKD. APPD. A1 1007 1007-KUR-PC-PID-1001 D3

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
FILE NAME : 1007-KUR-PC-PID-1001_REVD3

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

FOR HOGPL CITY GAS PIPELINE SYSTEM FOR KURUKSHETRA

PROCESS PARAMETERS DESIGN PARAMETERS


K K
FLUID NATURAL GAS DESIGN CLASS 300#

FLOW RATE 20 SCMH (MIN.) / 14160 SCMH (MAX.) DESIGN PRESSURE 49 kg/cm²g

INLET PRESSURE 19 kg/cm²g (MIN.) / 44 kg/cm²g DESIGN TEMPERATURE -29 / 65°C

OUTLET PRESSURE 16 kg/cm²g (MIN.) / 41kg/cm²g (MAX.) LOCATION CLASS - 4


OPERATING
0°C (MIN.) / 45°C (MAX.) PIPELINE CLASS 4
TEMPERATURE

J J

I I

FOR FUTURE PROVISION

H
H

G
G

PEHOWA

TYPICAL 4" TYPICAL 4" TYPICAL 4" TYPICAL 4" TYPICAL 4" TYPICAL 4" 4" TYPICAL
DETAIL-1 DETAIL-1 DETAIL-1 DETAIL-1 DETAIL-1 DETAIL-1 DETAIL-1

FROM DEVI OIL PUMP


6"-P-30HC-1032 F
1007-KUR-PC-PID-1001
F 6" 6"x4" 6" 6"x4" 6" 6"x4" 6" 6"x4" 6" 6"x4" 6" 6"x4" 6"x4" 6"
SHT_2 OF 3
FB FB FB FB FB FB FB
SV STATION-33 SV STATION-34 SV STATION-35 SV STATION-36 SV STATION-37 SV STATION-38 SV STATION-35
TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1 TYP. - 1
AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE AT A CHAINAGE
UP TO ~ 66.40 KM UP TO ~ 69.40 KM UP TO ~ 72.40 KM UP TO ~ 75.40 KM UP TO ~ 78.40 KM UP TO ~ 81.40 KM UP TO ~ 85.40 KM
D3 D3 D3 D3 D3 D3 D3
VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT VALVE PIT

E
E

SECTIONALISING VALVE (TYPICAL DETAIL - 1)

D
D

PG
(TYPICAL DETAIL)

PG

6"
INSTRUMENTATION
PIPING C
3/4"
C

2"x3/4"

2" 2"
2"
2"

3/4"

B
B
REFERENCE DRAWINGS CLIENT: PROJECT:
DRAWING TITLE DRAWING NUMBER HOGPL GAS PRIVATE LIMITED CGD PROJECT OF AMBALA -
1. ALL LINE NUMBERING AND EQUIPMENT TAG NUMBERING SHALL BE PRE-FIXED WITH PROJECT & AREA CODE AS "1007-KUR".
2. ALL INSTRUMENT TAG NUMBER SHALL BE PRE-FIXED WITH PROJECT AREA CODE AS "1007-KUR" AND P & ID NUMBER. KURUKSHETRA & KOLHAPUR DISTRICT
(HOGPL)
NOTES:- TITLE:
PIPING & INSTRUMENTATION DIAGRAM FOR
1. ALL INSTRUMENT SIGNALS SHALL BE INTERFACED TO STATION RTU.
2. VENT SHALL BE PROVIDED WITH FLAME ARRESTOR GOOSE NECK / RAIN HOOD WITH BIRD SCREEN. PMC: FACILITIES UP TO AT CHAINAGE 72.00 KM
3. ALL VENTS SHALL BE PROVIDED MIN. 3M HIGH FROM NEAREST HIGHEST OPERATING PLATFORM OR NEARBY D3 19.09.19 RE-ISSUED FOR CLIENT APPROVAL SKU BND AD
M/s. VCS QUALITY SERVICES PVT. LTD. SCALE: N.T.S TOTAL NO. OF SHTS: A
STRUCTURE WITHIN 15M WHICHEVER IS HIGHER. NON SPARKING MATERIAL (BRASS) SHALL BE USED FOR 3 OF 3
A D2 22.05.19 RE-ISSUED FOR CLIENT APPROVAL SKU BND AD B-10 SECOND FLOOR, BAJAJ BHAWAN
FLAPPER TYPE VENT CONNECTION
D1 12.03.19 ISSUED FOR CLIENT APPROVAL SKU BND AD SECTOR 3, NOIDA - 201301 SIZE JOB NO. DRAWING NUMBER REV.

REV. DATE DESCRIPTION PREP. CHKD. APPD. A1 1007 1007-KUR-PC-PID-1001 D3