[WBP4-CNTIC-SEC-PGCB-582]
Mirsharai 230kV GIS
1. [p.7] CT 2 차 결선 Collor 변경 : Black -> Green, 제어선과 구분필요
It is recommended to change the wires color of CT 2nd to distinguish from other control wires.

Drawing : 23204C114 9-E

2. [p.7] PT 2 차 결선 Collor 변경 : Black -> Green, 제어선과 구분필요


It is recommended to change the wires color of CT 2nd to distinguish from other control wires.
Drawing : 23204C114 9-F
3. [p.39] VT Close/Open 동작 접점 수정검토 요함(Close : HJ, Open : TJ)
Need to check the name of relay (HJ->TJ)
Drawing : : 23204C114 G-4, E-9, J-9
4. [p.42] CB Close 인터록 조건(ES 'b'접점) 수정검토 요함(기존 : ES 'a'접점)
Need to check CB interlock condition and terminal block’s contact (‘a’ or ‘b’)

Drawing : 23204C114 C, D-3

5. [p. 20.21.22] CB Closing coil(HQ) 및 Trip coil(TQ1,2) 저항값(ohm) 추가


Need to specify the specifications (ohm) of the closing coil and trip coil in the drawing.
Drawing : 23204C114 F-5,7,8
6. [p.42] 차단기 결상(K47A) 시 CB Close Block 회로 추가
It is recommended to add a funtion of CB closing block for K47A.

Drawing : 23204C114 H-3,4


[WBP4-CNTIC-SEC-PGCB-606]
Battery charger(DC 48V, 110V)

1. [p.5] Relay Setting 범위 추가 : DC OverVoltage/ DC UnderVoltage / Earth Fault


Need to specify the operation range of Relay in the drawing. (DC OverVoltage/ DC
UnderVoltage / Earth Fault)

Drawing : Bettery Charger Rectifier B-4


[WBP4-CNTIC-SEC-PGCB-613]
400kV CB Schematic & Wiring Diagram

1. [p.5] 결상 Timer(K16 relay) Setting 및 동작시간 표기 필요


Need to specify the operation range of the Timer(K16)

Drawing : (3)G71AHS-NA404-W620 E-4


2. [p.14] PSD 입력 부분 CT/PT 변환비 도면에 정보추가
Need to specify the ratio of CT and VT for PSD.

Drawing : (3)G71AHS-NA404-W620 A-6