Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

TECHNICAL

GUIDANCE
6.1/25

Wall ties at movement joints


(January 2016) (Second issue – supersedes April 2011)

Question
Can slip ties be used in place of225mm max wall ties at movement joints in masonry walls?
additional

Considerations
300mm max

n A
 vertical movement joint can affect the structural stability of a masonry wall. To maintain the stability of the masonry
225mm wall,
max on
either side of the joint, additional wall ties should be provided.
n N
 HBC Standards clause 6.1.18 and PD 6697 ‘Recommendations for the design of masonry structures to BS EN 1996-1-1 and
Figure
BS 1
EN 1996-2’, describe the provision of additional wall ties on either side of a vertical movement joint which passes through
one leaf of a cavity wall.
300mm max

Answer
Structural stability of a wall on either side of a vertical movement joint, through one leaf of a masonry cavity wall, can be
maintained by the provision of additional wall ties on either side of the joint. These ties should be located across the cavity within
225mm of each side of the joint and at maximum 300mm centres vertically (see 1Figure 1).
Figure
Alternatively, stability can be provided by the use of slip ties (see Figure 3) across the movement joint spaced at maximum 300mm
centres vertically (see Figure 2). In this case, additional wall ties, across the cavity, are not required and wall ties can be spaced at
normal spacings as if the movement joint was not there.
300mm max

225mm max

Figure 2
300mm max
300mm max

Figure 1 Figure 2

Plastic sleeve (debonded end)

Figure 3 Typical slip tie


300mm max Plastic sleeve (debonded end)

Page 1 of 1

NHBC, NHBC House, Davy Avenue, Knowlhill, Milton Keynes, Bucks MK5 8FP. Tel: 0344 633 1000
NHBC is authorised by the Prudential Regulation Authority and regulated by the
Typical slipFinancial
tie Conduct
Figure 2 Figure 3
Authority and the Prudential Regulation Authority.
HB2851 01/20

You might also like