Professional Documents
Culture Documents
BSCPL Tech Spec MLTP Botanical R00
BSCPL Tech Spec MLTP Botanical R00
BSCPL Tech Spec MLTP Botanical R00
This specification intends to cover the technical requirements of design, engineering, manufacture,
assembling, inspection and testing (as per latest Edison of IS8623) at manufacturer’s works,
packaging and delivery by road to the site, 3- Phase Four Wire, metal clad, indoor or outdoor Type,
LT Switchgear Panels complete assembly as specified hereinafter with all accessories and auxiliary
equipment for efficient and trouble- free operation.
Note:
1. Climatic Condition: The climatic conditions are prone to wide variations in ambient conditions
2. Scope of Manufacturer
• Test Equipment: The Vendor shall have the necessary arrangement of test equipment for
acceptance tests and routine tests as specified in the technical Specification. In case, test is
required to be done at different works, the Vendor shall clearly specify in the deviation sheet.
• Quality Assurance Plan the Vendor shall invariably furnish along with his offer the quality
assurance plan adopted for sub-supplies in the process of manufacturing all major
equipment/component.
• Drawings/Documents to be furnished by the bidder on receiving of the Purchase Order
The following drawings shall be submitted for approval within 1 week after receipt of
Purchase Order. Purchaser will accord approval at the earliest. Manufacturer shall start
manufacturing of the panels only after receiving the final approval of all the drawings and
the QA plan. Any work carried out before the approval shall be totally at supplier's risk.
o The design of layout and general arrangement along with complete dimensions shall be
submitted along with the offer.
o Complete assembly drawings of the switchgear showing plan, elevation and typical
sectional view.
o Foundation plan showing locations of channel sills, foundation bolts and anchors, floor
plans and openings.
o Complete wiring diagram including terminal wiring designations.
o Schematic control diagram for both AC and DC controls for the breaker, interlocks,
relays, instruments, space heaters etc.
SECTION – B: Technical Specifications Metal Clad Switchgear Panel
➢ REFERANCE STANDARDS: The design, manufacture and testing of the equipment shall comply
with the latest issue of the following Indian/International Standards, unless otherwise specified.
Equipments complying with equivalent standards shall also be acceptable.
➢ TECHNICAL PARAMETERS:
a. System Details
System Voltage: 415V ± 10%, 3-phase, 4 wire solidly grounded.
Frequency: 50Hz ± 3%
Control Supply: 230 Volts AC ± 10% (tapped from phase & neutral), 110V DC ± 10%
b. CONSTRUCTIONAL FEATURES
• The Circuit breaker shall be air brake type, 4 Pole (4-Pole type electrically operated, draw out type
(EDO)
• Main contacts shall have ample area and contacts pressure for carrying the rated current and the
short time rated tripping current of the breakers without excessive temperature rise which may
cause pitting or welding.
• Contacts shall have a minimum of moveable parts. It shall be designed such that no maintenance
shall be required under normal conditions of use. The contacts shall be replace- able.
• The temperature rise and maximum temperature on any part of the circuit breaker, while in service
under continuous full load conditions shall not exceed the permissible limits of temperature rise
as specified in the IEC- 694:1996 publication for alternating current circuit breakers.
• All MS parts of breakers and ferrous parts such as hangers, supports, bolts & nuts shall be hot dip
galvanized as per IS:2629 (latest edition) with zinc plating & olive green passivation. The material
for spring shall be rust proof.
• All circuit breakers and their drawings shall have phase indications as R-Red, Y-Yellow and B-
Blue or equivalent.
• All circuit breakers shall be electrically and mechanically trip free in TEST and SERVICE
positions with built in anti-pumping feature.
• The circuit breaker shall be provided with mechanical arc chutes which shall be removable at site
and magnetic blow out arc control device designed to permit rapid dispersion, cooling and
extinction of arc.
• The Circuit Breaker shall be fully draw out type. Suitable guides shall be provided to facilitate
easy withdrawal of the trolley.
• There shall be three positions for the draw out trolley; · "Full in" or "service" position - in this
position both power and control circuits shall be connected. This shall be the normal operating
position of the circuit breaker. · "Test" position - The power contacts shall be disconnected in this
position, but the control connections shall not be disturbed, it shall be possible to close and trip
the breakers in this position. · "Full out" position - Both power and control circuits shall be
disconnected in this position. It shall be possible to close the cubicle door in this position.
• The Circuit Breaker shall be lockable in "Service", "Test" and "Full out" positions. The earth
connection must remain connected at all the positions.
• All inter panel/compartments openings for wiring buses or for any other purposes shall be used
with PVC bushes so as to make each section vermin proof. The different materials used in the
making of switchgear units, such as bus insulation, bus supports etc. shall not support combustion.
• The ACB shall be provided with mechanical interlocks which will prevent sliding of breaker from
‘SERVICE’ to ‘TEST’ position or vice versa unless it is ‘OFF’
• It shall be possible to disconnect the breaker without having to open the door.
• The door opening shall not be possible unless breaker is in ‘TEST’ or ‘ISOLATE’ position
• i.e. the door opening shall not be possible with circuit breaker in the connected position
• Unless the door is closed, the sliding of breaker from ‘TEST’ to ‘SERVICE ’position shall not be
possible.
• The breaker housing shall have in-built service and test position limit switch.
• All accessories of circuit breaker like U/V release, shunt release, closing coil etc shall be accessible
from the front side of circuit breaker. It shall be possible to connect all auxiliary wiring from the
front of the circuit breaker
• Shunt trip coil and closing coil suitable for operation on 110 volts D.C. The closing coils and
tripping coils and other auxiliary devices shall operate satisfactorily at all voltages between 80%
and 110% of the rated voltage.
• The operating mechanism of the breaker shall store energy type, operated using pre- charged
springs. The springs shall have manual charging mechanism by operating the front lever and
electrically using inbuilt geared motor. The spring charging mechanism motor shall be rated for
operation on 240 volts A.C.
• Suitable mechanical indication for service, test and isolated positions should be provided.
• LED type Red, green, amber and white lamps shall be used to indicate breaker 'close, 'open', ‘trip
circuit healthy (for incomers)’ and ‘auto trip’ respectively.
• Mechanical - Close/ open, spring charged/ discharged, service position/test position/ isolated
position.
• Electrical- ON, OFF, auto-trip, trip circuit healthy (for incomers), R-Y-B phase indication (for
incomers).
Microprocessor based, electronic trip (for all Air circuit breakers) _(LSING)
The following features shall remain common for all the Air Circuit Breaker trip units:
• The microprocessor based electronic trip unit shall guarantee sound/healthy breaker operation
even in the presence of interference caused by electronic equipment, atmospheric disturbance or
discharges of electrical type. Moreover, the apparatus shall not generate any form of
electromagnetic interference, in compliance to IEC 60947-2
• The circuit breaker shall confirm to the latest amendments of IS: 8623/IEC 61439, All Circuit
Breaker shall be suitable for operation, at 50 Hz +/- 5%, and 415V +/- 10% AC voltage with
adequate thermal capacity for continuous operation.
• The Circuit breaker shall be air brake type, 4 Pole (4-Pole type electrically operated, Fixed type)
• Contacts shall have a minimum of moveable parts. It shall be designed such that no maintenance
shall be required under normal conditions of use. The contacts shall be replace- able.
• Electrical- ON, OFF, auto-trip, trip circuit healthy (for incomers), R-Y-B phase indication (for
incomers).
➢ Switchgear Cubicles (Common for All Panels)
• The switchgear shall be totally of enclosed type, dust and vermin proof. It shall compromise of
rigid and welded structure frame enclosed completely be metal sheet of 3mm for load bearing
members and 2mm for non-load bearing members.
• The Panel construction shall be Indoor Type under the basement area. Panel Stand to be provided
with Thick MS Channels of 2 Tonn Weight Bearing Capacity with Powder coated frame and legs
shall be provided for Each compartment and min 450mm Height is required.
• The panel partitioning shall be Form 3b, as per IEC-61439 i.e. all the individual sections shall be
totally separated from each other. All the partitioning shall be by metallic means only. Non-
metallic partition shall not be acceptable.
• All the Switchgears (ACBCs) shall be provided with minimum IP20/finger proof protection.
• i.e. when feeder doors are open, there should not be any live part visible / accessible. These shall
be achieved through standard shrouds/metallic partitions. FRP/Hylem sheets shall not be
acceptable.
• The sheet steel used in the fabrication of the switchgear housing shall be cold rolled thick &
levelled and finished smooth in such a manner that the complete structure shall be rigid, self-
supporting. All the steel panels enclosing a switchgear unit, hinged doors, partitions and
removable panels shall be provided with stiffeners to minimize flexing and vibration.
• Structures, buses and control wiring troughs shall be so designed and arranged as to make future
extensions readily feasible panel shall be both side extensible.
• Access to the circuit breaker operating mechanism shall be through compartment doors provided
with hinges and key type locks. The arrangement shall prevent expose of any live parts or circuits.
All compartment doors shall be so constructed that they will not seize in the event of fire within
the switchgear.
• Instruments shall be mounted on hinged type front doors. All doors shall have neoprene gaskets
wherever required.
• Panels shall be supported by strong hinges of concealed type and braced in such a manner as to
ensure freedom from sagging, bending and general distortion of panel or hinged parts.
• The layout of the component inside the module shall be liberal to facilitate maintenance and
interconnecting wiring between the components shall not be subjected to any undue stresses at the
bends.
• All the live parts which are accessible after opening of front cover/cable alley cover/back cover
shall be properly insulated or provided with insulating barrier to prevent accidental contact.
Removal facilities shall be provided for all such parts.
• Please note that self-threading screws shall not be used for panel fabrication.
• Suitable clamping arrangements shall be provided for cables and cable termination.
• There shall be three positions for the draw out trolley; · "Full in" or "service" position - in this
position both power and control circuits shall be connected. This shall be the normal operating
position of the circuit breaker. · "Test" position - The power contacts shall be disconnected in this
position but the control connections shall not be disturbed, it shall be possible to close and trip the
breakers in this position. · "Full out" position - Both power and control circuits shall be
disconnected in this position. It shall be possible to close the cubicle door in this position.
• The Circuit Breaker shall be lockable in "Service", "Test" and "Full out" positions. The earth
connection must remain connected at all the positions.
• All inter panel/compartments openings for wiring buses or for any other purposes shall be used
with PVC bushes so as to make each section vermin proof. The different materials used in the
making of switchgear units, such as bus insulation, bus supports etc. shall not support combustion.
• The horizontal busbars shall be insulated with heat shrinkable PVC sleeves of reputed make to
protect against approach to live parts. The vertical busbars shall be sleeved or shrouded by barriers.
• The busbars shall be amply sized to carry the rated continuous current under the specified ambient
temperature without exceeding temperature limits specified in IS: 8084. The thermal rating of the
bus-bars shall be designed to withstand the system fault current for 1 second without exceeding
the temperature limits.
• The bus bars shall be arranged and color coded according to IS: 5578 / IS: 11353.
• The busbars shall be rigidly supported at equal intervals to withstand maximum short circuit
stresses. The supports shall be of molded construction with built-in anti-tracking barriers. The
support materials shall be of DMC or fiberglass reinforced thermosetting plastic.
• A minimum of two bolts shall be used in bus-bar joints. Only high tensile electric galvanized bolts,
nuts and washers shall be used.
i. All joints shall be suitably treated to avoid oxidation of contact surfaces and bimetallic
corrosion and proper shrouds shall be provided for bus bar joints.
ii. Vendor shall submit a detailed sheet for selection of bus bar size with details of de -
rating factors taken into consideration due to ambient conditions, bus-bar
positioning, heat dissipation factor, skin effect, proximity effect etc. of panel
construction.
• The neutral bus shall be insulated from other grounded parts in the panels.
• Each terminal shall have only one wire terminated on it. For tap-offs, adjacent terminals with
shorting strips shall be used. 10% Spare terminal blocks shall be provided.
• Wire identification on marking strip shall correspond to the designation of the wiring diagrams.
All wire terminals on the equipment shall also be marked with the designation corre- sponding to
those of the wiring diagram.
• Wires shall be provided with printed numbered ferrules at both ends bearing the same numbers.
• Proper color coding should be followed to differentiate between the CT, control and metering
circuits.
• CT circuit - 2.5 Sq mm
• All auxiliary contacts whether spare or otherwise shall be wired and brought out to the terminal
blocks. Wiring between components within switchgear cubicle shall be done through the terminal
block only. Direct connection shall not be permitted.
• Current transformer secondary leads shall be brought on to the terminal of the terminal blocks
where facility for short circuiting and grounding of CT secondary shall be provided.
• All wiring shall be enclosed in plastic channels and neatly bunched and cleated. Wiring between
terminals of various devices shall be 'point to point' (no wire splitting or tee connections) with
wires neatly trucked along the back of the panels, adequately supported to prevent sagging or
damage due to vibration in transit and operation. Double pole M.C.B should be provided for
control supply to each of the panels.
• The secondary leads shall be terminated with Tinned Cooper rose terminals.
• The CTs shall be varnished, fiberglass tape insulated or cast resin, air-cooled type. Only super
enameled electrolytic grade copper wires shall be used.
• Rated ISF (Instrument Security Factor) shall be declared by the manufacturer & marked on the
CT.
• CTs shall be made with good engineering practices. Core winding shall evenly spread stress &
avoid stress concentration at any one point. Cast resin CTs shall be processed by hot curing method
under controlled vacuum conditions.
• The CTs shall conform to IS 2705: Part-I & II/IEC:185 with latest amendments.
• The CTs shall have marking and nameplate as per IS 2705 in addition to class of insulation & ISF.
The nameplate shall be securely fixed to the body of the CT.
• The indication lamp shall suit the panel’s hole of 22.5 mm dia. A LED type bulb of 230 volts, 50
Hz, 0.5 watt.
• While wiring these lamps, power supply to the lamp shall be derived through 6 Amps MCB for
protection purpose. The lens of the lamp shall be of glass or good quality heat resistant transparent
plastic material, which shall not discolor or deform. It shall be possible to replace the bulb from
the front easily.
• RED lamp shall be used to indicate the equipment is energized. GREEN lamp shall be used to
indicate the equipment is de-energized.
The colors for the indicating lamps shall be as per as per normal convention
system or as approved by the engineer-in-charge during Inspection.
• A 12-window annunciator with hooter shall be provided in the front door of the Bus-Coupler
panels with the following specifications: Alarm annunciation system shall be provided on the
control board by means of visual and audible alarm to draw the attention of the operator to the
normal operating conditions or the operation of some protective devices etc.
• The annunciation equipment shall be suitable for operation on 110V DC (selectively) for normal
operating conditions and 240 V AC for DC fail conditions.
• Each annunciator shall be provided with accept, reset and test push buttons.
• Special precaution shall be taken by the supplier to ensure that alarm conditions do not appear due
to influence of external electromagnetic / electrostatic interference on the annunciator wiring and
switching disturbances from the neighboring circuits within the panels.
• In case `RESET’ push button is pressed before abnormality is cleared, the lamps shall continue to
flash and shall go out only when `normal’ condition is restored.
• Provision of testing facilities for flasher and audible alarm circuit of annunciator shall also be
made. fault indication for overload, S/C, E/F to be provided.
• The nameplates on each module shall also furnish the following information by minimum letter
size of 12 mm:
• Compartment number.
• KW / Amp rating
• Description of the feeder
• EV Charger Outgoing Details as Per SLD
• SLD Aluminum Plate Engraved.
➢ Metal Treatment and Paint Finish (Common for all Panels)
• All sheet steel work used in the construction of the modules shall be pretreated with 7-tank
chemical process before applying the two coats of zinc chromate primer followed by synthetic
enamel/epoxy paint. The following procedure shall be followed for the panel 7-tank painting
procedure in the given sequence only:
• Degreasing: In this process the M.S. sheets shall be effectively cleaned by dipping in hot alkaline
degreasing solution for a period of about 10-20 minutes.
• Water Rinsing: After degreasing process, the M.S. sheets shall be rinsed into the water for a period
of about 1- 2 minutes to remove the loosened oil, grease and adhering alkali from the surface.
• De-rusting: In this process the M.S. sheets shall be dipped in to the dilute sulphuric acid for a
period of 30 minutes to remove oxide scales and rust from the surface.
• Water Rinsing: After the de-rusting process the M.S. sheets shall be rinsed in water for the period
of about 1- 2 minutes to remove the traces of acidic solution from the surface.
• Phosphating: In this process the M.S. sheets shall be dipped in to the zinc phosphate solution for
the period of about 30 minutes to facilitate durable coating of the paint on the metal surface.
• Water Rinsing: After the phosphating process the M.S. sheets shall be rinsed in to the water for
the period of about 1-2 minutes to remove the traces of phosphate solution from the surface.
• Passivation: In this process the M.S. sheets shall be dipped in to the de-oxalate solution for the
period of about 1 minute to retain and augment the effects of phosphating on the surface.
• After completion of 7-tank process a fine grained, smooth and compact coating of iron/zinc
phosphate shall be applied, this is an excellent base for paint and provides film protection against
corrosion. The coating shall meet the Indian Standard Specification IS: 3618-1966 class C.
• Drying: After the above pretreatment chemical process, the M.S. sheets shall be dried either by
means of hot air circulation oven or by means of blast of compressed air (air drying).
• Primer Coating: Primer coating with two coats of highly corrosion resistant zinc chromate primer
shall be done before applying the final paint finish.
• Paint Finish: The final finishing shall be epoxy paint of RAL-7032, matt finish powder coated.
Paint thickness shall not be of less than 80 microns. All paints shall be carefully selected to
withstand tropical heat and extremes of weather. The paint shall not scale off/crinkle by abrasion
due to normal handling.
➢ Digital Timer
• Digital Timer to be linked with Incomer automatically Turned on after Settable delay of from 5
seconds to 5 minutes settable delay time this is to be archived when power cut occurs.
The details of Apparatus to be captured from SLD, wherever mentioned applicable for all panels
to be considered in every panels.
SECTION – C: Bills of Material of Panels for all Panels
Description Nos
Incomer 2500 Amp ACB 1 Nos.
Outgoing 2500 Amp ACB 0 Nos.
Hooter 1 Nos
Annunciator 1 Nos
TNC Switch 1 Nos
Power Pack 15 Min. 1 Nos
CT 2500/5 Amp 4 Nos
PT 100 4 Nos
Digital Timer 1 Nos
Temp Scanner with RS 485 1 Nos
Emergency Switch 1 Nos
6inch Exhaust Fan As per Design
On – Off – Trip Indicator 1 Nos
R- Y- B Indicator 1 Nos
PT -1Ph 3 Nos
MPCB 1 Nos
Control MCBs 1 Nos
RCCB 1 Nos
MFM Meter 1 Nos
2500 Amp Bus Bar with 0.8A As per Design
Exhaust Fan 6inch As per Design
Control SP MCB 10KA As per Design
Lighting Switch Socket 16A As per Design
Illumination Lamp As per Design
Space Heater with Thermostat + As per Design
Incoming Cable Compartment As per Design
Outgoing Cable Compartment As per Design
Brass Double Compression Cable Gland As per Design
4Cx400Sqmm. Without Thimble
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
2. MLTP: 2500A 4P, ACB, QTY: 1 Nos
Description Nos
Incomer 2500 Amp ACB 1 Nos.
Outgoing 1000 Amp ACB 4 Nos.
Outgoing 800 Amp ACB 1 Nos.
Hooter 1 Nos
Annunciator 1 Nos
TNC Switch 1 Nos
Power Pack 15 Min. 1 Nos
CT 2500/5 Amp 8 Nos
PT 100 4 Nos
Digital Timer 1 Nos
Temp Scanner with RS 485 1 Nos
Emergency Switch 1 Nos
MFM Meter 2 Nos.
6inch Exhaust Fan As per Design
On – Off – Trip Indicator As per Design
R- Y- B Indicator As per Design
PT -1Ph 3 Nos
MPCB 1 Nos
Control MCBs As per Design
RCCB 1 Nos
Mini PLC 1 Nos
Accept – Reset Push Button 1 Nos
Reverse Power Relay 1 Nos
UV & OV Relay 1 Nos
-VE Ph Sequence Relay 1 Nos
2500 Amp Bus Bar with 0.8A As per Design
Exhaust Fan 6inch As per Design
Control SP MCB 10KA As per Design
Lighting Switch Socket 16A As per Design
Illumination Lamp As per Design
Space Heater with Thermostat + As per Design
Incoming Cable Compartment As per Design
Outgoing Cable Compartment As per Design
Brass Double Compression Cable Gland As per Design
4Cx400Sqmm. Without Thimble
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
3. PANEL-1: 1000A, QTY: 1 Nos
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
Description Nos
Incomer 1000 Amp ACB 1 Nos.
Outgoing 160 Amp ACB 4 Nos.
Outgoing 100 Amp ACB 4 Nos.
Outgoing 63 Amp ACB 15 Nos.
Outgoing 40 Amp ACB 0 Nos.
Hooter 1 Nos
Annunciator with RS485 1 Nos
TNC Switch 1 Nos
Power Pack 15 Min. 1 Nos
CT 1200/5 Amp 4 Nos
CT 600/5 Amp 3 Nos
CT 300/5 Amo 3 Nos
PT 100 4 Nos
Temp Scanner with RS 485 1 Nos
Emergency Switch 1 Nos
MFM Meter 3 Nos.
6inch Exhaust Fan As per Design
On – Off – Trip Indicator As per Design
R- Y- B Indicator As per Design
PT -1Ph 3 Nos
MPCB 1 Nos
Control MCBs As per Design
RCCB 1 Nos
1250 Amp Bus Bar with 0.8A As per Design
600 Amp Bus Bar with 0.8A As per Design
300 Amp Bus Bar with 0.8A As per Design
Exhaust Fan 6inch As per Design
Control SP MCB 10KA As per Design
Lighting Switch Socket 16A As per Design
Illumination Lamp As per Design
Space Heater with Thermostat + As per Design
Incoming Cable Compartment As per Design
Outgoing Cable Compartment As per Design
Brass Double Compression Cable Gland As per Design
4Cx300Sqmm. Without Thimble
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
4. PANEL-2 : 1000A, QTY: 1 Nos
Description Nos
Incomer 1000 Amp ACB 1 Nos.
Outgoing 160 Amp ACB 5 Nos.
Outgoing 100 Amp ACB 2 Nos.
Outgoing 63 Amp ACB 17 Nos.
Outgoing 40 Amp ACB 0 Nos.
Hooter 1 Nos
Annunciator with RS485 1 Nos
TNC Switch 1 Nos
Power Pack 15 Min. 1 Nos
CT 1000/5 Amp 4 Nos
CT 600/5 Amp 3 Nos
CT 300/5 Amo 3 Nos
PT 100 4 Nos
Temp Scanner with RS 485 1 Nos
Emergency Switch 1 Nos
MFM Meter 3 Nos.
6inch Exhaust Fan As per Design
On – Off – Trip Indicator As per Design
R- Y- B Indicator As per Design
PT -1Ph 3 Nos
MPCB 1 Nos
Control MCBs As per Design
RCCB 1 Nos
1250 Amp Bus Bar with 0.8A As per Design
600 Amp Bus Bar with 0.8A As per Design
300 Amp Bus Bar with 0.8A As per Design
Exhaust Fan 6inch As per Design
Control SP MCB 10KA As per Design
Lighting Switch Socket 16A As per Design
Illumination Lamp As per Design
Space Heater with Thermostat + As per Design
Incoming Cable Compartment As per Design
Outgoing Cable Compartment As per Design
Brass Double Compression Cable Gland As per Design
4Cx300Sqmm. Without Thimble
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
5. PANEL-3 : 1000A, QTY: 1 Nos
Description Nos
Incomer 1250 Amp ACB 1 Nos.
Outgoing 160 Amp ACB 5 Nos.
Outgoing 100 Amp ACB 3 Nos.
Outgoing 63 Amp ACB 20 Nos.
Outgoing 40 Amp ACB 7 Nos.
Hooter 1 Nos
Annunciator with RS485 1 Nos
TNC Switch 1 Nos
Power Pack 15 Min. 1 Nos
CT 1000/5 Amp 4 Nos
CT 600/5 Amp 3 Nos
CT 600/5 Amo 3 Nos
PT 100 4 Nos
Temp Scanner with RS 485 1 Nos
Emergency Switch 1 Nos
MFM Meter 3 Nos.
6inch Exhaust Fan As per Design
On – Off – Trip Indicator As per Design
R- Y- B Indicator As per Design
PT -1Ph 3 Nos
MPCB 1 Nos
Control MCBs As per Design
RCCB 1 Nos
1250 Amp Bus Bar with 0.8A As per Design
800 Amp Bus Bar with 0.8A As per Design
600 Amp Bus Bar with 0.8A As per Design
Exhaust Fan 6inch As per Design
Control SP MCB 10KA As per Design
Lighting Switch Socket 16A As per Design
Illumination Lamp As per Design
Space Heater with Thermostat + As per Design
Incoming Cable Compartment As per Design
Outgoing Cable Compartment As per Design
Brass Double Compression Cable Gland As per Design
4Cx300Sqmm. Without Thimble
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
6. PANEL-4 : 1000A, QTY: 1 Nos
Description Nos
Incomer 1000 Amp ACB 1 Nos.
Outgoing 160 Amp ACB 3 Nos.
Outgoing 100 Amp ACB 5 Nos.
Outgoing 63 Amp ACB 18 Nos.
Outgoing 40 Amp ACB 0 Nos.
Hooter 1 Nos
Annunciator with RS485 1 Nos
TNC Switch 1 Nos
Power Pack 15 Min. 1 Nos
CT 1000/5 Amp 4 Nos
CT 600/5 Amp 3 Nos
CT 800/5 Amo 3 Nos
PT 100 4 Nos
Temp Scanner with RS 485 1 Nos
Emergency Switch 1 Nos
MFM Meter 3 Nos.
6inch Exhaust Fan As per Design
On – Off – Trip Indicator As per Design
R- Y- B Indicator As per Design
PT -1Ph 3 Nos
MPCB 1 Nos
Control MCBs As per Design
RCCB 1 Nos
1250 Amp Bus Bar with 0.8A As per Design
800 Amp Bus Bar with 0.8A As per Design
600 Amp Bus Bar with 0.8A As per Design
Exhaust Fan 6inch As per Design
Control SP MCB 10KA As per Design
Lighting Switch Socket 16A As per Design
Illumination Lamp As per Design
Space Heater with Thermostat + As per Design
Incoming Cable Compartment As per Design
Outgoing Cable Compartment As per Design
Brass Double Compression Cable Gland As per Design
4Cx400Sqmm. Without Thimble
Note: Manufacturer to provide detailed Bills of Material with foreseeing the SLD
Description Nos
MCCB 160 Amp 25kA Thermal Magnetic based 1
Spreader Link +Extended Rotary Handle 1
Indicating light LED type (ON/OFF/TRIP) 3
Neutral Link 1
Control SP MCB 10KA C-Curve 3
Brass Double Compression Cable Gland For 1
4Cx70Sqmm. Without Thimble
Metal Enclosure 1
STAND with Base Frame around 500mm Height 1
8. PANEL-5 : 100A PDB PANEL, QTY: 17 Nos
Description Nos
MCCB 100 Amp 25kA Thermal Magnetic based 1
Spreader Link +Extended Rotary Handle 1
Indicating light LED type (ON/OFF/TRIP) 3
Neutral Link 1
Control SP MCB 10KA C-Curve 3
Brass Double Compression Cable Gland For 1
4Cx25Sqmm. Without Thimble
Metal Enclosure 1
STAND with Base Frame around 500mm Height 1
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Client: XXXXX
Client’s Order No.: -
Project Name & No. .: XXXXX
Inspector’s Name: XXXXX
Report date: DD/MM/YYYY
Report No.: LT PANEL/FY-23-24/PROJECT ID
INSPECTION INFORMATION:
PO No.: XXXXX
Materials Inspected: LT PANEL RATED XX XX AMP
Date(s) of Visit(s): DD/MM/YYYY
Date of Previous Visit: N/A
Date of Next Scheduled Visit: N/A
P. O. Status: Complete Incomplete
SUPPLIER/SUB-SUPPLIER DATA:
Supplier: XXXXX
Location: XXXXX
Primary Contact: XXXXX
Phone: XXXXX
E-mail : XXXXX
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
RECOMMENDED ACTION:
Remarks:
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
ATTENDEES
MATERIAL INSPECTED
PRODUCT / MATERIAL / ITEM NAME ORDERED QUANTITY PRESENTED THIS VISIT ACCEPTED THIS VISIT ACCEPTED TO DATE
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
DOCUMENTS USED
SCOPE OF INSPECTION
Attachment 1 to this Inspection Report. (All Test equipment details with Calibration report)
MANDATORY TOOLS REQUIRED FROM SUPPLIER: HV TESTER, INSULATION RESISTANCE TESTER, CURRENT INJECTION KIT, RELAY TEST KIT, Multi Meter, Clamp
Meter, CRM TESTER, CONTINUITY METER
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
INSPECTION DETAILS
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
1. EQUIPMENT DETAILS
PANEL JOB NO
INCOMER-1 SERIAL NO
INCOMER -2SERIAL NO
INCOMER-3 SERIAL NO
OUTGOIN-1 SERIAL NO
OUTGOIN-2 SERIAL NO
OUTGOIN-3 SERIAL NO
OUTGOIN-4 SERIAL NO
OUTGOIN-5 SERIAL NO
OUTGOIN-6 SERIAL NO
OUTGOIN-7 SERIAL NO
OUTGOIN-7 SERIAL NO
OUTGOIN-7 SERIAL NO
OUTGOIN-7 SERIAL NO
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
2. PRELIMINARY CHECKS
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
check the panel metabolic containment and accessories physical condition for any visual damages
Check all the enclosure of all Electricals with gears are connected to the earthing system
Check all socket outlets , PE points & doors are properly connected to the earthing system.
check the installation of earthing system as per approved drawing schematic diagram
Check thermal overload relay model as per the approved specification
Check LSIG relay mode as per the approved specification.
Check timer setting specified as per the approved specification
Check Colours of wire used as per the approved specification
Check bus bar identification as per the approved specification
Check earth connection to metal frame in all sections
Check Earth continuity test is satisfactory
Check control circuit specified as per the wiring drawing
Check Terminal arrangement is as specified in the wiring diagram
Check indicator lamp for ON/OFF control and trip working correctly
Check remote operation working correctly
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Check for electrical interlock & mechaical interlock is as per design scheme
Check voltmeter function , Ammeter & MFM Functions
Check paint colour and finish as specified as per the approved specification
Check panel is neat and clean
Check sld's are attached inside the door
Check doors are properly aligned
Check support for incoming cable termination is provided
Check breaker contacts / Condition of spreaders and clearances
Check inspected door handles and locking bar with LOCK & KEY
Check panel lights & condition of Switch - Sockets
Check all breaker handles for on off and trip
Check automatic transfer operation / Mechanical & Electrical interlock if any
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Checking Results
1000 Vdc - 1 mn
B Phase & Ground (Bus bar-1)
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Checking Results
AC Socket
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
6. SIGNALING CHECK :
7. TRIPING TEST:
Relay Name with Feeder Relay Operational Settings Relay Test Set Value Injected Current Pickup value Trip Time
details
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Relay Name with Feeder Relay Operational Settings Relay Test Set Value Injected Current Pickup value Trip Time
details
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
N
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
CT: 1
Manufacturer :
Ratio :
Burden:
Phase Winding Primary current value Secondary current measured value Theorical Ratio Calculated Ratio Results
L1 1S1-1S2
L2 1S1-1S2
L3 1S1-1S2
CT: 2
Manufacturer :
Ratio :
Burden:
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Phase Winding Primary current value Secondary current measured value Theorical Ratio Calculated Ratio Results
L1 1S1-1S2
L2 1S1-1S2
L3 1S1-1S2
CT: 3
Manufacturer :
Ratio :
Burden:
Phase Winding Primary current value Secondary current measured value Theorical Ratio Calculated Ratio Results
L1 1S1-1S2
L2 1S1-1S2
L3 1S1-1S2
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
MFM-1 :
Manufacturer :
Scale :
Model :
Serial No :
Indicator reading (Vac) Injected value (Vac) Measured value (Vac) % Error
L1-L2
L2-L3
L1-L3
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
L1
L2
L3
MFM-2 :
Manufacturer :
Scale :
Model :
Serial No :
Indicator reading (Vac) Injected value (Vac) Measured value (Vac) % Error
L1-L2
L2-L3
L1-L3
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
L1
L2
L3
MFM-3 :
Manufacturer :
Scale :
Model :
Serial No :
Indicator reading (Vac) Injected value (Vac) Measured value (Vac) % Error
L1-L2
L2-L3
L1-L3
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
L1
L2
L3
Manual mode:
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Automatic mode:
Conditions Operations Actions Bus voltage Results
FACTORY ACCEPTANCE REPORT : LT PANEL
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
NON-CONFORMANCES
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
Prepared by: Darshit vyas Reviewed by: Arvind Singh Bhadoria Approved by: Ashwin R.
28. Ceiling Fans Crompton Greaves/ Bajaj / Havells As per PAX Capacity
29. Wall Mounted Fans Havells / Bajaj / Almonard. As per PAX Capacity
30. FRLS PVC conduits & Accessories (Heavy duty) VIP/ NELCO/PRECISION ISI Marked
31. GI Conduits & Accessories Bharat Industries / Supreme/ AKG. ISI Marked
32. Copper Conductor FRLS PVC Insulated Wires Finolex / RR Kabel /POLYCAB Type Tested Design and Fire resistant
33. Modular Switches & Socket Outlets Legrand- MOASIC /Anchor -ROMA/ ISI MARKED
Schneider-LIVIA
34. Weather proof Switches & Sockets Legrand /Anchor / Schneider ISI MARKED
35. Industrial Socket Outlets – Metal Clad type Legrand / Schneider / Hager ISI MARKED
36. Industrial Socket Outlets – Thermoplastic moulded type Mennekes /Scame / NEPTUNE-Bals ISI MARKED
37. Raceways/ PVC Trunking Schneider/ Honey well/ Legrand. Type Tested Design and Fire resistant more than
2 Hrs.
38. Perforated / Ladder Type cable tray NEIDAX / Profab / OBO BETTERMEN/ >125 Micron Coating or as per specification
39. 11 KV HT VCB ABB/ SCHINDER / SIEMENS /L&T As Per Configuration
40. 11 KV HT RMU ABB /SCHINDER / SIEMENS /L&T As per Configuration
41. 11 KV HT Panel (OEM VCB Panel) LOTUS SWGR / LOAD CONTROLS/ ACE A System House shall be CPRI Approved design
ELECTROTREND /SWATI SWITCHGEAR for Indoor/Outdoor application
/or any CPRI APPROVED SYSTEM
HOUSE
42. Distribution Transformer VIJAY TRAFO / KIRLOSKAR OEM shall have CPRI Approved design for
ELECTRIC/Sudhir Power / TMC India/ Indoor/Outdoor application for offered Rating or
Essenar /ATLAS or any BIS Approved Rating above required Specification.
MFg.
43. DG Set Approved Vendors KIRLOSKAR /SUDHIR/SUPERNOVA --
44. Alternator NA --
APPROVED MAKES OF MATERIALS
IMPORTANT: -