General Specifications

0° to 45°C (32° to 113°F) – Rev A (Prior to May 2018)

Expansion Module
Operating Temperature
0° to 60°C (32° to 140°F) – Rev B (After May 2018)
Storage Temperature -20° to 70°C (-4° to 158°F)
Humidity 5 to 95% (non-condensing)
Environmental Air No corrosive gases permitted
Vibration IEC60068-2-6 (Test Fc)
Shock IEC60068-2-27 (Test Ea)
Enclosure Type Open Equipment
UL61010-2-201 file E139594, Canada & USA
Agency Approvals CE (Safety: EN61010-2-201 and I0+
Immunity: EN61131-2: 2007) I1+
I2+
Noise Immunity NEMA ICS3-304 I3+
EU Directive See the “EU Directive” topic in the BRX Help File.
I4+
Weight 98g (3.5 oz) I5+
I6+
Heat Dissipation 2.5W I7+
Software Version Required Do-more! Designer Version 2.1, or later.
*Meets EMC and Safety requirements. See the D.O.C. for details.

BX-08AD-1

BX-08AD-1
Analog Current Sinking
Input Expansion Module
8-ch, 0-20/4-20mA, 16-bit
I/O Terminal Blocks sold separately. (See Connector Options Spec. table inside.)

Analog Current Sinking Input Specifications WARNING: To minimize the risk of potential safety problems, you should
follow all applicable local and national codes that regulate the installation and
Inputs per Module 8 operation of your equipment. These codes vary from area to area and it is your
responsibility to determine which codes should be followed, and to verify that the
Commons 1
equipment, installation, and operation are in compliance with the latest revision
Module Signal Input Range 0-20mA, 4-20mA (Default) of these codes.
Signal Resolution 16 bit, 15 bit (Default) Equipment damage or serious injury to personnel can result from the
failure to follow all applicable codes and standards. We do not guarantee the
Resolution Value of LSB (1 LSB = 1 count) products described in this publication are suitable for your particular applica-
(least significant bit) 0-20mA = 0.305μA tion, nor do we assume any responsibility for your product design, installation,
(@ 16 bit resolution) 4-20mA = 0.244μA or operation.
If you have any questions concerning the installation or operation of this
Input Impedance 125Ω±0.1%, 1/10th watt equipment, or if you need additional information, please call Technical Support at
All Channel Update Rate 45ms (8 channels) 770-844-4200.
Over Current Circuit Detection Time < 1second This publication is based on information that was available at the time it was
printed. At AutomationDirect.com® we constantly strive to improve our products
Max Continuous Overload (Voltage) 0.5Watts (e.g. ±100V @ 5mA) and services, so we reserve the right to make changes to the products and/or
Sample Duration Time 5μs per channel publications at any time without notice and without any obligation. This publica-
tion may also discuss features that may not be available in certain revisions of
Hardware Filter Characteristics Low Pass 1st order, -3dB @ 144Hz the product.
Conversion Method Successive approximation
Linearity Error (end to end) ±0.09% of range
Input Stability and Repeatability ±0.035% of range (after 10 min. warmup)
Full Scale Calibration Error ±0.1% of range Do-more BRX Manual available at
Offset Calibration Error ±0.1% of range www.automationdirect.com/pn/doc/manual/BX-08AD-1
Accuracy vs. Temperature ±25PPM / ºC maximum
Maximum Inaccuracy 0.1% of range (inc. Temp drift)
Maximum Crosstalk -96dB, 1 LSB
Channel to Backplane Isolation 1800VAC applied for 1 second

IMPORTANT!
Channel to Channel Isolation None
Loop Fusing (external) Fast-acting 0.032A recommended
Backplane Power Consumption 0.1W Hot-Swapping Information
Class 2 or LPS power supply
Note: This device cannot be Hot Swapped.
External DC Power Required 24VDC (±20%)
25mA
Document Name Edition/Revision Date
BX-08AD-1 1st Ed. RevB 11/3/2020
Copyright 2021, AutomationDirect.com Incorporated/All Rights Reserved Worldwide.

Tech Support 770-844-4200 Your Automation Foundation!™


Connector Options Specifications
Terminal Block Kit, 90-degree screw type. For use with BRX 10-point
Module Installation
BX-RTB10 PLCs, BRX 16-point expansion modules and all analog and To remove, depress
temperature expansion modules. Kit includes (2) 10-pin 3.8mm plugs.
Terminal Block Kit, 180-degree spring clamp type. For use with BRX
1 To Install, remove
Connector Cover
disengagement plungers
at top and bottom
BX-RTB10-1 10-point PLCs, BRX 16-point expansion modules. Kit includes (2) 10-pin of module
3.8mm plugs.
Terminal Block Kit, 180-degree screw type. For use with BRX 10-point
BX-RTB10-2 PLCs, BRX 16-point expansion modules and all analog and
temperature expansion modules. Kit includes (2) 10-pin 3.8mm plugs.
ZIPLink PLC I/O cable, 20-position terminal block to 24-pin connector,
ZL-BXEM-CBL20 24AWG, cable length 0.5 meter (1.6ft). For use with BRX 16-point expan- PWR

sion modules. RUN


RUN
TERM
STOP
ZIPLink PLC I/O cable, 20-position terminal block to 24-pin connector, ERR

ZL-BXEM-CBL20-1 24AWG, cable length 1meter (3.3ft). For use with BRX 16-point expan- TX

sion modules. RX

2
ZIPLink PLC I/O cable, 20-position terminal block to 24-pin connector, LNK

ZL-BXEM-CBL20-2 24AWG, cable length 2meter (6.6ft). For use with BRX 16-point expan- ACT

sion modules.
ZIPLink PLC I/O cable, 20-position terminal block to pigtail connection, Align
ZL-BXEM-CBL20-1P 24AWG, cable length 1meter (3.3ft). For use with BRX 16-point expan-
sion modules. expansion
ZIPLink PLC I/O cable, 20-position terminal block to pigtail connection,
connectors, insert,
ZL-BXEM-CBL20-2P 24AWG, cable length 2meter (6.6ft). For use with BRX 16-point expan- and listen for “Click”
sion modules. as the lock engages
ZL-RTB20 ZIPLink Two Level Feedthrough Module, 20-pole, 35mm, DIN mount.

ZL-RTB20-1 ZIPLink Three Level Feedthrough Module, 20-pole, 35mm, DIN mount. Dimensional Information
3.25″
[82.6mm] 1.08″
[27.5mm]

Terminal Block Connector Specifications


Part Number BX-RTB10 BX-RTB10-1 BX-RTB10-2
Connector Type Screw Type-90° Spring Clamp Type-180° Screw Type-180°
Pitch 3.81mm 3.81mm 3.81mm 4.57″ 4.24″
[116.2mm] [107.8mm]
Recommended <1.77 lb·in <1.77 lb·in
N/A
Screw torque (0.2 N·m) (0.2 N·m)
Screwdriver
2.5mm 2.5mm 2.5mm
Blade Width
1.00″
Equiv. Dinkle part # EC381V-10P-BK ESC381V-10-BK EC381F-10P-BK [25.4mm]

2X Ø #8 Thru all

I/O Wiring I/O Wiring


Terminal Block Input Wiring
Analog Current Sinking Input Circuits
INTERNAL *An Edison S500-32-R 0.032A fast-acting fuse is recommended
MODULE CIRCUITRY for all analog voltage inputs, analog outputs, and current loops.
1C – *Fuse
I0+ In+
125Ω
CH0 ADC 2-Wire 4-20 mA 0.032A
I1+ Transmitter
CH1 ADC WX
I2+
125Ω
1C/COM
125Ω
CH2 ADC +
I3+
+ -
Power
1C
125Ω
CH3 ADC 2-Wire Transmitter Supply
I4+
CH4 ADC
I5+ 125Ω

CH5 ADC *Fuse


I6+ 125Ω
+ In+
CH6 ADC 0.032A
I7+ 125Ω
1C/COM WX
125Ω
CH7 ADC 3-Wire Current +
Transmitter - +
COM
COM –
24VDC User
COM 3-Wire Transmitter Supplied Power
COM
COM
*Fuse
COM + In+
0.032A
COM 4-Wire 4-20 mA
Transmitter – 1C/COM WX
COM
0V + –
- + AC or DC
24V+ ISOLATED ANALOG User Supplied Transmitter Power
CIRCUIT POWER 4-Wire Transmitter
24 VDC
Class 2 or LPS NOTE: Shield should be connected only at one end, to ground at the
User Supplied ISOLATED ANALOG source device.
Power CIRCUIT COMMON

Sales 800-633-0405 www.do-moreplcs.com