Professional Documents
Culture Documents
Crankcase Pressure Regulators
Crankcase Pressure Regulators
Crankcase pressure regulators have several main parts which are made with particular materials as
follows:
• Crankcase pressure regulators's body is made of hot forged brass
• Solder connections are made of copper tube
• Bellow is made of austenitic stainless steel
• Shutter is made of austenitic stainless steel
• Setting screw is made of brass bar
• Setting spring is made of spring steel
• Outlet seal gaskets are made of Chloroprene rubber (CR)
INSTALLATION
Crankcase pressure regulators series 3320 are installed in the suction line between the evaporator and
the compressor. Normally there are no other components installed downstream, between the valve
outlet and the compressor. This is to ensure that the outlet of regulator senses the true crankcase
pressure of the compressor.
The location of crankcase pressure regulator is in the suction line between the evaporator and the
compressor. The purpose of this installation is to ensure that the outlet of regulator senses the true
crankcase pressure of the compressor because generally there are no other components between the
valve outlet and the compressor.
SELECTION
A correct selection of crankcase pressure regulators series 3320 is possible if complete system
information are available. The selection involves these basic items:
1. Refrigerant
2. Evaporator capacity, at system working conditions.
3. Designed evaporating temperature (saturated
pressure) at design load condition.
4. Maximum allowable suction pressure. Recommended by the compressor or unit manufacturer; this
data is the valves setting.
5. Allowable pressure drop across the valves at design load condition
The following requirements have to be considered for selecting the correct crankcase pressure
regulators:
1. Refrigerant
2. Evaporator capacity, at system working conditions
3. Designed evaporating temperature (saturated pressure) at design load condition
4. Maximum allowable suction pressure (recommended by the compressor or unit manufacturer)
5. Allowable pressure drop across the valves at design load condition
The pressure drop difference between items 3 and 4 determines how much of the valve stroke is
utilized. The valve setting should be kept as high as possible without exceeding the recommendation of
the compressor manufacturer. When the full stroke of the valve is used, the only thing that will increase
the valve capacity is to take more pressure drop across the valve. Since excessive suction line pressure
losses penalize system capacity, the pressure drop across the 3320 regulator should be kept to a
minimum, the lower the evaporator temperature, the less pressure drop allowed. The refrigerating
capacities indicated on tables 3A, 4A, 5A, 6A are based on a reference liquid temperature of 36,7 °C.
In point (3) and (4) there are the difference in pressure drop which determines how much of the valve
stroke is utilized. Please note that The valve setting should be kept as high as possible without
exceeding the recommended setting from manufacturer. When the full stroke of the valve is used, the
only thing that will increase the valve capacity is to take more pressure drop across the valve. Because
excessive suction line pressure losses penalize system capacity, the pressure drop across regulator
should be kept to a minimum. The lower the evaporator temperature, the less pressure drop allowed.
Sizing
For optimum performance, it is important to select a KVL valve according to system conditions and
application.
The following data must be used when sizing a KVL valve:
• Refrigerant: KVL 12-22: HCFC, HFC and HC KVL 28-35: HCFC and non-flammable HFC
• Evaporator capacity: Qe in [kW]
• Liquid temperature ahead of expansion valve: tl in [°C]
• Suction temperature ahead of compressor: ts in [°C]
• Maximum suction pressure after the regulator: PS in [bar]
• Connection type: flare or solder
• Connection size in [in.] or [mm]
Selecting a correct crankcase pressure regulator valve based on the system conditions and application is
necessary to ensure system best performance.
There are several factors that must be considered to determine the proper size of crankcase pressure
regulator valve:
• Refrigerant
• Evaporator capacity: Qe in [kW]
• Liquid temperature ahead of expansion valve: tl in [°C]
• Suction temperature ahead of compressor: ts in [°C]
• Maximum suction pressure after the regulator: PS in [bar]
• Connection type: flare or solder
• Connection size in [in.] or [mm]
Design / Function
The Crankcase pressure regulator type KVL opens at pressure fall on the outlet side, i.e. when the
suction pressure ahead of the compressor drops below the set value. The KVL only regulates based on
the outlet pressure. Pressure variations on the inlet side of the regulator do not affect the degree of
opening since the KVL is equipped with an equalization bellows.
Crankcase pressure regulator will open if the pressure on the outlet side decreases, which may happen
when the suction pressure ahead of the compressor decreases below the set value. This valve only
regulates based on the outlet pressure. Because the valve is equipped with equalization bellows,
pressure variations on the inlet side of the regulator do not have significant effect to the degree of
opening.
This bellows has an effective area corresponding to that of the valve seat. The regulator is also
equipped with an effective damping device (9) against pulsations, which normally occur in a
refrigeration plant. The damping device helps to ensure long life of the regulator without impairing
regulation accuracy.
There are an effective area on the bellows corresponding to that of the valve seat. The regulator also
comes complete with a damping device to provide protection against pulsations which can normally
occur in a refrigeration system. The damping device helps to ensure long life for the regulator without
impairing regulation accuracy.
INSTALLATION INSTRUCTIONS
To insure best performance, CRO's must be applied and selected correctly. This is covered thoroughly
in Bulletin 90-10. However, proper installation procedures are equally important. All of the information
in the Application section of 90-10 should be reviewed before installing CRO valves.
VALVE LOCATION
CRO's are normally installed downstream of any other suction line controls or accessories. However,
on some applications it may be advisable, or necessary for special purposes, to locate other system
components, e.g., an accumulator, downstream of the CRO. This is satisfactory as long as the CRO
valve is intended to function as a crankcase pressure regulating valve only.
Mounting location of crankcase pressure regulating valve is downstream of any other suction line
controls or accessories. It is recommended to install other system components, e.g., an accumulator,
downstream of the crankcase pressure regulator. This is satisfactory as long as the CRO valve is
intended to function as a crankcase pressure regulating valve only.
CRO's may be installed in any position – whichever best suits the application and permits easy
adjustment and accessibility. However, consideration should be given to locating these valves so that
they don't act as an oil trap or that solder cannot run into the internal parts during brazing in the suction
line. Since the CRO(T)-6 and CRO(T)-10 are hermetic, there is no way to disassemble them and clean
out any solder that gets trapped in the internal parts.
Crankcase pressure regulator can be installed in any position according to the system application which
allows an easy access and adjustment. Be careful when placing it so that it does not act as an oil trap
and to prevent solder from entering the internal parts during soldering in the suction line. Because it is
hermetic, it can not be disassembled to lean out any solder that gets trapped in the internal parts.
The CRO-4 has a 3/8” adjustment screw on top of the adjustment housing. The CRO(T)-6 and
CRO(T)-10 have a valve cap and a hex adjustment in the adjustment housing. Remove the cap and use
a 1/4” hex wrench for the CRO(T)-6 and a 5/16” hex wrench for the CRO(T)-10. A clockwise rotation
increases the setting while a counterclockwise rotation decreases the setting.
How to adjust crankcase pressure regulator valves: First, prepare a proper size of hex wrench that you
need. Crankcase pressure regulator valve has a 3/8” adjustment screw on top of the adjustment housing.
Another type of crankcase pressure regulator may have a valve cap and a hex adjustment in the
adjustment housing. You can remove the cap and then turn the adjustment screw clockwise or
counterclockwise as per requirement by using a proper hex wench. Turning the adjustment screw
clockwise increases the valve setting while turning it counterclockwise decreases the setting.
When CRO's are installed in parallel, each should be adjusted the same amount. If one valve has been
adjusted more than the other, best performance will occur if both are adjusted all the way in before
resetting them an equal amount.
Because crankcase pressure regulator valves are installed in parallel, each should be adjusted the same
amount. If one valve has been adjusted more than the other, best performance will occur if both are
adjusted all the way in before resetting them an equal amount.
SERVICE INSTRUCTIONS
The CRO-4 can be disassembled for inspection and cleaning, however, the CRO(T)-6 and CRO(T)-10
are hermetic and cannot be disassembled for cleaning. Replacement is usually necessary if they become
inoperative. If a CRO fails to open, close properly, or won't adjust, it is probably due to solder or
other foreign materials lodged in the port. It is sometimes possible to dislodge these materials by
turning the adjustment nut all the way in with the system running. If the CRO(T)-6 or CRO(T)-10
develop a refrigerant leak around the spring housing, it probably has been overheated during
installation or the bellows failed due to severe compressor pulsations. In either case, if the valve fails in
the open position, the valve must be replaced.
Some type of crankcase pressure regulator valves can be disassembled for inspection and cleaning
purposes. But in some applications you may find crankcase pressure regulator valves which are
hermetic so that they can not be disassembled for cleaning and when these valves are faulty, they
should be replaced with a new one. If there is foreign material lodged in the port, it may cause
crankcase pressure regulator valve fails to open, close properly, or won’t adjust. To overcome this
problem you can simply dislodge those materials by turning the adjustment nut all the way in with the
system running. When there is refrigerant leak around the spring housing, it may be caused by
overheating during installation or the bellows has failed due to severe compressor pulsations. If if the
valve fails in the open position, it must be replaced.
Miller, Rex & Mark R. Miller. (2006). Air Conditioning and Refrigeration.
CRANKCASE PRESSURE REGULATING VALVES
Crankcase pressure regulating valves are designed to prevent overloading of the compressor motor.
They limit the crankcase pressure during and after a defrost cycle or after a normal shutdown period.
When properly installed in the suction line, these valves automatically throttle the vapor flow from the
evaporator until the compressor can handle the load. They are available in the range of 0 to 60 psig.
The purpose of crankcase pressure-regulating valve is to protect the compressor motor from
overloading by limiting the crankcase pressure during and after a defrost cycle or after a normal
shutdown period. Crankcase pressure regulating valves are installed in the suction line and these valves
automatically throttle the vapor flow from the evaporator until the compressor can handle the load. The
range of these valves is 0 to 60 psig.
Operation of the Valve
Crankcase pressure-regulating valves (CROS) are sometimes called suction pressure-regulating valves.
They are sensitive only to their outlet pressure. This would be the compressor crankcase or suction
pressure. To indicate this trait, the designation describes the operation: close on rise of outlet pressure,
or CRO. As shown in Fig. 11-26, the inlet pressure is exerted on the underside of the bellows and on
top of the seat disc. Since the effective area of the bellows is equal to the area of the port, the inlet
pressure cancels out and does not affect valve operation. The valve-outlet pressure acting on the bottom
of the disc exerts a force in the closing direction. This force is opposed by the adjustable spring force.
These are the operating forces of the CRO. The CRO’s pressure setting is determined by the spring
force. Thus, by increasing the spring force, the valve setting or the pressure at which the valve will
close is increased.
Crankcase pressure-regulating valve is also known as suction pressure-regulating valve. This valve is
sensitive only to their outlet pressure (compressor crankcase or suction pressure). To indicate this trait,
the designation describes the operation: close on rise of outlet pressure, or CRO.
How the valve operates: the inlet pressure is exerted on the underside of the bellows and on top of the
seat disc. Since the effective area of the bellows is equal to the area of the port, the inlet pressure
cancels out and does not affect valve operation. The valve-outlet pressure acting on the bottom of the
disc exerts a force in the closing direction. This force is opposed by the adjustable spring force. These
are the operating forces of the CRO. The spring force will determine the CRO’s pressure setting. By
increasing the spring force, the valve setting or the pressure at which the valve will close is increased.
As long as the valve-outlet pressure is greater than the valve-pressure setting, the valve will remain
closed. As the outlet pressure is reduced, the valve will open and pass refrigerant vapor into the
compressor. Further reduction of the outlet pressure will allow the valve to open to its rated position,
where the rated pressure drop will exist across the valve port. An increase in the outlet pressure will
cause the valve to throttle until the pressure setting is reached.
The valve will remain closed as long as the valve-outlet pressure is greater than the valve-pressure
setting. When the outlet pressure drops, the valve will open and pass refrigerant vapor into the
compressor. Further reduction of the outlet pressure will allow the valve to open to its rated position,
where the rated pressure drop will exist across the valve port. When there is an increase in the outlet
pressure, the valve will be throttled until it has reached the pressure setting.
The operation of a valve of this type is improved by an antichatter device built into the valve. Without
this device, the CRO would be susceptible to compressor pulsations that greatly reduce the life of a
bellows. This feature allows the CRO to function at low-load conditions without any chattering or other
operation difficulties.
An antichatter device can improve the valve operation. This device is built into the valve. Without this
device, the CRO would be susceptible to compressor pulsations that greatly reduce the life of a
bellows. This feature allows the CRO to function at low-load conditions without any chattering or other
operation difficulties.
Valve Location
As Fig. 11-27 indicates, the CRO valve is applied in the suction line between the evaporator and the
compressor. Normally, the CRO is installed downstream of any other controls or accessories. However,
on some applications it may be advisable or necessary to locate other system components, such as an
accumulator, downstream of the CRO. This is satisfactory as long as the CRO valve is applied only as a
crankcase pressure-regulating valve. CRO valves are designed for application in the suction line only.
They should not be applied in hot–gas bypass lines or any other refrigerant line of a system. Crankcase
pressure-regulating valves are installed in the suction line between the evaporator and the compressor.
The mounting location of this valve is in the suction line between the evaporator and the compressor.
Usually, it is installed downstream of any other controls or accessories. It is recommended to install
other system components, e.g., an accumulator, downstream of the crankcase pressure regulator. This is
satisfactory as long as the CRO valve is applied only as a crankcase pressure-regulating valve. CRO
valves are designed for application in the suction line only. They should not be applied in hot–gas
bypass lines or any other refrigerant line of a system. Crankcase pressure-regulating valves are installed
in the suction line between the evaporator and the compressor.
When CROs are installed in parallel, each should be adjusted the same amount. If one valve has been
adjusted more than the other, best performance will occur if both are adjusted all the way in before
resetting them an equal amount.
If crankcase pressure regulator valves are installed in parallel and it is desirable to obtain the best
performance, then each valve must be adjusted to the same amount. If one valve has been adjusted
more than the other, both valves should be adjusted all the way in before resetting them an equal
amount.
Service
Since CRO valves are hermetic and cannot be disassembled for inspection and cleaning, they are
usually replaced if inoperative. If a CRO fails to open, close properly, or will not adjust, solder or other
foreign material is probably lodged in the port. It is sometimes possible to dislodge these materials by
turning the adjustment nut all the way in with the system running. If the CRO develops a refrigerant
leak around the spring housing, it probably has been overheated during installation or the bellows have
failed due to severe compressor pulsations. In either case, the valve must be replaced.
Because these valves are hermetic, they cannot be disassembled for inspection and cleaning purposes.
If they found to be faulty, they should be replaced with a new one. If there is foreign material lodged in
the port, it may cause crankcase pressure regulator valve fails to open, close properly, or won’t adjust.
To overcome this problem you can simply dislodge those materials by turning the adjustment nut all the
way in with the system running. When there is refrigerant leak around the spring housing, it may be
caused by overheating during installation or the bellows have failed due to severe compressor
pulsations. If that happens, the valve must be replaced.