BUSBAR SIZE CALCULATION

PROJECT : M/s. CPWD, ANANTHAPUR


CLIENT : M/s. CPWD
CONTRACTOR : M/s. KMV

CALCULATION OF BUSBAR (Ampere)


Main Busbar Rating
INPUT DATA:

Voltage = 433 V
Ampres = 2500 A
Busbar material = Aluminium
Density factor for Aluminium = 0.8
No. of busbar runs (Phase) = 2
No. of busbar runs (Neutral) = 1

TO FIND :
Phase (W X T) in mm 125 x 12.7
Neutral (W X T) in mm 125 x 12.7
Total cross Sectional Area of busbar = 1587.5 Sq mm

Amount of Current can flow the Total cross sectional area = ?

W - Width of Busbar
T - Thickness of Busbar

SOLUTION:
Total current = W x T x No. of Runs x Density factor

= 125 x 12.7 x 2 x 0.8


Total current can flow = 2540 A

CONCLUSION: Hence the busbar selected for the full load current rating will be adequate for short time rating

PPD:AKN CKD:RGN