INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 1 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
PLACE OF INSPECTION:
Mr. Muhammad Anas Bajwa - API Inspector
ATTENDEES:
OGDCL Qadir Pur Gas Field Mr. Nasir – BV NDT Lead
Date: 19-OCT-2023
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 1 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 2 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Disclaimer: This report is truly based on the actual findings observed at the place and time of inspection. This report does not apply any type
of warranty against the above listed inspected item/s, neither it is eligible for court or legal purpose and the owner of the inspected item/s is strictly
bound to practice its contractual and regulatory responsibilities concerned with the integrity and safety of the operation of equipment/s and
surroundings. TÜV Rheinland Arabia LLC and its staff shall not be accountable in any case for any damage, loss or incident caused by the
inspected item/s.
Contents
1 INSPECTION SUMMARY: ................................................................................................................. 4
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 2 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 3 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
INSPECTION SUMMARY
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 3 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 4 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
1 INSPECTION SUMMARY:
External and internal inspections, were conducted on the Filter Coalescer FC-9704, situated at
OGDCL Qadir Pur Field. During inspection time no major abnormalities observed.
CHIP NGAI
Manufacturer ENGINEERING Construction Code ASME Sec Viii Div. 1
WORKS
Year of Built 2002 Name of Process Natural Gas
1. SCOPE OF INSPECTION:
Atmospheric Corrosion
CO2
Wet H2S
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 4 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 5 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
3 REFERENCE DOCUMENTS:
API-510 Pressure Vessel Inspection Code: In-service Inspection, Rating, Repair, and
Alteration
Saddle supports were found to be in satisfactory condition, and no major anomalies were
observed.
Crevice corrosion was observed on the saddle support insulation during the inspection.
The visual condition of all nozzle weld joints was found to be satisfactory, but rust was
Vessel shells, dish ends, and welds were inspected for evidence of dents and bulges, and
The vessel was found to be free of any major cuts and gouges during the visual
inspection.
During the inspection, insulation was found to be detached on the bottom dish end.
The overall condition of the shells and both dishes was found to be satisfactory.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 5 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 6 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
5 INTERNAL INSPECTION:
The maximum pitting observed was at a depth of 2-4 mm, with additional smaller pitting
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Severe uniform corrosion and rusting were observed on the inside surface of the shell
and bottom.
6 RECOMMENDATION/REPAIR:
External corrosion on the bottom dish end and its support needs to be removed, and the
proper paint coating should be applied after the corrosion is removed.
It is recommended to promptly repair and reattach the detached insulation on the bottom
dish end to ensure proper insulation and maintain the equipment's efficiency and safety.
SS inlet distributer, retaining grating, tie rods, stand pips, tube plate, demister paid, old
filters, and vortex breaker was found satisfactory.
The inside surface of the bottom dish end needs to be inspected in the next turnaround
interval.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 6 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 7 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
7 CONCLUSIONS:
Based on the results of visual inspection and the overall assessment of the pressure vessel, it is
concluded that Filter Coalescer FC-9004 is safe to operate at the current operating parameters until
the next recommended inspection interval.
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
8 ANNEXE:
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 7 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 8 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Annexure A
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 8 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 9 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
8.1 Annexure A – VISUAL INSPECTION FINDINGS
SR.NO. REFERENCE PHOTOGRAPHS OBSERVATIONS AND RECOMMENDATIONS
Observation:
1
Recommendation:
N/A
Observation:
N/A
Observation:
During the inspection, insulation was found
3
Recommendation:
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 9 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 10 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Observation:
The maximum pitting observed was at a depth
of 2-4 mm, with additional smaller pitting
present at the bottom.
4
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Recommendation:
The pitted area needs to be repaired using
Balzona as per the specified procedure to be
followed.
Observation:
Product deposit and uniform corrosion were
observed on the bottom surface.
5 Recommendation:
It need to be clean.
Observation:
The condition of old filters was found
satisfactory during inspection time.
6
Recommendation:
N/A
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 10 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 11 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Observation:
SS inlet distributer was found with out sign of
7 cracking during inspection time.
Recommendation:
N/A
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Observation:
Demister pad found satisfactory during
8 inspection time.
Recommendation:
N/A
Observation:
Insulation was found satisfactory during
9 inspection time.
Recommendation:
N/A
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 11 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0452 Rev: 00 SHEET: Page 12 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Observation:
Minor crack was observed on the concrete
10 foundation during inspection time.
Recommendation:
It need to be repair.
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Observation:
Grounding connection was found intact.
Resistance reading was not shown.
11
Recommendation:
Resistance read shall be checked annually and
need to be written on site.
Observation:
The rust was observed on the manway cover
12 plate.
Recommendation:
It need to be clean and apply the paint.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 12 of 12