MAINTENANCE
EVERY DAY
a. Outside.
Thermal fluid:
Pumps:
idmanuals\sec_4787.97e
Check all:
Strainers:
Check strainers in thermal fluid system (only first month after installation; after
time every three months.
Switch box
a. Lamptest
if\manuals\sec_4787.97e
YAIILEF @i FAM i MARINE AND INDIISTRIES RV TEI EPHONE- 1.24 424 RONAN
INFORMATION
EVERY*MONTH
. Safety equipment:
a. Flow switches
Maximal thermostats
Check maximal thermal fluid thermostat. For that purpose you decrease the set
point of the maximum thermal fluid thermostat during operation. Installation has
to stop and alarm lamp “maximum thermal fluid” is lightened. Turn adjusting
knob of thermostat to the original set point value.
Check maximum flue gas thermostat. For that purpose you decrease the set point
of the maximum flue gas thermostat during operation. Installation has to stop and
alarm lamp “maximum flue gas” is lightened. Turn adjusting knob of thermostat
back in the original position. Do not forget to press reset button on the thermostat.
anuals\sec_4787.97e
For checking open valve just above leakage device and fill up with a small quantity of
thermal fluid. Leakage alarm will be generated and burner and circulating pump will be
switched off. After test drain leakage device by opening valve behind leakage device.
. Pumps:
Coupling.
Filling pump
Start second fuel oil transfer pump and ensure yourself of a good function.
Automatic standby
i\Mmanuals\sec_4787.97e
9.2.6. Valves
ifmanuals\sec_4787.97e
Burner:
Do not increase the capacity of your installation. (for capacity see page 4).
Overfiring of your heat exchanger can cause cracking of the thermal fluid
and damage to the coils.
Expansion tank:
a. Open drain and be sure that there is no condensated water any more in the
expansion tank.
i:\Manuals\sec_4787.97e
LATERM @EHE Gt @k EH BE AAADIAILC AAIR IAIRIICTRIFe DV TTI CMIIMNAIF. 1.94 4N4A RANANN
~ BRIN ze) Wiley
4, EVERY YEAR
Thermal fluid
Take a sample of your thermal fluid and have its condition checked by e.g.
the supplier of the fluid.
Burner installation
We advice you to have the installation checked by one of our service engineers
every year.