Professional Documents
Culture Documents
ShrutiThakkar CA2
ShrutiThakkar CA2
ROY ENGINEERING
COLLEGE
Power System II
(PC-EE-601)
Introduction
Introduction to Symmetrical Fault in Power Systems addresses anomalous
system performance in the event of a symmetrical three-phase fault, or
symmetrical short circuit. Such situations are brought about in the system by
unintentional defective operation, equipment insulation failure, or flashover of
lines produced by a lightning strike.
Symmetrical faults, also known as balanced faults, are a type of fault that can
occur in a power system where the fault current is the same in all three phases.
These faults can have significant implications on the stability and protection of
the power system, and it's important to understand their characteristics to
minimize their effects.
3-phase Fault
The Symmetrical fault conditions are analysed on per phase basis using
Thevenin’s Theorem or Bus Impedance Matrix.
Sequence Components:
An unbalanced system of ‘n’ related vectors can be resolved into ‘n’
system of balanced vectors called Symmetrical components of original
vectors
In a Three phase system, the three unbalanced vectors either V a, Vb, Vc or
Ia, Ib, Ic can be resolved into three balanced system of vectors. The vectors
of the balanced system are called Symmetrical components of the original
system
The symmetrical components of Three Phase system are as follows:
Positive Sequence Components
Negative Sequence Components
Zero Sequence Components
Importance:
The calculation of fault current involves applying Ohm's law, which states that
current (I) equals voltage (V) divided by impedance (Z). By determining the
system voltage and fault impedance, we can calculate the fault current using the
formula:
I=V/Z
Where:
Example Scenario
Let's consider a three-phase power system with a fault occurring on one of the
transmission lines. The fault is assumed to be symmetrical, meaning the fault
current and impedance are the same in all three phases.
Protective Devices:
To mitigate the effects of symmetrical faults, protective devices such as relays
are used. These devices detect abnormal conditions and quickly isolate the
faulted section of the system, preventing further damage and minimizing
disruption to the rest of the power system.