INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 1 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
PLACE OF INSPECTION:
Mr. Muhammad Anas Bajwa - API Inspector
ATTENDEES:
OGDCL Qadir Pur Gas Field Mr. Nasir – BV NDT Lead
Date: 23-OCT-2023
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 1 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 2 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Disclaimer: This report is truly based on the actual findings observed at the place and time of inspection. This report does not apply any type
of warranty against the above listed inspected item/s, neither it is eligible for court or legal purpose and the owner of the inspected item/s is strictly
bound to practice its contractual and regulatory responsibilities concerned with the integrity and safety of the operation of equipment/s and
surroundings. TÜV Rheinland Arabia LLC and its staff shall not be accountable in any case for any damage, loss or incident caused by the
inspected item/s.
Contents
1 INSPECTION SUMMARY: ................................................................................................................. 4
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 2 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 3 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
INSPECTION SUMMARY
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 3 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 4 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
1 INSPECTION SUMMARY:
Only visual External and internal inspections, were conducted on the Regenerator Gas Scrubber
V-9209, situated at OGDCL Qadir Pur Field. During inspection time no major abnormalities
observed.
1. SCOPE OF INSPECTION:
Atmospheric Corrosion
CO2
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 4 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 5 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Wet H2S
Amin Corrosion
3 REFERENCE DOCUMENTS:
API-510 Pressure Vessel Inspection Code: In-service Inspection, Rating, Repair, and
Alteration
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
External protective coatings were found to be damaged on the flange nozzle and at
Saddle supports were found to be in satisfactory condition, and no major anomalies were
observed.
The visual condition of all nozzle weld joints was found to be satisfactory.
Vessel shells, dish ends, and welds were inspected for evidence of dents and bulges, and
The vessel was found to be free of any major cuts and gouges during the visual
inspection.
The overall condition of the shells and both dishes was found to be satisfactory.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 5 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 6 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
5 INTERNAL INSPECTION:
Internal condition of shell and bottom was found satisfactory.
No corrosion and rusting were observed on the inside surface of the shell.
Internally, bottom dish end surface cannot inspect due to limited access.
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
6 RECOMMENDATION/REPAIR:
Deteriorated paint spots and deliberately removed paint areas need to be repainted.
Apply the protective coating to all shell surfaces as well as the flange to nozzle.
External corrosion on the bottom dish end and its support needs to be removed, and the
proper paint coating should be applied after the corrosion is removed.
The inside surface of the bottom dish end needs to be inspected in the next turnaround
interval.
7 CONCLUSIONS:
Based on the results of visual inspection, overall assessment of the pressure vessel, it is
concluded that Regeneration Gas Scrubber V-9209 is safe to operate at the current operating
parameters until the next recommended inspection interval.
8 ANNEXES:
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 6 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 7 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Annexure A
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 7 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 8 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
8.1 Annexure A – VISUAL INSPECTION FINDINGS
SR.NO. REFERENCE PHOTOGRAPHS OBSERVATIONS AND RECOMMENDATIONS
Observation:
satisfactory.
1
Recommendation:
N/A
Observation:
N/A
Observation:
Recommendation:
N/A
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 8 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 9 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Observation:
The internal condition of vessel found
4
satisfactory.
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Recommendation:
N/A
Observation:
The condition of demister paid was found
satisfactory.
5 Recommendation:
N/A
Observation:
The condition of foundation was found
satisfactory.
Recommendation:
N/A
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 9 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 10 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
ANNEXURE B
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 10 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 11 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
Operating Temperature 84 F0
® TÜV, TUEV und TUV are registered trademarks. Any use or application requires prior approval.
Material SA 516 Gr 70
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 11 of 12
TÜV Rheinland Arabia LLC
Pakistan Branche
Industrial Services
INSPECTION REPORT
REPORT NUMBER: I01-PE-23-10-0461 Rev: 00 SHEET: Page 12 of 12
Contract No.: PROC-SERVICES/CB/CORR-5243/2021
N/A API 510 Section 7.1 Corrosion Rate
Corrosion Rate (LT) mm/year
Determination
N/A API 510 Section 7.1 Corrosion Rate
Corrosion Rate (ST) inch/year
Determination
N/A
MAWP (Shell) till the next inspection1 Psig
Calculations
Next Recommended External N/A
Year
Inspection Interval
Next Recommended Internal N/A
Year
Inspection Interval
1. Calculated for assessment purpose only. This allowable working pressure shall not exceed the original
design condition, until/unless rerating to be carried out by engineering.
TÜV Rheinland Arabia LLC Pakistan Branch – 108, Block J-1, Johar Town, Lahore TUVR-PAK-IS-003-PV-Rev-00
www.tuv.com UAN: +92 42 111 TUV (888) 877 / Fax: +92 42 3595 7560
Email: Pakistan@sa.tuv.com Page 12 of 12