Professional Documents
Culture Documents
145kV Manual1 For CD
145kV Manual1 For CD
145kV Manual1 For CD
FOR
145kV 40kA GAS INSULATED SWITCHGEAR
IMPORTANT NOTICE
Please read this manual before attempting to install and operate this
equipment.
This manual and accompanying drawings should be considered a
permanent part of the equipment. They should be stored in a location
that is readily available for review and reference at all times.
145kV 40kA Gas Insulated Switchgear
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
improtant information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and serivce this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instructin manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-2-
145kV 40kA Gas Insulated Switchgear
CONTENT
SAFETY PRECAUTION
2. INSTALLATION OF GIS
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-3-
GIS GENERAL & TECHNICAL DATA
FOR
145kV 40kA GIS
IMPORTANT NOTICE
Before attempting to install and operate this equipment, please read and fully
understand all of thd system's SAFETY and Operating/Maintenance.
This manual and all accompanying drawings should be considered a permanent
part of the equipment. They should be stored in a location that is readily available
for review and reference at all times.
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
improtant information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and serivce this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instructin manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-5-
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
◆ DO NOT REMOVE the unit's shunt bar or grounding terminal. Doing so could
subject personnel to hazardus voltage that can shock, burn or cause death.
Before removing the unit's shunt bar or grounding terminal for mainternance or repairs
(conducted only. By authorized repair personnel), make sure that power to the unit's
main circuit has been switched OFF, and use a grounding wire or condenser.
After completing such maintenance and/or repair work, securely reinstall the unit's
shunt bar and grounding terminal before restoring power to the unit's main circuit.
◆ To prevent electric shock that could burn or otherwise injure personnel, DO NOT
ALLOW personnel to touch low- or high-voltage circuits while the GIS equipment is
being operated.
◆ Never use manual operating handle when power line(main circuit) is alive.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-6-
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
◆ DO NOT ENTER the GIS's room until you have confirmed that its interior inviron-
ment has ventilated, and contains at least 18% density of oxygen.
Personnel entering before confirming oxygen and ventilation levels could be overcome
by fumes that cause choking and suffocation.
◆ To prevent injuries resulting from falls, DO NOT ALLOW personnel to climb, sit on,
lean aginst, or otherwise mount the GIS equipment except when conducting official
equipment inspections by authorized personnel.
◆ Since 0.2 ~ 0.5 kg/㎠ (20 ~ 50kpa) SF 6 gas or dry air is filled in the gas tank and
the bushing during transportation, never open the stop valve before assembling.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-7-
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
◆ DO NOT TOUCH the GIS's heater directly with ungloved hands. Because the heater
operates at high temperatures, doing so could cause burns.
◆ To avoid accidental jnjuries. Do not begin equipment inspections until first confirming
that the GCB and all related equipment have been 1) turned OFF and 2) are fully
de-energized.
◆ When conducting inspections of the GIS unit, do not remove any of the unit's panels
and covers until first confirming that the unit's internal gas pressure has been fully
released. Loosening the unit's panels and covers while the unit is still pressurized
could cause injury to personnel resulting from contact with bolts and other parts that
were blown loose by releasing internal gas pressures.
◆ To prevent moisture seepage from water and other sources, KEEP all doors and
access panels on the GIS closed and securely fastend.
◆ To prevent damage to the surface of the unit's operating-mechanism box (as well as
moisture seepage that could result from such damage), DO NOT ALLOW personnel
to climb onto or lean against any portion of the operating-mechanism box.
◆ To prevent moisture within the equipment, leave the LCP's heater ON at all times.
◆ To assure proper gas pressure, DO NOT open/close valves when operating the GIS.
◆ To prevent gas leakage, DO NOT loosen any blots on the GIS or its piping. Panels
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-8-
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
on the GIS closed and access panels on the GIS closed and securely fastend.
◆ Operate the GIS only within the range of its rated gas pressures. If the GIS's gas
pressure drops below its rated level, contact your Hyundai's representative to check
for depleted gas supplies and/or system leaks.
◆ The operating oil and lubricant in the oil-gydraulic operating mechanism should be
used only designated brands.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
-9-
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
INDEX
PAGE
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 15 -
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
The gas insulated switchgear (GIS) is a substation unit comprising switchgear and
buses enclosed in a grounded metallic sheath and filled with pressurixed SF 6 gas.
This construction can minimize total substation size, improve safety and economy
and attain a high reliability and labor-saving maintenance using the merits of insulation
space reduction and simplicity.
Hyundai. The first, delivered GIS to SAMSUNG SEMI-CONDUCTOR CO. in 1989.
Since than many GIS units have been shipped for use in outdoor, indoor and
underground substation with favorable operation results.
Although the GIS has many excellent features as described below, some care should
be taken in practical applications to make the best use of these merits.
(4) Inspection
It is usually necessary to inspect and maintain the circuit breaker, when a
specified number of switching operations has been reached. In the case, the
inspection is usually done on the site without movement. If required, units can
be dismounted structurally for inspection and maintenance.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 17 -
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
4. GENERAL SPECIFICATION
4.1 GENERAL
This specification covers the technical features for the 145kV SF6 Gas Insulated
Switchgear (GIS) installed indoor and outdoor for 145kV Substation.
Unless otherwise specified in this specification, the equipments will be complied with
the latest version of the following standards.
- High voltage metal enclosed switchgear : IEC 60517
- High voltage alternating current circuit breaker : IEC 62271-100
- Alternating current disconnector and earthing switch : IEC 62271-102
- Voltage transformers : IEC 60044-2
- Current transformers : IEC 60044-1
- Specification and acceptance of new sulphur hexafluoride
: IEC 60376, 60376A
60376B
a) Maximum : +55℃
b) Minimum : -5 ℃
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 21 -
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
5. TECHNICAL SPECIFICATION
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 22 -
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 23 -
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
1) The LCC comprises the necessary control switch, gas alarm, indication for
operating circuit breakers, disconnectors and earthing switches as per each
relevant GIS bay and terminal strips for connection the remote.
2) Rated control voltage : 125
: 110 V dcV dc
3) Rated voltage for heating : 220 V ac
5.8 PAINTING
1) All surface of GIS enclosure will be throughly cleaned by sand blasting before
painting and coated with epona primer and followed by two further coats of high
quality paints on external surface.
2) The final color of painting on outer surface of metal parts of GIS and local control
panel : RAL 7035
3) Gas pipe and fittings for SF6 gas control system : Yellow color
4) Base, steel structure, platform : Hot-dip galvanized
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 24 -
145kV 40kA GIS/ GENERAL & TECHNICAL DATA
(1) Guaranteed leakage rate of SF 6 gas in each gas compartment is not more
than 1%(volume) per annum.
(2) The setting of SF 6 gas pressure by gas density switch as per each compart-
ment of GIS are as follows:
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 25 -
INSTALLATION MANUAL
FOR
145kV 40kA GIS
IMPORTANT NOTICE
Before attempting to install and operate this equipment, please read and fully
understand all of thd system's SAFETY and Operating/Maintenance.
This manual and all accompanying drawings should be considered a permanent
part of the equipment. They should be stored in a location that is readily available
for review and reference at all times.
145kV 40kA GIS/ INSTALLATION
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
improtant information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and serivce this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instructin manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 24 -
145kV 40kA GIS/ INSTALLATION
◆ DO NOT REMOVE the unit's shunt bar or grounding terminal. Doing so could
subject personnel to hazardus voltage that can shock, burn or cause death.
Before removing the unit's shunt bar or grounding terminal for mainternance or repairs
(conducted only. By authorized repair personnel), make sure that power to the unit's
main circuit has been switched OFF, and use a grounding wire or condenser.
After completing such maintenance and/or repair work, securely reinstall the unit's
shunt bar and grounding terminal before restoring power to the unit's main circuit.
◆ To prevent electric shock that could burn or otherwise injure personnel, DO NOT
ALLOW personnel to touch low- or high-voltage circuits while the GIS equipment is
being operated.
◆ Never use manual operating handle when power line(main circuit) is alive.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 25 -
145kV 40kA GIS/ INSTALLATION
◆ DO NOT ENTER the GIS's room until you have confirmed that its interior inviron-
ment has ventilated, and contains at least 18% density of oxygen.
Personnel entering before confirming oxygen and ventilation levels could be overcome
by fumes that cause choking and suffocation.
◆ To prevent injuries resulting from falls, DO NOT ALLOW personnel to climb, sit on,
lean aginst, or otherwise mount the GIS equipment except when conducting official
equipment inspections by authorized personnel.
◆ Since 0.2 ~ 0.5 kg/㎠ (20 ~ 50kpa) SF 6 gas or dry air is filled in the gas tank and
the bushing during transportation, never open the stop valve before assembling.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 26 -
145kV 40kA GIS/ INSTALLATION
◆ DO NOT TOUCH the GIS's heater directly with ungloved hands. Because the heater
operates at high temperatures, doing so could cause burns.
◆ To avoid accidental jnjuries. Do not begin equipment inspections until first confirming
that the GCB and all related equipment have been 1) turned OFF and 2) are fully
de-energized.
◆ When conducting inspections of the GIS unit, do not remove any of the unit's panels
and covers until first confirming that the unit's internal gas pressure has been fully
released. Loosening the unit's panels and covers while the unit is still pressurized
could cause injury to personnel resulting from contact with bolts and other parts that
were blown loose by releasing internal gas pressures.
◆ To prevent moisture seepage from water and other sources, KEEP all doors and
access panels on the GIS closed and securely fastend.
◆ To prevent damage to the surface of the unit's operating-mechanism box (as well as
moisture seepage that could result from such damage), DO NOT ALLOW personnel
to climb onto or lean against any portion of the operating-mechanism box.
◆ To prevent moisture within the equipment, leave the LCP's heater ON at all times.
◆ To assure proper gas pressure, DO NOT open/close valves when operating the GIS.
◆ To prevent gas leakage, DO NOT loosen any blots on the GIS or its piping. Panels
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 27 -
145kV 40kA GIS/ INSTALLATION
on the GIS closed and access panels on the GIS closed and securely fastend.
◆ Operate the GIS only within the range of its rated gas pressures. If the GIS's gas
pressure drops below its rated level, contact your Hyundai's representative to check
for depleted gas supplies and/or system leaks.
◆ The operating oil and lubricant in the oil-gydraulic operating mechanism should be
used only designated brands.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 28 -
145kV 40kA GIS/ INSTALLATION
INDEX
PAGE
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 34 -
145kV 40kA GIS/ INSTALLATION
Installation of the
5
Basic unit
Installation of the
6
Each unit
Measurement of
7
contact Resistance
Withstand High
24
voltage test for GIS
Detaching the VT
30
unit
Final Assembly of
25
Cable Head
Gas Piping
31
Exchanging of
26
Absorbent
Exchanging of
32
absorbent
Evacuation and Gas 1. Refer to the test planning about the work
27
Refilling details in the mark
Evacuation and
33
Gas refilling 2. Refer to this instructin about the work
Gas leakage test details in the mark
28
Gas leakage test 3. The work from No.19 to No.23 should be done
34
the same times as the number of the cable
Measurement of heads.
29
Moisture
Measurement of
35
Moisture
Repair painting
37
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 35 -
145kV 40kA GIS/ INSTALLATION
BASIC PLATE
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 36 -
145kV 40kA GIS/ INSTALLATION
(3) Checking horizontal level of the basic plate. Measure the Horizontal level of the
basic plate, and confirm that difference between maximum height and minimum
height is lower than 2mm, Record the result.
Measuring point should be the center of each bay, and record the measured
value, This value is used on deciding the datum height for installation.
2.2.1 Draw the center line of main buses and each bay on the foundation as datum
line. Draw it not to be extinguished.
About measure and position, refer to the foundation plan.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 37 -
145kV 40kA GIS/ INSTALLATION
Measure the height between the surface of the basic plate and the center of a bus bar
In this case, set from 0 to 5mm by considering the basic plate level and consult our
engineer.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 38 -
145kV 40kA GIS/ INSTALLATION
Adjust the center of each bay until fitting to the datum point drawn on the foundation.
When confirming for center on the GIS base, use a centering tool like the punch.
Weld the spots between GIS base and the basic plate.
Clean the welding parts and remove dust, oil and paints.
Protect the apparatus near the welding parts not to spoil them.
3.6 WELDING
Weld firmly liner, the basic plate and GIS base at arrow mark indicated parts in
following figure.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 39 -
145kV 40kA GIS/ INSTALLATION
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 40 -
145kV 40kA GIS/ INSTALLATION
Provide the specified protection measures against dust and humidity ( called protection
against dust and others, hereinafter ) for the main circuit connection work ( called
docking, hereinafter ) of the GIS installation and assembly works.
1) Clothes
The personnel directly engaged in docking must wear the following dust-
proof clothes. Those without the dust-proof clothes must not stand near
the docking place or within the area surrounded by the dust-proof wall.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 41 -
145kV 40kA GIS/ INSTALLATION
2) Wearing
When wearing dust-proof clothes.
Clean wearing place and confirm environmental condition.
It should be done the same control as docking, if control is impossible, provide
a dust-proof locker room near the docking place for the personnel to change
his dust-proof clothes. Keep clear inside of the room.
Remove the transportation cover from the docking part then coyer it
shown in figure.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 43 -
145kV 40kA GIS/ INSTALLATION
The protection against wind is provided to prevent the following foreign matter
from entering into the apparatus; dust blown up by a strong wind; chips created
in the work, and to also prevent the grease used in the assembly from sticking
onto the apparatus.
Therefore, when it is very windy or when a gust of wind is likely to occur, provide
the wind-proof wall made of prevention sheet or vinyl sheet, around the installation
place or the working place.
The wind-proof wall is similar to the overall dust-proof in the item 4.1.2 6)
As the preparation for sudden rain during the work, locate water-proof sheets,
ropes near the docking place to protect the docking section, parts and tools.
If the relative humidity around the docking place exceeds 80%, take some
countermeasure to reduce humidity during docking, for example, blow dry air.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 44 -
145kV 40kA GIS/ INSTALLATION
(1) Sprinkle the minimum quantity of water required to prevent dust over the
docking place and its surroundings, and clean the places every now and then.
(2) If there are things creating dust near the docking place, cover them with the
sheet, or sprinkle sufficient water over them to prevent dust from spreading.
(3) When wastes are created during docking, put them into a waste basket as
soon as possible.
(4) Always remove metal chips, detached paint layers and other foregn matter
with the vacuum cleaner, during the work.
(5) Do net carry out any work creating a lot of dust (grinding, drilling concrete
scraping, welding) in the dust-proof room.
If necessary, do it when docking is not done.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 45 -
145kV 40kA GIS/ INSTALLATION
Remove the transportation cover when docking is ready to start or when temporary
apparatus location and countermeasures against dust are ready.
It is necessary to minimixe the time during which the inside of the apparatus is
exposed to the open air (from the transportation cover removal to docking).
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 46 -
145kV 40kA GIS/ INSTALLATION
5.2.3 Pay attention to the following items during transportation cover removal.
(1) Remove detached paint layers, chips and dust by the vacuum cleaner when
taking the bolts nuts off the transportation cover.
(2) Use fingers to remove the O-ring from the insulation spacer groove.
Do not use a metal rod or other tools to remove it.
(3) Do not damage the gas sealing surfaces of the tank and insulation spacer,
after removing the transportation cover.
(4) Remove the protruding type transportation cover carefully and slowly so
that the conductor will not come out together.
As for removal of the both ends protruding type transportation cover, at
first, reove the bolts and nuts, slide the transportation cover downwards
as far as it goes by its own weight, then pull out the transportation cover
in a parallel direction with the conductor.
(5) After removing the transportation cover, confirm that there is no foreign matter
on the Insulator surface (flat type transportation cover), inside the tank, or on
the conductor surface (protruding type transportation cover).
If foreign matters are found, wipe them away with the clean bleached cotton
cloth having been soaken in Freon solvent.
Then, wrap that part of apparatus with a clean vinyl sheet to prevent the
foreign matter from entering inside the apparatus.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 47 -
145kV 40kA GIS/ INSTALLATION
(6) As for protruding type transportation cover removl, at first, hook the wire rope
at the protruding part of the transportation cover, (if necessary use the track
crane), before removing the bolts and nuts, then remove the transportation
cover slowly.
When the clearance is made bdtween the transportation cover and the tank,
hang the conductor with a clean vinyl rope before the conductor is separated
from the transportation cover. Then, remove the transportation cover.
Do not remove the hanging rope until docking.
(1) Preparation
As for the unit equipped with the studs, pull out two studs at sides (or near the
sides to use them as centering guides for the both units to be connected.)
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 48 -
145kV 40kA GIS/ INSTALLATION
(2) Stud Cleaning
Wipe the compound, paint layer out of the stud, with wastes.
FOLD UP INSIDE
FOLD UP INSIDE
about 20m
Clean the surface of the insulator with the clean vleached and folded up cloth
(called white cloth, hereinafter) having been soaked in Freon solvent so that no
foreign matter will remain.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 49 -
145kV 40kA GIS/ INSTALLATION
Wipe the contact grease (B8) out of the contact surface of the contact attached
on insulator and put a small quantity of new contact grease to form thin layer.
In this case, do not adhere to insulator.
Clean the surface of the conductor with shite cloth having been soaked in Freon
solvent. Do not wipe the contact grease of the contact surface of the conductor's
contact.
CLEANING OF O-RING
6.2.2 Methods
Apply the most suitable one of the following methods A and B depending on the
place.
(1) Method A
Put the rust preventive compound on the surface with fingers in some degree
that the color of flange is turned the color of compound.
In this case, using a brush is no problem, but do not leave fur of brush.
(2) Method B
Put a small amount of compound on the white cloth, then rub the surface with the
cloth until the compound spread and form a thin layer.
6.4 DOCKING
6.4.1 Preparation
Prepare for lifting of the GIS unit.
Attach chain blocks to the both sides of GIS base to prepare for pulling in the
GIS unit.
This work should be done before taking off the transportation cover.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 52 -
145kV 40kA GIS/ INSTALLATION
6.4.2 Docking
Pull in the GIS unit with centering both bay's bus bar center until fitting conductors
to contacts, by operating chain blocks.
As docking is done two parts together, centering should be done carefully.
Adjust the position of the GIS units until fitting center of conductor and entering
guide studs into the bolt hole of the flange smoothly, fit O-ring fixed into the
groove of the insulator and the tank flange.
Confirm that O-ring is not fallen off from the groove and any foreign matters are
not stayed in the tank.
In case of increasing the resister at if impossible, detach there and connect again
after checking conductors and contacts.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 53 -
145kV 40kA GIS/ INSTALLATION
6.4.4 Nut tightening
Adapt washers to studs except the guide stud after touching the flange of the tank
with the O-ring.
Tighten pair or nuts facing each other slowly.
Return guide studs and tighten nuts. Final tightening is done by the torque wrench
which has been set to the specified torque value.
Check tightness of the nuts of the opposite side by the torque wrench.
The relationship between the screw size and torque value is as follows.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 54 -
145kV 40kA GIS/ INSTALLATION
Draw the check mark after confirming the tightening thrque with red
felt pen one by one
6.4.5 Confirming of installation position and adjusting confirm the installation position
according to chapter 5, adjusting studs for a bellow.
Length of the bellow © should be kept within the limit written in the drawings for
site. Tighten A and B nuts after adjusting.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 55 -
145kV 40kA GIS/ INSTALLATION
7.1 GENERAL
Connect earthing wire in according to the following sequence.
7.1.2 Clean the contacting surface of the terminal with wire brush or sand paper to get
rid of paint, rust, foreign materials.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 100 -
145kV 40kA GIS/ INSTALLATION
8. PIPING WORK
8.1 GENERAL
It is recommended that the brazing, bending and jointing work should be carried out
by a small number of people who have had plenty of practice beforehand.
To practice brazing, make a test piece as shown in the following figure and look at
the longitudinal cutting and examine the brazed part.
Gas piping work should be done under the same working control which is applied
for the docking work. Working should be done carefully not to let dust or foreign
matter intrude into the tank of the apparatus through the piping.
Fabricate pipings and attach it according to the gas compartment system drawing.
Clean original copper pipe by menas of passing cloths dipped with freon solvent.
The clothes are bound to a piano wire.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 101 -
145kV 40kA GIS/ INSTALLATION
Calculate the lengths of copper pipe necessary from the piping route drawings
or by actual measurement and cut accordingly using a pipe cutter or cutting
machine. Cut the pipe into lengths slightly longer than the calculated actually
measured lengths.
Take care that the cutting plane is at right angle and that the pipe is not crushed
crushed while cutting.
Bend the pipes where necessary according to the piping route drawing or as
indicated by actual measurement using a pipe bender.
Check that there are no splits or folds and that the pipe has not been crushed
where it has been bent.
(1) When piping has been bent as necessary, fit temporarily and check carefully
the cutting and bending work. The trial fitting should be done with brazing joints
inserted.
(2) Cut off the excess pipe using the pipe cutter.
(3) Bevel the inner and outer diameter of both ends of the copper pipe.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 102 -
145kV 40kA GIS/ INSTALLATION
Assemble the copper pipe and brazing joint and turn the joint by hand to make
sure it does not be caught anywhere and that it turns smoothly.
8.2.6 Brazing
Torque kgf/cm
M 10 250
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 103 -
145kV 40kA GIS/ INSTALLATION
M 12 450
After tightening the nuts and bolts wipe away any anti-corrosive compound which
has been squeezed out around the flange with a cloth.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 104 -
145kV 40kA GIS/ INSTALLATION
9. PUTTING OF ABSORBENT
Put absorbent into the absorber after docking according to the following way. This
work should be made after docking and piping is over, but just before evacuation,
this work should be finished as soon as possible, and carry out under the same
working control as docking.
Parts to be put into absorbent are all absorber except for GCB and VT. Don't loosen
bolts of absorbers for GCB and VT. Because SF 6 gas is filled in it.
After docking, put absorbent into absorbers indicated mark in the following
figure.
Select the absorber needed putting in adsorbent in following the above examples
and referring to SF 6 gas piping System Diagram, consulting with our engineer.
Take off the snap ring with pryer and pull out the spacer and the absorbent bag.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 105 -
145kV 40kA GIS/ INSTALLATION
Throw away absorbent in the absorbent bag and pour in new absorbent to the degree
that the string of the absorber bag can be bind. Seal up the mouth of the exclusive
bag in which remained new absorbent exists, and preserve it in yhr private can, but
use absorbent early that exits in the opened bag.
Reassemble a sack of absorbent, a spacer and a snap ring into the absorbers.
Clean the absorber and insert a new O-ring, then put the rust protection compound
and attach it as it is safer.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 106 -
145kV 40kA GIS/ INSTALLATION
10.1 GENERAL
The SF6 gas filling is carried out after the GIS has been assembled depending on
the starte of the gas section.
For equipment transported containing N 2 gas at a pressure of 0.2~0.5kg/㎠.G.
For parts to be connectedat the site (The GIS itself and piping).
The gas filling is to be carried out after it gas been confirmed that the assembling
work and the work detailed below have been completed.
10.2.2 Check that all the nuts and bolts, the foundation bolts and adjustment bolts have
been securely tightened.
10.2.3 Check that the gas piping work has been completed.
The stop valves fitted to the GIS are all closed during transportation.
Check that they are closed.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 108 -
145kV 40kA GIS/ INSTALLATION
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 109 -
145kV 40kA GIS/ INSTALLATION
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 110 -
145kV 40kA GIS/ INSTALLATION
(1) Leak test method
1) Test all the tank and piping connections for leaks using the SF 6 gas detector.
2) The SF 6 gas detector detects freon gas so where a leak is detected smear
the spot with soapy water to confirm the leakage. Wipe away the soapy
water after configuration.
When there is a large amount of moisture mixed in the SF 6 gas, the dielectric
strength of the GIS decreases. To prevent this the moisture contact of the SF 6
gas is measured to check that it is below the control valve.
2) Remove the covers from the vacuum valves in each gas section being
measured and fit the hygrometer sensor unit to the vacuum pumping stop
valves.
4) Open the needle valve of the sensor unit just enouh to allow a little gas to
escape and wait for the meter to stabilize.
━━━━━━━━━━━━━━━━━━━━ ━━━━━━━━━━ ━━━━━━━━━━━━━━━━━━━━
- 111 -
145kV 40kA GIS/ INSTALLATION
5) After the meter has settled close the needle valve, take a reading of the
meter indication and calculate the moisture content.
6) After measurement, close the vacuum valve and remove the hydrometer
sensor unit.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 112 -
145kV 40kA GIS/ INSTALLATION
Check working for GIS installation, work item by work item, by using check sheet in
the form prescribed in this chapter.
Check the condition of the base and the base plate by using the check sheet in the
form of No. 2 check list.
Use one check sheet a substation.
Check appearance of parts by using the check sheet in the form of No.3.
Use one check a substation and check the number of parts by a invoice.
Check the condition of preparing work for docking by using the check sheet in the
form of No. 4, 5.
Use one check sheet a docking part.
Creat a series number in a blank of the right upper "connecting No." on the check
sheet to correspond the docking part with check sheet as one to one.
(1) Check the condition of docking parts by using the check sheet in the form of
No. 4, 5
(2) Use check sheet No. 4,5 at the docking part of single phase type bus.
(3) Creat a series number in the same way.
━━━━━━━━━━━━━━━━━━━━ ━━━━━━━━━━ ━━━━━━━━━━━━━━━━━━━━
- 113 -
145kV 40kA GIS/ INSTALLATION
Check the connecting condition of gas piping by using the check sheet in
the form of No. 9.
Use one check sheet a bay.
Check the connecting condition of wiring by using the check sheet in the
form of No. 10.
Use one check sheet a bay.
Check the condition of GIS by using the check sheet is the form of No. 11.
Use one check sheet a bay.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 114 -
OPERATION & MAINTENANCE
FOR
145kV 40kA CB
IMPORTANT NOTICE
Before attempting to install and operate this equipment, please read and fully
understand all of thd system's SAFETY and Operating/Maintenance.
This manual and all accompanying drawings should be considered a permanent
part of the equipment. They should be stored in a location that is readily available
for review and reference at all times.
145kV 40kA GlS/CB
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
important information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and service this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instruction manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 89 -
145kV 40kA GlS/CB
◆ DO NOT REMOVE the unit's shunt bar or grounding terminal. Doing so could
subject personnel to hazardous voltage that can shock, burn or cause death.
Before removing the unit's shunt bar or grounding terminal for maintenance or repairs
(conducted only. By authorized repair personnel), make sure that power to the unit's
main circuit has been switched OFF, and use a grounding wire or condenser.
After completing such maintenance and/or repair work, securely reinstall the unit's
shunt bar and grounding terminal before restoring power to the unit's main circuit.
◆ To prevent electric shock that could burn or otherwise injure personnel, DO NOT
ALLOW personnel to touch low- or high-voltage circuits while the GIS equipment is
being operated.
◆ Never use manual operating handle when power line(main circuit) is alive.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 90 -
145kV 40kA GlS/CB
◆ DO NOT ENTER the GIS's room until you have confirmed that its interior environ-
ment has ventilated, and contains at least 18% density of oxygen.
Personnel entering before confirming oxygen and ventilation levels could be overcome
by fumes that cause choking and suffocation.
◆ To prevent injuries resulting from falls, DO NOT ALLOW personnel to climb, sit on,
lean against, or otherwise mount the GIS equipment except when conducting official
equipment inspections by authorized personnel.
◆ Since 0.2 ~ 0.5 kg/㎠ (20 ~ 50kpa) SF 6 gas or dry air is filled in the gas tank and
the bushing during transportation, never open the stop valve before assembling.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 91 -
145kV 40kA GlS/CB
◆ DO NOT TOUCH the GIS's heater directly with ungloved hands. Because the heater
operates at high temperatures, doing so could cause burns.
◆ To avoid accidental injuries. Do not begin equipment inspections until first confirming
that the GCB and all related equipment have been 1) turned OFF and 2) are fully
de-energized.
◆ When conducting inspections of the GIS unit, do not remove any of the unit's panels
and covers until first confirming that the unit's internal gas pressure has been fully
released. Loosening the unit's panels and covers while the unit is still pressurized
could cause injury to personnel resulting from contact with bolts and other parts that
were blown loose by releasing internal gas pressures.
◆ To prevent moisture seepage from water and other sources, KEEP all doors and
access panels on the GIS closed and securely fastened.
◆ To prevent damage to the surface of the unit's operating-mechanism box (as well as
moisture seepage that could result from such damage), DO NOT ALLOW personnel
to climb onto or lean against any portion of the operating-mechanism box.
◆ To prevent moisture within the equipment, leave the LCP's heater ON at all times.
◆ To assure proper gas pressure, DO NOT open/close valves when operating the GIS.
◆ To prevent gas leakage, DO NOT loosen any blots on the GIS or its piping. Panels
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 92 -
145kV 40kA GlS/CB
on the GIS closed and access panels on the GIS closed and securely fastened.
◆ Operate the GIS only within the range of its rated gas pressures. If the GIS's gas
pressure drops below its rated level, contact your Hyundai's representative to check
for depleted gas supplies and/or system leaks.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 93 -
145kV 40kA GIS/CB
INDEX
PAGE
1. General ------------- 7
2. Ratings ------------- 8
3. Construction ------------- 9
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 99 -
145kV 40kA GIS/CB
1. GENERAL
The type 145SP-K1 gas circuit breaker is a high performance, large capacity
single pressure dead tank type gas circuit breaker.
This circuit breaker has improved voltage withstanding and breaking
characteristics, due to the utilization of the excellent dielectric and arc quenching
capability of SF6 (sulphur hexafluoride) gas.
The 145SP-K1 gas circuit breaker has following characteristics.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 100 -
145kV 40kA GIS/CB
2. RATINGS
Type 145SP-K1 gas circuit breaker is manufactured on IEC 62271-100 and the
ratings are as follows.
rated voltage
insulation
level Lightning impulse withstand 650kV peak
voltage
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 101 -
145kV 40kA GIS/CB
3. CONSTRUCTION
Outline and construction of type 145SP-K1 circuit breaker are illustrated in fig. 1.
This circuit breaker consists of 3 pole interrupter parts in single gas enclosure and
an operating mechanism as shown in Fig. 2.
- Inside the single gas enclosure, which is grounded, 3-pole interrupt parts are
supported by insulation support (3) and current path is formed by both side
connecting conductor (14).
- Each interrupter part consists of fixed contact part (7,8), moving contact
part (9), puffer cylinder (12) and thermal chamber (11) 3-pole moving contacts
are directly connected to insulation rod (4) through a cross-head (13) and
simultaneously driven by the one motor-spring mechanism (15).
- Fixed contact part consists of fixed main contact (finger type ) (8) and fixed
arc contact (13)
Moving contact part contains moving main contact (9) and moving arc contact.
- Absorbent (2) to keep SF 6 gas pure is located at low part of the gas
enclosure.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 102 -
145kV 40kA GIS/CB
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 103 -
145kV 40kA GIS/CB
DESCRIPTION
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 104 -
145kV 40kA GIS/CB
DESCRIPTION
A. CLOSED POSITION
B. OPENING : MAIN CONTACT IN OPEN POSITION
C. OPENING : ARCING CONTACT IN OPEN POSITION
D. OPEN POSITION
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 105 -
145kV 40kA GIS/CB
This cause the SF6 gas to be forced in the direction opposite to the movement
of the moving contact components, through the valve (8) into the thermal
expansion chamber (6) and through the insulating nozzle (1), thus extinguishes
the arc.
With large short-circuit currents the extinguishing gas between the fixed arcing
contact (2) and the moving arcing contact (4) is heated by the arc's energy and
filled into thermal expansion chamber (6) at high pressure.
When the current passes through zero, the gas flows back from the thermal
expansion chamber (6) through the insulating nozzle (1) and extinguisher the arc.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 106 -
145kV 40kA GIS/CB
DESCRIPTION
1. CLOSING SPRING 10. OPENING LATCH
2. MOTOR 11. OPENING ARM
3. GEARING SYSTEM 12. OPENING SPRING
4. CRANK SHAFT 13. AUXILIARY SWITCH
5. DISC CAM 14. DAMPER
6. RATCHET SYSTEM
7. CLOSING LATCH
8. CLOSING COIL
9. TRIP COIL
- Controlling, indicating instruments are arranged for easy visibility at the front
of operating mechanism box.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 107 -
145kV 40kA GIS/CB
- Manual operation with the manual operating lever should be done according
to the guide described in " caution label".
"Caution"
You should never use the manual operating lever in the motor-spring operating
mechanism except the case of emergency, for example DC control voltage shut
down.
- Procedures
(1) Confirm that control power source is interrupted, before use of the manual
operating button.
(2) Confirm the SF6 gas is normal.
(3) Push the manual operating button.
GCB executes the opening operation.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 108 -
145kV 40kA GIS/CB
4.1. SCOPE
The instruction book is applied to the 145kV 40kA 2000/1250A GIS.
The information provides including general construction detail and operation
/maintenance structure.
4.2. Description
The mechanism is a spring-operated mechanism where the interrupters are opened
and closed solely by helical coil spring.
The mechanism stores operating energy in two sets of springs assemblies.
( the closing spring and opening spring. )
The closing spring are charged under normal conditions using a charging motor and gear
box assembly, a nd it can be manually charged if necessary.
During the closing operation, the mechanism moves to the CLOSED position and
simultaneously charges the opening spring using the stored energy of the closing
spring.
The mechanism contains enough stored energy in the CLOSED position with the closing
and opening spring charged to perform an open-close-open(O-C-O) operation without
re-charging.
The mechanism is available for use with all common operating voltages.
Acceptable fluctuation in the operating voltages are per ANSI standard .
The standard CB is supplied with the two trip coil is capable of independently
tripping the CB.
The mechanism is equipped with the Heater for anti-condensation of humidity.
The mechanism contains the following major components.(Fig 5.)
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 120 -
145kV 40kA GIS/CB
The circuit breaker is operated by a opening spring (11) and a closing spring (6).
Both coil spring colums are located in the main frame, on the top of CB.
The closing spring charged by means of motor (8)with an adapted ratchet system(14)
or by manual handle.
Rotation with manual handle (10) of gear box in the clockwise direction charges the
closing spring.
The rotation should be stopped after a good audible crank noise from the drive.
(This noise caused by the closing bit, which hooked up at closing latch(4).
The further rotation could damage the drive. At releasing of closing latch (4)
the charged closing spring (6) rotate the disc cam (3) counterclockwise, turn the CB
driving axle (12) in clockwise closing of CB and charges the opening spring (11)
in the same time.
At releasing of opening latch (1) the charged opening spring (11) rotate the CB
driving axle(12) counter clockwise (opening of CB). The releasing of latches (1,4)
is possible by remote control electrically at control room or by manual directly at local.
The auxiliary switches position indicator and counter are driven by push-pull bars.
The driving lever is fixed directly to the CB driving axle end.
After completed charging process , the limit switch (15) (micro switch), via magnetic
contact stops the motor operation. The control disc cam are mounted onto crank shaft end.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 121 -
145kV 40kA GIS/CB
After completed closing process , the limit switch (15) starts the motor operation, and
charges the closing spring (6) again. Manual handle (10) operation is possible after
opening the locked door onto drive cover. Likewise after opening this door the Operation
of drive by push button.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 123 -
145kV 40kA GIS/CB
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 125 -
145kV 40kA GIS/CB
Caution : -The manual charging tools can be used only for charging of the
closing spring and cannot be used for manual discharging of it,
since the free wheel (which is placed in worm wheel) acts in
charging direction only.
- After complete of manual charging, Check whether the limit switch
is operated properly.
- Tripping circuits
Drive is equipped with two independent tripping coils. These can be operated
manually by push button or by electrically from local cabinet respectively
remote from control room. When the breaker is in open position auxiliary
contacts interrupt the circuits of tripping coils.
- Closing circuit
The closing coil can be operated manually by push-button or by electrically
from local control cabinet resp. remote from control room.
When the breaker is closed, the auxiliary contact interrupts the circuit of closing
coil.
- Interlocking at tripping
The tripping coils can be energized across auxiliary contacts only when
breaker is closed.
When gas density is too low gas density monitor interrupt the energizing of
interlocking relays, which open the circuits of tripping coils.
- Interlocking at closing
The closing coil can be energized across auxiliary contacts only when breaker
is opened.
Anti pumping relay cancels the persisting closing signal after successful
completion of closing operation.
When gas density is too low gas density monitor interrupt energizing of
interlocking relay, which open the circuit of closing coil.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 128 -
145kV 40kA GIS/CB
6. Mechanism Lubrication
Table 1.
Lubrication schedule for Mechanism
Item Frequency Grease
Bevel gears of Gear box 3 years or 1000 operation Silicon grease 55M
Worm wheel
Ratchet system 3 years or 1000 operation Silicon grease 55M
Outer surface of spring guide 3 years or 1000 operation Silicon grease 55M
Component of opening latch 3 years or 1000 operation Silicon grease 55M
Component of closing latch 3 years or 1000 operation Silicon grease 55M
Disc cam 3 years or 1000 operation Silicon grease 55M
*Caution
- Ensure
: that the closing/opening spring is discharged
- Ensure the breaker is in the open position
- Ensure the all cotrol power is disconnected
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 129 -
145kV 40kA GIS/CB
*Caution : The incorrect adjustment of gap causes the malfunction of
opening/closing operation
- After replace the limit S/W, In order to be charged by the closing spring at
minimum DC control voltage, the resetting work for limit s/w & control cam
should be done very exactly and checked carefully.
After finish the setting work, take the adhesive loctite one by one on the
wrench bolt(M6).
- If the limit s/w is stopped too early, the spring is not charged in the
ordinary position.
If the limit s/w is stopped too lately, the closing latch and closing bit will be
damaged sereously.
Table 3.
Periodical Inspection
Routine
Classification
Inspection Tempory
(Patrollin Ordinary Detailed Inspection
Description Inspection Inspection
Inspection)
1) In case of any
abnormality
2) After 10 times of
Every 6 years at breaking at rated
Every 3 years or the initial stage, interruping current.
Periodic Interval 1000 times of no- and afterward carring 3) After 1000 times
Daily
or switching times loaad switching out refering to the of breaking at rated
operation. initial stage inspection normal current.
results. 4) After 2000 times of
no-load or small
current switching
operations.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 131 -
145kV 40kA GIS/CB
Table 4.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 132 -
145kV 40kA GIS/CB
Table 5.
Inspection item and
No. kind of Trouble Causes
Countermeasurements
Manual closing 2-1) Poor adjustment of gap Adjust the gaps as clause 7-1) or
2
is impossible or mechanical abnormality replace the latch part
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 133 -
OPERATION & MAINTENANCE
FOR
145kV 40kA ES/DS
IMPORTANT NOTICE
Before attempting to install and operate this equipment, please read and fully
understand all of thd system's SAFETY and Operating/Maintenance.
This manual and all accompanying drawings should be considered a permanent
part of the equipment. They should be stored in a location that is readily available
for review and reference at all times.
145kV 40kA GIS DS/ES
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
important information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and service this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instruction manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 120 -
145kV 40kA GIS DS/ES
◆ DO NOT REMOVE the unit's shunt bar or grounding terminal. Doing so could
subject personnel to hazardous voltage that can shock, burn or cause death.
Before removing the unit's shunt bar or grounding terminal for maintenance or repairs
(conducted only. By authorized repair personnel), make sure that power to the unit's
main circuit has been switched OFF, and use a grounding wire or condenser.
After completing such maintenance and/or repair work, securely reinstall the unit's
shunt bar and grounding terminal before restoring power to the unit's main circuit.
◆ To prevent electric shock that could burn or otherwise injure personnel, DO NOT
ALLOW personnel to touch low- or high-voltage circuits while the GIS equipment is
being operated.
◆ Never use manual operating handle when power line(main circuit) is alive.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 121 -
145kV 40kA GIS DS/ES
◆ DO NOT ENTER the GIS's room until you have confirmed that its interior environ-
ment has ventilated, and contains at least 18% density of oxygen.
Personnel entering before confirming oxygen and ventilation levels could be overcome
by fumes that cause choking and suffocation.
◆ To prevent injuries resulting from falls, DO NOT ALLOW personnel to climb, sit on,
lean against, or otherwise mount the GIS equipment except when conducting official
equipment inspections by authorized personnel.
◆ Since 0.2 ~ 0.5 kg/㎠ (20 ~ 50kpa) SF 6 gas or dry air is filled in the gas tank and
the bushing during transportation, never open the stop valve before assembling.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 122 -
145kV 40kA GIS DS/ES
◆ DO NOT TOUCH the GIS's heater directly with ungloved hands. Because the heater
operates at high temperatures, doing so could cause burns.
◆ To avoid accidental injuries. Do not begin equipment inspections until first confirming
that the GCB and all related equipment have been 1) turned OFF and 2) are fully
de-energized.
◆ When conducting inspections of the GIS unit, do not remove any of the unit's panels
and covers until first confirming that the unit's internal gas pressure has been fully
released. Loosening the unit's panels and covers while the unit is still pressurized
could cause injury to personnel resulting from contact with bolts and other parts that
were blown loose by releasing internal gas pressures.
◆ To prevent moisture seepage from water and other sources, KEEP all doors and
access panels on the GIS closed and securely fastened.
◆ To prevent damage to the surface of the unit's operating-mechanism box (as well as
moisture seepage that could result from such damage), DO NOT ALLOW personnel
to climb onto or lean against any portion of the operating-mechanism box.
◆ To prevent moisture within the equipment, leave the LCP's heater ON at all times.
◆ To assure proper gas pressure, DO NOT open/close valves when operating the GIS.
◆ To prevent gas leakage, DO NOT loosen any blots on the GIS or its piping. Panels
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 123 -
145kV 40kA GIS DS/ES
on the GIS closed and access panels on the GIS closed and securely fastened.
◆ Operate the GIS only within the range of its rated gas pressures. If the GIS's gas
pressure drops below its rated level, contact your Hyundai's representative to check
for depleted gas supplies and/or system leaks.
◆ The operating oil and lubricant in the oil-hydraulic operating mechanism should be
used only designated brands.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 124 -
145kV 40kA GIS DS/ES
INDEX
PAGE
1. General ------------- 7
2. Ratings ------------- 7
3. Construction ------------- 9
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 130 -
145kV 40kA GIS DS/ES
1. GENERAL
HHI's 3-position switch and earthing switch has three isolating chambers or
one set filled with 4.0 bar SF 6 gas and one driven operator.
These equipments are operated by means of motor driving or motor charged-spring
operating mechanism.
2. RATINGS
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 131 -
145kV 40kA GIS DS/ES
TABLE 2. RATINGS OF LINE EARTHING SWITCH
1. Type-form 145SP-LES2
2. Rated frequency, Hz 60Hz
3. Rated short-time current , kA rms 40kA 3sec
4. Rated peak withstand current, kA peak 104kA
Short circuit current making
5. 104kA
capability, kA peak
Power-frequency test voltage,
6. 275 kV rms
1 min, kV rms
Lightning impulse withstand voltage,
7. 650kV peak
1.2 x 50μ sec, kV peak
8. partial discharge level Below 10 pC at 92kV
9. Type of operating mechanism Motor Spring
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 132 -
145kV 40kA GIS DS/ES
3. CONSTRUCTION
Fig 1. 145SP-3PS1
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 133 -
145kV 40kA GIS DS/ES
Fig 2. 145SP-3PS2
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 134 -
145kV 40kA GIS DS/ES
3.2 LINE EARTHING SWITCH (TYPE 145 SP-LES2)
Internal construction
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 135 -
145kV 40kA GIS DS/ES
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 136 -
145kV 40kA GIS DS/ES
Fig. 4 show the construction and moving principle of the driving unit.
This unit is motor operation type.
The geared-motor(1) rotates the geneva wheel(8), which is
operated by sprocket chain.
At the same time, main shaft is rotated by geneva gear(7).
3-position contact is inserted to ES fixed contact or DS fixed
contact, and motor(1) is not rotated when limit switch(9) is operated.
Driving unit also contains auxiliary switch(12), 3-position indicator,
DS counter, ES counter and terminal jack(18).
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 137 -
145kV 40kA GIS DS/ES
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 138 -
145kV 40kA GIS DS/ES
The motor (1), which is mounted on the driving unit, rotates the gear (2) and charges
the snap spring (3) when the snap spring is charged to over the center line, the snap
spring is being released and so the released energy of snap spring moves the lever
(4).
The rotating energy of converted to linear operation by guide with cross head and
moves the moving contacts of each phase simultaneously through insulation rod conn-
ected to the cross head of main switch.
Driving unit also contains auxiliary switch (10), terminal block, on-off indicator(8)
and counter(9).
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 139 -
145kV 40kA GIS DS/ES
For the disconnecting switch and earthing switch, finely long intervals of mainten-
ances might be possible because of it's simple and sealed off construction.
6.1 STANDARD
6.2.1 In case of being unsealed-off and inspecting, confirm that the disconnecting
switch and earthing switch are disconnected with all power source and gas is
not remaining in the enclosure.
6.2.3 In case of the lack of spare parts before inspection inform to HHI.
6.2.4 Before inspection, confirm the number and kind of required parts.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 140 -
145kV 40kA GIS DS/ES
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 141 -
TABLE 3. MAINTENANCE AND INSPECTION STANDARD
9 Measurement of the Connect the moisture meter to Less than 1000 PPM If measured value
moisture contents the SF6 gas filling and exhausting (V01) exceeds the controlled
pipe and measure the moisture value, replace the
- - ○
content in SF6 gas absorbent under the
recommendation of
special inspection
10 Lubrication Lubricate the following points by No exhaustion of Put grease on
the optional demand grease appropriate point
Moving parts of the - ○ ○
driving unit
55M Link of auxiliary switch
grease and ON-OFF indicator
Pins of the connecting - ○ ○
parts
TABLE 4. PROCEDURES AND RECOMMENDATIONS FOR INSPECTION
2 ON-OFF indicator
5 Interlocking coil
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 173-
145kV 40kA GIS DS/ES
2 ON-OFF indicator
5 Interlocking coil
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 174-
OPERATION & MAINTENANCE
FOR
POTENTIAL TRANSFORMER
IMPORTANT NOTICE
Before attempting to install and operate this equipment, please read and fully
understand all of thd system's SAFETY and Operating/Maintenance.
This manual and all accompanying drawings should be considered a permanent
part of the equipment. They should be stored in a location that is readily available
for review and reference at all times.
145kV 40kA Gas Insulated Switchgear
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
important information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and service this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instruction manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 156 -
145kV 40kA Gas Insulated Switchgear
◆ DO NOT REMOVE the unit's shunt bar or grounding terminal. Doing so could
subject personnel to hazardous voltage that can shock, burn or cause death.
Before removing the unit's shunt bar or grounding terminal for maintenance or repairs
(conducted only. By authorized repair personnel), make sure that power to the unit's
main circuit has been switched OFF, and use a grounding wire or condenser.
After completing such maintenance and/or repair work, securely reinstall the unit's
shunt bar and grounding terminal before restoring power to the unit's main circuit.
◆ To prevent electric shock that could burn or otherwise injure personnel, DO NOT
ALLOW personnel to touch low- or high-voltage circuits while the GIS equipment is
being operated.
◆ Never use manual operating handle when power line(main circuit) is alive.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 157 -
145kV 40kA Gas Insulated Switchgear
◆ DO NOT ENTER the GIS's room until you have confirmed that its interior environ-
ment has ventilated, and contains at least 18% density of oxygen.
Personnel entering before confirming oxygen and ventilation levels could be overcome
by fumes that cause choking and suffocation.
◆ To prevent injuries resulting from falls, DO NOT ALLOW personnel to climb, sit on,
lean against, or otherwise mount the GIS equipment except when conducting official
equipment inspections by authorized personnel.
◆ Since 0.2 ~ 0.5 kg/㎠ (20 ~ 50kpa) SF 6 gas or dry air is filled in the gas tank and
the bushing during transportation, never open the stop valve before assembling.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 158 -
145kV 40kA Gas Insulated Switchgear
◆ DO NOT TOUCH the GIS's heater directly with ungloved hands. Because the heater
operates at high temperatures, doing so could cause burns.
◆ To avoid accidental injuries. Do not begin equipment inspections until first confirming
that the GCB and all related equipment have been 1) turned OFF and 2) are fully
de-energized.
◆ When conducting inspections of the GIS unit, do not remove any of the unit's panels
and covers until first confirming that the unit's internal gas pressure has been fully
released. Loosening the unit's panels and covers while the unit is still pressurized
could cause injury to personnel resulting from contact with bolts and other parts that
were blown loose by releasing internal gas pressures.
◆ To prevent moisture seepage from water and other sources, KEEP all doors and
access panels on the GIS closed and securely fastened.
◆ To prevent damage to the surface of the unit's operating-mechanism box (as well as
moisture seepage that could result from such damage), DO NOT ALLOW personnel
to climb onto or lean against any portion of the operating-mechanism box.
◆ To prevent moisture within the equipment, leave the LCP's heater ON at all times.
◆ To assure proper gas pressure, DO NOT open/close valves when operating the GIS.
◆ To prevent gas leakage, DO NOT loosen any blots on the GIS or its piping. Panels
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 159 -
145kV 40kA Gas Insulated Switchgear
on the GIS closed and access panels on the GIS closed and securely fastened.
◆ Operate the GIS only within the range of its rated gas pressures. If the GIS's gas
pressure drops below its rated level, contact your Hyundai's representative to check
for depleted gas supplies and/or system leaks.
◆ The operating oil and lubricant in the oil-hydraulic operating mechanism should be
used only designated brands.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 160 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 166 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 167 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 168 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 169 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 170 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 171 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 172 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 173 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 174 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 175 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 176 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 177 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 178 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 179 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 180 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 181 -
145kV 40kA Gas Insulated Switchgear
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 182 -
OPERATION & MAINTENANCE
FOR
CURRENT TRANSFORMER
IMPORTANT NOTICE
Before attempting to install and operate this equipment, please read and fully
understand all of thd system's SAFETY and Operating/Maintenance.
This manual and all accompanying drawings should be considered a permanent
part of the equipment. They should be stored in a location that is readily available
for review and reference at all times.
145kV 40kA GIS/ CT
SAFETY PRECAUTION
IMPORTANT MESSAGES
◆ Before attempting to install and operate this equipment, read this manual carefully to obtain
important information regarding safety, handling, installation and maintenance procedures.
◆ Signal words such as DANGER, WARNING, CAUTION, NOTICE and Safety instruction.
◆ Such words are used to alert the reader that sections so marked contain important safety
information that must be carefully reviewed to assure safe and efficient inspection of this
equipment.
◆ Only qualified personnel are authorized to install, inspect, operate and service this
equipment according to all applicable codes and established safety practices.
◆ The manual is written for a qualified person or a person who has knowledge of the GIS.
When handling the equipment, please read the manual carefully and understand the
contents and follow the instruction of the qualified person.
◆ A qualified person must :
(1) Carefully read this entire instruction manual.
(2) Be skilled in the installation, construction or operation of the equipment and be aware
of the hazards involved.
(3) Be trained and authorized to safety energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
(4) Be trained and authorized to perform the service, maintenance or repair of this
equipment.
(5) Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, nonflammable clothing, etc., in accordance with
established practices.
(6) Be trained in rendering first aid.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 179 -
145kV 40kA GIS/ CT
◆ DO NOT REMOVE the unit's shunt bar or grounding terminal. Doing so could
subject personnel to hazardous voltage that can shock, burn or cause death.
Before removing the unit's shunt bar or grounding terminal for maintenance or repairs
(conducted only. By authorized repair personnel), make sure that power to the unit's
main circuit has been switched OFF, and use a grounding wire or condenser.
After completing such maintenance and/or repair work, securely reinstall the unit's
shunt bar and grounding terminal before restoring power to the unit's main circuit.
◆ To prevent electric shock that could burn or otherwise injure personnel, DO NOT
ALLOW personnel to touch low- or high-voltage circuits while the GIS equipment is
being operated.
◆ Never use manual operating handle when power line(main circuit) is alive.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 180 -
145kV 40kA GIS/ CT
◆ DO NOT ENTER the GIS's room until you have confirmed that its interior environ-
ment has ventilated, and contains at least 18% density of oxygen.
Personnel entering before confirming oxygen and ventilation levels could be overcome
by fumes that cause choking and suffocation.
◆ To prevent injuries resulting from falls, DO NOT ALLOW personnel to climb, sit on,
lean against, or otherwise mount the GIS equipment except when conducting official
equipment inspections by authorized personnel.
◆ Since 0.2 ~ 0.5 kg/㎠ (20 ~ 50kpa) SF 6 gas or dry air is filled in the gas tank and
the bushing during transportation, never open the stop valve before assembling.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 181 -
145kV 40kA GIS/ CT
◆ DO NOT TOUCH the GIS's heater directly with ungloved hands. Because the heater
operates at high temperatures, doing so could cause burns.
◆ To avoid accidental injuries. Do not begin equipment inspections until first confirming
that the GCB and all related equipment have been 1) turned OFF and 2) are fully
de-energized.
◆ When conducting inspections of the GIS unit, do not remove any of the unit's panels
and covers until first confirming that the unit's internal gas pressure has been fully
released. Loosening the unit's panels and covers while the unit is still pressurized
could cause injury to personnel resulting from contact with bolts and other parts that
were blown loose by releasing internal gas pressures.
◆ To prevent moisture seepage from water and other sources, KEEP all doors and
access panels on the GIS closed and securely fastened.
◆ To prevent damage to the surface of the unit's operating-mechanism box (as well as
moisture seepage that could result from such damage), DO NOT ALLOW personnel
to climb onto or lean against any portion of the operating-mechanism box.
◆ To prevent moisture within the equipment, leave the LCP's heater ON at all times.
◆ To assure proper gas pressure, DO NOT open/close valves when operating the GIS.
◆ To prevent gas leakage, DO NOT loosen any blots on the GIS or its piping. Panels
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 182 -
145kV 40kA GIS/ CT
on the GIS closed and access panels on the GIS closed and securely fastened.
◆ Operate the GIS only within the range of its rated gas pressures. If the GIS's gas
pressure drops below its rated level, contact your Hyundai's representative to check
for depleted gas supplies and/or system leaks.
◆ The operating oil and lubricant in the oil-hydraulic operating mechanism should be
used only designated brands.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 183 -
145kV 40kA GIS/ CT
INDEX
PAGE
1. General ------------------------ 7
2. Construction ------------------------ 7
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 189 -
145kV 40kA GIS/ CT
1. GENERAL
2. CONSTRUCTION
The terminals of the CT are marked P1, P2, etc. for the primary side and
S1, S2, etc. for the secondary terminals as shown Fig. 2.
Terminals that have the same numbering subscripts have the same
instantaneous polarity, as for example, terminals P1 and S1, or P2 and S2.
Connect CT leads to the corresponding terminals of outlet box.
Following cautions must be observed in connection and in service.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 190 -
145kV 40kA GIS/ CT
(1) Insulate all leads so that they will not in contact with any other leads or ground
parts.
(2) Ground one side of the secondary circuit unless doing so will interfere with the
proper operation of instruments.
(4) The secondary terminals must be closed through a burden or by the short-
circuiting lead.
Fig. 1 shows the internal construction of metal tank (1) with the arrangements of
current transformers (3).
Current transformers are mounted on the supporting plated (8) and the center of
current transformer.
Secondary leads of current transformer carried out through the terminal box(7) to
the local control panel.
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 191 -
145kV 40kA GIS/ CT
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 192 -
145kV 40kA GIS/ CT
━━━━━━━━━━━━━━━━━━━━
━━━━━━━━━━
━━━━━━━━━━━━━━━━━━━━
- 193 -