Professional Documents
Culture Documents
Jos Intern
Jos Intern
Jos Intern
ACKNOWLEDGEMENT
First of all I want to give special thanks to God for his protection and guidance to me to
accomplish this internship successfully. Next to this I would like our University’s head of
school of Electrical Engineering and Computer to prepare this internship program for me and
also for supervisors those who helped in the time of internship program so that I could gain
practical skills and strengthen for theoretical skills.
Finally the company EEP which gives us the opportunity to work as an interns, and all the
people who had helped us during the internship period special thanks to Ms, Tigist, our
Supervisor and adviser for his good kindness and also for all the members of Power grid
black lion the whole operation team and also special thanks to EIABC campus.
ABSTRACT
A Substation receives electrical power from generating station via incoming transmission line
and delivers electrical power through feeders and this is used for controlling the power on
different routes. Substations are integral part of a power system and form important part of
transmission and distribution network of electrical power system.
Nowadays the demand for Gas Insulated Substation (GIS) is increasing over the world for
efficient utilization of electric power and space. In this a gas insulated substations is
investigated or studied since they are more advantageous though, they use same protective
devices or equipment when compared to air insulated substations. They are compact,
requiring little maintenance, more reliable, have longer service life (more than 50 years) and
safer. The compactness is due to the use of SF6 gas, which has high dielectric strength at
moderate pressure for phase to phase and phase to ground insulation.
Basically, Sub-station consists of power transformers, circuit breakers, relays, isolators, ear
thin switches, current transformers, voltage transformers, Capacitor banks, control and
protection system, SCADA etc.
This internship report covers the important equipment & their function in a GIS. And also an
attempt is made to cover the general operation of Substation and Checks the observations to
be made. As a part of case study we are going to visit a 132/15kv GIS in Black Lion
LIST OF FIGURE
Fig 1:1 propose structural- Corporate TSO .................................................................................... 3
Fig 2.2 SF6 gas vacuum................................................................................................................... 6
Fig 2.3 shows lighting arrestor ........................................................................................................ 8
Fig 2.4 Sf6 circuit breaker ............................................................................................................. 10
Fig 2.5 Bus-bar .............................................................................................................................. 11
Fig 2. 6 Transformer ...................................................................................................................... 13
Fig 2.7 shows the conservator ....................................................................................................... 15
Fig 3. 8 Earthing transformer ........................................................................................................ 18
Fig 2.9 Auxiliary Transformers ..................................................................................................... 18
Fig 2. 10 DC battery ..................................................................................................................... 20
Fig 2.11 Shows the Capacitor Bank............................................................................................... 20
Fig 2.12 Control room and Protection room ................................................................................. 22
Fig 2.13 SCADA system ................................................................................................................. 23
LIST OF TABLE
Table 4. 1 Interruption duration and frequency of different faults of Nov 2019 EC ..................... 34
Table 4. 2 shows how often interruptions caused for operation and maintenance purpose and how
many are caused by other power system faults. ............................................................................. 34
Table 4. 3 Shows how often interruptions caused for operation and maintenance purpose and
how many are caused by other power system faults. ..................................................................... 35
ABBREVIATION
CB Circuit Breaker
CT Current Transformer
SCADA Supervisory control and data Acquisition
EELP Ethiopia electric light power
EELPA Ethiopian Electric Light Power and Authority
EEPCO Ethiopian Electric Power Corporation
EEP Ethiopian Electric Power
GIS Gas insulated substation
OLTC On load tap changer
SF6 Sulphur hexafluoride
VT Voltage Transformer
Kv Kilo volt
MVA Mega volt ampere
Fig Figure
P.f power factor
GIS Gas isolated substation
AIS Air isolated substation
CONTENTS
ACKNOWLEDGEMENT ...................................................................................................... i
ABSTRACT ...............................................................................................................................ii
LIST OF FIGURE.................................................................................................................... iii
LIST OF TABLE ...................................................................................................................... iv
CONTENTS .............................................................................................................................. vi
CHAPTER ONE ........................................................................................................................ 1
INTRODUTION ........................................................................................................................ 1
1.1 Introduction of sub-station ............................................................................................... 1
1.2 Back ground OF EEP ................................................................................................... 1
1.2.4 Values ........................................................................................................................ 2
1.3 Back ground of Black Lion GIS ................................................................................... 3
Fig 1.3 Background of black lion substation ............................................................................. 4
CHAPTER TWO ....................................................................................................................... 5
2. Over Flow Work System in Black lion Substation ................................................................ 5
Black Lion has 12 outgoing lines with15 KV, 3 power transformers that are step down with
size 132//15, rating 50MVA. ..................................................................................................... 5
2.1. Gas-Insulated Substations............................................................................................ 5
2.2. Some Important Equipment’s used in Black lion GIS and Their Usage ......................... 7
2.2.1 Lightning Arrestor ..................................................................................................... 7
2.2.2. Voltage (Potential) Transformer (VT) ...................................................................... 8
2.2.3. Current Transformer (CT) ........................................................................................ 8
2.2.4 Earthing Switch ......................................................................................................... 9
2.2.5 Circuit breakers.......................................................................................................... 9
2.2.6 Bus- Bar ................................................................................................................... 11
2.2.7 Transformer ............................................................................................................. 12
2.2.8 Automatic tap changer ............................................................................................. 13
2.3 Some parts of the power transformer and their usage:- ................................................. 14
2.3 Inspections taken from the transformer body ............................................................... 17
2.3.1 Oil Temperature ....................................................................................................... 17
CHAPTER ONE
INTRODUTION
The present-day electrical power system is AC. i.e. electric power is generated, transmitted
and distributed in the form of alternating current. It is delivered to the consumers through a
large network of transmission and distribution. At many places in the line of the power
system, it may be desirable and necessary to change some characteristic (e.g. voltage, AC to
DC, frequency, power factor etc.) of electric supply. Generated voltage at the power station
is stepped up to high voltage for transmission of electric power. The assembly of apparatus
(e.g. transformer etc.) used for this purpose is the sub-station. Similarly, near the
consumer’s localities, the voltage may have to be stepped down to utilization level. Hence
the continuity of supply depends to a considerable extent upon the successful operation of
sub-stations
1.2.1History
The company was formed in 1956 as the Ethiopian Electric Light & Power Authority
(EELPA), which bundled all Ethiopian activities around electricity in a single organization.
In 1996, EELPA was split into the Ethiopia Electric Authority (EEA), taking over all
regulating activities and a company, Ethiopian Electric Power Corporation (EEPCo),
bundling all activities from power generation to household delivery. In 2013, EEPCo was
again split up into two companies, Ethiopian Electric Utility and Ethiopian Electric Power.
Ethiopian Electric Power was formed by Council of Ministers Regulation No.302/2013
Ethiopian Electric Power owns and operates the Ethiopian national power grid with all high
voltage power transmission lines above 66kV including all attached electrical substations
and almost all power plants within the national power grid (with the exception of some co-
generation power plants belonging to the state-owned Ethiopian Sugar Corporation).
Ethiopian Electric power is almost the state monopoly in generating electric power for the
national power grid, although Ethiopia also allows Independent Power Producers to
construct and to operate power plants for delivering power to the national grid since 2017.
To provide adequate and quality electricity generation, transmission, distribution and sales
services, through continuous improvement of utility management practices responsive to the
socio-economic development and environmental protection need of the public
1.2.4 Values
Executive
secretary
Black lion gas insulated substation is located in Addis Ababa around Mexico and it supplies
a large part of city. It is a transformer substation. The majority of the sub-stations in the
power system are concerned with the changing of voltage level of electric supply hence
transformer is the main component employed to change the voltage level.
This is one of the biggest new substations in Addis Ababa. Its gas insulated substation and
uses sulphur hexafluoride gas. It has 12 outgoing lines with15 KV, 3 power transformers
that are step down with size 132//15KVA each transformer has 50 MVA.
BL substation has taken from Sebeta and Addis west, but now taken only from Sebeta.
When more power is needed it can take from Addis west, since it’s a new substation. Its
connected by ring system i:e unless in the case of black out(* when all substation generation
station out from system during high load occurrence interruption takes place so all power
will be shut down no electricity in the whole country) it will get incoming voltage.
Substation can be categorized based on voltage level, structure and insulation system
applied. We can classify substation based on their voltage level to transmit power from
generation to consumer, like generation substation, transmission substation, distribution
substation, switches substation and collector substation. Based on the structural system used
substation can be classified as in door, outdoor and underground substation. Based on
insulation system applied substations can be AIS or GIS.
GIS Technology was originally invented in Japan, and then developed in various countries
between 1968 and 1972.The development and design of GIS and compressed Gas Insulated)
equipment have been progressed drastically for the last three decades throughout the world
because of the excellent insulation properties of Sulphur hexafluoride (SF6) gas .
CHAPTER TWO
Black Lion has 12 outgoing lines with15 KV, 3 power transformers that are step down with
size 132//15, rating 50MVA.
Black ion substation taken from Sebeta and Addis West ,its connected by ring system i:e
unless in the case of black out(* when all substation generation station out from system
during high load occurrence interruption takes place so all power will be shut down no
electricity in the whole country) it will get incoming voltage .
As we know that generated voltage is not the same in magnitude as the voltage reached in
the substation there will be loss due to many affects some of them are capacitive, inductive
and resistive.
A GIS also has different voltage level of substation starting from 12 kV to 800 kV in which
the major structures are contained in a sealed environment with sulphur Hexafluoride gas as
the insulating medium. The GIS equipment such as compact substations where there is
insufficient space for an open air substation or the land costs are prohibitive. Because GIS
occupies less space compared to conventional AIS. In addition to this, it is very much
required to establish an electrical substation at load canter. Establishing a substation at load
centre is quite economical and profitable. As it reduces length of feeders which intern result
in the voltage regulation improvement. However, space will be the main obstruction of
establishing a GIS uses a superior dielectric gas, SF6, at moderate pressure for phase- to
phase and phase- to - ground insulation.
The high voltage conductors, circuit breaker interrupters, switches, current transformers,
and voltage transformers are in SF6 gas inside grounded metal enclosures.
As a result, GIS is more reliable and requires less maintenance than AIS. Gas insulated
substations offer other advantages in addition to the reduced space requirements. Because
the substation is enclosed in a building, a GIS is less sensitive to pollution, as well as salt,
sand or large amounts of snow. Although the initial cost of building a GIS is higher than
building an air insulated substation, the operation and maintenance costs of a GIS are less.
The primary applications for gas insulated substations include: High voltage installations,
Urban Installations and Environmentally Sensitive Installations.
SF6 has two to three times the insulating ability of air at the same pressure. SF6 is about
100 times better than air for interrupting arcs. It is the universally used interrupting medium
for high voltage circuit breakers, replacing the older mediums of oil and air. SF6
decomposes in the high temperature of an electric arc, but the decomposed gas recombines
back into SF6 so well that it is not necessary to replenish the SF6 in GIS. There are some
reactive decomposition by-products formed because of the trace presence of moisture, air,
and other contaminants. The quantities formed are very small. Molecular sieve absorbents
inside the GIS enclosure eliminate these reactive by-products. SF6 is supplied in 50 - kg gas
cylinders in a liquid state at a pressure of about 6000KPa for convenient storage and
transport. Gas handling systems with filters, compressors, and vacuum pumps are
commercially available. Best practices and the personnel safety aspects of SF6 gas handling
are covered in international standards (IEC, 1995)
This substation is GIS (GAS insulated sub-station) i:e GIS is preferable than AIS because
of:-
2.2. Some Important Equipment’s used in Black lion GIS and Their
Usage
high voltage across the open secondary and may permanently affect the accuracy of the
transformer. The current transformers in our substation differ by their rating:-
The incoming circuit breaker type is Sf6 type. So that sulphur hexafluoride (SF6) gas is
used as the arc quenching medium. The SF6 is an electro-negative gas and has a strong
tendency to absorb free electrons. The contacts of the breaker are opened in a high pressure
flow of SF6 gas and an arc is struck between them. The conducting free electrons in the arc
are rapidly captured by the gas to form relatively immobile negative ions. This loss of
conducting electrons in the arc quickly builds up enough insulation strength to extinguish
the arc. The SF6 circuit breakers have been found to be very effective for high power and
high voltage service. It consists of fixed and moving contacts enclosed in a chamber (called
arc interruption chamber) containing SF6 gas.
This chamber is connected to SF6 gas reservoir. When the contacts of breaker are opened,
the valve mechanism permits a high pressure SF6gas from the reservoir to flow towards the
arc interruption chamber. The fixed contact is a hollow cylindrical current carrying contact
fitted with an arc horn. The moving contact is also a hollow cylinder with rectangular holes
in the sides to permit the SF6 gas to let out through these holes after flowing along and
across the arc. The tips of fixed contact, moving contact and arcing horn are coated with
copper-tungsten arc resistant material. Since SF6gas is costly, it is reconditioned and
reclaimed by suitable auxiliary system after each operation of the breaker.
The outgoing 15 KV line breaker is vacuum circuit breaker. i.e, vacuum is used as the arc
quenching medium. Since vacuum offers the highest insulating strength, it has far superior
arc quenching properties than any other medium. For example, when the contacts of the
breaker are opened in vacuum, an arc is produced between the contacts by the ionization of
metal vapours of contacts. However, the arc is quickly extinguished because the metallic
vapours, electrons and ions produced during arc rapidly condense on the surfaces of the
circuit breaker contacts, resulting in quick recovery of dielectric strength.
They are preferable due to their characteristics of compact, reliable, longer life, no fire
hazards, no generation of gas during and after operation, ability to interrupt any fault
current, require little maintenance and are quiet in operation, ability to withstand lightning
surge, low arc energy, low inertia and hence require smaller power for control mechanism.
The vacuum circuit breaker is very efficient, preferable, recent modern technology circuit
breaker but it only used for small voltage output like in our substation.
Bus bars are the most important component in substation network. They have the capacity
of holding up to several hundred volts.
Advantages:
Low initial cost
Less maintenance cost
Simple operation
Any fault on the system is fed by all the generating capacity, resulting in very large
fault currents.
2.2.7 Transformer
It is Three phase transformer: - a single phase units are used in a bank of three transformers
linked together this is preferable by considering:-
Fig 2. 6 Transformer
As the high voltage winding is wound outside the LV winding it is easier to get the tapping
connections out to the tap changer.
It has four essential features:-
Selector switches: - these switches select the physical tap position on the
transformer winding and, because of their construction, cannot and must not or
break the load current.
Reactors (inductors):- the load current must never be interrupted during a tap
change .Therefore during each tap change, there is an interval where two
voltage taps are spanned, they are used in the circuit to increase the impedance
of the selector circuit and limit the amount of current circulating due to this
voltage difference.
Under normal load conditions, equal load current flows in both halves of the reactor
windings and the fluxes balance out giving no resultant flux in the core. but during the tap
change, the selector switches are selected to different taps and circulating current will flow
in the reactor circuit, this circulating current will create a flux and the resulting inductive
reactance will limit the flow of the circulating current. (With no flux there is no inductance
and, therefore, no voltage drop due to inductance, but there will be small due to resistance).
• Vacuum switch: - it’s like circuit breaker that makes and breaks current during the
tap changing sequence.
• Bypass switch:-operates during tap changing sequence but at no time, does it make
or break load current, through it does make before break connection.
The operating mechanism for the OLTC is motor driven; manual operation is used in the
event of motor failure. The sequence of operation is mechanically linked, or interlocked, to
ensure that all contacts always operate in their correct order .Any failure of the operating
mechanism can result in severe damage to the transformer and tap changers.
mounted at the top of the transformer tank and connected to the transformer tank by a pipe
and which uses for store the oil to flow to radiator. Oil in the transformer tank expands and
contracts according to the heat developed and cause the level of the oil in the conservator to
rise and fall. It has 3 main purposes that are:-
It maintains the oil level in the tank.
It provides space for the expansion of oil when the temperature of the transformer
varies.
It prevent transformer oil from moisture (which reduces dielectric strength of oil)
when it breaths.
d. Tank: - Basically this is a container used to keep windings (both) and cooling oil.
e. Drain valve: This valve is used for taking damaged Oil from the oil tank for the proper
oil collection this Valve is situated under the oil tank.
f. Radiator: This one used for cooling oil which circulated hot and cool oil can be transfer
to the conservator, there exist fan inside it.
The radiators must be thorouly inspected prior to assembly to be certain that no water or
foreign material is in the oil space .to prevent condensation it is good not to open radiator at
lower temperature.
If there is any evidence of moisture, the radiator must be thorouly dried either by blowing
hot air through or flushing with hot oil. In any case it is desirable to flush out the cooling
equipment thorouly with hot oil if at all possible.
Radiator valves should be closed until immediately prior to final oil-filling, hence all
cooling equipment must be installed prior to final oil-filling.
g. Bushings:-
It is an insulated device that allows an electrical conductor to pass safely through grounded
conductor transformer. When an energized conductor in near a material at earth potential, it
can form very high field strengths, especially where the field lines are forced to curve
sharply around the earthed .The bushing controls the shape and strength of the field and
reduces the electrical stresses in the insulating material & are made of porcelain material.
Since it is oil filled leakage of the oil maybe occurred, that is we have seen once in our
substation .it is hallow inside it there is oil.
h. Breather
It is to prevent entry of most air in the transformer tank after its breath out .even a small
amount of moistures absorbed by the oil reduces the insulating properties of the oil
considerably. Used for absorb the moisture content of oil and sucked air.
i. Silica jell
It is Chemical material that is found on the breather basically its blue or brown colour one
after the absorption it become pink
j. Cooling tube
Are used to cool the transformer oil. The transformer oil is circulated through the cooling
tubes. The circulation of the oil may either be natural or forced. In natural circulation, when
the temperature of the oil raises the hot oil naturally rises to the top and the cold oil sinks
downward. Thus, the oil naturally circulates through the tubes. In forced circulation, an
external pump is used to circulate the oil.
k. Explosion vent
The explosion vent is used to expel boiling oil in the transformer during heavy internal
faults in order to avoid the explosion of the transformer. During heavy faults, the oil rushes
out of the vent. The level of the explosion vent is normally maintained above the level of
the conservatory tank.
l .Porcelain bush: Used for preventing unwanted leakage of electricity.
Alarm”-Used for showing alarm at the control room when temp is above
connected system and are used to provide a relatively low impedance path to ground there
by maintaining the system neutral at or near ground potential
We use three auxiliary transformers in Black Lion for each power transformer all auxiliary
transformers work mutually and fed the entire substation.
The fuse element made of low melting point if fault occurs it will blow out and disconnect
the power supply. Thus need to replace after every operation.
It provide a grounding below ground surface in and around the substation which will have
uniformly zero potential with respect to ground and lowest earth resistance to insure that all
non-current carrying parts connected to the earthing system shall be uniformly at zero
potential with respect to ground.
2.6 Dc Battery
A battery converts chemical energy to electrical energy by a chemical reaction. Usually the
chemicals are kept inside the battery. It is used in a circuit to power other component. A
battery produces direct current (DC) electricity (electricity that flows in one direction, and
does not switch back and forth). A battery can provide electricity in area that do not have
electric power distribution.
Black Lion GIS substation has 48V and 125 V DC batteries. The 48V battery is used for
small signal device (for protection) and for dc equipment. But 125V battery is used for
lighting purpose. In order to increase the current the Dc batteries are connected in series.
Fig 2. 10 DC battery
Improving power factor means reducing the phase difference between voltage and current.
Since the majority of loads are of inductive nature, they require some amount of
reactive power for them to function. A capacitor or bank of capacitors installed
parallel to the load provides this reactive power.
Mimic Panels
Provide a representation of the physical layout or process that the panel will control.
This type of panel is beneficial when needing to quickly view a system from a
central control room.
Control panel
Control panels contain meters, control switches and recorders located in the control
building also called a doghouse. These are used to control the substation equipment,
to send power from one circuit to another or to open or to shut down circuits when
needed.
Protection panel
Control and Relay panel is most important equipment of the substation as it work as
Shield guard for all substation equipment’s and electrical network. Moreover,
these panels are useful to control the flow of electricity as per the Voltage class and detect
the Faults in transmission lines.
Communication panel
Exchange of information between different parts of the power system (both ends of
power lines) require establishment of some kind of channels to provide a media for
communication of relay protection systems.
Metering panel
To operate and maintain power systems efficiently, it is very important to have
accurate information about system values, and the mission of metering systems is to
provide this information.
However, real power system currents and voltages may reach very high numbers (thousands
of amperes and volts respectively). To measure these values, they need to be reduced too
much lower numbers that metering equipment can safely handle. For voltages a nominal
value is usually 120 V, phase-to-neutral or phase-to-phase, and for currents nominal values
are 1 A or 5 A. Transformation of currents and voltages is performed by instrument
transformers which have their secondary windings connected to both relay and instrument
equipment.
All metering equipment available in the substation can be split in the following
functional groups: -
Ammeters – measure current
Voltmeters – measure voltage
Ohmmeters – measure resistance, impedance
Wattmeter – measure active power
Var meters– measure reactive power
A SCADA system gather information, transfer the information back to a central site, the
alters the home station a fault has occurred, carrying out necessary analysis and control,
such as determining if the fault is critical, and displaying the information in a logical and
organized fashion.
Advantage of SCADA:-
Closing procedure
Grounding
Line isolator
Bus bar isolator
Line breaker
Circuit breaker
Opening procedure
Circuit breaker
Bus bar isolator
Line isolator
Grounding
CHAPTER THREE
The four-month internship program comprises of general and specific objectives, both
added to produce skilled man power in engineering aspects.
To apply the theoretical knowledge that the student acquires in the class room to the
practical activities.
To join real world or practical view from theoretical knowledge gained from
university for long period of time.
Hence I have going for internship at electrical power substation our daily work was
voltage level of electric supply hence transformer is the main component employed to
change the voltage level. From Sebeta sub-station, electric power at 132 kV is
transmitted by 3-phase, 3-wire overhead system to the outskirts of the city and
underground in the city. Here, electric power is received by the primary grid sub-station
which reduces the voltage level to 15 kV for secondary transmission. This substation is
GIS type. Also this substation is terminal sub-station is one in which the line supplying
to the substation terminates or ends. It is located at the end of the main line. The
incoming 132 kV main line terminates at the sub-station it will not pass through the
substation as outgoing line. The only outgoing lines are the output voltage of the
transformer (15KV).This distribution substation has only one 132kV radial incoming
feeder from Sebeta substation. The substation supplies approximately 115,884
customers including residential and commercial.
And Also I can definitely able to see the new mobile substation .This mobile
substation is movable substation hence the name mobile indicates this all the
substation equipment’s are came from china all assembled it’s all out door
substation type ..,,the transformer ,circuit breaker ,lightning arrestor, earthing
transformer ,current transformer, voltage transformer ,etc…….This mobile
substation carry only six lines that are going below the road but it is temporary
maximum it can work for 2 years . The purpose of the newly developed mobile
substations is mainly to guarantee quick restoration of power supply after a major
fault in a substation.
Internships have been hailed for integrating theoretical education with practical experience
in enabling to develop our professional knowledge and professional skills. Hence the
internship improve and make it practical implement that different theoretical
knowledge. Therefore we gain knowledge of the qualifications and duties of a position and
can explore their interest in a field. We proposed to spend one month with an experienced
principal to test the validity of the premise that an internship could serve as a
practical preparation ground for practical training. In participating in this experience,
we hoped to increase our qualifications and gain practical knowledge that we could apply
to our own position as principal As result of the entries, we were able to make sense of the
wave of information and experiences we were introduced to in the field. In addition, we
would also reflect with our site engineer, an experienced teacher and supervisor, or other
administrators when we found it necessary to pursue another perspective on decisions or
issues related to the internship. As a result of our practical skills has three regulation
processes, the performance of organization tasks as well as observation, discussion and
reflection, we discovered three themes
Our analysis of general employer team playing skills or examinations suggests the
skills into four main areas. Our future employers will want to see evidence of this skill and
work experience can help us to demonstrate them.
Self-reliance skills: indicating that we can work independently. It shows our self-
awareness, knowing our strengths. It also organizes self and priorities through rearranging
commitments to get the job.
General skills: those skills that could be used in any situation and across all sectors. It
helps us to develop demonstrate flexibility .To act as problem solver in every work place.
To develops the knowledge that skill.
Specialist skills: these are often gained through our studies, such as subject specific
knowledge or technical skills .To has experience or understanding of how a particular
organization is structured or to know.
Be innovative: Take advantage of what makes you unique and do not try to fill the same
roles as your full-time co-workers. Think about ways you can be innovative in your role and
focus on the advantages and different perspectives an intern can bring.
Build a brand: Social networks provide a great opportunity to build your personal brand,
and great entrepreneurs know the importance of managing their online identity.
Impact our company: One of the things people love about working for start-ups or small
companies is the ability to have an impact on the direction of the company. The projects are
worked with three different organizations. This has allowed us to take ownership for some
large projects and really create our own position on our team.
Adapt: we use internship as an opportunity to learn new skills and test out our
knowledge. Working on side projects can be a great way to develop new
capabilities and explore other fields or roles within the company. We uses internship as an
opportunity to gain the skills we need and change it in to a path that better fits our interests,
skills, and goals. Working on side projects and meeting others within the company
can be helpful in this transition. We try to develop self-motivation, and self-confidence.
During our four month stay we have gained some entrepreneurship skills. As an employee
we have good understanding of the methods to follow to search for a job in either
government, private sectors. In generally in our internship period we have gained
knowledge of how to create privet owned jobs.
3.7.2 Inspection
Once a day at 9:00 pm local time all equipment will be inspected .for the incoming line
132KV inspection will be taken from each transformer like:
GCB SF6 gas pressure
Lightning arrestor counter
Tap changer counter
Tap position
Oil level
Temperature
Oltc transformer oil level
CHAPTER FOUR
4.1 INTRODUCTION
The goal of any power system is to deliver electricity to its customers in an economical and
reliable manner. Unless this power is planned and maintained reliable, it causes adverse
economic, social and political effect due to interruption costs and power outages on both the
utility and its customers.
This paper presents the study of current power system reliability assessment of Black lion,
analyses its causes and improvements by reduce power interruption caused by earth fault
and short circuit in power transmission feeder line.
Since Addis Ababa is the capital city of the country and a preferred location for most of the
industries, considerable share of the electric power supply is directed towards the city. Due
to this fact, Addis Ababa has been the load center of Ethiopian electric power system. Black
lion substation is one of the substations found in Addis Ababa that face distribution
inefficiency, repetitive and sporadic power interruptions and power quality problems.
The people in the capital city and different towns in Ethiopia are facing problems because it
is associated with their livelihood. All residential, commercial and industrial customers are
victims of the problem. Especially for factories and industries, it is really challenging to
tolerate power interruption since it causes much revenue loss within hours of interruption.
So, the root cause of this problem should first be identified, and the possible solution should
be investigated.
4.2 Statement of the problem
4.4 Methodology
Black lion substation has been supplied from main grid that is interconnected system (ICS).
Ethiopian Electric Power is a service provider of electric power in the country. A 132kV
transmission line is stretched into the substation then, the distribution system in the city has
a primary voltage of 15 kV. And also, this voltage value is stepped down to 380V/220 in
three phase and single phase respectively. The Project detects the location of fault in
transmission lines from the base station in kilometres using an Arduino board. It uses the
standard concept of AC impedance i.e., when an AC voltage is applied at the feeder end
through a series reactance of the overhead transmission line, then current would vary
depending upon the location of fault. When there is a short circuit or open circuit, the
voltage across series reactance changes accordingly and fed to an ADC to develop
precise digital data which the programmed Arduino would display using LCD in kilometres.
Determine
Searching the Developi Result
Design
Identify related specificatio ng and
the circuit
the literature n of the simulatio conclusi
problem selected n on
material
Table 4 line 11 is interrupted many times by Earth fault and short circuit.
BL09 - - - - - - - -
BL010 3:43 8 4:54 6 6:51 2 - 2
BL011 6:02 6 15:50 14 21:53 3 - 1
BL012 0:18 2 0:05 1 - - - -
TOTAL 18:04 54:53 47:59
Chart Title
3
2.5
1.5
0.5
0
BLO1 BLO2 BLO3 BLO4 BLO5 BLO6 BLO7 BLO8 BLO9 BLO10 BLO11 BLO12
As we have seen from the above table line 11 is interrupted many times by Earth fault and
short circuit. Power interruption from Sebeta according to time table for transmission
work(132kv) on 30/03/12 from 06:15to 10: 55
The following Table 5: shows how many interruption durations are caused for operation and
maintenance purpose and how many are caused by other power system faults.
Table 4. 2 shows how often interruptions caused for operation and maintenance
purpose and how many are caused by other power system faults.
Bl01 - - -
Bl02 - - -
Bl03 - - -
Bl04 3:45 23:12 26:57
Bl05 2:35 23:10 25:45
Bl06 1:41 10:28 12:09
Bl07 - - -
Bl08 - - -
Bl09 - - -
Bl010 3:43 29:36 33:19
Bl011 6:02 53:53 39:53
Bl012 0:18 0:05 0:23
Total 18:04 24 158:28
Table 4. 3 Shows how often interruptions caused for operation and maintenance
purpose and how many are caused by other power system faults.
From the above tables we try to see the reliability indices of Black lion distribution system.
The availability of power for Customers from this substation is performed on the medium
voltage side of the customer transformers (15kV). The reliability is highly affected by
outages occurred on the customer side secondary distribution lines which unable to collect
data for analysis due to lack of resource, lack of organized data and advanced technology at
the substation to view the performance of the customer side secondary distribution network.
Electrical accidents are the leading cause of death in the industry (Cawley, 2000). Electrical
accidents tend to occur less frequently than other types of accidents, yet when they do occur
they tend to be far more severe. Nowadays transmission faults are the most severe and that
why is most scholars resemble on this idea.
Lekshmi.M has discussed Sectionalizing method in 1959: This procedure risks
reducing transmission reliability, because it depends on physically cutting and splicing
the cable. Dividing the cable into successively smaller sections and measuring both ways
with an ohmmeter or high -voltage insulation resistance (IR) tester enable to narrow
down search for a fault. This laborious procedure normally involves repeated cable
excavation
All the above methods discussed in the above have their own drawbacks. So, by standing
from the power engineer’s point of view we are modifying and upgrading the basic method
of locating fault by overcoming the drawbacks of the above methods to certain extent using
AC impedance concept.
Result: In this method, the short circuit fault at a particular distance in the transmission
line can be located using simple AC impedance measurement enables to rectify fault
efficiently. Circuit can be tested with different resistor values to simulate various fault
conditions. It displays exact location of short circuit.
At normal condition which means the switches are opened, the LCD displays NF (No Fault)
on the three phase lines of R, Y and B.
At the time of pressing the switches which means that creating fault manually we get a
detection on the LCD display. For example when we press s1 it displays Distance: 80 km, at
the time of pressing s2 it displays Distance: 90 km the same manner happens to the rest
switches on the three phase R, Y, and B.
The LEDs glow indicates there is no fault in transmission line means the limit
switches are normally opened. Whereas the LEDs off indicates there is a fault in
transmission line and the limit switches will be in the normally open state.
CHAPTER FIVE
5.1 RECOMMENDATION
In this substation the outgoing current ratio is 800:1 but the outgoing cable size capacity
carry current is 400:1 so the company should have to change the cable size in order to carry
800:1 amp.
I recommended to the Wollo University that the theoretical part we learnt should be helped
by practical knowledge. And internship program should be available more than once.
Because this program will help for the student to recognize theoretical with practical
knowledge.
5.2 Conclusion
This internship program has played an important role in my eye opening experience to the
outside world. Also I have seen a lot and I have learned more than enough by correlating
my classroom studies throughout this practice time.
Additionally I have learned on different control parts, protection parts, and instruments, I
also worked as an operator by using suitable principles and procedures. Throughout
executing my work task I have faced a number of challenges since I have been sent to face
the outside challenges and to overcome all the problems by finding solution. I have also left
my kindly recommendations for some problems.
I have proposed one solution and give suggestion to others problems. Throughout this
internship period I have gained a number of benefits in terms of improving practical skills,
theoretical knowledge, interpersonal communication skills, entrepreneurship skills,
leadership skills and in terms of understanding about work ethics and related issues. Of the
end of this I conclude that the grounding method at all electric power plant should be
according to their voltage level.
Reference
[1]. Raghu Raja Kalia, Preeti Abrol, ’Design and implementation of wireless live
wire fault detector and protection in remote areas’, IEEE, (2014), vol. 97, No.17
[2]. Pooja.P.S, Lekshmi.M, ’Fault detection technique to pinpoint incipient fault , IEEE
(2015),
[3]. D-P-Kothari-I-J-Nagrath ‘Modern-Power-Systems-Analysis’
[4]. Hadi Sadat ,power system Analysis-1
[5]. Wikipedia encyclopedia
[6] M.E.El-Hawary, Electric power system design and Analysis, Reston publishing
company,
Virginia, 2002.
[7] M Rustebakke, ―Electric utility systems and practice? Johan Wiley and Sons, Network,
1983.
[8]Website: www.eepco.gov.et
[9] Electrical power system 2
[6]The substation mentors also support us necessary materials to our report
[7].From my exercise material and my supervisor Mr. Tigist.
Appendixes
Source code
// include the library code: else {
#include <LiquidCrystal.h> lcd.setCursor(0, 0);
// initialize the library with the numbers of the interface lcd.write("R: ");
pins lcd.setCursor(3, 0);
LiquidCrystal lcd(12, 11, 5, 4, 3, 2); lcd.print(dist1);
// define phase control pins lcd.setCursor(4, 0);
int phase[3] = {7, 8, 9}; lcd.write(" KM");
int distance(int inputVoltage) { }
if (inputVoltage >= 890 && inputVoltage < 920) { digitalWrite(phase[0], LOW);
return 90; digitalWrite(phase[1], HIGH);
} delay(500);
else if (inputVoltage >= 850 && inputVoltage < 890) { int dist2 = distance(analogRead(A0));
return 80; if (dist2 == 0) {
} lcd.setCursor(8, 0);
else if (inputVoltage >= 750 && inputVoltage < 850) { lcd.write("Y: ");
return 70; lcd.setCursor(11, 0);
} lcd.write("NF ");
else if (inputVoltage >= 600 && inputVoltage < 750) { }
return 60; else {
} lcd.setCursor(8, 0);
else return 0 ; lcd.write("Y: ");
} lcd.setCursor(11, 0);
void setup() { lcd.print(dist2);
// set up the LCD's number of columns and rows: lcd.setCursor(12, 0);
lcd.begin(16, 2); lcd.write(" KM");
// set pin mode for phase relays }
for (int j = 0; j < 3; j++) { digitalWrite(phase[1], LOW);
pinMode(phase[j], OUTPUT); digitalWrite(phase[2], HIGH);
} delay(500);
} int dist3 = distance(analogRead(A0));