4.1 INTRODUCTION
‘This chapter deals with the power distribution from
the 4 wire input to the de power distribution from
power supply. Refer to figure 4.1 for the power
distribution in block diagram. For specific details,
refer to the system schematics at the end of this
chapter.
4.2 SYSTEM OVERVIEW
The system input power is a 4-wire connection:
3 phases with a green wire ground. The ground
system must be continuous from the ground origin
to the machine ground terminal. Conduit will not
suffice as a current carrying component in the
ground system.
Check the voltage plate attached to the
control to determine the correct voltage
required for the control.
NOTE
‘The incoming phases do not have to be
phased for correct operation of this control.
AC POWER DISTRIBUTION
‘The incoming power is switched on and off by the
main disconnect. The output goes through fuses
FU1, 2, and 3. The output of these fuses then branch
to three different circuits.
‘The major branch circuit is to the spindle motor
controller. 1L1, 1L2, and 1L3 is connected to FU4,
FUS, and FU6. The output of these fuses on wires
2L1, 2L2, and 2L3 is connected to contactor CR3.
The output of CR3 supplies power to the spindle
controller at pins T, S, and R and the spindle motor
fan overload, MOLI. The output of MOLI is wires
Tl and T2 which are connected to the spindle motor
fan at terminals U and V. 5L1, SL2, and 5L3 have a
transient filter across the three phases to catch
transients caused by CR3 opening.
A single phase branch is from 1L1 and 1L2 through
FU7 and FU8 to wires 3L1 and 3L2 to the input of
transformer T1. The input of transformer T1 is,
multi-tapped to give it the ability to handle different
input voltages. The appropriate connections are:
208 vac: connect 3L1 to HI, 3L2 to H2, jumper HI
to H4 and H2 to HS.
230 vac: connect 3L1 to Hi, 3L2 to H3, jumper HI
to H4 and H3 to H6.
416 vac: connect 3L1 to H1, 3L2 to HS, jumper H2
toH4,
460 vac: connect 3L1 to HI, 3L2 to H6, jumper H3
toH4.
‘Transformer T1 supplies 115 vac @ 4.3 amps to the
ow level power supply and the monitor. T1 is
designed with a split bobbin transformer with a
gound shield inserted between the the primary and
secondary to reduce the capacitance coupling. It
also as an air gap that will saturate at about 160
volts, which means that transients above 160 volts
will not be coupled to the load. The RC network on
the secondary further reduces any fast rising
voltages.
Asecond branch circuit is from 1L2 and 1L3 to
transformer T2 through fuses FU9 and FU10 and
wires 4L2 and 41.3. Transformer T2 has a multi
tapped primary that can be tapped for the following
voltages.
208 vac:connect 4L3 to H1, 4L2 to H6, jumper HI
to H5 and H2 to HE.
230 vac:connect 4L3 to HI, 4L2 to H7, jumper HI
to H5 and H3 to H7.
245 vac: connect 4L3 to H1, 41.2 to H8, jumper HI
to H5 and H4 to H8.
416 vac:connect 4L3 to H1, 41.2 to H6, jumper H2
to HS.
460 vac: connect 4L3 to H1, 412 to H7, jumper H3
to HS.
490 vac: connect 4L3 to H1, 4L2 to H8, jumper H4
to HS.
SSF
4111
INCOMING, <4
POWER 2 |SPINDLE
aWiRE ig DRIVE
GROUND
2.
s2vac ‘axis
115 vac va vag axis |
m mR ne POWER
CRT ee ‘SUPPLY
MONITOR|
1225 voc] Jov
s9vac
COMPUTER Rae
POWER 115 vac —>|
‘SUPPLY ORIVE
ov
vt
115 VAC +|
24 VDC
; 1 Power | | YAS
496 OX. HARD FLOPPY SUPPLY 4
MOTHER DISK DISK
BOARD DRIVE DRIVE
24
Zaxis
oc
wo ov ove |_|
400
BOARD
A axis
ORVE
KEY
BOARD
AUX aur {OY __| vertaur
808 BOARD [15VAC_| BOARD
Coe 115 VAC
soc |
xe 24voc
808, ov
BOARD
vor,
BOARD
Figure 4-1. Power Distribution - Functional Block Diagram
42e crime tn
‘! 3
31542958
YASKAWA
‘SPINDLE DRIVE
31942616
AUF
31506101
CR 456
31942745
31503497
ona LeTLAUF
31044036
MOTHER BOARD 31943798
495 VOLT PS
31949828 31842304 31943888 (9) & OPTIONAL
BMDC ASS'Y XTPS BRIDGEPORT DRIVE
Figure 4-2: Electrical Cabinet Breakdown (with Part Numbers)
43————
‘Transformer T2 supplies the 115 vac @ 3 amps
from both windings for the AUF board, 92 or 100
vac @ 12 amps from both windings for the DC
motor drives, and 19 vac @ 10 amps for the 24 Volt
DC power supply.
NOTE
The two 115 volt AC windings on this
transformer are wired so that they appear as,
230 volts AC center tapped. This voltage is
required to operate the Tool Arm and the
Carousel motors. The 92/100 volts AC for
the motor power supply is also wired as a
184/200 center tapped voltage.
24 VOLT DC POWER SUPPLY
The 19 volts AC from terminal 15 on transformer
T2is connected to FUI through wire 8. The output
FULL is connected to the AC input of BR1 through
wire 9. The output of this seconary coil at terminal
16 is connected to the other side of the AC bridge,
BRI, through wire 7. The minus output of BRI is
connected to C1 and the input terminal of the AUF
at connector JP12 pin 2A through wire 39. The
positive output of BR1 is connected to FU12
through wire 18. The output of FU12 is connected
to the input of the AUF at connector JP12 pin 1A
through wire 40. This power supply is rated at 6
amps de maximum.
The 24 volts DC on the AUF card is used to supply
power to the Z brake, the perimeter door guard shot
pin, the high gear solenoid, the spindle off light, the
‘work light, the low gear solenoid, the stop pin
solenoid, and the A-axis brake, if this option is
installed.
115 AND 230 VOLT SUPPLY
‘Terminals 11 and 12 of transformer T2 are
jumpered together and tied to chassis ground
through wire 2. This connection forms the center
tap for these two windings and the chassis ground
referance for the axis drive motor power supply.
Wire 2 also connects to the AC input terminal on
the AUF at connector JP22 pin 1A.
‘The 115 volt AC output of T2 at terminal 9 is,
connected to FU14 through wire 94. The output of
FUI4 is connected to the 115 volt AC input on the
AUF at connector JP22 pin 3A through wire 4. The
other 115 volt AC output at terminal 14 is
connected to FU15 through wire 95. The other side
of FUIS is connected to the 115 volt AC input
terminal of the AUF at connector JP22 pin 2A. The
voltage measured from the 115 volt input terminals
(2A and 3A) to chassis ground is 115 volts. But
when terminal 2A is measured to terminal 3A, the
voltage is 230 volts AC. The outputs of the AUF is
wired to use 115 volts AC while the outputs of the
LeTLAUF is wired to use the 230 volts AC.
‘The 115 volts AC on the AUF is used to supply
power to the following:
1. The cabinet fan through fuse FU4.
2. The miscellaneous outputs through fuse FU3.
3. The CRT enclosure fan through fuse FU6.
4, The flood coolant receptacle through fuse
FUI
5. The lube pump motor through fuse FU8.
6. The index relay through fuse FU9.
On the LeTLAUF both phases of the 240 volts AC
are fused with fuses FU1 and FU2. The LoTLAUF
supplies voltages to the following:
1. 115 volts AC to the tool unclamp solenoid.
2. 115 volts AC to the air blast solenoid.
3, 240 volts AC to the tool arm motor.
4, 240 volts AC to the carousel motor.
5. 240 volts AC to the tool arm motor brake.
THE DC MOTOR POWER SUPPLY
‘Transformer T2 is tapped at 92 volts AC and 100
volts AC. These two taps permit a choice of 128 or
140 volts DC applied to the axis motor drive cards.4. Power Distribution
The voltage may have to be selected to
accommodate the weight of the Z axis when
accelerating to rapid in the plus direction. The 92
volt taps are terminals 10 and 13. The 100 volt taps
are terminals 17 and 18. To change voltages, change
wire 1 from terminal 13 to terminal 18 and wire 3
from terminal 10 to terminal 17.
Wire 1 is connected from terminal 13 to CB16. The
output of CB16 is connected to D1 through wire 5,
Wire 3 is connected from terminal 10 to CB17. The
output of CB17 is connected to D2 through wire 6.
The DC output of D1 and D2 is connected to the
plus side of the filter capacitor and the bleed
resister through wire 50. _
Wire 2 connects the transformer terminals 11. and
12 to the minus side of the capacitor and the bleed
resistor. The positive output of the power supply,
wire 50, connects to JP3 pin 3 on all axis drive
cards, The negative output of the power supply,
wire 2, connects to JP3 pin 1 on all axis drive cards.
JP3 pin 2 on al axis drive cards is connected to
chassis ground.
4.3 SYSTEM PROTECTION
43.1 Signal Ground
Each module, separated device or separate circuit,
is referenced to the System Ground as close as
practical to the System Ground Stud. Because these
circuits branch out independently from the ground
stud, they will not carry current from other modules.
The Signal Ground (a zero-volt reference) is con-
nected to the protective ground at only one point.
43.2 Shielding
Certain shiélded cables for signal purposes are
continuous shields grounded at one end only (the
point closest to the System Ground Stud).
4.3.3 Noise Suppression
Suitable RC circuits are applied across ac relays and
starters as well as at the main 3 phase ac induction
motor for the spindle. De relays are protected by
diodes.
FUSE CHART
FUSE # |VALUE_| DESCRIPTION | PART# _| LOCATION _|REMARKS
FUL, 2,3 50 amps _| FLRS 600 vac 31542293 _| DISC #1 FOR 200/240 VAC
} FUL. 2.3. [25 amps _| FLRS 600 vac __} 31542292_| DISC #1 FOR 440 VAC _
ISE REDUCER FOR USE W/25 AMPS 31542285_| DISC #1 USE W/31542292
FUI3 Samps__| MCR.S 250 vac__| 31542838_| TB-1
[FULA Samps _ | 229-2AG-5 250vac| 11597535__ | AUFFUIA __|COOLANT PUMP.
|FU2A,3A,4A,6A AUF FU2, 3, 4
|FU7A.8A.9A __|2.5 amps _| 22902.5 250vac__| 31542413 _| 6,7, 8,9
FUSA 10 amps__| MDA 250 vac 31542411_| AUF FS.
FUIB, 2B Samps | MDA 250 vac 31508852 | LeTLAUF F1,2|
Figure 4-3. Fuse Chart
Ee
4544 PROTECTIVE GROUND
Protective ground is required. It minimizes
the exposure to personal shocks in the
event of circuit shorts or other mal-
functions. Failure to ensure protective
ground may create electrical shock hazard,
causing serious personal injury or death.
Protective Ground (Chassis or Safety Ground)
establishes a low impedance path from the electrical
cabinet and other mechanical parts of the system to
earth ground. Protective Ground assures that all
conductive parts of the enclosure are safe. If any
circuit inadvertently touches the chassis, the voltage
will be reduced to zero and the enclosure will be
safe to touch. Because safety requirements vary in
different localities, be sure to consult local govern-
ing codes. These codes take precedence over the
practical guidelines presented, which are based upon:
National Electrical Code;
California "Electrical Safety Orders"; and
Pennsylvania "Electrical Safety Regulations".
‘The four methods listed below are commonly used
to establish earth ground:
Continuous Metal Water Pipe — When
properly buried, length is installed below the
permanent moisture level, impedance is
typically 3 ohms.
Copper Stake (3/4 in. dia, 6-8 ft. long). — When
properly driven into the ground below
permanent moisture level, the impedance of this
type is typically below 5 ohms.
Fourth Wire Ground — Although a copper
ground stake is preferred, an alternative is a
fourth wire for ground included with the power
wires from the enclosure ground stud to the
power company service panel ground bus. (See
Note 1, below.)
Other Metal Electrodes (Well Castings or the
Like) — Must be well chosen since they
‘generally exceed an impedance of 5 ohms but
are well below 25 ohms.
NOTE1
‘The resistance of the earth ground connection
is measured from the enclosure ground stud,
through the ground wire, to the earth ground
connection; then through the earth ground to
another earth ground connection (at least 20
feet away), and through its associated wire to
another ground stud. The resistance should
not exceed 5 ohms. The wire used between
the ground stud and the earth ground should
be AWG10 or larger and should be braided
cable to minimize resistance at high
frequencies (cable resistance less than 0.075
ohm). The ground wire should be inspected
for mechanical abuse periodically.
4.5 VAC DISTRIBUTION BRANCH
The 115 vac output from TI feeds the DX power
supply, color monitor, and hour meter. The 115 vac
distribution branch originates at transformer T2 and
steps the line voltage down to 115 vac single phase.
46 24 VDC POWER SUPPLY DISTRIBUTION
‘The 24 vdc Power Supply provides +24 vde power
that is fed to the AUF board and is used by the
following devices:
1. Pneumatics - The pneumatic system provides
power to the power drawbar assembly, to knock
‘out the tool during a tool change cycle. It also
enables gearbox shifting, and supplies air to the
air blast system, to blow chips away from the
spindle.
Emergency Stop Switch — The Front Panel
switches provide communications between the
machine and the operator. Power to the
EMERGENCY STOP is from the AUF board.
rr3.
‘When pressed, the E-STOP switch will remove 4.7 VOLTAGE
power from the servomotors, stop the spindle This machine was designed for 240 vac or 460 vac.
‘motor, disable the spindle control system, and However, it may be re-tapped to run on 200 vac
stop all functions in the process (tool change,
coolants, ete.) The signal is transmitted to the ps==xxy
machine controller (BMDC) board where the Reaxcen
proper firmware is enabled to control the logic
circuitry on the AUF board. This logic circuitry
is used to control the electromechanical devices
in the system.
HOME Switches ~ A home switch is located on
each axis. When a home switch is activated, a
path is created to ground for the logic circuitry
‘on the AUF board.
Before changing any wires, ensure
personal safety by opening disconnect
installed in control enclosure door.