Pec 2017 CH04

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 126

ARTICLE 4.

0 - FLEXIBLE CORDS AND CABLES

Chapter 4 Equipment for General Use


ARTICLE 4.0 - FLEXIBLE CORDS AND approximately the same current as the line-to-neutral
CABLES currents of the other conductors and shall be considered
to be a current-carrying conductor.
4.0.1 General
On a 4-wire, 3-phase, wye circuit where more than 50
percent of the load consists of nonlinear loads, there
4.0.1.1 Scope. This article covers general requirements,
are harmonic currents present in the neutral conductor
applications, and construction specifications for flexible
and the neutral conductor shall be considered to be a
cords and flexible cables.
current-carrying conductor.
FPN: UL 817, Cord Sets and Power-Supply Cords, allows the
use of flexible cords manufactured in accordance with UL 62, An equipment grounding conductor shall not be
Flexible Cords and Cables. See 4.0.1.10 and 4.0.1.12 for flexible considered a current-carrying conductor.
cords that are part of a listed cord set or power-supply cord.
Where a single conductor is used for both equipment
4.0.1.2 Other Articles. Flexible cords and flexible grounding and to carry unbalanced current from other
cables shall comply with this article and with the conductors, as provided for in 2.50.7.11 for electric
applicable provisions of other articles of this Code. ranges and electric clothes dryers, it shall not be
4.0.1.3 Suitability. Flexible cords and flexible cables considered as a current-carrying conductor.
and their associated fittings shall be suitable for the (B) Ultimate Insulation Temperature. In no case
conditions of use and location. shall conductors be associated together in such a way
4.0.1.4 Types. Flexible cords and :flexible cables shall with respect to the kind of circuit, the wiring method
conform to the description in Table 4.0.1.4. used, or the number of conductors such that the limiting
temperature of the conductors is exceeded.
4.0.1.5 A.mpacities for Flexible Cords and Cables.
(C) Engineering Supervision. Under engineering
(A) Ampacity Tables. Table 4.0. l .5(A)(l) provides the supervision, conductor ampacities shall be permitted to
allowable ampacities, and Table 4.0. l .5(A)(2) provides be calculated in accordance with 3.10.2.6(C).
the ampacities for flexible cords and flexible cables with
not more than three current-carrying conductors. These 4.0.1.6 Markings.
table shall be used in conjunction with applicable end- (A) Standard Markings. Flexible cords and flexible
use produ r tandards to ensure selection of the proper cables shall be marked by means of a printed tag
size and type. \Vbere cords and cables are used in attached to the coil reel or carton. The tag shall contain
ambien mperatures other than 30°C, the temperature the information required in 3.10.3.17(A). Types S, SC,
correc ·o fa tors from Table 3.10.2.6(B)(2)(a) that SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO,
correspond to the 'emperature rating of the cord or cable SJO, SJT, SITO, SJTOO, SO, SOO, ST, STO, STOO,
shall be applied to the ampacity in Table 4.0.l.5(A)(l) SEW, SEOW, SEOOW, SIEW, SJEOW, SJEOOW,
and Table 4.0. 1. -(A)(- ). Cords and cables rated SJOW, SJTW, SJTOW, SJTOOW, SOW, SOOW, STW,
1o-0 c hall u e correction factors in the 90°C STOW, and STOOW flexible cords and G, G-GC, PPE,
column of Table 3.I0.2.6(B)(2)(a) for temperature and W flexible cables shall be durably marked on the
correction. \\'here the number of current-carrying surface at intervals not exceeding 610 mm with the type
conductors exceeds three, the allowable ampacity or the designation, size, and number of conductors. Required
ampacity of each conductor shall be reduced from the markings on tags, cords, and cables shall also include
three-conductor rating as shown in Table 4.0. l .5(A)(3). the maximum operating temperature of the flexible cord
FPN: See Informative Appendix B, Table B. 3.10.2.6(B)(2) or flexible cable.
(11), for adjustment factors for more than three current-carrying
conductors in a raceway or cable with load diversity. (B) Optional Markings. Flexible cords and cable types
listed in Table 4.0.1.4 shall be permitted to be surface
A neutral conductor that carries only the unbalanced marked to indicate special characteristics of the cable
current from other conductors of the same circuit shall materials. These markings include, but are not limited
not be required to meet the requirements of a current- to, markings for limited smoke, sunlight resistance, and
carrying conductor. so forth.
In a 3-wire circuit consisting of two phase conductors
and the neutral conductor of a 4-wire, 3-phase, wye-
connected system, a common conductor carries
279
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0.1.4 Flexible Cords and Flexible Cables
Nominal Insulation
Braid
Thickness
Trade Type umber of on Each Outer
Name Letter Voltage mm' Conductors Insulation mmi mm Conductor Covering Use
Lamp C 300 0.75 - 1.25 2 or more Thermoset or 0.75-1.25 0.76 Cotton one Pendant or Dry Not b.3rd.
cord thermoplastic portable locations usage
600 2.0- 5.5 2.0 5.5 1.14
Elevator £1 ,2,J.~ 2 or more
300 0.50 - 30 Thermoset 0.50 - 1.25 0.5 1 Cotton Three cotton; Elevator Unclassified
cable outer one lighting and locations
or 1.65 - 3.5 0.76 flame- control
retardant and
600 3.5 - 5.5 1.14 moisture-
8.0- 30 1.52 resistant

0.50- 1.25 0.51 Flexible


nylon jacket
1.65 - 3.5 0.76
3.5 - 5.5 1.14
8.0-30 1.52
Elevator EO'"'' 300 0.50 - 30 2 or more Thermoset 0.50 - 1.25 0.51 Cotton Three cotton; Elevator Unclassified
cable outer one Iighting and locations
or l.65 - 3.5 0.76 flame- control
retardant and
600 3.5 - 5.5 1.)4 moisture-
8.0 - 30 1.52 resistant
One cotton Hazardous
and a neo- (classified) locations
prene jacket

Elevator ETP' ·' 300 or Rayon Thermoplastic Hazardous (classified) locations


cable 600

ETI" 300 or None One cotton


600 or equivalent
and a
thermoplastic
jacket

Electric EV'•6 600 0.75 - 250 2 or more plus Thermoset 0. 5- 1.65 0.76 Optional Oil - resistant Electric Wet Extra-
vehicle grounding with optiooa I (0.51) thermo et vehicle locations bard
cable conductor(s), plus nylon charging usage
optional hybrid 2.0 - 5.5 1.14
data, signal (0.76)
communications,
and optical fiber 8.0 - 30 1.52
cables (1.14)
38 - 100 2.03
(1.52)
125 - 250 2.41
(1.90)
EVJ'·' 300 0.75 - 3.5 0.75 - 3.5 0.76 Hard
(0.51 ) usage
EVE'·6 600 0.75 - 250 2 or more plus Thennoplasiic 0.75 - 1.65 0.76 Oil - resistant Extra-
grounding elastomer (0.51 ) thermoplastic bard
cooductor(s), plus with optional elastomer usage
optional hybrid nylon 2.0 - 5.5 1.14
data, signal (0.76)
communications,
and optical fiber 8.0- 30 1.52
cables ( 1.14)
38-100 2.03
(1.52)
125 - 250 2.41
(1.90)
EVJE'·6 300 0.75- 3.5 0.75 - 3.5 0.76 Hard
(0.51) usage
EVT 5•6 600 0.75 - 250 2 or more plus Thermoplastic 0.75 - 1.65 0.76 Oil - resistant Extra-
grounding with optional (0.51) thermoplastic hard
conductor(s), plus nylon usage
optional hybrid 2.0-5.5 1.14
data, signal (0.76)
communications}
and optical fiber 8.0 - 30 1.52
cables (1.14)
38 - 100 2.03
( 1.52)

125 - 250 2.4 1


( l.90)
EVJT'·6 300 0.75 - 3.5 0.75 - 3.5 0.76 Hard
(0.51) usage
(Continues)

280
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0.1.4 Continued
... - "' _._ . ". -----. . .,. .. -~- ·----·..---·-·-- ·-·-- - -. ----- -·
Nominal
Insulation
Braid
Thickness
Trade Type Number of o n Each Outer
Name Letter Voltage m m' Conductors Insulation mm' mm Conductor Covering Use

Portable G 2000 3.5 - 250 2-6 plus Thermoset 3.5 • 30 1.52 Oil- resistant Portable and extra- hard usage
power grounding tbermoset
cable conductor(s) 38 · 100 2'°3
125 - 250 2Al
G-GC' 2000 3.5. 250 3-6 plus Tbennoset 3.5 - 30 1.52 Oil- resistant
grounding thermoset
conductors and 38 · 100 2.03
I ground cbeck
conductor 125 - 250 2.41

Heater HPD 300 0.75 - 3.5 2, 3, or4 Thennoset 0.75 - 1.25 0.38 None Cotton or Portable Dry Not hard
cord rayon heaters locations usage
1.65 · 3.5 0.76
8
Parallel HP 300 0.75 - 3.5 2 or 3 Oil- resistant 0.75 1.25 1.14 None Oil- resistant Portable Damp Not bard
heater thennoset the,moset locations usage
cord 1.65 1.52
2.0 2.41
3.5
Thennoset HSJ 300 0.75-3.5 2, 3, or 4 Thennoset 0.75 - 1.25 0.76 None Cotton and Portable Damp Hard
jacketed thermoset or locations usage
heater 1.65 · 3.5 1.14 po1iable
cords HSJO 300 0.75 · 3.5 Oil- resistant Cotton and heaters Damp
thermoset oil- resistant and wet
tbermoset locations
HSJOW' 300 0.75 · 3.5 Damp
locations
HSJOO 300 0.75 - 3.5
HSJOO' 300 0.75 · 3.5 Damp
and wet
locations
Non- NISP-1 300 0.50 - 0.75 2 or 3 Thermoset 0.50 · 0.75 0.38 "lone Thermoset Pendant Damp Not hard
integral or locations usage
parallel MSP-2 300 0.75 · l.25 0. 75 - 1.25 0. 76 ponable
cords
NISPE- 1' 300 0.50 - 0.75 Thermoplastic 0.50 - 0.75 0.38 Thermoplasuc
ela tamer elastomer
'.\ISPE-2 8 300 0.75 - 1.25 0. 75 - L5 0.76
XISPT- 18 300 o. · o . o.75 Thermopla,"tic o.:o- o.;s 0.3 Thennoplast,c
XISPT-2' 300 o.-5 · 1.25 o.-5- L 5 o.- 6

Twisted PD 300 o.-5 - I 25 :? or more Therrnoset or o.-5 - !.25 0.76 Conan Conon or Pendant Dry Not hard
portable rhermop :l.S!i rayon or locations usage
cord 600 :! .O - 5 5 l.65 -5.5 1.1 4 portable
Portable PPE- _ooo 3.5- :?50 l -6p?us Thermop as:, 3.5 - 30 1.52 Oil- resistant Portable, extra- hard usage
po\ver o~onal e l~ torner thermoplastic
cable ground.mg 38 - 100 2.03 elastomer
conducto S)
125 · 250 2.41
Hard S' 600 0.75 - 30 ~ or more Tnennoset 0.75 - 1.6· 0.76 None Thermoset Pendant Damp Extra-
service or locations hard
cord 2.0 - 5.5 l.14 portable usage
8.0 · 30 1.52
Flexible SC'·' 0 600 8.0 · 125 I or more Thermoset .0 - 30 1.52 Thermoset Portable, extra- hard usage
stage and
lighting 38 - 100 2.03
power
cable 125 2.4 1
SCE 7· ' 0 600 Thermoplastic Thennoplastic
elastomer elastomer
SCT'· ' 0 600 Thermoplastic Thermoplastic
Hard SE' 600 0.75 - 30 2 or more Thermoplastic 0.75 · 1.65 0.76 None Thermoplastic Pendant Damp Extra-
service elastomer elastomer or locations hard
cord 2.0 - 6.75 1.14 portable usage
8.0 -30 1.52
SEW'·' 600 Damp
and wet
locations
SEOW' 600 Oil- resistant Damp
thermoplastic locations
elastomer
SEOW'·' 600 Damp
and wet
locations
..... - -~ ••· • •• ·•·••---~·-••••'• w~..,.,.._.,q.,.
- (Continues)

281
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0. 1.4 Continued

Nominal
Insulation
Braid
Thickness
Trade Type Number of on Each Outer
Name Letter Voltage mm' Conductors Insulation mm' mm Conductor Covering Use
Hard SEOO' 600 0.75 - 30 2 or more Oil- resistant 0.75 - 1.65 0.76 None Oil- resistant Pendant or Damp Extra-
service thermoplastic thermoplastic portable locations hard
cord elastomer 2.0 - 6.75 1.14 elastomer usage
SEOOS 7•9 600 8.0-30 1.52 Damp
and wet
locations
Junior SJ 300 0.75 - 5.5 2-6 Thermoset 0 .75 - 4.25 0.76 None Thermoset Pendant or Damp Hard
hard portable locations usage
service 5.5 1.14
cord
SJE 300 Thermoplastic Thermoplastic
elastomer elastomer
SJEW' 300 Damp
and wet
locations
SJEO 300 Oil- resistant Damp
thermoplastic locations
elastomer
SJEOW9 300 Damp
and wet
locations
SJEOO 300 Oil- resistant Damp
thermoplastic locations
elastomer
SJEOOW' 300 Damp
and wet
locations
SJO 300 Thermoset Oil- resistant Damp
thermoset locations
SJOVt' 300 Damp
and wet
locations
SJOO 300 Oil- resistant Damp
thermoset locations
SJOOW' 300 Damp
and wet
locations
SIT 300 Thermoplastic Thermoplastic Damp
locations
SJTW' 300 Damp
and wet
locations
SJTO 300 Oil- resistant Damp
thermoplastic locations
SJTOW' 300 Damp
and we
locations
SJTOO 300 Oil- resistant Damp
thermoplastic locations
SJTOOW9 300 Damp
and wet
locations
Hard SO' 600 0.75 - 30 2 or more Thermoset 0.75 - 1.65 0.76 Tone Oil- resistant Pendant or Damp Extra-
service thermoset portable locations hard
cord usage
SOW'·' 600 Damp
and wet
locations
SOO' 600 Oil- resistant 2.0 -4.65 1.14 Damp
thermoset locations
8.0 - 30 1.52
SOOW'·' 600 Damp
and wet
locations
AU SP-1 300 0.50 - 0.75 2 or 3 Thermoset 0 .50 - 0.75 0.76 None None Pendant or Damp Not hard
thennoset portable locations usage
parallel SP-2 300 0.75 - 1.25 0.75 - 1.25 1.14
cord
SP-3 300 0.75 - 5.5 0.75 - 1.25 1.52 Refrigera-
tors room air
1.65, 2.0 2.03 condition-
ers, and as
3.5 2.41 pennitted in
4.22 .2 .7(B)
5.5 2.80

(Continues)
282
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0.1.4 Continued

Nominal
Insulation
Braid
Thickness
Trade Type Number of on Each Outer
Name Letter Voltage mm2 Conductors Insulation mm2 mm Conductor Covering Use
All SPE-1 8 300 0.50- 0.75 2 or 3 Thermoplastic 0.50 - 0.75 0.76 None None Pendant or Damp Not hard
elastomer elastomer portable locations usage
(thermo-
plastic) SPE-2' 300 0.75 - 1.25 0.75 - 1.25 l.1 4 Refrigera-
parallel tors room air
cord SPE-3' 300 0.75 - 5.5 0.75 - 1.25 1.52 condition-
ers, and as
1.65 2.03 permitted in
2.0 4.22.2.7(B)
2.41
3.5 2.8
5.5
All ther- SPT - 1 300 0.50 - 0.75 2 or 3 Thermoplastic 0.50- 0.75 0.76 None None Pendant or Damp Not hard
moplastic portable locations usage
parallel
cord SPT-l W' 300 2 Damp
and wet
locations
SPT-2 300 0.75 - l.25 2 or 3 0.75 - l.25 l.14 Damp
locations
SPT - 2W" 300 2 Damp
and wet
locations
SPT - 3 300 0.75 - 5.5 2 or 3 0.75 - l.25 1.52 Refrigera- Damp Not hard
tors room air locations usage
1.65 2.03 condition-
ers, and as
2.0 2.41 permitted in
4.22.2.7(B)
3.5 2.8
5.5
Range, SRO 300 5.5 - 22 3 or4 Thermoset 5.5 - 22 1.14 None Thermoset Portable Damp Ranges,
dryer locations dryers
cable SRDE 300 5.5 -22 3 or4 Thermoplastic None Thermoplastic
elastomer elastomer
SRDT 300 5.5 - 22 3 or 4 Thermoplastic None Thermoplastic
Hard ST' 600 0.75 - 30 2 or more Thermoplastic 0.75 - l.65 0.76 None Thermoplastic Pendant or Damp Extra-
service portable locations hard
cord 2.0 - 4.65 1.14 usage
STW'·9 600 Damp
8.0 - 30 l.52 and wet
locations
STO' 600 Oil- resistant Damp
thermoplastic locations
STOW'·9 600 Damp
and wet
locations
STOO' 600 Oil- resistant Damp
thermoplastic locations
STOOW' 600 Damp
and wet
locations
Vacuum sv 300 0.75 - 1.25 2 or 3 Therrnoset 0.75 - l.25 0.38 None Thermoset Pendant or Damp Not bard
cleaner portable locations usage
cord SVE 300 Thermoplastic Thermoplastic
elastomer elastomer
SVEO 300 Oir- resistant
thermoplastic
SVEOO 300 Oir- resistant elastomer
thermoplastic
elastomer
SVO 300 Thermoset Oir- resistant
thermoset
svoo 300 Oil- resistant Oir- resistant
thermoset thermoset
SVT 300 Thermoplastic Thermoplastic
SVTO 300 Thermoplastic Oil-resistant
thermoplastic
SVTOO 300 Oil-resistant
thermoplastic
Parallel TPT" 300 0.125 2 Thermoplastic 0.125 0.76 None Thermoplatic Attached to Damp Not hard
tinsel an appliance locations usage
cord

(Continues)

283
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0.1.4 Continued

Nominal
Insulation
Braid
Thickness
Trade Type Number of on Each Outer
Name Letter Voltage mm' Conductors Insulation mm 2 mm Conductor Covering Use

Jacketed
tinsel
TST" 300 0.125 2 Thermoplastic 0. 125 0.38 None Thermoplatic Attached to
an appliance
I Damp
locations
I
Not h:ird
usage
cord
Portable W' 2000 3.5 - 250 I -6 Them10set 3.5 - 30 1.52 O il- resistant Portable, extra- hard usage
power thennoset
cable 251 - 500 I 38 - 100 2.03
125 - 250 2.41
251 - 500 2.80
Notes:
All types listed in Table 4.0. 1.4 shall have individual conductors twisted together, except for Types HPN, SP-I , SP-2, SP-3, SPE-1, SPE-2, SPE-3, SPT-1, SPT-2,
SPT-3, SPT-1 W, SPT-2W, TPT, NISP-1, NISP-2, NISPT-1 , NISPT-2, NISPE-1, NISPE-2, and three-conductor parallel versions of SRD, SRDE, and SRDT.
The individual conductors of all cords, except those of heat-resistant cords, shall have a thermoset or thermoplastic insulation, except that the equipment grounding
conductor, where used, shall be in accordance with 4.0.2.4(B).
'Rubber-filled or varnished cambric tapes shall be permitted as a substitute for the inner braids.
' Elevator traveling cables for operating control and signal circuits shall contain nonmetallic fillers as necessary to maintain concentricity. Cables shall have steel
supporting members as required for suspension by 6.20.5. l. In locations subject to excessive moisture or corrosive vapors or gases, supporting members of other
materials shall be pennitted. Where steel supporting members are used, they shall run straight through the center of the cable assembly and shall not be cabled with
the copper strands of any conductor.
ln addition to conductors used for control and signaling circuits, Types E, EO, ETP, and ETT elevator cables shall be permitted to incorporate in the construction
one or more 0.50 mm2 telephone conductor pairs, one or more coaxial cables, or one or more optical fibers. The 0.50 mm' conductor pairs shall be permitted to be
covered with suitable shielding for telephone, audio, or higher frequency communications circuits; the coaxial cables shall consist of a center conductor, insulation,
and a shield for use in video or other radio frequency communications circuits. The optical fiber shall be suitably covered with flame-retardant thermoplastic. The
insulation of the conductors shall be rubber or thermoplastic of a thickness not less than specified for the other conductors of the particular type of cable. Metallic
shields shall have their own protective covering. Where used, these components shall be permitted to be incorporated in any layer of the cable assembly but shall
not run straight through the center.
' Insulations and outer coverings that meet the requirements as flame retardant, limited smoke, and are so listed, shall be permitted to be marked for limited smoke
after the Code type designation.
'Elevator cables in sizes 0.50 1nm' through 2.0 w.m' (l .6 mm dia.) are rated 300 rnlt.s, and izes 5.5 mm1 (2.6 mm dia.)through 30 mm' are rated 600 volts. 3.5 mm'
(2.0 mm dia.)is rated 300 volts with a 0.76 mm insulation thickness and 600 volts with a l.14 mm insulation thickness.
5Conductor size for Types EV, EVJ, EVE, EVJE, EVT, and EVJT cables apply t0 nonpower-limited circuits only. Conductors of power-limited (data, signal, or

communications) circuits may extend beyond the stated AWG size range. All conductors shall be insulated for the same cable voltage rating.
6Insulation thickness for Types EV, EVJ, EVEJE, EVT, and EVJT cables of nylon construction is indicated in parentheses.

'Types G, G-GC, S, SC, SCE, SCT, SE, SEO, SEOO, SEW, SEO\\:, SEOO\\", 0. SOO, O\\", SOOW, ST, STO, STOO, STW, STOW, STOOW, PPE, and W shall
be permitted for use on theater stages, in garages, and elsewhere where flexible cords are permitted by this Code.
' The third conductor in Type HPN shall be used as an equipment grounding conductor only. The insulation of the equipment grounding conductor for Types SPE-1,
SPE-2, SPE-3, SPT-1, SPT-2, SPT-3, NISPT-1 , NISPT-2, N!SPE-1, and :\1SPE-2 hall be permitted to be thennoset polymer.
9 Cords that comply with the requirements for outdoor cords and are so listed sha be permitted to be designated as weather and water resistant with the suffix "W'
after the Code type designation. Cords with the "W' suffix are suitable for use in wet locations and are sunlight resistant.
'"The required outer covering on some single-conductor cables may be integral with the insu ation.
"Types TPT and TST shall be permitted in lengths not exceeding 2500 mm where anacbed directly, or by means of a special type of plug, to a portable appliance
rated at 50 watts or less and of such nature that extreme flexibility of the cord is essential.

284
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0.1.S(A)(l) Allowable Ampacity for Flexible Cords and Flexible Cables [Based on Ambient
Temperature of 30°C. See 4.0.1.13 and Table 4.0.1.4.
Thermoset Types C, E, EO, PD, S, SJ, SJO, SJOW,
SJOO, SJOOW, SO, SOW, SOO, SOOW, SP-1, SP-2,
SP-3, SRD, SV, SVO, SVOO, NISP-1, NISP-2
Thermoplastic Types ETP, ETT, NISPE-1, NISPE-2,
NISPT-1, NISPT-2, SE, SEW, SEO, SEOO, SEOW, Types HPD,
SEOOW, SJE, SJEW, SJEO, SJEOO, SJEOW, SJEOOW, HPN, HSJ,
SJT, SJTW, SJTO, SJTOW, SJTOO, SJTOOW, SPE-1, SPE-2, SPE-3, SPT-1, HSJO, HSJOW,
Size mm 2 Thermoplastic SPT-IW, SPT-2, SPT-2W, SPT-3, ST, STW, SRDE, SRDT, STO, STOW, STOO, HSJOO,
(mm dia.) Types TPT, TST STOOW, SVE, SVEO, SVEOO, SVT, SVTO, SVTOO HSJOOW
Column A" Column Bb
0.125< 0.5 - -
0 .50(0.80) - 5d '
0.75(1.0) 7 10 10
1.25(1.2) - 10 13 15
2.0(1.6) - 15 18 20
3.5(2.0) - 20 25 30
5.5(2.6) - 25 30 35
8.0(3.2) - 35 40
14 45 55 -
22 - 60 70 -
30 80 95 -
' 1 ne allowable currents under Column A app>I y to three-conductor cords and other multlcon< uctor cords connected to ut1 hzat1on e qrnp ment so that
only three-conductors are current-carrying.
bToe allowable currents under Colrnnn B apply to two-conductor cords and other multiconductor ·ords connected to utilization equipment so that
only two conductors are current-carrying.
·Tinsel cord.
<E e,·ator cab es only.
•-;- amperes for ele,·ator cables onl, : 2 amperes for other t: . es.

Table 4.0.l.5(A)(2) Ampacity of Cable Types SC SCE, SCT, PPE, G, G-GC, and W. [Based on Ambient
Temperature of 30°C. See Table 4.0.1.4.
Size [mm~ 60°C 1s c
0 90°c
(mm)) DI p p DI E2 F3 D' Ez F3
3:5 : - 3! :6 37 31 - 42 35
.;: ..::
. -- ..... .
- ..
~ r - 52 43 - 59 49
- - - ""I
55 4 70 65 57 80 74
"- 65

- -, 63 95 88 77 105 99 87

-
-- 05 96 84 125 11 5 10 1 140- 130 114

30 1-!0 128 112 170 152 133 190 174 152

-- 165 150 131 195 178 156 220 202 177


Sil 19· 173 151 230 207 181 260 234 205

60 225 199 174 265 238 208 300 271 237

0 260 230 20 1 3 10 275 241 350 31 3 274

100 300 265 232 360 317 277 405 361 3 16


1~5 340 296 259 405 354 310 455 402 352

150 375 330 289 445 395 346 505 449 393

175 420 363 318 505 435 381 570 495 433

200 455 392 343 54 5 469 410 61 5 535 468

250 5 15 448 392 620 537 470 700 613 536


'The ampac1ties under subneaamg u shall be p errmtted. tor smgle-conctuctor Typ es ~C. ~L.t., ~Ll , Pl'b, and w cable only where the mct1v1ctua1 conductors are not
installed in raceways and are not in physical contact with each other except in lengths not to exceed 600 mm where passing through the wall of an enclosure.
1The ampacities under subheading E apply to two-conductor cables and other multiconductor cables connected to utilization equipment so that only two conductors

are current-carrying.
3The ampacities under subheading F apply to three-conductor cables and other m ulticonductor cables connected to utilization equipment so that only three conductors

are current-carrying.

285
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
Table 4.0.l.5(A)(3) Adjustment Factors for More (B) Attachment Plugs. Where used as permitted in
Than Three Current-Carrying Conductors in a 4.0.l.10(A)(3), (A)(6), and (A)(8), each flexible cord
Flexible Cord or Flexible Cable shall be equipped with an attachment plug and shall be
energized from a receptacle outlet or cord connector
Number of Percent ofVaue in Table 4.0.1.S(A) body.
Conductors (1) and Table 4.0.1.5(A)(2) Exception: As p ermitted in 3. 68.2.47.

4-6 80 4.0.1.12 Uses Not Permitted. Unless specifically


7-9 70 permitted in 4.0. 1. 10, flexib le cables, flexible cords
sets and power supply cords shall not be used for the
10 - 20 50
following:
21 - 30 45
(1) As a substitute for the fixed wiring of a structure
31 -40 40
41 and above 35 (2) Where run through holes in walls, structural
ceilings, suspended ceilings, dropped ceilings, or
4.0.1 .10 Uses Permitted. floors

(A) Uses. Flexible cords and flexible cables shall be (3) Where run through doorways, windows, or
used only for the following: similar openings

(1) Pendants. (4) Where attached to building surfaces

(2) Wiring of luminaires. Exception to (4) : Flexible cord and flexible cable shall
be p ermitted to be attached to building surfaces in
(3) Connection of portable luminaires portable accordance with the provisions of 3.68.2.47(B)
and mobile signs, or appliances.
(5) Where concealed by walls, floors, or ceilings or
(4) Elevator cables. located above suspended or dropped ceilings
(5) Wiring of cranes and hoists. Exception to (5): Flexible cord and flexible cable shall
(6) Connection of utilization equipment to facilitate be p ermitted if contained within an enclosure f or use in
frequent interchange. Other Spaces Used for Environmental Air as permitted
by 3.0.l.22(C}(3).
(7) Prevention of the transmission of noise or
vibration. (6) Where installed in raceways, except as otherwise
permitted in this Code
(8) Appliances where the fastening means and
mechanical connections are specifically (7) Where subject to physical damage
designed to permit ready removal for 4.0.1.13 Splices. Flexible cord shall be used only in
maintenance and repair, and the appliance continuous lengths without splice or tap where initially
is intended or identified for flexible cord installed in applications permitted by 4.0.1.1 O(A). The
connection. repair of hard-service cord and junior hard-service cord
(9) Connection of moving parts. (see Trade Name column in Table 4.0.1.4) 2.0 mm2 (1.6
mm dia) and larger shall be permitted if conductors
(10) Where specifically permitted elsewhere in this
are spliced in accordance with 1.10.1.14(B) and the
Code.
completed splice retains the insulation, outer sheath
(11) Between an existing receptacle outlet and properties, and usage characteristics of the cord being
an inlet, where the inlet provides power to spliced.
an additional single receptacle outlet. The
4.0.1.14 Pull at Joints and Terminals. Flexible cords
wiring interconnecting the inlet to the single
and flexible cables shall be connected to devices and
receptacle outlet shall be a Chapter 3 wiring
to fittings so that tension is not transmitted to joints or
method. The inlet, receptacle outlet, and
terminals.
Chapter 3 wiring method, including the
flexible cord and :fittings, shall be a listed Exception: Listed portable single-pole devices that
assembly specific for this application. are intended to accommodate such tension at their
terminals shall be permitted to be used with single-
conductor flexible cable.

286
ARTICLE 4.0 - FLEXIBLE CORDS AND CABLES
FPN: Some methods of preventing pull on a cord from being 4.0.2.3 Grounded-Conductor Identification. One
transmitted to joints or terminals include knotting the cord, conductor of :flexible cords that is intended to be used
winding with tape, and using support or strain-relief fittings.
as a grounded circuit conductor shall have a continuous
marker that readily distinguishes it from the other
4.0.1.15 In Show Windows and Showcases. Flexible
conductor or conductors. The identification shall
cords used in show windows and showcases shall be
consist of one of the methods indicated in 4.0.2.3(A)
Types S, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO,
through (F).
SJOO, SJT, SITO, SJTOO, SO, SOO, ST, STO, STOO,
SEW, SEOW, SEOOW, SJEW, SJEOW, SJEOOW, (A) Colored Braid. A braid finished to show a white
SJOW, SJOOW, SJTW, SJTOW, SJTOOW, SOW, or gray color and the braid on the other conductor or
SOOW, STW, STOW, or STOOW. conductors finished to show a readily distinguishable
solid color or colors.
Exception No. I: For the wiring of chain-supported
luminaires. (B) Tracer in Braid. A tracer in a braid of any color
contrasting with that of the braid and no tracer in the
Exception No. 2: As supply cords for portable luminaires
braid of the other conductor or conductors. No tracer
and other merchandise being display ed or exhibited.
shall be used in the braid of any conductor of a flexible
4.0.1.16 Overcurrent Protection. Flexible cords not cord that contains a conductor having a braid finished to
smaller than 0.75 mm2 (1.0 mm dia.), and tinsel cords show white or gray.
or cords having equivalent characteristics of smaller
Exception: In the case of Types C and PD and cords
size approved for use with specific appliances, shall
having the braids on the individual conductors .finished
be considered as protected against overcurrent in
to show white or gray. In such cords, the identifying
accordance with 2.40.1.5 .
marker shall be permitted to consist of the solid white
or gray finish on one conductor, provided there is a
4.0.1.17 Protection from Damage. Flexible cords and
colored tracer in the braid of each other conductor.
flexible cables shall be protected by bushings or fittings
where passing through holes in covers, outlet boxes, or (C) Colored Insulation. A white or gray insulation on
similar enclosures. one conductor and insulation of a readily distinguishable
color or colors on the other conductor or conductors for
In industrial establishments where the conditions of
cords having no braids on the individual conductors.
maintenance and supervision ensure that only qualified
persons service the installation, flexible cords and For jacketed cords furnished with appliances, one
:flexible cables shall be permitted to be installed in conductor having its insulation colored light blue, with
aboveground raceways that are no longer than 15 000 the other conductors having their insulation of a readily
mm to protect the flexible cord or flexible cable from distinguishable color other than white or gray.
physical damage. Where more than three current- Exception: Cords that have insulation on the individual
carrying conductors are installed within the raceway, conductors integral with the jacket.
the allowable ampacity shall be reduced in accordance
with Table 4.0.1.5(A)(3). The insulation shall be permitted to be covered with an
outer finish to provide the desired color.
4.0.2 Construction Specifications (D) Colored Separator. A white or gray separator on one
conductor and a separator of a readily distinguishable
4.0.2.1 Labels. Flexible cords shall be examined and solid color on the other conductor or conductors of
tested at the factory and labeled before shipment. cords having insulation on the individual conductors
integral with the jacket.
4.0.2.2 Construction.
(E) Tinned Conductors. One conductor having the
(A) Conductors. The individual conductors of a individual strands tinned and the other conductor or
flexible cord or :flexible cable shall have copper flexible conductors having the individual strands untinned for
stranding and shall not be smaller than the sizes cords having insulation on the individual conductors
specified in Table 4.0.1.4. integral with the jacket.
(B) Nominal Insulation Thickness. The nominal (F) Surface Marking. One or more ridges, grooves, or
thickness of insulation for conductors of flexible cords white stripes located on the exterior of the cord so as to
and flexible cables shall not be less than specified in identify one conductor for cords having insulation on
Table 4.0.1.4. the individual conductors integral with the jacket.
287
ARTICLE 4.2 - FIXTURE WIRES
4.0.2.4 Equipment Grounding Conductor 4.0.3.6 Fittings. Connectors used to connect length-
Identification. A conductor intended to be used as an of cable in a run shall be of a type that locks firm ly
equipment grounding conductor shall have a continuous together. Provisions shall be made to prevent opening
identifying marker readily distinguishing it from the or closing these connectors while energized. Suitable
other conductor or conductors. Conductors having means shall be used to eliminate tension at connector-
a continuous green color or a continuous green color and terminations.
with one or more yellow stripes shall not be used for
4.0.3.7 Splices and Terminations. Portable cable-
other than equipment grounding conductors. Cords or
shall not contain splices unless the splices are of the
cables consisting of integral insulation and a jacket
pe1manent molded, vulcanized types in accordance
without a nonintegral grounding conductor shall be
with 1.1 O. l.14(B). Terminations on pmiable cables
pe1mitted to be green. The identifying marker shall
rated over 600 volts, nominal, shall be accessible only
consist of one of the methods in 4.0.2.4(A) or (B).
to authorized and qualified personnel.
(A) Colored Braid. A braid finished to show a
ARTICLE 4.2 - FIXTURE WIRES
continuous green color or a continuous green color with
one or more yellow stripes. 4.2.1.1 Scope. This article covers general requirements
and constrnction specifications for fixture wires.
(B) Colored Insulation or Covering. For cords having
no braids on the individual conductors, an insulation of 4.2.1.2 Other Articles. Fixture wires sha]l comply with
a continuous green color or a continuous green color this article and also with the applicable provisions of
with one or more yellow stripes. other articles of this Code.
FPK: For application in luminaires, see Article 4.10.
4.0.2.5 Attachment Plugs. Where a flexible cord is
provided with an equipment grounding conductor and 4.2.1.3 Types. Fixture wires shall be of a type listed
equipped with an attachment plug, the attachment plug in Table 4.2.1.3, and they shall comply with all
shall comply with 2.50.7.9(A) and (B). requirements of that table . The fixture wires listed in
Table 4.2 .1.3 are all suitable for service at 600 volts,
4.0.3 Portable Cables Over 600 Volts, ~ominal nominal, unless othenvise specified.
FPN: Thennoplastic insulation may stiffen at temperatures lower
4.0.3.1 Scope. Part 4.0.3 applies to single and than - I 0°C., Thermoplastic insulation may also be deformed
multi.conductor portable cables used to connect mobile at normal temperatures where ·subjected to pressure, such as at
equipment and machinery. points of support.

4.0.3.2 Construction. 4.2.1.5 Allowable Ampacities for Fixture Wires. The


allowable ampacity of fixture wire shall be as specified
(A) Conductors. The conductors shall be 3.5 mm 2 (2.0
in Table 4.2.1.5.
mm dia.) copper or larger and shall employ flexible
stranding. o conductor shall be used under such conditions
that its operating temperature exceeds the temperature
(B) Equipment Grounding Conductor(s). An
specified in Table 4.2.1.3 for the type of insulation
equipment grounding conductor(s) shall be provided
involved.
in cables with three or more conductors. The total area
shall not be less than that of the size of the equipment FP : See 3. I0.2.6(A)(3) for temperature limitation of conductors.
grounding conductor required in 2.50.6.13. 4.2.1.6 M inimum Size. Fixture wires shall not be
smaller than 0.75 mrn2 (1.0 mm dia.).
4.0.3.3 Shielding. All shields shall be connected to an
equipment grounding conductor. 4.2.1.7 Number of Conductors in Conduit or Tubing.
The number of fixture wires permitted in a single
4.0.3.4 Equipment Grounding Conductors. conduit or tubing shall not exceed the percentage fill
Equipment grounding conductors shall be connected in specified in Table 10 .1.1.1.
accordance with Parts 2.50.6 and 2.50.7.
4.2.1.8 Grounded Conductor Identification. Fixture
4.0.3.5 Minimum Bending Radii. The mmunum wires that are intended to be used as grounded conductors
bending radii for portable cables during installation and shall be identified by one or more continuous white
handling in service shall be adequate to prevent damage stripes on other than green insulation or by the means
to the cable. described in 4.0.2.3(A) through (E).
288
ARTICLE 4.2 - FIXTURE WIRES
4.2.1.9 Marking. 4.2.1.14 Overcurrent Protection. Overcurrent
protection for fixture wires shall be as specified in
(A) Method of Marking. Thermoplastic insulated
2.40.1.5.
fixture wire shall be durably marked on the surface at
intervals not exceeding 610 mm. All other fixture wire ARTICLE 4.4 - SWITCHES
shall be marked by means of a printed tag attached to 4.4.1 Installation
the coil, reel, or carton.
4.4.1.1 Scope. The provisions of this article apply to
(B) Optional Marking. Fixture wire types listed in all switches, switching devices, and circuit breakers
Table 4.2.1.3 shall be permitted to be surface marked used as switches operating at 1 000 volts and below,
to indicate special characteristics of the cable materials. unless specifically referenced elsewhere in this Code
These markings include, but are not limited to, markings for higher voltages.
for limited smoke, sunlight resistance, and so forth.
4.4.1.2 Switch Connections.
4.2.1.10 Uses Permitted. Fixture wires shall be
permitted (1) for installation in luminaires and in similar (A) Three-Way and Four-Way Switches. Three-
equipment where enclosed or protected and not subject way and four-way switches shall be wired so that
to bending or twisting in use, or (2) for connecting all switching is done only in the ungrounded circuit
luminaires to the branch-circuit conductors supplying conductor. Where in metal raceways or metal-armored
the luminaires. cables, wiring between switches and outlets shall be in
4.2.1.12 Uses Not Permitted. Fixture wires shall not be accordance with 3.0.l.20(A).
used as branch-circuit conductors except as permitted Exception: Switch loops shall not require a grounded
elsewhere in this Code. conductor.
Table 4.2.1.3 Fixture Wires

Insulation of
Thickness Maximum
Type Outer Operating
Name Letter Insulation mm 2 mm Covering Temperature Applications Provisons
Heat-resistant rubber-covered fixture FFH-2 Heat-resistant rubber 0.75 - 1.25 0.76 Nonmetallic 15°c Fixture wiring
wiring - flexible stranding covering
Cross-linked synthetic 0.75 - 1.25 0.76
polymer
ECTFE - solid or 7-strand HF Ethylene chlorotrifluoro- 0.75 - 2.0 0.38 None 150°C Fixture wiring
ethylene

ECTFE - fleXJo!e stranding HFF Ethylene chlorotrifluoro- 0.75 - 2.0 0.38 None 150°C Fixture wiring
ethylene

Tape insulated fixrure wire - solid or KF- 1 Aromatic polyimide tape 0.75 - 5.5 0.14 None 200°c Fixture wiring - limited to 300 volts
-strand
KF -2 Aromatic polyimide tape 0.75 - 5.5 0.2 1 None 200°c Fixture wiring
Tape insulated fixrure wire - f!eXJole KFF- 1 Aromatic polyimide tape 0.75 - 5.5 0.14 None 200°c Fixture wiring - limited to 300 volts
stranding
KFF-1 Aromatic polyim.ide tape 0.75 - 5.5 0.21 None 200°c Fixture wiring
Perfluoro-alkoxy - solid or ?-strand PAF Per:fluoro-alkoxy 0.75 - 2.0 0. 51 None 250°c Fixture wiring (nickel or nickel-
(nickel or nickel-coated copper) coated copper)
Perfluoro-alkoxy - flexible stranding PAFF Per:fluoro-alkoxy 0.75 - 2.0 0.51 None 1so 0 c Fixture wiring
Fluorinated ethylene propylene fixture PF Fluorinated ethylene o. 5- ~.o 0.51 None 200°C Fixture wiring
w ire - solid or 7-strand propy ene
Fluorinated ethylene propylene fixture PFF Fluorinated ethylene 0.75 - 2.0 0.51 Kone 150°c Fixture wiring
wire - flexible stranding propylene

Fluorinated ethylene propylene fixture PGF Fluorinated ethylene 0. 5 - 2.0 0.36 Glass braid 200°c Fixture wiring
wire - solid or 7-strand propylene
Fluorinated ethylene propylene fixture PGFF Fluorinated ethylene 0.75 - 2.0 0.36 Glass braid 1so0 c Fixture wiring
wire - flexible stranding propylene
Extruded polytetrafluoroethylene - PTF Extruded 0.75 - 2.0 0.51 None 2so 0 c Fixture wiring (nickel or nickel-
solid or 7-strand (nickel or nickel- polytetrafluoroethylene coated copper)
coated copper)
Extruded polytetrafluoroethylene - PTFF Extruded 0.75 - 2.0 0.5 1 None 150°c Fixture wiring (nickel or nickel-
flexible stranding 0.125-0.012 mm' polytetrafluoroethylene coated copper)
(silver or nickel-coated copper)
(Con tinues)

289
ARTICLE 4.2 - FIXTURE WIRES
Table 4.2.1.3 Continued

Insulation of
Thickness Maximum
Type Outer Operating
Name Letter Insulation mm 2 mm Covering Temperature Applications Provisons
Heat-resistant rubber-covered fixture RFH- 1 Heat-resistant rubber 0.75 38 Nonmetallic 75°c fixture wiring - limited to 300
wiring - solid or 7-srrand covering volts
RFH-2 Heat-resistant rubber 0.75 - 1.25 0.76 None or 1s•c Fixture wiring
nonmetallic
Cross-linked synthetic covering
polymer
Heat-resistant cross-linked synthetic RFHH-2* Cross-linked synthetic 0.75 - 1.25 0.76 ' one or 90°c Fixture wiring
polymer-insulated fixture wire - solid polymer nonmetallic
or 7-strand RF HH-3* 0.75 - 1.25 1.14 CO\'ering
Silicone insulated fixture wire - solid SF-I Silicone rubber 0.75 0.38 Xonmetallic 200' C fixture wiring - limited to 300
or ?-strand covering volts
SF-2 Silicone rubber 0.75 - 3.5 0.76 :-orunetal ic 200°C Fixture wiring
covering
5.5 1.14
Silicone insulated fixture wire - flexible SFF- 1 Silicone rubber 0.75 0.38 :-;onmeiallic 150' C Fixture wiring - limited to 300
stranding covcnng volts
SFF-2 Silicone rubber 0.75 - 3.5 0. 6 :-;onmet:illic 150' C Fixture wiring
CO\'mr."'
5.5 1.14

Thermoplastic covered fix ture wire - TF* Thermoplastic 0.75 - 1.25 0.76 ~one 60'C Fixture wiring
solid or 7-strand

Thermoplastic covered fixture wire TFF* Thermoplastic 0.75 - 1. 25 o.- 6 :-;or.e 60· C Fixture wiring
- flexible stranding
Heat-resistant thermoplastic covered TF • Thermoplastic 0.75 - 1.25 0.3 . -~:c=- 9'"C Fi.~ture wiring
fixture wire - solid or 7-strand ~ ;e:e.:. (!:
~~ \~C:

Heal-resistant thetmoplastic covered TFF ·• Therm.o plast1c 0.75 - 1.25 0.3 --~:c=- '( Fixrure wiring
fixture wire - flexible stranded ·:..:i ~---C C
e..;r.=.-Z:e:::
Cross-linked polyolefin insulated XF* Cross-linked pol~o din o.75 - ~.o o.-6 :,.;~ ::OT FLxture "inng - limited to 300
fixture wire - solid or ?-strand
.. ..5 _5 - ..,
. . . -:c
I \'Cits

I
Cross-linked polyolefin insulated XFF• C ross-lmked po yole:ir: 0 -5- - ~ o -6 , c::e ::O'C rLxture wiring - limited to 300
fixture wire - flexible stranded ,olt
3..5 -5..5. '.,
---~
Modified ETFE - solid or 7 strand ZF '.\fodified ethylene o-~ - ~ (i,3_ ~·o::e 150°(' Fixture wiring
tetrafl.uoroethy enc

Modified ETFE - Flexible stranding ZFF Modified ethylene o -s- ~o 0.3 ~ e 150°C F ixture w iring
tetrafluoroethylcnc

High temp, modified ETFE - solid or ZHF :vfodified ethylene o.-5 -'.'. C 0.3 ~ one 2oo•c Fixture wiring
7 strand tetrafluoroethylcnc
*lnsulat1ons and outer coverings that meet the requirements of flame retardant, limited smoke, anc are so listed. shall oe penrutted to be marked for l1m1ted smoke after the Code type
designation.

Table 4.2.1.5 Allowable Ampacity for Fixx.tures


Wires

Size [mm 2 (mm)] Allowable Amp acity


0.75 (1.0) 6
1.25 (1.2) 8
2.0 (1.6) 17
3.5 (2.0) 23
5.5 (2.6) 28

290
ARTICLE 4.4 - SWITCHES
(B) Grounded Conductors. Switches or circuit lighting control switches on a branch circuit shall not
breakers shall not disconnect the grounded conductor exceed five, and the number connected to any feeder
of a circuit. on the load side of a system or main bonding jumper
shall not exceed 25. For the purpose of this exception,
Exception: A switch or circuit breaker shall be
a neutral busbar, in compliance with 2.0.1.2(B) and to
permitted to disconnect a grounded circuit conductor
which a main or system bonding jumper is connected
where all circuit conductors are disconnected
shall not be limited as to the number of electronic
simultaneous(v, or where the device is arranged so that
lighting control switches connected.
the grounded conductor cannot be disconnected until
all the ungrounded conductors of the circuit have been FPN: The provision for a (future) grounded conductor is to
complete a circuit path for electronic lighting control devices.
disconnected.
(C) Switches Controlling Lighting Loads. The 4.4.1.3 Enclosure.
grounded circuit conductor for the controlled (A) General. Switches and circuit breakers shall be of
lighting circuit shall be installed at the location the externally operable type mounted in an enclosure
where switches control lighting loads that listed for the intended use. The minimum wire-bending
are supplied by a grounded general-purpose space at terminals and minimum gutter space provided
branch circuit serving bathrooms, hallways, in switch enclosures shall be as required in 3 .12.1.6.
stairways, or rooms suitable for human habitation
Exception No. 1: Pendant-and surface-type snap
or occupancy as defined in the applicable building
switches and knife switches mounted on an open-face
code. Where multiple switch locations control the
switchboard or panelboard shall be p ermitted ·without
same lighting load such that the entire floor area
enclosures.
of the room or space is visible from the single or
combined switch locations, the grounded circuit Exception No. 2: Switches and circuit breakers installed
conductor shall only be required at one location. in accordance with 1.10.2.2(1), (a)(2}, (a)(3), or (a)(4)
A grounded conductor shall not be required to be shall be permitted without enclosures.
installed at lighting switch locations under any of
(B) Used as a Raceway. Enclosures shall not be used
the following conditions:
as junction boxes, auxiliary gutters, or raceways for
( 1) Where conductors enter the box enclosing conductors feeding through or tapping off to other
the switch through a raceway, provided that switches or overcurrent devices, unless the enclosure
the raceway is large enough for all contained complies with 3.12.1.8.
onductors, including a grounded conductor
4.4.1.4 Damp or Wet Locations.
(- ) \\bere the box enclosing the switch is accessible
(A) Surface-Mounted Switch or Circuit Breaker.
for the installation of an additional or replacement
A surface-mounted switch or circuit breaker shall be
abl ,·i out removing finish materials
enclosed in a weatherproof enclosure or cabinet that
C' ) \\ b re \\it he \\·ith integral enclosures shall comply \Yith 3.12.1 .2.
om ly ,.· b " .0.1.I.:- (E )
(B) Flush-\Iounted Switch or Circuit Breaker.
(4 ) \\b re ligh · g in ar a controlled bv A flush-mounted switch or circuit breaker shall be
au oma 1 means equipped \Yith a weatherproof cover.
( -) \"\"bere a \,·itch control a receptacle load (C) Switches in Tub or Shower Spaces. Switches shall
not be installed within tubs or shower spaces unless
The grounded conductor shall be extended to any
installed as part of a listed tub or shower assembly.
switch location as necessary and shall be connected to
switching deYices that require line-to-neutral voltage 4.4.1.5 Time Switches, Flashers, and Similar Devices.
to operate the electronics of the switch in the standby Time switches, flashers, and similar devices shall be of
mode and shall meet the requirements of 4.4.2.3. the enclosed type or shall be mounted in cabinets or
boxes or equipment enclosures. Energized parts shall
Exception: The connection requirement shall become
be barriered to prevent operator exposure when making
effective on January 1, 2020. It shall not apply to
manual adjustments or switching.
replacement or retro.fit switches installed in locations
prior to local adoption of 4.4.1.2(C) and where the Exception: Devices mounted so they are accessible only
grounded conductor cannot be extended without to qualified persons shall be permitted without barriers,
removing finish materials. The number of electronic provided they are located within an enclosure such

291
ARTICLE 4.4 - SWITCHES
that any energized parts within 152 mm of the manual Exception No. 2: On busway installations, tap nvitches
adjustment or switch are covered by suitable barriers. employing a center-pivoting handle shall be pennitzed
to be open or closed with either end of the handle in
4.4.1.6 Position and Connection of Switches.
the up or down position. The switch position shall be
(A) Single-Throw Knife Switches. Single-throw knife clearly indicating and shall be visible from the flo or or
switches shall be placed so that gravity will not tend to from the usual point of operation.
close them. Single-throw knife switches, approved for
use in the inverted position, shall be provided with an 4.4.1 .8 Accessibility and Grouping.
integral mechanical means that ensures that the blades
(A) Location. All switches and circuit breakers used as
remain in the open position when so set.
switches shall be located so that they may be operated
(B) Double-Throw Knife Switches. Double-throw from a readily accessible place. They shall be installed
knife switches shall be permitted to be mounted so that such that the center of the grip of the operating handle
the throw is either vertical or horizontal. Where the of the switch or circuit breaker, when in its highest
throw is vertical, integral mechanical means shall be position, is not more than 2 000 mm above the floor or
provided to hold the blades in the open position when working platform.
so set.
Exception No. 1: On busway installations, fused
(C) Connection of Switches. Single-throw knife switches and circuit breakers shall be permitted to be
switches and switches with butt contacts shall be located at the same level as the busway. Suitable means
connected such that their blades are de-energized when shall be provided to operate the handle of the device
the switch is in the open position. Bolted pressure from the floor.
contact switches shall have barriers that prevent
Exception No. 2: Switches and circuit breakers installed
inadvertent contact with energized blades. Single-throw
adjacent to motors, appliances, or other equipment that
knife switches, bolted pressure con- tact switches,
they supp(i· shall be permitted to be located higher than
molded case switches, switches with butt contacts and
_ 000 mm to be accessible by portable means.
circuit breakers used as switches shall be connected so
that the terminals supplying the load are de-energized Exception o. 3: Hookstick operable isolating s,1litches
when the switch is in the open position. shall be pennitted at greater heights.
Exception: The blades and terminals supplying the (B) Yoltage Between Adjacent Devices. A snap switch
load of a switch shall be permitted to be energized hall not be grouped or ganged in enclosures with other
when the switch is in the open position where the nap \\itches, receptacles, or similar devices, unless
switch is connected to circuits or equipment inherent~v they are arranged so that the voltage between adjacent
capable of providing a backfeed source of power. For d ,-ice does not exceed 300 volts, or unless they
such installations, a permanent sign shall be installed ar installed in enclosures equipped with identified,
on the switch enclosure or immediately adjacent to ecurely installed barriers between adjacent devices.
open switches with the following words or equivalent:
(C) ~1ultipole Snap Switches. A multipole, general-
WARNING - LOAD SIDE TERM!- NALS MAY BE
e ap witch shall not be permitted to be fed from
ENERGIZED BY BACKFEED. The warning sign or
more than a single circuit unless it is listed and marked
label shall comply with 1.10.1.21 (b).
a a t\Yo-circuit or three-circuit switch.
4.4.1.7 Indicating. General-use and motor-circuit FP:'\: ~ __l0.1.7 for di connect requirements where more than
switches, circuit breakers, and molded case switches, one cir uit supplie a switch.
where mounted in an enclosure as described in 4.4.1.3,
shall clearly indicate whether they are in the open (off) 4.4.1.9 Provisions for General-Use Snap Switches.
or closed (on) position.
(A) Faceplates. Faceplates provided for snap switches
Where these switch or circuit breaker handles mounted in boxes and other enclosures shall be installed
are operated vertically rather than rotationally or so as to completely cover the opening and, where
horizontally, the up position of the handle shall be the the switch is flush mounted, seat against the finished
closed (on) position. surface.
Exception No. 1: Vertically operated double-throw (B) Grounding. Snap switches, including dimmer
switches shall be permitted to be in the closed (on) and similar control switches, shall be connected to an
position with the handle in either the up or down position. equipment grounding conductor and shall provide a

292
ARTICLE 4.4 - SWITCHES
means to connect metal faceplates to the equipment of insulating material shall be noncombustible and
grounding conductor, whether or not a metal facep late not less than 2.54 mm in thickness, but they shall be
is installed. Metal faceplates shall be grounded. Snap permitted to be less than 2.54 mm in thickness iffonned
switches shall be considered to be part of an effective or reinforced to provide adequate mechanical strength.
ground-fault current path if either of the following
conditions is met: 4.4.1.10 Mounting of Snap Switches.
(1) The switch is mounted with metal screws to (A) Surface Type. Snap switches used with open wiring
a metal box or metal cover that is connected on insulators shall be mounted on insulating material
to an equipment grounding conductor or to that separates the conductors at least 13 mm from the
a nonmetallic box with integral means for surface wired over.
connecting to an equipment grounding conductor.
(B) Box Mounted. Flush-type snap switches mounted
(2) An equipment grounding conductor or equipment in boxes that are set back of the finished surface as
bonding jumper is connected to an equipment permitted in 3.14.2.6 shall be installed so that the
grounding termination of the snap switch. extension plaster ears are seated against the surface.
Flush-type snap switches mounted in boxes that are
Exception No. 1 to (BJ: Where no means exists within the
flush with the finished surface or project from it shall
snap-switch enclosure for connecting to the equipment
be installed so that the mounting yoke or strap of the
grounding conductor, or where the wiring method
switch is seated against the box. Screws used for the
does not include or provide an equipment grounding
purpose of attaching a snap switch to a box shall
conductor, a snap switch without a connection to an
be of the type provided with a listed snap switch,
equipment grounding conductor shall be pemzitted f or
or shall be machine screws having 32 threads per
replacement purposes on(Y. A snap s1vitch v.:ired under
inch or part of listed assemblies or systems, m
the provisions o_fthis exception and located ·within 2 500
accordance with the manufacturer's instructions.
mm vertical!;~ or 1 500 mm horizontally, of ground or
exposed grounded metal obj ects shall be provided with
4.4.1.11 Circuit Breakers as Switches. A hand-
a fa ceplate of nonconducting noncombustible material
operable circuit breaker equipped with a lever or handle,
with nonmetallic attachment screws, unless the switch
or a power- operated circuit breaker capable of being
mounting strap or yoke is nonmetallic or the circuit is
opened by hand in the event of a power failure, shall
protected by a ground-fault circuit interrupter.
be permitted to serve as a switch if it has the required
Exception No. 2 to (BJ: Listed kits or listed assemblies number of poles.
shall not be required to be connected to an equipment FPN: See the provisions contained in 2.40.7.2 and 2.40.7.4.
grounding conductor if all of the following conditions
are met: 4.4.1.12 Grounding of Enclosures. Metal enclosures
(JJ The device is provided with a nonmetallic for switches or circuit breakers shall be connected to
faceplate that cannot be installed on any other an equipment grounding conductor as specified in Part
type of device, 2.50.4. Metal enclosures for switches or circuit breakers
used as service equipment shall comply with the
(2) The device does not have mounting means to
provisions of Part 2.50.5. Where nonmetallic enclosures
accept other configurations offaceplates,
are used with metal raceways or metal-annored cables,
(3) The device is equipped with a nonmetallic yoke, provision shall be made for connecting the equipment
and grounding conductor(s).
(4) All parts of the device that are accessible after Except as covered in 4.4.1.9(b), Exception No. 1,
installation of the faceplate are manufactured of nonmetallic boxes for switches shall be installed with a
nonmetallic materials. wiring method that provides or includes an equipment
grounding conductor.
Exception No. 3 to (BJ: A snap switch with integral
nonmetallic enclosure complying with 3.0.l.l 5(e) shall
4.4.1.13 Knife Switches.
be permitted without a connection to an equipment
grounding conductor. (A) Isolating Switches. Knife switches rated at over
1200 amperes at 250 volts or less, and at over 1 000
(C) Construction. Metal faceplates shall be of ferrous
amperes at 251 to 1000 volts, shall be used only as
metal not less than O. 76 mm in thickness or of nonfe1Tous
isolating switches and shall not be opened under load.
metal not less than 1.02 mm in thickness. Faceplates
293
ARTICLE 4.4 - SWITCHES
(B) To Interrupt Currents. To interrupt currents over 1 shall be listed and shall be used only for controlling the
200 amperes at 250 volts, nominal, or less, or over 600 loads permitted by (d)(l) and (d)(2).
amperes at 251 to 600 volts, nominal, a circuit breaker
(1) Noninductive Loads. oninductive loads other
or a switch of special design listed for such purpose
than tungsten-filament lamps not exceeding the
shall be used.
ampere and voltage ratings of the switch.
(C) General-Use Switches. Knife switches of ratings
(2) Inductive Loads. Inductive loads not exceeding
less than specified in 4.4.1.13(a) and (b) shall be
the ampere and voltage ratings of the switch.
considered general-use switches.
Where particular load characteristics or limitations
FPN: See the definition of General-Use Switch in Article 1.1. are specified as a condition of the listing, those
(D) Motor-Circuit Switches. Motor-circuit switches re triction shall be observed regardless of the
shall be permitted to be of the knife-switch type. ampere rating of the load.

FPN: See the definition of a Motor-Circuit Switch in Article 1.1. The ampere rating of the switch shall not be less
than 15 ampere· at a voltage rating of 347 volts ac.
4.4.1.14 Rating and Use of Snap Switches. Switches Flush-type snap switches rated 347 volts ac shall
shall be used within their ratings and as indicated in not be readily interchangeable in box mounting with
4.4.l .14(A) through (F). switche identified in -1-.4.l.14(a) and (b).
FPN No. 1: For switches on signs and outline lighting, see 6.0. 1.6. (E) Dimmer S,\'itches. General-use dimmer switches
FPN No. 2: For switches controlling motors, see 4.30.7.3, shall be used only to control pennanently installed
4.30.9.9, and 4.30.9 .10. incandescent luminaire , unle ·: listed for the control of
other load and in talled a cordingl y.
(A) Alternating-Current General-Use Snap Switch.
A form of general-use snap switch suitable only for use (F) Cord- and Plug-Connected Loads. Where a
on ac circuits for controlling the following: snap switch or control deYi e i u · d to control cord-
and plug-connected equipment on a general-purpose
(1) Resistive and inductive loads not exceeding the
branch circuit, each snap witch o ontrol de\ ice
ampere rating of the switch at the voltage applied
controlling receptacle outlet or ord connectors that
(2) Tungsten-filament lamp loads not exceeding the are supplied by permanently conne ted cord pendants
ampere rating of the switch at 230 or 115 volts shall be rated at not less than th rating of the maximum
(3) Motor loads not exceeding 80 percent of the permitted ampere rating or etting of the O\·ercurrent
ampere rating of the switch at its rated voltage device protecting the receptacle or cord connector ,
as provided in 2.10.2.4(b).
(B) Alternating-Current or Direct-Current General-
FP 1: See 2.10.3. 1(a) and 4.0. J. J O( a )( l ) fo r equi ·a!ency to
Use Snap Switch . A fonn of general-use snap switch a receptacle outlet of a cord connector that i ,upplied by a
suitable for use on either ac or de circuits for controlling permanentl y connected cord pendant.
the following:
Exception: Wh ere a snap switch or control device
(1) Resistive loads not exceeding the ampere rating is used to control not more than one receptacle 0 11 a
of the switch at the voltage applied. branch circuit, the switch or control device shall be
(2) Inductive loads not exceeding 50 percent of the permitted to be rated at not less than the rating of the
ampere rating of the switch at the applied voltage. receptacle.
Switches rated in horsepower are suitable for
controlling motor loads within their rating at the 4.4.2 Construction Specifications
voltage applied.
4.4.2.1 Marking.
(3) Tungsten-filament lamp loads not exceeding the
ampere rating of the switch at the applied voltage (A) Ratings. Switches shall be marked with the current,
ifT-rated. voltage, and, if horsepower rated, the maximum rating
for which they are designed.
(C) CO/ALR Snap Switches. Snap switches rated
20 amperes or less directly connected to aluminum (B) Off Indication. Where in the off position, a
conductors shall be listed and marked CO/ALR. switching device with a marked OFF position shall
completely disconnect all ungrounded conductors to the
(D) Alternating-Current Specific-Use Snap Switches load it controls.
Rated for 347 Volts. Snap switches rated 347 volts ac

294
ARTICLE 4.6 - RECEPTACLES, CORD CONNECTORS AND ATTACHMENT PLUGS (CAPS)
4.4.2.3 Electronic Lighting Control Switches. 4.6.1.3 Receptacle Rating and Type.
Electronic lighting control switches shall be listed. (A) Receptacles. Receptacles shall be listed and
Electronic lighting control switches shall not introduce marked with the manufacturer's name or identification
current on the equipment ground- ing conductor during and voltage and ampere ratings.
normal operation. The requirement to not introduce
(B) Rating. Receptacles and cord connectors shall be
current on the equipment grounding conductor shall
rated not less than 15 amperes, 125 volts, or 15 amperes,
take effect on January 1, 2020.
250 volts, and shall be of a type not suitable for use as
Exception: Electronic lighting control switches lampholders.
that introduce current on the equipment grounding FPN: See 2.10.2.4(B) for receptacle ratings where installed on
conductor shall be permitted for applications covered branch circuits.
by 4.4.l.2(C), Exception. Electronic lighting control
switches that introduce current on the equipment (C) Receptacles for Aluminum Conductors.
grounding conductor shall be listed and marked for use Receptacles rated 20 amperes or less and designed for
in replacement or retrofit applications only. the direct connection of aluminum conductors shall be
marked CO/ALR.
4.4.2. 7 Knife Switches Rated 600 to 1 000 Volts. (D) Isolated Ground Receptacles. Receptacles
Auxiliary contacts of a renewable or quick-break type incorporating an isolated grounding conductor
or the equivalent shall be provided on all knife switches connection intended for the reduction of electrical
rated 600 to 1 000 ·olts and designed for use in breaking noise (electromagnetic interference) as permitted in
current over 200 amperes. 2.50.7.17(D) shall be identified by an orange triangle
located on the face of the receptacle.
4.4.2.8 Fused Switches. A fused switch shall not haYe
(1) Isolated Equipment Grounding Conductor
fuses in parallel except as permitted in 2.40.1.8.
Required. Receptacles so identified shall be used
only with equipment grounding conductors that
4.4.2.9 Wire-Bending Space. The wire-bending
are isolated in accordance with 2.50. 7.17 (D).
space required by 4.4.1.3 shall meet Table 3.12.1.6(b)
spacings to the enclosure wall opposite the line and load (2) Installation in :\"onmetallic Boxes. Isolated
te1minals. ground receptacles installed in nonmetallic boxes
shall be covered with a nonmetallic faceplate.
ARTICLE 4.6 - RECEPTACLES, CORD
Exception: Where an isolated ground receptacle is
CONNECTORS, AND ATTACHMENT PLUGS
installed in a nonmetallic box, a meral faceplate shall
(CAPS)
be permitted if the box contains a f eature or accessory
that permits the effective grounding of the faceplate.
4.6.1.1 Scope. This article covers the rating, type,
and installation of receptacles, cord connectors, and (E) Controlled Receptacle Marking. All nonlocking-
attachment plugs (cord caps). type, 125- or 250-volt, 15- and 20-ampere receptacles
that are controlled by an automatic control device, or
4.6.1.2 Definitions. that incorporate control feature s that remo-ve power from
the receptacle for the purpose of energy management or
Child Care Facility. A building or structure, or portion
building automation, shall be permanently marked with
thereof, for educational, supervisory, or personal care
the symbol shown in Figure 4.6. l .3 (E) and the word
services for more than four children 7 years old or less.
"controlled."
Outlet Box Hood. A housing shield intended to fit over
For receptacles controlled by an automatic control
a faceplate for flush-mounted wiring devices, or an
device, the marking shall be located on the receptacle
integral component of an outlet box or of a faceplate for
face and visible after installation.
flush-mounted wiring devices. The hood does not serve
to complete the electrical enclosure; it reduces the risk In both cases where a multiple receptacle device is
of water coming in contact with electrical components used, the required marking of the word "controlled"
within the hood, such as attachment plugs, current taps, and symbol shall denote which contact device(s) are
surge protective devices, direct plug-in transfonner controlled.
units, or wiring devices. Exception: The marking shall not be required for
receptacles controlled by a wall switch that provide the
required room lighting outlets as permitted by 2.10.3. 21.
295
ARTICLE 4.6 - RECEPTACLES, CORD CONNECTORS AND ATTACHMENT PLUGS (CAPS)
(F) Receptacle with USB Charger. A 125- or 250-volt, (1) Grounding-Type Receptacles. Where a
15- or 20-ampere receptacle that additionally provides grounding means exists in the receptacle enclosure
Class 2 power shall be listed and constructed such that or an equipment grounding conductor is installed
the Class 2 circuitry is integral with the receptacle. in accordance with 2.50.7.l(C), grounding-type
receptacles shall be used and shall be connected

C)
Controlled
to the equipment grounding conductor in
accordance with 4.6. l.4(C) or 2.50.7 .1 (C).

Figure 4.6.1.3(E) Controlled Receptacle Marking (2) Non-Grounding-Type Receptacles. Where


Symbol. attachment to an equipment grounding conductor
4.6.1.4 General Installation Requirements. does not exist in the receptacle enclosure, the
Receptacle outlets shall be located in branch circuits installation shall comply with (D)(2)(a), (D)(2)
in accordance with Part 2.10.3. General installation (b), or (D)(2)(c).
requirements shall be in accordance with 4.6.1.4(A) a. A non-grounding-type receptacle(s) shall be
through (F). per-mitted to be replaced with another non-
(A) Grounding Type. Except as provided in 4.6.1.4(D), grounding-type receptacle(s).
receptacles installed on 15- and 20-ampere branch A on-grounding-type receptacle(s) shall be
circuits shall be of the grounding type. Grounding- permitted to be replaced with a ground-fault
type receptacles shall be installed only on circuits of ir i interrupter-type of receptacle(s). These
the voltage class and current for which they are rated, "a les or -heir cover plates shall be marked
except as provided in Table 2.10.2.4(B)(2) and Table ··:-;:o Eq · ment Gro nd." An equipment
2.10.2.4(B)(3 ). ct· g conduc or shall not be connected
(B) To Be Grounded. Receptacles and cord connector . om e gro d-fault circuit-interrupter-type
that have equipment grounding conductor contact r - le o any outlet supplied from the
shall have those contacts connected to an equiprnen· gro d-fault circuit-interrupter receptacle.
grounding conductor. A non-grounding-type receptacle(s) shall be
Exception No. I : Receptacles mounted on ponab e per-mitted to be replaced with a grounding-
and vehicle-mounted generators in accordance wi h type receptacle(s) where supplied through
2.50.2.15. a ground-fault circuit interrupter. Where
grounding-type receptacles are supplied
Exception No. 2: Replacement receptacles as permitted through the ground-fault circuit interrupter,
by 4.6.l.4(D). grounding-type receptacles or their cover plates
(C) Methods of Grounding. The equipment grounding shall be marked "GFCI Protected" and "No
conductor contacts of receptacles and cord connectors Equipment Ground," visible after installation.
shall be grounded by connection to the equipment An equipment grounding conductor shall not
grounding conductor of the circuit upplying the be connected between the grounding-type
receptacle or cord connector. receptacles.
FPN: For installation requirement for the reducrion of electrical FPN No. 1: Some equipment or appliance manufacturers require
noise, see 2.50.7. l 7(D). that the branch circuit to the equipment or appliance includes an
equipment grounding conductor.
The branch-circuit wiring method shall include or FPN No. 2: See 2.50.6.5 for a list of a cord-andplug-connected
pro-vide an equipment grounding conductor to which equipment or appliances that require an equipment grounding
the equipment grounding conductor contacts of the conductor.
receptacle or cord connector are connected.
(3) Ground-Fault Circuit Interrupters. Ground-
FPN No. 1: See 2.50.6.9 for acceptable grounding means. fault circuit-interrupter protected receptacles
FPN No. 2: For extensions of existing branch circuits, see shall be provided where replacements are made
2.50. 7.1. at receptacle outlets that are required to be so
(D) Replacements. Replacement of receptacles shall protected elsewhere in this Code.
comply with 4.6.1.4(D)(l) through (D)(6), as applicable. Exception: Where replacement of the receptacle type
Ground-fault circuit interrupter type receptacles shall is impracticable, such as where the outlet box size will
be installed in a readily accessible location. not permit the installation of the GFCI receptacle,
the receptacle shall be p ermitted to be replaced with
296
ARTICLE 4.6 - RECEPTACLES , CORD CONNECTORS AND ATTACHMENT PLUGS (CAPS)
a new receptacle of the existing type, where GFCI be a device assembly or box cover listed and identified
protection is provided and the receptacle is marked for securing by a single screw.
"GFCI Protected" and "No Equipment Ground,"
(D) Position of Receptacle Faces. After installation,
in accordance with 4.6.J.4(D)(2) (a), (b), or (c), as
receptacle faces shall be flush with or project from
applicable.
faceplates of insulating material and shall project a
(4) Tamper-Resistant Receptacles. Listed tamper- minimum of 0.4 mm from metal faceplates,
resistant receptacles shall be provided where
Exception: Listed kits or assemblies encompassing
replacements are made at receptacle outlets that
receptacles and nonmetallic faceplates tha.t cover the
are required to be tamper-resistant elsewhere
receptacle face, where the plate cannot be installed on
in this Code, except where a non-grounding
any other receptacle, shall be permitted.
receptacle is replaced with another non-grounding
receptacle. (E) Receptacles in Countertops. Receptacle assemblies
for installation in countertop surfaces shall be listed for
(5) Weather-Resistant Receptacles. Weather-
countertop applications.Where receptacle assemblies
resistant receptacles shall be provided where
for countertop applications are required to provide
replacements are made at receptacle outlets that
ground-fault circuit-interrupter protection for personnel
are required to be so protected elsewhere in this Code.
in accordance with 2.10.1.8, such assemblies shall be
(E) Cord- and Plug-Connected Equipment. The permitted to be listed as GFCI receptacle assemblies for
installation of grounding-type receptacles shall not be countertop applications.
used as a requirement that all cord-and plug-connected
(F) Receptacles in Work Surfaces. Receptacle
equipment be of the grounded type.
assemblies and GFCI receptacle assemblies listed
FPN: See 2.50.6.5 for types of cord-and plug-connected for work surface or countertop applications shall be
equipment to be grounded. permitted to be installed in work surfaces.
(F) Noninterchangeable Types. Re eptacles connected (G) Receptacle Orientation. Receptacles shall not
to circuits that have different voltages, frequencies, or be installed in a face-up position in or on counte1iop
types of current ( ac or de) on the ame premises shall be surfaces or work surfaces unless listed for countertop or
of such design that the atta hm m plug used on these work surface applications.
circuits are not interchangeable.
(H) Receptacles in Seating Areas and Other Similar
4.6.1.5 Receptacle Mounting. Rec ptacles shall be Surfaces. In seating areas or similar surfaces,
mounted in identified boxes or a emblies. The boxes receptacles shall not be installed in a face-up position
or assemblies shall be securely fast ned in place unless unless the receptacle is any of the following:
otherwise permitted elsewhere in thi Code. Screws ( 1) Part of an assembly listed as a furniture power
used for the purpose of attaching receptacles to a box distribution unit, if cord-and plug-connected
shall be of the type provided ,vith a li ted receptacle,
or shall be machine screws having 3 ... thread per inch (2) Part of an assembly listed either as household
or part of listed assemblies or system , in accordance furnishings or as commercial furnishings
with the manufacturer's instructions. (3) Listed either as a receptacle assembly for
(A) Boxes That Are Set Back. Receptacles mounted countertop applications or as a GFCI receptacle
in boxes that are set back from the finished surface as assembly for countertop applications
pennit- ted in 3.14.2.6 shall be installed such that the (4) Installed in a listed floor box
mounting yoke or strap of the receptacle is held rigidly
(I) Exposed Terminals. Receptacles shall be enclosed
at the finished surface.
so that live wiring terminals are not exposed to contact.
(B) Boxes That Are Flush. Receptacles mounted in
(J) Voltage Between Adjacent Devices. A receptacle
boxes that are flush with the finished surface or project
shall not be grouped or ganged in enclosures with other
therefrom shall be installed such that the mounting yoke
receptacles, snap switches, or similar devices, unless
or strap of the receptacle is held rigidly against the box
they are arranged so that the voltage between adjacent
or box cover.
devices does not exceed 300 volts, or unless they
(C) Receptacles Mounted on Covers. Receptacles are installed in enclosures equipped with identified,
mounted to and supported by a cover shall be held securely installed ba.ITiers between adjacent devices.
rigidly against the cover by more than one screw or shall

297
ARTICLE 4.6 - RECEPTACLES, CORD CONNECTORS AND ATTACHMENT PLUGS (CAPS)
4.6.1.6 Receptacle Faceplates (Cover Plates). 4.6.1.8 Noninterchangeability. Receptacles, cord
Receptacle faceplates shall be installed so as to completely connectors, and attachment plugs shall be constructed
cover the opening and seat against the mounting surface. such that receptacle or cord connectors do not accept an
attachment plug with a different voltage or current rating
Receptacle faceplates mounted inside a box having a
from that for which the device is intended. However, a
recess-mounted receptacle shall effectively close the
20-ampere T-slot receptacle or cord connector shall be
opening and seat against the mounting surface.
pennitted to accept a 15-ampere attachment plug of the
(A) Thickness of Metal Faceplates. Metal faceplates same voltage rating. Non-grounding-type receptacles
shall be of ferrous metal not less than 0.76 mm in and connectors shall not accept grounding-type
thickness or of nonferrous metal not less than 1.02 mm attachment plugs.
in thickness.
4.6.1.9 Receptacles in Damp or Wet Locations.
(B) Grounding. Metal faceplates shall be grounded.
(A) Damp Locations. A receptacle installed outdoors in
(C) Faceplates of Insulating Material. Faceplates of a location protected from the weather or in other damp
insulating material shall be noncombustible and not less locations shall ha...-e an enclosure for the receptacle
than 2.54 mm in thickness but shall be permitted to be that in weatherproof \,.·he the re eptacle is co\·ered
less than 2.54 mm in thickness if formed or rein- forced (attach.me pug cap o erred and receptacle coYers
to provide adequate mechanical strength. closed).
(D) Receptacle Faceplate (Cover Plates) with An i a ·on 'table for wet locations shall also be
Integral Night Light and/or USB Charger. A fl o ·dered suitable for damp locations.
device cover plate that additionall; proYides a nigh
_-\ re eptacle shall be considered to be in a location
light and/or Class 2 output connecto ) ~hall be ·-ted
. -ec ed from the weather where located under
and constructed such that the night ligh- an ·o C ass
roo ed open porches, canopies, marquees, and the
2 circuitry is integral with the flush deYi
like, and will not be subjected to a beating rain or
4.6.1.7 Attachment Plugs, Cord Connectors., and wa-er runoff. All 15- and 20-ampere, 125- and 250-
Flanged Surface Devices. All attach.me pl Yolt nonlocking receptacles shall be a listed weather-
cord connectors, and :flanged surface deYices C ets resistant type.
and outlets) shall be listed and marked ·wi he FPN: The types of receptacles covered by this requirement are
manufacturer's name or identification and voltage and identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD
ampere ratings. 6-2012, Wiring Devices - Dimensional Specifications.

(A) Construction of Attachment Plugs and Cord (B) Wet Locations.


Connectors. Attachment plugs and cord connectors (1) Receptacles of 15 and 20 Amperes in a Wet
shall be constructed so that there are no exposed Location. Receptacles of 15 and 20 amperes
current-carrying parts except the prongs, blades, or installed in a wet location shall have an enclosure
pins. The cover for wire terminations shall be a part that that is weatherproof whether or not the attachment
is essential for the operation of an attachment plug or plug cap is inserted. An outlet box hood installed
connector (dead-front construction). for this purpose shall be listed and shall be
identified as "extra duty." Other listed products,
(B) Connection of Attachment Plugs. Attachment
enclosures, or assemblies providing weatherproof
plugs shall be installed so that their prongs, blades, or
protection that do not utilize an outlet box hood
pins are not energized unless inserted into an energized
need not be marked "extra duty."
receptacle or cord connectors. No receptacle shall be
installed so as to require the insertion of an energized FPN No. 1: Requirements for extra-duty outlet box hoods are
found in ANSI/UL 5l4D-2013, Cover Plates for Flush-Mounted
attachment plug as its source of supply. Wiring Devices. . "Extra duty" identification and requirements
(C) Attachment Plug Ejector Mechanisms. are not applicable to listed receptacles, faceplates, outlet boxes,
enclosures, or assemblies that are identified as either being suitable
Attachment plug ejector mechanisms shall not adversely for wet locations or rated as one of the outdoor enclosure-type
affect engagement of the blades of the attachment plug numbers of Table 110.28 that does not utilize an outlet box hood.
with the contacts of the receptacle. Exception: 15- and 20-ampere, 125- through 250-volt
(D) Flanged Surface Inlet. A flanged surface inlet receptacles installed in a wet location and subject to
shall be installed such that the prongs, blades, or pins routine high-pressure spray washing shall be permitted
are not energized unless an energized cord connector is to have an enclosure that is weatherproof when the
inserted into it. attachment plug is removed.
298
ARTICLE 4.6 - RECEPTACLES, CORD CONNECTORS AND ATTACHMENT PLUGS (CAPS)
All 15- and 20-ampere, 125- and 250-volt nonlocking- (2) A green-colored pressure wire connector body (a
type receptacles shall be listed and so identified as the wire barrel).
weather-resistant type.
(3) A similar green-colored connection device, in
FPN No. 2: The types of receptacles covered by this requirement the case of adapters. The grounding terminal
are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA
of a grounding adapter shall be a green-colored
WD 6-2002, Standard for Dimensions of Attachment Plugs and
Receptacles. rigid ear, lug, or similar device. The equipment
grounding connection shall be so designed that it
(2) Other Receptacles. All other receptacles cannot make contact with current-carrying parts
installed in a wet location shall comply with (B) of the receptacle, adapter, or attachment plug.
(2)(a) or (B)(2)(b). The adapter shall be polarized.
a. A receptacle installed in a wet location, where (4) If the terminal for the equipment grounding
the product intended to be plugged into it is not conductor is not visible, the conductor entrance
attended while in use, shall have an enclosure bole shall be marked with the word green or
that is weatherproof with the attachment plug ground, the letters G or GR, a grounding symbol,
cap inserted or removed. or otherwise identified by a distinctive green
b. A receptacle installed in a wet location where color. If the terminal for the equipment grounding
the product intended to be plugged into it will conductor is readily removable, the area adjacent
be attended while in use (e.g., portable tools) to the terminal shall be similarly marked.
shall have an enclosure that is weatherproof FPN: See FPN Figure 4.6.l.10(B)(4).
when the attachment plug is removed.
(C) Grounding Terminal Use. A grounding terminal
(C) Bathtub and Shower Space. Receptacles shall not shall not be used for purposes other than grounding.
be installed within or directly over a bathtub or shower
(D) Grounding-Pole Requirements. Grounding-
stall.
!) pe attachment plugs and mating cord connectors and
(D) Protection for Floor Receptacles. Standpipes of receptacles shall be designed such that the equipment
floor receptacles shall allow floor-cleaning equipment grounding connection is made before the current-
to be operated without damage to recepta les. carrying connections. Grounding-type devices shall be
(E) Flush Yiounting with Faceplate. The enclosure for so designed that grounding poles of attachment plugs
a receptacle installed in an outlet box flush-mounted in cannot be brought into contact with current-carrying
a finished hall be made weatherproof b means of parts of receptacles or cord connectors.
f ra ep are assembly that provides a watertight (E) Use. Grounding-type attachment plugs shall be
co ,·een the plate and the finished surface. used only with a cord having an equipment grounding
4.6.1.10 Grounding-Type Receptacles, Adapters, conductor.
Cord Connectors, and Attachment Plugs. FPN: See 2.50.6.14 for identification of grounding conductor
terminals.
(A) Grounding Poles. Grounding-type receptacles,
cord onnecrors, and attachment plugs shall be provided 4.6.1.11 Connecting Receptacle Grounding Terminal
·wi one fixed grounding pole in addition to the circuit to Box. The connection of the receptacle grounding
pole-. The grounding contacting pole of grounding- terminal shall comply with 2.50.7.17.
type plug-in ground-fault circuit interrupters shall be 4.6.1.12 Tamper-Resistant Receptacles. All 15-
permitted to be of the movable, self-restoring type on and 20-ampere, 125- and 250-volt nonlocking-type
circuits operating at not over 150 volts between any two receptacles in the areas specified in 4.6.1.12(1) through
conductors or any conductor and ground. (7) shall be listed tamper-resistant receptacles.
(B) Grounding-Pole Identification. Grounding-type (1) Dwelling units in all areas specified in 2.10.3.3
receptacles, adapters, cord connections, and attachment and 5.50.2.4
plugs shall have a means for connection of an equipment
grounding conductor to the grounding pole. (2) Guest rooms and guest suites of hotels and motels

A terminal for connection to the grounding pole shall be (3) Child care facilities
designated by one of the following: (4) Preschools and elementmy education facilities
(1) A green-colored hexagonal-headed or -shaped
terminal screw or nut, not readily removable.
299
ARTICLE 4.8 - SWITCHBOARDS, SWITCHGEARS AND PANELBOARDS
hazardous (classified) locations shall comply \Vith the

® FPN Figure 4.6.1.10(B)(4) One Example of a


applicable provisions of Articles 5.0 through 5.17.

4.8.1.3 Support and Arrangement of Busbars and


Conductors.
Symbol Used to Identify the Termination Point for
an Equipment Grounding Conductor. (A) Conductors and Busbars on a Switchboard,
( 5) Business offices, corridors, waiting rooms and Switchgear, or Panelboard. Conductors and bus bars on
the like in clinics, medical and dental offices and a switchboard, switchgear, or panelboard shall comply
outpatient facilities with 4.8. l.3(A)(l ), (A)(2), and (A)(3) as applicable.

( 6) Subset of assembly occupancies described (1) Location. Conductors and busbars shall be located
in 5 .18.1.2 to include places of waiting so as to be free from physical damage and shall
transpo1iation, gymnasiums, skating rinks, and be held finnly in place.
auditoriums (2) Service Panelboards, Switchboards and
(7) Dormitories S·nitchgear. Baniers shall be placed in all service
panelboards. -,\·itchboards and switchgear such
FPN: This requirement would include receptacles identified as
5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2016, TViring that no ur insulated. uns>rounded service busbar
Devices - Dimensional Specifications. or ef\"ice terminal is exposed to inadvertent
contact by . er:-.on - or maintenance equipment
Exception to (1), (2), (3), (4), (5), (6), and (7) :
whil ·en-i ing oad t rminations.
Receptacles in the following locations shall not be
required to be tamper resistant: (3) Same Yertical Section. Other than the required
interconne rions and ' ontrol \\·iring, only those
(I) Receptacles located more than I 700 mm above
conductors that are in ended for tem1ination in
the.floor.
a Y ni al ection of a ·v,·itchboard or S\Vitchgear
(2) Receptacles that are part of a luminaire or shall be located in tha- -ec ion.
appliance.
Exception: n is requirement shall not appZr to service
(3) A single receptacle or a duplex receptacle for two pane/boar is ~\-i } p rm·is ·ons for more than anl! service
appliances located within the dedicated space disconnecr . i · ·-hin a sina e enclosure as permitted in
for each appliance that, in normal use, is not 4.8.3.7, Excep ions i, ~, and 3.
easily moved from one place to another and that
(B) Overheating and Inductive Effects. The
is cord-and plug-connected in accordance with
arrang men- of usbars and conductors shall be such as
4.0.l .lO(A)(6), (A)(7), or (A)(8) .
to amid o,;er-- ating due to inductive effects.
(4) Nongrounding receptacles used for replacements
(C) "Csed a Senice Equipment. Each switchboard,
as permitted in 4.6.l.4(D)(2)(a).
S\\·itchgear. or anel oard. if used as service equipment,
shall be proYided \:\·irh a main bonding jumper sized in
ARTICLE 4.8 - SWITCHBOARDS,
accordan e ,,ith ~.: 0.- .9{D) or the equivalent placed
SWITCHGEAR, AND PANELBOARDS
within the panelboard or one of the sections of the
switchboard or ,\·it hg ar for connecting the grounded
4.8.1 General
ervice conductor on it supply side to the switchboard,
s,Yitchgear. or panelboard frame. All sections of a
4.8.1.1 Scope. This aiiicle covers switchboards,
switchboard or witchgear shall be bonded together
switchgear, and panelboards. It does not apply to
using an equipment bonding jumper or a suppiy-side
equipment operating at over l 000 volts, except as
bonding jumper sized in accordance with 2.50.6.13 or
specifically referenced elsewhere in the Code.
Table 2.50.5.13 as appropriate.
4.8.1.2 Other Articles. Switches, circuit breakers, and Exception: Switchboards, switchgem: and pane/boards
overcurrent devices used on switchboards, switchgear, used as service equipment on high-impedance grounded
and panelboards and their enclosures shall comply neutral systems in accordance with 2.50.2.17 shall not
with this article and also with the requirements of be required to be provided with a main bonding jumper:
Articles 2.40, 2.50, 3. 12, 4.4, and other articles that
(D) Terminals. In switchboards, switchgear, and
apply. Switchboards, switchgear, and panelboards in
panelboards, load tenninals for field wiring, including

300
ARTICLE 4.8 - SWITCHBOARDS, SWITCHGEARS AND PANELBOARDS
grounded circuit conductor load te1111inals and system in accordance with 2.50.2.1 7 shall be legibly
connections to the equipment grounding conductor and pem1anently field marked as follows:
bus for load equipment grounding conductors, shall
CAUTION: HIGH-IMPEDANCE GROUNDED
be so located that it is not necessary to reach across
NEUTRAL AC SYSTEM OPERATING - VOLTS
or beyond an uninsulated ungrounded bus in order to
BETWEEN CO DUCTORS AND MAY OPERATE
make connections.
- VOLTS TO GROUND FOR INDEFINTTE
(E) Bus Arrangement. PERIODS UNDER FAULT CONDITIONS
(1) AC Phase Arrangement. Alternating-current (4) Ungrounded DC Systems. A switchboard,
phase arrangement on 3-phase buses shall be A, switchgear, or panelboard containing an ungrounded
B, C from front to back, top to bottom, or left to de electrical system in accordance with 2.50.8.10
right, as viewed from the front of the switchboard, shall be legibly and permanently field marked as
switchgear, or panelboard. The B phase shall be follows:
that phase having the higher voltage to ground on CAUTION: UNGROUNDED DC SYSTEM
3-phase, 4-wire, delta-connected systems. Other OPERATING - VOLTS BETWEEN
bus bar arrangements shall be pem1itted for additions CONDUCTORS
to existing installations and shall be marked.
(5) Resistively Grounded DC Systems. A
Exception: Equipment within the same single section or switchboard, switchgear, or panelboard
multisection switchboard, switchgear, or pane/board as containing a resistive connection between
the meter on 3-phase, 4-wire, delta-connected systems current-canying conductors and the grounding
shall be permitted to have the same phase configuration system to stabilize voltage to ground shall be
as the metering equipment. legibly and permanently field marked as follows:
FPN: See 1.10.1.15 for requirements on marking the busbar CAUTION: DC SYSTEM OPERATING- VOLTS
or phase conductor having the higher \'Oltage to ground where
supplied from a 4-wire, delta-connected . stem.
BETWEEN CO TDUCTORS A .D MAY OPERATE
- VOLTS TO GRO D FOR INDEFINITE
(2) DC Bus Arrangement. Direct-current PERJODS Ui .DER FAULT CONDITIONS
ungrounded buse. hall be permitted to be in any
order. Arrangement of de buses hall be field (G) .'.\Iinimum Wire-Bending Space. The minimum
marked a to polarity. grounding sy r m. and wire-bending space at terminals and minimum gutter
nominal rnltage. space provided in switchboards, switchgear, and
panelboards shall be as required in 3.12.1.6.
(F) s,,itchboard. s,,itchgear. or Panelboard
Identification. A caution sign( ) or a lab~!{ ) p oYided 4.8.1.4 Field Identification Required.
in accordance ·with 4. . l.3(F) l ) through (F)( 5) shall (A) Circuit Directory or Circuit Identification.
comply with 1.1 0.1._ l(B). Every circuit and circuit modification shall be legibly
identified as to its clear, evident, and specific purpose or
(1) High-Leg Identification. A --it hboard,
use. The identification shall include a degree of detail
switchgear, or panelboard containing a -\\·ire.
that allows each circuit to be distinguished from all
delta-connected system wh re the midpoint of
others. Spare positions that contain unused overcurrent
one phase winding is grounded shall be legibly
devices or switches shall be described accordingly. The
and permanently field marked as follmYs:
identification shall be included in a circuit directory
"Caution Phase Has Volts to Ground" that is located on the face or inside of the panel door in
the case of a panelboard and at each switch or circuit
(2) Ungrounded AC Systems. A switchboard,
breaker in a switchboard or switchgear. No circuit shall
switchgear, or panelboard contammg an
be described in a manner that depends on transient
ungrounded ac electrical system as permitted in
conditions of occupancy.
2.50.2.2 shall be legibly and permanently field
marked as follows : (B) Source of Supply. All switchboards, switchgear,
and panelboards supplied by a feeder(s) in other than
"Caution Ungrounded System Operating - Volts
one- or two-family dwellings shall be permanently
Between Conductors"
marked to indicate each device or equipment where the
(3) High-Impedance Grounded Neutral AC power originates. The label shall be permanently affixed,
System. A switchboard, switchgear, or panelboard of sufficient durability to withstand the environment
containing a high- impedance grounded neutral ac involved, and not handwritten.
301
ARTICLE 4.8 - SWITCHBOARDS, SWITCH GEARS AND PANELBOARDS
4.8.1.5 Clearance for Conductor Entering Bus 4.8.2.4 Conductor Insulation. An insulated
Enclosures. Where conduits or other raceways enter a used within a switchboard or switchgear ha!
switchboard, switchgear, floor-standing panelboard, or shall be flame retardant, and shall be rated not les rha
similar enclosure at the bottom, approved space shall the voltage applied to it and not less than the ,·olt2.=e
be provided to permit installation of conductors in the applied to other conductors or busbars with which i:
enclosme. The wiring space shall not be less than shown may come into contact.
in Table 4.8.1.5 where the conduit or raceways enter or
4.8.2.5 Location of Switchboards and Switchgear.
leave the enclosure below the bus bars, their supports, or
Switchboards and switchgear that have any exposed
other obstructions. The conduit or raceways, including
live parts shall be located in permanently dry location-
their end fittings, shall not rise more than 75 mm above
and then only where under competent supervision and
the bottom of the enclosure.
accessible only to qualified persons. Switchboards and
Table 4.8.1.5 Clearance for Conductors Entering switchgear shall be located such that the probability of
Bus Enclosures damage from equipment or processes is reduced to a
Minimum Spacing Between mm1murn.
Bottom of Enclosure and 4.8.2.6 Grounding of Instruments, Relays, Meters,
Busbars, Their Supports, and Instrument Transformers on Switchboards
or Other Obstructions and Switchgear. Instruments, relays, meters, and
Conductor (mm) instrument transformers located on switchboards and
Insulated busbars, 200 switchgear shall be grounded as specified in 2.50.9.1
their supports, or through 2.50.9.9.
other obstructions
250 4.8.3 Panelboards
Noninsulated busbars
4.8.3.1 General. All panelboards shall have a rating not
4.8.1.7 Unused Openings. Unused openings for circuit
less than the minimum feeder capacity required for the
breakers and switches shall be closed using identified
load calculated in accordance with Part 2.20.3, 2.20.4,
closures, or other approved means that provide
or 2.20.5 as applicable.
protection substantially equivalent to the wall of the
enclosure. 4.8.3. 7 Overcurrent Protection. In addition to the
requirement of 4.8.3.1, a panelboard shall be protected
4.8.2 Switchboards and Switchgear
by an overcurrent protective device having a rating not
4.8.2.1 Switchboards and Switchgear in Damp or greater than that of the panelboard. This overcurrent
Wet Locations. Switchboards and switchgear in damp protective device shall be located within or at any point
or wet locations shall be installed in accordance with 3.12.1.2. on the supply side of the panelboard.
Exception No. 1: Individual protection shall not be
4.8.2.2 Location Relative to Easily lgnitible Material.
required for a panelboard used as service equipment
Switchboards and switchgear shall be placed so as to
with multiple disconnecting means in accordance
reduce to a minimum the probability of communicating
with 2.30.6.2. In panelboards protected by three or
fire to adjacent combustible materials. Where installed
more main circuit breakers or sets offuses, the circuit
over a combustible floor, suitable protection thereto
breakers or sets offuses shall not supply a second bus
shall be provided.
structure within the same panelboard assemb~y.
4.8.2.3 Clearances.
Exception No. 2: Individual protection shall not be
(A) From Ceiling. For other than a totally enclosed required for a panelboard protected on its supp~y side by
switchboard or switchgear, a space not less than two main circuit breakers or two sets offuses having a
900 mm shall be provided between the top of the combined rating not greater than that ofthe panelboard.
switchboard or switchgear and any combustible ceiling, A panelboard constructed or wired under this exception
unless a noncombustible shield is provided between the shall not contain more than 48 overcurrent devices.
switchboard or switchgear and the ceiling. For the purposes of determining the max imum of 48
(B) Around Switchboards and Switchgear. Clearances
overcurrent devices, a 2-pole or a 3-pole circuit breaker
around switchboards and switchgear shall comply with shall be considered as two or three overcurrent devices,
respectively.
me provi ions of 1.10.2.1
ARTICLE 4.8 - SWITCHBOARDS, SWITCH GEARS AND PANELBOARDS
Exception No. 3: For existing pane/boards, individual to an equipment grounding conductor. Where the
protection shall not be required for a pane/board used panelboard is used with nonmetallic raceway or cable
as service equipment for an individual residential or where separate equipment grounding conductors are
occupancy. provided, a terminal bar for the equipment grounding
conductors shall be secured inside the cabinet. The
(A) Snap Switches Rated at 30 Amperes or Less.
terminal bar shall be bonded to the cabinet and
Panel-boards equipped with snap switches rated at 30
panelboard frame, if of metal; otherwise it shall be
amperes or less shall have overcurrent protection of200
connected to the equipment grounding conductor that is
amperes or less.
run with the conductors feeding the panelboard.
(B) Supplied Through a Transformer. Where a
Exception: Where an isolated equipment grounding
panelboard is supplied through a transformer, the
conductor is provided as permitted by 2.50. 7.17(D), the
overcurrent protection required by 4.8.3.7 shall be
insulated equipment grounding conductor that is run
located on the secondary side of the transformer.
with the circuit conductors shall be permitted to pass
Exception: A pane/board supplied by the secondary side through the pane/board without being connected to the
of a transformer shall be considered as protected by the panelboards equipment grounding terminal bar.
overcurrent protection provided on the primary side of
Equipment grounding conductors shall not be connected
the transformer where that protection is in accordance
to a terminal bar provided for grounded conductors or
with 2.40.2.1(C)(l) .
neutral conductors unless the bar is identified for the
(C) Delta Breakers. A 3-phase disconnect or purpose and is located where interconnection between
overcurrent device shall not be connected to the bus of equipment grounding conductors and grounded circuit
any panelboard that has less than 3-phase buses. Delta conductors is permitted or required by Article 2.50.
breakers shall not be installed in panelboards.
(D) Back-Fed Devices. Plug-in-type overcurrent 4.8.3.12 Grounded Conductor Terminations.
protection devices or plug-in type main lug assemblies Each grounded conductor shall terminate within the
that are backfed and used to terminate field-installed panelboard in an individual terminal that is not also
ungrounded supply conductors shall be secured in place used for another conductor.
by an additional fastener that requires other than a pull Exception: Grounded conductors of circuits with
to release the device from the mounting means on the parallel conductors shall be permitted to terminate
panel. in a single terminal if the terminal is identified for
connection of more than one conductor.
4.8.3.8 Panelboards in Damp or Wet Locations.
Panelboards in damp or we locations hall be installed 4.8.4 Construction Specifications
to compt "\\ith 3.L.l._.
4.8.4.1 Panels. The panels of switchboards and
4.8.3.9 E nclosure. Panelboards shall be mounted in S\Vitchgear shall be made of moisture-resistant,
cabinets, cutout boxes, or identified enclosures and noncombustible material.
shall be dead-front.
Exception: Pane/boards other than of the dead-front, 4.8.4.2 Busbars. Insulated or bare busbars shall be
external(y operable type shall be permitted where rigidly mounted.
accessible only to qualified p ersons.
4.8.4.3 Protection oflnstrument Circuits. Instruments,
4.8.3.10 Relative Arrangement of Switches and pilot lights, voltage (potential) transformers, and other
Fuses. In panelboards, fuses of any type shall be switchboard or switchgear devices with potential
installed on the load side of any switches . coils shall be supplied by a circuit that is protected by
standard over-current devices rated 15 amperes or less.
Excep tion: Fuses installed as part ofservice equipment
in accordance with the provisions of 2.30. 7.5 shall be Exception No. 1: Overcurrent devices rated more than
permitted on the line side of the service switch. 15 amperes shall be permitted where the interruption
of the circuit could create a hazard. Short-circuit
4.8.3.11 Grounding of Panelboards. Panelboard protection shall be provided.
cabinets and panelboard frames, if of metal, shall be in Exception No. 2: For ratings of 2 amperes or less,
physical contact with each other and shall be connected special types of enclosed fuses shall b<; permitted.

303
ARTI CLE 4.8 - SWITCHBOARDS, SWITCH GEARS AND PANELBOARDS
(C) Back Wire-Bending Space. Where a raceway o:-
4.8.4.4 Component Parts. Switches, fuses, and cable entry is in the wall of the enclosure opposite a
fuseholders used on panelboards shall comply with the removable cover, the distance from that wall to th
applicable requirements of Articles 2.40 and 4.4. cover shall be permitted to comply with the distan ~,
required for one wire per terminal in Table 3.12.1 .6(.-\ J.
4.8.4.5 Maximum Number of Overcurrent Devices. The distance between the center of the rear emf\·
A panelboard shall be provided with physical means to and the nearest termination for the entering conductor:
prevent the installation of more overcmTent devices than shall not be less than the distance gi en in Table
that number for which the panelboard was designed, 3.12.1.6(B).
rated, and listed.
4.8.4.7 Minimum Spacings. The distance between
For the purposes of this section, a 2-pole circuit breaker bare metal parts, busbars, and so forth shall not be less
or fusible switch shall be considered two overcurrent than specified in Table 4.8.4.7.
devices; a 3-pole circuit breaker or fusible switch shall
Where close proximity does not cause excessi ve
be considered three overcurrent devices.
heating, parts of the same polarity at switches, enclosed
fuse , and so forth shall be permitted to be placed as
4.8.4.6 Wire-Bending Space Within an Enclosure
close together as convenience in handling will allow.
Containing a Panelboard.
Exception: The distance shall be permitted to he less
(A) Top and Bottom Wire-Bending Space. The
than that specified in Table 4.8.4. 7 at circuit breakers
enclosure for a panelboard shall have the top and
and 1ritches and in listed components installed in
bottom wire-bending space sized in accordance with
sii·itchboards, switchgea,~ and pane/boards·.
Table 3.12.1.6(B) for the largest conductor entering or
leaving the enclosure. Table 4.8.4.7 Minimum Spacings Between Bare
Metal Parts
Exception No. 1: Either the top or bottom ivire-bending
Opposite
space shall be permitted to be sized in accordance it'ith
Polarity
Table 3.12.1.6(A) for a pane/board rated 225 amperes
Where Opposite
or less and designed to contain not over 48 overczm·ent
Mounted Polarity
devices. For the purposes of this exception, a 2-pole or
on the Where Live
a 3-pole circuit breaker shall be considered as t,1,•o or
Same Held Free Parts to
three overcurrent devices, respectivezv.
Surface in Air Ground'''
Exception No. 2: Either the top or bottom ·wire-bending
Yoltage (mm) (mm) (mm)
space fo r any pane/board shall be p ennitted to be si=ed
in accordance with Table 3.12.J.6(a) where at least . ot o\·er 19.1 12.7 12.7
one side wire-bending space is sized in accordance L - YOlt ,
with Table 3.12.1.6(b) for the largest conductor to be nominal
terminated in WZJ side ·wire-bending space. >lot over
Exception No . 3: The top and bottom wire-bending
:2 -oYOlt , 31.8 19.1 12.7
nominal
space shall be p ermitted to be sized in accordance with
Table 3.12.1 . 6(a) spacings if the panelboard is designed ot o\·er
and constructedfor wiring using only a ·ingle 90-degree 1000 volts, 50.8 25.4 25.4
bend for each conductor, including the grounded circuit nominal
~For spacmg ben,·een live part, and doors of cabmets, see 3. 12.2.2(A) (I),
conductor, and the wiring diagram shows and specifies (1). and (3)
the method of wiring that shall be used.
4.8.4.9 Panelboard Marking. Panelboards shall be
Exception No. 4: Either the top or the bottom wire- durably marked by the manufacturer with the voltage
bending space, but not both, shall be permitted to be and the current rating and the number of ac pha. es
sized in accordance with Table 3.12.1 .6(a) where there or de buses for which they are designed and with the
are no conductors terminated in that space. manufacturer's name or trademark in such a manner so
as to be visible after installation, without disturbing the
(B) Side Wire-Bending Space. Side wire-bending
interior parts or wiring.
space shall be in accordance with Table 3.12.l.6(A)
for the largest conductor to be terminated in that FP : Spacing Standards of IEC is different from ·E 1A
UL Standards. For more information, refer to appropriate !EC
space.
Stru1dards.

304
ARTICLE 4.9 - INDUSTRIAL CONTROL PANELS
4.9.2 Installation
ARTICLE 4.9 - INDUSTRIAL CONTROL
PANELS 4.9.2.1 Conductor - Minimum Size and Ampacity.
The size of the industrial control panel supply conductor
4.9.1 General shall have an ampacity not less than 125 percent of the
full-load current rating of all heating loads plus 125
4.9.1.1 Scope. This article covers industrial control percent of the full-load current rating of the highest
panels intended for general use and operating at 1000 rated motor plus the sum of the full-load current ratings
volts or less. of all other connected motors and apparatus based on
FPN: AN SI/UL 508A Standard for Industrial Control Panels, is a their duty cycle that may be in operation at the same
safety standard for industrial control panels. time.
4.9.2.2 Overcurrent Protection.
4.9.1.3 Other Articles. In addition to the requirements
of Article 4.9, industrial control panels that contain (A) General. Industrial control panels shall be provided
branch circuits for specific loads or components, or are with overcurrent protection in accordance with Parts
for control of specific types of equipment addressed 2.40.1, 2.40.2, and 2.40.9
in other articles of this Code, shall be constructed and (B) Location. This protection shall be provided for
installed in accordance with the applicable requirements each incoming supply circuit by either of the following:
from the specific articles in Table 4.9 .1.3.
(1) An overcurrent protective device located ahead
of the industrial control panel.
Table 4.9.1.3 Other Articles
(2) A single main overcurrent protective device
located within the industrial control panel. Where
Equipment/Occupancy Article Section overcurrent protection is provided as part of the
Branch Circuits 2.10
industrial control panel, the supply conductors
shall be considered as either feeders or taps as
Luminaires 4. 10
covered by 2.40.2.2.
Motors, motor circuits, and 4.30
controllers (C) Rating. The rating or setting of the overcmTent
Air-conditioning and refrigerating 4.40 protective device for the circuit supplying the industrial
equipment control panel shall not be greater than the sum of the
Capacitors 4.60.1.8, largest rating or setting of the branch-circuit short-
4.60.1 .9
circuit and ground-fault protective device provided with
Hazardous (classified) locations 5.0, 5.1 , 5.2, the industrial control panel, plus 125 percent of the full-
5.3, 5.5
load current rating of all resistance heating loads, plus
Commercial garages; aircraft 5.11, 5.1 3,
tbe sum of the full-load currents of all other motors and
hangars; motor fuel dispensing 5.14, 5.15,
facilities; bulk storage plants ; 5.16,and apparatus that could be in operation at the same time.
spray applications, dipping, and 5.17.4
Exception: Where one or more instantaneous trip circuit
coating processes; and inhalation
anesthetizing locations breakers or motor short-circuit protectors are used for
Cranes amd hoist 6. 10
motor branch-circuit short-circuit and ground-fault
protection as permitted by 4.30.4.2(c), the procedure
Electrically driYen or controlled 6.75 specified above for determining the maximum rating
irrigation ma h.ine- of the protective device for the circuit supplying the
Elerntors. dumbwaiters, escalators, 6.20 industrial control panel shall apply with the following
rnO\ing walks, wheelchair lifts, and provision: For the purpose of the calculation, each
stainny chair lifts
instantaneous trip circuit breaker or motor short-
Industrial rnachiner:y 6. 0
circuit protector shall be assumed to have a rating
Resistors and reactors 4.70 not exceeding the maximum percentage of motor full-
load current permitted by Table 4.30.4.2 for the type of
Transforrners 4.50 control panel supply circuit protective device employed
Class 1, Class 2, and Class 3 7.25 Where no branch-circuit short-circuit and ground-fault
remote-control, signaling, and protective device is provided with the industrial control
power-limited circuits

305
ARTICLE 4.9 - INDUSTRIAL CONTROL PANELS
panel for motor or combination of motor and non-motor permitted for additions to existing installations, and the
loads, the rating or setting of the overcurrent protective phases shall be permanently marked.
device shall be based on 4.30.4.2 and 4.30.4.3, as
4.9.3.5 Wiring Space.
applicable.
(A) General. Industrial control panel enclosures shall
4.9.2.3 Short-Circuit Current Rating. not be used as junction boxes, auxiliary gutters, or
raceways for conductors feeding through or tapping
(A) Installation. An industrial control panel shall not be
off to other switches or overcurrent devices or other
installed where the available short-circuit fault current
equipment, unless the conductors fill less than 40
exceeds its short-circuit current rating as marked in
percent of the cross-sectional area of the wiring space.
accordance with 4.9.3 .11(4).
In addition, the conductors, splices, and taps shall not
(B) Documentation. If an industrial control panel is fill the wiring space at any cross section to more than 75
required to be marked with a short-circuit current rating percent of the cross-sectional area of that space.
in accordance with 4.9.3.11 (4), the available short-
(B) Wire Bending Space. Wire bending space within
circuit current at the industrial control panel and the
industrial control panels for field wiring terminals shall
date the short-circuit current calculation \Vas performed
be in accordance with the requirements in 4 .30.1.1 O(B).
shall be documented and made available to those
authorized to inspect the installation. 4.9.3.7 Spacings. Spacings in feeder circuits between
uninsulated live parts of adjacent components, between
4.9.2.11 Disconnecting Means. Disconnecting m ans unin ulated li\·e parts of components and grounded or
that supply motor loads shall comply with Part 4.30.9. accessible non-{;urrent-carrying metal parts, between
uninsula ed live parts of components and the enclosure,
4.9.2.31 Grounding. Multisection industrial control and at field \,-iring terminals shall be as shown in Table
panels shall be bonded together with an equipment ..~o..6(D).
grounding conductor or an equivalent equipment Exception: Spacings shall be permitted to be less than
grounding bus sized in accordance with Table 2.50.6.13 . those specified in Table 4.30.8.6(D) at circuit breakers
Equipment grounding conductors shall be connected and s,i·irches and in listed components installed in
to this equipment grounding bus or to an equipmen industrial control panels.
grounding termination point provided in a single-
section industrial control panel. 4.9.3.9 Service Equipment. Where used as service
4.9.3 Construction Specifications equipment, each industrial control panel shall be of the
type that is suitable for use as service equipment.
4.9.3.1 Enclosures. Table 1.10.2.3 shall be used as the
basis for selecting industrial control panel enclosures \\ nere a grounded conductor is provided, the industrial
for use in specific locations other than hazardous control panel shall be provided with a main bonding
(classified) locations. The enclosures are not intended to jumper, ized in accordance with 2.50.2.9(D), for
protect against conditions such as condensation, icing, connecting the grounded conductor, on its supply side,
corrosion, or contamination that may occur within the to the industrial control panel equipment ground bus or
enclosure or enter via the conduit or unsealed openings. equipment ground terminal.

4.9.3.3 Busbars and Conductors. Industrial control


4.9.3.11 Marking. An industrial control panel shall be
panels utilizing busbars shall comply with 4.9.3.3(A)
marked with the following information that is plainly
and (B).
visible after installation:
(A) Support and Arrangement. Busbars shall be
(1) Manufacturer's name, trademark, or other
protected from physical damage and be held firmly in
descriptive marking by which the organization
place.
responsible for the product can be identified.
(B) Phase Arrangement. The phase arrangement on
(2) Supply voltage, number of phases, frequency, and
3-phase horizontal common power and vertical buses
full-load current for each incoming supply circuit.
shall be A, B, C from front to back, top to bottom, or
left to right, as viewed from the front of the industrial (3) Industrial control panels supplied by more than
control panel. The B phase shall be that phase having one electrical source where more than one
the higher voltage to ground on 3-phase, 4-wire, delta- disconnecting means is required to disconnect all
connected systems. Other busbar arrangements shall be circuits 50-volts or more within the control panel

306
ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS
shall be marked to indicate that more than one to both sides of a hanging rod, this space includes
disconnecting means is required to de-energize the volume below the highest rod extending 300 mm
the equipment. The location of the means on either side of the rod on a plane horizontal to the
necessary to disconnect all circuits 50-volts or floor extending the entire length of the rod. See Figure
more shall be documented and available. 4.10.1.2.
(4) Short-circuit current rating of the industrial 4.10.1.5 Live Parts. Luminaires, portable luminaires,
control panel based on one of the following: lampholders, and lamps shall have no live parts nonnally
exposed to contact. Exposed accessible terminals in
a. Short-circuit current rating of a listed and
lampholders and switches shall not be installed in metal
labeled assembly
lurninaire canopies or in open bases of portable table or
b. Short-circuit current rating established utilizing floor luminaires.
an approved method
Exception: Cleat-type lampholders located at least
FPN: ANSI/UL 508A, Standard for Industrial Control Panels, 2500 mm above the floor shall be permitted to have
Supplement SB, is an example of an approved method.
exposed terminals.
Exception to (4): Short-circuit current rating markings
4.10.1.6 ListingRequired.All luminaires, lampholders,
are not requiredfor industrial control panels containing
and retrofit kits shall be listed.
only control circuit components.
4.10.1.8 Inspection. Luminaires shall be installed such
(5) If the industrial control panel is intended as
that the connections between the luminaire conductors
service equipment, it shall be marked to identify
and the circuit conductors can be inspected without
it as being suitable for use as service equipment.
requiring the disconnection of any part of the wiring
(6) Electrical wiring diagram or the identification unless the luminaires are connected by attachment
number of a separate electrical wiring diagram plugs and receptacles.
or a designation referenced in a separate w iring
diagram.
(7) An enclosure type nwnber shall marked on the
industrial control panel en losure.

ARTICLE 4.10 - LL~Il~AIRES, 1 800mm


or I
rod height 600 mm l
L.\..\IPHOLDERS, _.\.."'\!) L.\..\IPS I

I soomm
I I
4.10.1 General

4.10.1.1 Scope. This arti le oYers luminaires, portable


luminaires, lampholders. pendants, incandescent
filament lamp , arc lamps. electric-discharge lamps, Figure 4.10.1.2 Closet Storage Space.
decorative ligb · g producrs, lighting accessories for
temporary se.asonal and holiday use, portable flexible 4.10.2 Luminaire Locations
lighting producrs_ and the wiring and equipment
4.10.2.1 Luminaires in Specific Locations.
forming part of such products and lighting installations.
(A) Wet and Damp Locations. Luminaires installed in
4.10.1.2 Definition. wet or damp locations shall be installed such that water
cannot enter or accumulate in wiring compartments,
Closet Storage Space. The volume bounded by the
lampholders, or other electrical parts. All luminaires
sides and back closet walls and planes extending from
installed in wet locations shall be marked, "Suitable
the closet floor vertically to a height of 1800 mm or to
for Wet Locations." All luminaires installed in damp
the highest clothes-hanging rod and parallel to the walls
locations shall be marked "Suitable for Wet Locations"
at a horizontal distance of 600 mm from the sides and
or "Suitable for Damp Locations."
back of the closet walls, respectively, and continuing
vertically to the closet ceiling parallel to the walls at a (B) Corrosive Locations. Luminaires installed in
horizontal distance of 300 mm or the width of the shelf, corrosive locations shall be of a type suitable for such
whichever is greater; for a closet that permits access locations.

307
ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS
(C) In Ducts or Hoods. Luminaires shall be permitted 4.10.2.3 Luminaires over Combustible Material.
to be installed in commercial cooking hoods where all Lampholders installed over highly combustible material
of the following conditions are met: shall be of the unswitched type. Unless an individual
switch is pro-vided for each luminaire, lampholders
(1) The luminaire shall be identified for use within
shall be located at least 2 500 mm above the floor or
commercial cooking hoods and installed such
shall be located or guarded so that the lamps cannot be
that the temperature limits of the materials used
readily removed or damaged.
are not exceeded.
(2) The luminaire shall be constructed so that all 4.10.2.5 Luminaires in Sholv Windows. Chain-
exhaust vapors, grease, oil, or cooking vapors are supported luminaires used in a show window shall be
excluded from the lamp and wiring compartment. permitted to be externally ·wired. No other externally
Diffusers shall be resistant to thermal shock. wired luminaires shall be used.
(3) Parts of the luminaire exposed within the hood
shall be corrosion resistant or protected against 4.10.2.7 Luminaires in Clothes Closets.
corrosion, and the surface shall be smooth so as
(A) Luminaire Types Permitted. Only luminaires of
not to collect deposits and to facilitate cleaning.
the foll owing types shall be pennitted in a closet:
(4) Wiring methods and materials supplying the
(1 ) Surface-mounteu or recessed incandescent or
luminaire(s) shall not be exposed within the
LED luminair s wi h 'omplete y enclosed light
cooking hood.
source
FPN: See 1.10.1.1 1 for conductors and equipment exposed to
deteriorating agents. (2) Surfac -mounted or recessed fl uorescent
luminaire
(D) Bathtub and Shower Areas. No parts of cord-
connected luminaires, chain-, cable-, or cord-suspended (3) Surface-mounted fluorescent or LED luminaires
luminaires, lighting track, pendants, or ceiling- identified as suitable for installation within the
suspended (paddle) fans shall be located within a zone clo et storage space
measured 900 mm horizontally and 2 500 mm vertically
(B) Luminaire Types ~ot Permitted. Incandescent
from the top of the bathtub rim or shower stall threshold.
luminaires with open or partially enclosed lamps
This zone is all encompassing and includes the space
and pendant luminaires or lampholders shall not be
directly over the tub or shower stall. Luminaires located
permitted.
within the actual outside dimension of the bathtub or
shower to a height of 2 500 mm vertically from the top (C) Location. The mm1mum clearance between
of the bathtub rim or shower threshold shall be marked luminaires installed in clothes closets and the nearest
for damp locations, or marked for wet locations where point of a closet storage space shall be as follows:
subject to shower spray. ( 1) 300 1mn for surface-mounted incandescent or
(E) Luminaires in Indoor Sports, Mixed-Use, and LED luminaires with a completely enclosed light
All-Purpose Facilities. Luminaires subject to physical source installed on the wall above the door or on
damage, using a mercury vapor or metal halide lamp, the ceiling.
installed in playing and spectator seating areas of
indoor sports, mixed-use, or all-purpose facilities shall (2) 150 nun for surface-mounted fluorescent
be of the type that protects the lamp with a glass or luminaires installed on the wall above the door or
plastic lens. Such luminaires shall be permitted to have on the ceiling.
an additional guard. (3) 150 nun for recessed incandescent or LED
(F) Luminaires Installed in or Under Roof Decking. luminaires with a completely enclosed light
Luminaires installed in exposed or concealed source installed in the wall or the ceiling.
locations under metal-corrugated sheet roof decking (4) 150 mm for recessed fluorescent luminaires in-
shall be installed and supported so there is not less stalled in the wall or the ceiling.
than 38 mm measured from the lowest surface of the
roof decking to the top of the luminaire. (5) Surface-mounted fluorescent or LED luminaires
shall be permitted to be installed within the closet
4.10.2.2 Luminaires Near Combustible Material.
storage space where identified for this use.
Luminaires shall be constructed, installed, or equipped
with shades or guards so that combustible material is
not subjected to temperatures in excess of 90°C.
308
ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS
4.10.2.9 Space for Cove Lighting. Coves shall have 4.10.4 Luminaire Supports
ad-equate space and shall be located so that lamps and
equipment can be properly installed and maintained. 4.10.4.1 Supports.
(A) General. Luminaires and lampholders shall be
4.10.3 Provisions at Luminaire Outlet Boxes,
securely supported. A luminaire that weighs more than
Canopies, and Pans
3 kg or exceeds 400 mm in any dimension shall not be
4.10.3.1 Space for Conductors. Canopies and outlet supported by the screw shell of a lampholder.
boxes taken together shall provide sufficient space so
(B) Metal or Nonmetallic Poles Supporting
that luminaire conductors and their connecting devices
Luminaires. Metal or nonmetallic poles shall be
are capable of being installed in accordance with
permitted to be used to support luminaires and as a
3.14.2.2.
raceway to enclose supply conductors, provided the
4.10.3.2 Temperature Limit of Conductors in Outlet following conditions are met:
Boxes. Luminaires shall be of such construction or
(1) A pole shall have a handhole not less than 50
installed so that the conductors in outlet boxes shall not
mm x I 00 mm with a cover suitable for use in
be subjected to temperatures greater than that for which
wet locations to provide access to the supply
the conductors are rated.
terminations within the pole or pole base.
Branch-circuit wiring, other than 2-wire or multiwire
Exception No. I: No handhole shall he required in a
branch circuits supplying power to luminaires connected
pole 2500 mm or less in height abovegrade where the
together, shall not be passed through an outlet box that
supply wiring method continues without splice or pull
is an integral part of a luminaire unless the luminaire is
point, and where the interior of the pole and any splices
identified for through-wiring.
are accessible by removing the luminaire.
FPN: See 4.10.6.1 ?(C) for wiring supplying power to luminaires
connected together. Exception No. 2: No handhole shall be required in
a pole 6000 mm or less in height abovegrade that is
4.10.3.3 Outlet Boxes to Be Covered. In a completed provided with a hinged base.
installation, each outlet box shall be provided with a (2) Where raceway risers or cable is not installed
cover unless covered by means of a luminaire canopy, within the pole, a threaded fitting or nipple
lampholder, receptacle, or similar device. shall be brazed, welded, or attached to the pole
opposite the handhole for the supply connection.
4.10.3.4 Covering of Combustible Material at Outlet
Boxes. Any combustible wall or ceiling finish exposed (3) A metal pole shall be provided \Yith an equipment
be-tween the edge of a luminaire canopy or pan and an grounding terminal as fo llO\\-s:
outlet box having a surface area of 1 160 mm2 or more a. A pole with a handhole shall have the
shall be covered with noncombustible material. equipment grounding terminal accessible from
the handhole.
4.10.3.5 Connection of Electric-Discharge and LED
Luminaires. b. A pole with a hinged base shall have the
equipment grounding tenninal accessible
(A) Independent of the Outlet Box. Electric-discharge within the base.
and LED luminaires supp01ied independently of the
outlet box shall be connected to the branch circuit Exception to (3) : No grounding terminal shall be
through metal raceway, nonn1etallic raceway, Type required in a pole 25 00 mm or less in height abovegrade
MC cable, Type AC cable, Type MI cable, nonmetallic ,rhere the su.pp(v wiring method continues without
sheathed cable, or by flexible cord as permitted in splice or p ull, and where the interior of the pole and
4.10.6.15(B) or 4.10.6.15(C). any splices are accessible by removing the luminaire.

(B) Access to Boxes. Electric-di charge and LED (4) A metal pole with a hinged base shall have the
luminaire surface mounted OYer concealed outlet, pull. hinged base and pole bonded together.
or junction boxes and designed not to be supported (5) Metal raceways or other equipment grounding
solely by the outlet box shall be provided with suitable conductors shall be bonded to the metal pole with
openings in the back of the luminaire to provide access an equipment grounding conductor recognized by
to the wiring in the box. 2.50.6.9 and sized in accordance with 2.50.6.13.

309
ARTICLE 4.10 - LUM! 1ARIES, LAMPHOLDERS AND LAMPS
(6) Conductors in vertical poles used as raceway shall 4.10.5.5 Methods of Grounding. Luminaires and
be supported as provided in 3. 0 .1.19. equipment shall be mechanically connected to an
equipment grounding conductor as specified in 2.50.6.9
4.10.4.7 Means of Support. and sized in accordance with 2.50.6.13.
(A) Outlet Boxes. Outlet boxes or :fittings installed as Exception No. 1: Luminaires made ofinsulating material
required by 3.14.2.9 and complying with the provisions that is directly wired or attached to outlets supplied by
of 3.14.2.13(A)(l) and 3.14.2.13(A)(2) shall be a wiring method that does not provide a ready means
permitted to support luminaires. for grounding attachment to an equipment grounding
conductor shall be made of insulating material and
(B) Suspended Ceilings. Framing members of
shall have no exposed conductive parts.
suspended ceiling systems used to support luminaires
shall be securely fastened to each other and shall be Exception No. 2: Replacement luminaires shall be
securely attached to the building structure at appropriate permitted to connect an equipment grounding conductor
intervals. Luminaires shall be securely fastened to the from the outlet in compliance with 2.50.7.J(C). The
ceiling framing member by mechanical means such luminaire shall then comply with 4.10.5.3.
as bolts, screws, or rivets. Listed clips identified for
Exception No. 3: Where no equipment grounding
use with the type of ceiling framing member(s) and
conductor exists at the outlet, replacement luminaires
luminaire(s) shall also be permitted.
that are GFCI protected shall not be required to be
(C) Luminaire Studs. Luminaire studs that are not connected to an equipment grounding conductor.
a part of outlet boxes, hickeys, tripods, and crowfeet
4.10.5.7 Equipment Grounding Conductor
shall be made of steel, malleable iron, or other material
Attachment. Luminaires with exposed metal parts shall
suitable for the application.
be provided with a means for connecting an equipment
(D) Insulating Joints. Insulating joints that are not grounding conductor for such luminaires.
designed to be mounted with screws or bolts shall have
4.10.6 Wiring of Luminaires
an exterior metal casing, insulated from both screw
connections. 4.10.6.1 Luminaire Wiring - General. Wiring on or
within luminaires shall be neatly arranged and shall not
(E) Raceway Fittings. Raceway :fittings used to support
be exposed to physical damage. Excess wiring shall be
a luminaire(s) hall be capable of supporting the weight
avoided. Conductors shall be arranged so that they are
of the complete fixture assembly and lamp(s) .
not subjected to temperatures above those for which
(F) Busways. Luminaires shall be permitted to be they are rated.
connected to busways in accordance with 3.68.2.8(C).
4.10.6.3 Polarization of Luminaires. Luminaires shall
(G) Trees. Outdoor Iuminaires and as ociated be wired so that the crew hell of lampholder are
equipment shall be permitted to be supported by trees. connected to the ame luminaire or ircuit conductor
FPN No. 1: See 2.25.1.26 for restrictions for suppon of overhead or terminal. The grounded onductor, \.;here connected
conductors. to a screw shell lampholder. shal be connected to the
FPN No. 2: See 3.0.1.S(D) for protection of conductors.
screw shell.

4.10.5 Grounding 4.10.6.5 Conductor Insulation. Luminaires shall be


wired with conductors having insulation suitable for
4.10.5.1 General. Luminaires and lighting equipment the environ-mental conditions, current, voltage, and
shall be grounded as required in Article 2.50 and Part temperature to which the conductors will be subjected.
4.10.5.
FPN: For ampacity of fixture wire, maximum operating
4.10.5.3 Luminaire(s) with Exposed Conductive temperature, voltage limitations, minimum wire size, and other
information, see Article 4.2.
Parts. Exposed metal parts shall be connected to an
equipment grounding conductor or insulated from the 4.10.6.7 Pendant Conductors for Incandescent
equipment grounding conductor and other conducting Filament Lamps.
surfaces or be inaccessible to unqualified personnel.
(A) Support. Pendant lampholders with permanently
Lamp tie wires, mounting screws, clips, and decorative
attached leads, where used for other than festoon
bands on glass spaced at least 38 mm from lamp
wiring, shall be hung from separate stranded rubber-
terminals shall not be required to be grounded.
covered conductors that are soldered directly to the
circuit conductors but supported independently thereof.
310
- /

ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS


I
I
(B) Size. Unless part of listed decorative lighting (C) Support. Flexible cords shall be secured to the
assemblies, pendant conductors shall not be smaller under-sides of showcases such that all of the following
than 3.5 mm2 (2.0 mm dia.) for mogul-base or medium- conditions are ensured:
base screw shell lampholders or smaller than 0.75
(1) The wiring is not exposed to physical damage.
mm2 (1.0 mm dia.) for intermediate or candelabra-base
lampholders. (2) The separation between cases is not in excess of
50 mm, or more than 300 mm between the first
(C) Twisted or Cabled. Pendant conductors longer
case and the supply receptacle.
than 900 mm shall be twisted together where not cabled
in a listed assembly. (3) The free lead at the end of a group of showcases
has a female fitting not extending beyond the
4.10.6.9 Protection of Conductors and Insulation. case.

(A) Properly Secured. Conductors shall be secured (D) No Other Equipment. Equipment other than show-
in a manner that does not tend to cut or abrade the cases shall not be electrically connected to showcases.
insulation. (E) Secondary Circuit(s). Where showcases are cord-
connected, the secondary circuit(s) of each electric-
(B) Protection Through Metal. Conductor insulation
discharge lighting ballast shall be limited to one
shall be protected from abrasion where it passes through
showcase.
metal.
4.10.6.15 Cord-Connected Lampholders and
(C) Luminaire Stems. Splices and taps shall not be
Luminaires.
located within luminaire arms or stems.
(A) Lampholders. Where a metal lampholder is
(D) Splices and Taps. No unnecessary splices or taps
attached to a flexible cord, the inlet shall be equipped
shall be made within or on a luminaire.
with an insulating bushing that, if threaded, is not
FPN: For approved means of making connections, see 1.10.1.14. smaller than raceway size 10 mm. The cord hole shall
(E) Stranding. Stranded conductors shall be used for be of a size appropriate for the cord, and all burrs and
wiring on luminaire chains and on other movable or fins shall be removed in order to provide a smooth
flexible parts. bearing surface for the cord.

(F) Tension. Conductors shall be arranged so that the Bushing having holes 7 mm in diameter shall be
weight of the luminaire or movable parts does not put permitted for use with plain pendant cord and holes 11
tension on the conductors. mm in diameter with reinforced cord.

4.10.6.12 Cord-Connected Showcases. Individual (B) Adjustable Luminaires. Luminaires that require
show-cases, other than fixed, shall be permitted to be adjusting or aiming after installation shall not be
connected by flexible cord to permanently installed required to be equipped with an attachment plug or cord
receptacles, and groups of not more than six such connector, provided the exposed cord is of the hard-
showcases shall be per-mitted to be coupled together usage or extra-hard-usage type and is not longer than
by flexible cord and separable locking-type connectors that required for maximum adjustment. The cord shall
with one of the group connected by flexible cord to a not be subject to strain or physical damage.
permanently installed receptacle. (C) Electric-Discharge and LED Luminaires.
Electricdischarge and LED luminaires shall comply
The installation shall comply with 4.10.6.12(A) through
with (1), (2), and (3) as applicable.
(E).
(1) Cord-Connected Installation. A luminaire or a
(A) Cord Requirements. Flexible cord shall be of the listed assembly in compliance with any of the
hard-service type, having conductors not smaller than conditions in (a) through (c) shall be permitted
the branch-circuit conductors, having ampacity at least to be cord connected provided the luminaire is
equal to the branch-circuit overcurrent device, and located directly below the outlet or busway, the
having an equipment grounding conductor. cord is not subject to strain or physical damage,
FPN: See Table 2.50.6.13 for size of equipment grounding and the cord is visible over its entire length except
conductor. at terminations.
(B) Receptacles, Connectors, and Attachment Plugs. (a) A luminaire shall be pennitted to be connected
Receptacles, connectors, and attachment plugs shall be with a cord terminating in a grounding-type
of a listed grounding type rated 15 or 20 amperes. attachment plug or busway plug.
311
ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS
(b) A luminaire assembly equipped with a strain 4.10.6.21 Feeder and Branch-Circuit Conductors
relief and canopy shall be permitted to use and Ballasts. Feeder and branch-circuit conductors
a cord connection between the luminaire within 75 mm of a ballast, LED driver, power supply, or
assembly and the canopy. The canopy shall be transformer shall have an insulation temperature rating
permitted to include a section of raceway not not lower than 90°C, unless supplying a luminaire
over 150 mm in length and intended to facilitate marked as suitable for a different insulation temperature.
the connection to an outlet box mounted above
4.10.7 Construction of Luminaires
a suspended ceiling.
4.10.7.1 Combustible Shades and Enclosures.
(c) Listed luminaires connected usmg listed
Adequate airspace shall be provided between lamps and
assemblies that incorporate manufactured
shades or other enclosures of combustible material.
wiring system connectors in accordance with
6.4.1.1 OO(C) shall be permitted to be cord 4.10.7.5 Luminaire Rating.
connected. (A) Marking. All luminaires shall be marked with
(2) Provided with Mogul-Base, Screw Shell the maximum lamp wattage or electrical rating,
Lampholders. Electric-discharge luminaires manufacturer 's name, trademark, or other suitable
provided with mogul-base, screw shell means of identification. A luminaire requiring supply
lampholders shall be permitted to be connected wire rated higher than 60°C shall be marked with
to branch circuits of 50 amperes or less by the minimum supply wire temperature rating on the
cords complying with 2.40.1 .5. Receptacles and luminaire and shipping carton or equivalent.
attachment plugs shall be permitted to be of a (B) Electrical Rating. The electrical rating shall include
lower ampere rating than the branch circuit but the voltage and frequency and shall indicate the current
not less than 125 percent of the luminaire full- rating of the unit, including the ballast, transfonner,
load current. LED driver power supply, or autotransformer.
(3) Equipped with Flanged Surface Inlet. Electric- 4.10.7 .13 Portable Luminaires.
discharge luminaires equipped with a flanged
surface inlet shall be permitted to be supplied by (A) General. Portable luminaires shall be wired with
cord pendants equipped with cord connectors. flexible cord recognized by 4.0.1.4 and an attachment
Inlets and connectors shall be permitted to be of plug of the polarized or grounding type. Where used
a lower ampere rating than the branch circuit but with Edison-base lampbolders, the grounded conductor
not less than 125 percent of the lurninaire load shall be identified and attached to the screw shell and
current. the identified blade of the attachment plug.

4.10.6.17 Luminaires as Raceways. Luminaires hall (B) Portable Handlamps. In addition to the provisions
not be used as a raceway for circuit conducto unless of 4.10.7.13(A), portable handlamp shall comply with
they comply with 4.10.6. l 7(A), (B), or (C). the following:
(A) Listed. Lurninaires listed and marked for use a a (1) Metal shell, paper-lined lampholder shall not be
raceway shall be permitted to be used as a ra ewa . used.
(B) Through-Wiring. Lurninaires identified for (- ) Handlamps hall be equipped with a handle of
through-wiring, as permitted by 4.10.2.2, shall be molded compo if on or other insulating material.
permitted to be used as a raceway.
(3) Handlamp hall be equipped with a substantial
(C) Luminaires Connected Together. Luminaires guard attached to the lampholder or handle.
designed for end-to-end connection to form a
continuous assembly, or luminaires connected together (4) Yietallic guards shall be grounded by means of an
by recognized wiring methods, shall be permitted to equipment grounding conductor run with circuit
contain the conductors of a 2-wire branch circuit, or conductors within the power-supply cord.
one multiwire branch circuit, supplying the connected
(5) Portable handlamps shall not be required to be
luminaires and shall not be required to be listed as a
grounded where supplied through an isolating
raceway. One additional 2-wire branch circuit separately
transformer with an ungrounded secondary of not
supplying one or more of the connected luminaires shall
over 50 volts.
also be permitted.
FPN: See Article 1.1 for the definition of Multiwire Branch 4.10.7.15 Cord Bushings. A busrung or the equivalent
Circuit. shall be provided where flexible cord enters the base
312
ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS
or stem of a portable luminaire. The bushing shall be 4.10.10.6 Temperature.
of insulating material unless a j acketed type of cord is
(A) Combustible Material. Luminaires shall be
used.
installed so that adjacent combustible material will not
4.10.8 Installation of Lampholders be subjected to temperatures in excess of 90°C.
4.10.8.1 Screw Shell Type. Lampholders of the screw (B) Fire-Resistant Construction. Where a luminaire
shell type shall be installed for use as lampholders is recessed in fire-resistant material in a building of
only. Where supplied by a circuit having a grounded fire-resistant construction, a temperature higher than
conductor, the grounded conductor shall be connected 90°C but not higher than 150°C shall be considered
to the screw shell. acceptable if the luminaire is plainly marked for that
service.
4.10.8.4 Double-Pole Switched Lampholders. Where
supplied by the ungrounded conductors of a circuit, the (C) Recessed Incandescent Luminaires. Incandescent
switching device oflampholders of the switched type shall luminaires shall have thermal protection and shall be
simultaneously disconnect both conductors of the circuit. identified as thermally protected.
Exception No. 1: Thermal protection shall not be
4.10.8.7 Lampholders in Wet or Damp Locations.
required in a recessed luminaire identified for use and
Lampholders installed in wet locations shall be listed
installed in poured concrete.
for use in wet locations. Lampholders installed in damp
locations shall be listed for damp locations or shall be Exception No. 2: Thermal protection shall not be
listed for wet locations. required in a recessed luminaire whose design,
construction, and thermal performance characteristics
4.10.8.8 Lampholders Near Combustible Material. are equivalent to a thermalZv protected luminaire and
Lamp holders shall be constructed, installed, or equipped are identified as inherently protected.
with shades or guards so that combustible material is 4.10.10.7 Clearance and Installation.
not subjected to temperatures in excess of 90°C.
(A) Clearance.
4.10.9 Lamps and Auxiliary Equipment (1) ~on-Type IC. A recessed luminaire that is not
identified for contact with insulation shall have all
4.10.9.1 Bases, Incandescent Lamps. An incandescent recessed parts spaced not less than 13 mm from
lamp for general use on lighting branch ircuits shall combustible materials. The points of support and
not be equipped with a medium base if rated over 300 the trim finishing off the openings in the ceiling,
watts. or with a mogul base if rared oYer 1 500 watts. wall, or other finished surface shall be permitted
Special base or other de"i e hall be used for over 1 to be in contact with combustible materials.
500 watts.
(2) Type IC. A recessed luminaire that is identified
4.10.9.2 Electric-Discharge Lamp Auxiliary for contact w ith insulation, Type IC, shall be
Equipment. permitted to be in contact with combustible
materials at recessed parts, points of support,
(A) Enclosures. Auxiliary equipment for electric- and portions passing through or finishing off the
discharge lamps shall be enclosed in noncombustible opening in the building structure.
cases and treated as sources of heat.
(B) Installation. Thermal insulation shall not be
(B) Switching. Where supplied by the ungrounded installed above a recessed luminaire or within 75
conductors of a circuit, the switching device of mm of the recessed luminaire 's enclosure, wiring
auxiliary equipment shall simultaneously disconnect all compartment, ballast, transfonner, LED driver, or
conductors. power supply unless the luminaire is identified as Type
IC for insulation contact.
4.10.10 Special Provisions for Flush and Recessed
Luminaires 4.10.10.8 Wiring.
(A) General. Conductors that have insulation suitable
4.10.10.1 General. Luminaires installed m recessed for the temperature encountered shall be used.
cavities in walls or ceilings, including suspended
ceilings, shall comply with 4.10.10.6 through 4.10.11.5. (B) Circuit Conductors. Branch-circuit conductors
that have an insulation suitable for the temperature

313
ARTICLE 4.10 - LUMINARIES, LAMPHOLDERS AND LAMPS
encountered shall be pe1mitted to terminate in the (2) Simple Reactance Ballasts. A simple reactance
luminaire. ballast in a fluorescent luminaire with straight
tubular lamps shall not be required to be thennally
(C) Tap Conductors. Tap conductors of a type suitable
protected.
for the temperature encountered shall be permitted to
run from the luminaire terminal connection to an outlet (3) Exit Luminaires. A ballast in a fluorescent exit
box placed at least 300 mm from the luminaire. Such luminaire shall not have thermal protection.
tap conductors shall be in suitable raceway or Type AC
(4) Egress Luminaires. A ballast in a fluorescent
or MC cable of at least 450 mm but not more than 1 800
luminaire that is used for egress lighting and
mm in length.
energized only during a failure of the normal
4.10.11 Construction of Flush and Recessed supply shall not have thermal protection.
Luminaires
(F) High-Intensity Discharge Luminaires.
4.10.11.1 Temperature. Luminaires shall be constructed
(1) Recessed. Recessed high-intensity luminaires
such that adjacent combustible material is not subject to
designed to be installed in wall or ceiling cavities
temperatures in excess of 90°C.
shall have thermal protection and be identified as
4.10.11.3 Lamp Wattage Marking. Incandescent lamp thermally protected.
luminaires shall be marked to indicate the maxim.um
(2) Inherently Protected. Thermal protection shall
allowable wattage of lamps. The markings shall be
not be required in a recessed high-intensity
permanently installed, in letters at least 6 mm high, and
luminairewhose design, construction, and thermal
shall be located where visible during relamping.
performance characteristics are equivalent to a
4.10.11.4 Solder Prohibited. No solder shall be used in thermally protected luminaire and are identified
the construction of a luminaire recessed housing. as inherently protected.
4.10.11.5 Lampholders. Lampholders of the crew (3) Installed in Poured Concrete. Thermal
shell type shall be of porcelain or other uitable protection shall not be required in a recessed
insulating materials. high-intensity discharge luminaire identified for
use and installed in poured concrete.
4.10.12 Special Provisions for Electric-Discharge
Lighting Systems of 1000 Volt or Less (4) Recessed Remote Ballasts. A recessed remote
balla t for a high-intensity discharge luminaire
4.10.12.1 General.
shall have thermal protection that is integral with
(A) Open-Circuit Voltage of 1000 Volts or Less. the ballast and shall be identified as thermally
Equipment for use with electric-discharge lighting protected.
systems and designed for an open-circuit voltage of
(5) Metal Halide Lamp Containment. Luminaires
1000 volts or less shall be of a type identified for such
that use a metal halide lamp other than a thick-
service.
glass parabolic reflector lamp (PAR) shall be
(B) Considered as Energized. The terminals of an provided with a containment barrier that encloses
electric-discharge lamp shall be considered as energized the lamp, or shall be provided with a physical
where any lamp terminal is connected to a circuit of means that only allows the use of a lamp that is
over 300 volts. Type 0.
(C) Transformers of the Oil-Filled Type. Transformers FPN: See ANSI Standard C78.389, American National Standard
of the oil-filled type shall not be used. for Electric Lamps - High Intensity Discharge, Methods of
Measuring Characteristics.
(D) Additional Requirements. In addition to complying
(G) Disconnecting Means.
with the general requirements for luminaires, such
equipment shall comply with Part 4.10.12. (1) General. In indoor locations other than dwellings
and associated accessory structures, fluorescent
(E) Thermal Protection - Fluorescent Luminaires.
luminaires that utilize double-ended lamps and
(1) Integral Thermal Protection. The ballast of a contain ballast(s) that can be serviced in place
:fluorescent luminaire installed indoors shall have shall have a disconnecting means either internal or
integral thermal protection. Replacement ballasts external to each luminaire. For existing installed
shall also have thermal protection integral with luminaires without disconnecting means, at the
the ballast. time a ballast is replaced, a disconnecting means
314
ARTICLE 4.10- LUMINARIES, LAMPHOLDERS AND LAMPS
shall be installed. The line side terminals of the ballast, transformer, LED driver, or power supply is
disconnecting means shall be guarded. to be installed on combustible low-density cellulose
fiberboard, it shall be marked for this condition or
Exception No. 1: A disconnecting means shall not
shall be spaced not less than 3 8 mm from the surface
be required for luminaires installed in hazardous
of the fiberboard. Where such luminaires are partially
(classifi,ed) location(s).
or wholly recessed, the provisions of 4.10.10.1 through
Exception No . 2: A disconnecting means shall not 4.10.11.5 shall apply.
be required for luminaires that provide emergency FPN: Combustible low-density cellulose fiberboard includes
illumination required in 7.0.4.2. sheets, panels, and tiles that have a density of 320 kg/m3 or less
and that are formed of bonded plant fiber material but does not
Exception No. 3: For cord-and-plug-connected include solid or laminated wood or fiberboard that has a density in
luminaires, an accessible separable connector or an excess of320 kg/m3 or is a material that has been integrally treated
accessible plug and receptacle shall be permitted to with fire-retarding chemicals to the degree that the flame spread
serve as the dis-connecting means. index in any plane of the material will not exceed 25, determined
in accordance with tests for surface burning characteristics of
Exception No. 4: Where more than one luminaire is building materials. See ANSI/ASTM E84-2015a, Standard
installed and supplied by other than a multiwire branch Test Method for Surface Burning Characteristics of Building
Materials or ANSI/UL 723- 2013, Standard for Test for Surface
circuit, a disconnecting means shall not be required
Burning Characteristics ofBuilding Materials.
for every luminaire when the design of the installation
includes disconnecting means, such that the illuminated 4.10.12.8 Equipment Not Integral with Luminaire.
space cannot be left in total darkness. (A) Metal Cabinets. Auxiliary equipment, including
(2) Multiwire Branch Circuits. When connected reactors, capacitors, resistors, and similar equipment,
to multiwire branch circuits, the disconnecting where not installed as part of a luminaire assembly,
means shall simultaneously break all the supply shall be enclosed in accessible, permanently installed
conductors to the ballast, including the grounded metal cabinets.
conductor. (B) Separate Mounting. Separately mounted ballasts,
(3) Location. The disconnecting means shall be transformers, LED drivers, or power supplies that are
located so as to be accessible to qualified persons listed for direct connection to a wiring system shall not
before servicing or maintaining the ballast. be required to be additionally enclosed.
Where the disconnecting means is external to the (C) Wired Luminaire Sections. Wired luminaire
luminaire, it shall be a single device, and shall be sections are paired, "·ith a ballast(s) supplying a lamp
attached to the luminaire or the luminaire shall be or lamp in both. For interconnection between paired
located v.rithin sight of the disconnecting means. units, it hall be permissible to use raceway size 10 mm
4.10.12.5 Direct-Current Equipment. Luminaires flexible metal conduit in lengths not exceeding 7600
installed on de circuits shall be equipped with auxiliary rn.m, in conformance ·with Article 3.48. Luminaire wire
equipment and resistors designed for de operation. The operating at line voltage, supplying only the ballast(s)
lurninaires shall be marked for de operation. of one of the paired luminaires, shall be permitted in the
4.10.12.6 Open-Circuit Voltage Exceeding 300 Volts. same raceway as the lamp supply ·wires of the paired
Equipment having an open-circuit voltage exceeding luminaires.
300 volts shall not be installed in dwelling occupancies
4.10.12.9 Autotransformers. An autotransformer that
unless such equipment is designed so that there will be
is used to raise the voltage to more than 300 volts, as
no exposed live parts when lamps are being inserted,
part of a ballast for supplying lighting units, shall be
are in place, or are being removed.
supplied only by a grounded system.
4.10.12.7 Luminaire Mounting.
4.10.12.10 Switches. Snap switches shall comply with
(A) Exposed Components. Lurninaires that have 4.4.1.14.
exposed ballasts, transformers, LED drivers, or
power supplies shall be installed such that ballasts, 4.10.13 Special Provisions for Electric-Discharge
transformers, LED drivers, or power supplies shall not Lighting Systems of More Than 1 000 Volts
be in contact with combustible material unless listed for 4.10.13.1 General.
such condition.
(A) Listing. Electric-discharge lighting systems with
(B) Combustible Low-Density Cellulose Fiberboard. an open-circuit voltage exceeding I 000 volts shall be
Where a surface-mounted lurninaire containing a listed and installed in conformance with that listing.

315
ARTICLE 4.10 - LUMI TARIES , LAMPHOLDERS AND LAMPS
(B) Dwelling Occupancies. Equipment that has an (C) Adj acent to Combustible Materials. Transfonners
open-circuit voltage exceeding 1000 volts shall not be shall be located so that adjacent combustible material:
installed in or on dwelling occupancies. are not subjected to temperatures in excess of 90°C.
(C) Live Parts. The terminal of an electric-discharge 4.10.13.6 Exposure to Damage. Lamps hall not be
lamp shall be considered as a live part. located where normally exposed to physical damage.
(D)AdditionalRequirements. In addition to complying 4.10.13.7 Marking. Each luminaire or each secondary
with the general requirements for luminaires, such circuit of tubing having an open-circuit voltage of
equipment shall comply with Part 4.10.13. over 1000 volts shall have a clearly legible marking in
FP : For signs and outline lighting, see Article 6.0.
letters not less than 6 mm high reading "Caution volt ·.'·
The voltage indicated shall be the rated open-circuit
4.10.13.2 Control. voltage. The caution sign(') or label(s) shall comply
(A) Disconnection. Luminaires or lamp installation with 1.10.l .2l(B).
shall be controlled either singly or in groups by an 4.10.14 Lighting Track
externally operable switch or circuit breaker that opens
all un-grounded primary conductors. 4.10.14.1 Installation.

(B) Within Sight or Locked Type. The switch or (A) Lighting Track. Lighting track shall be permanently
circuit breaker shall be located within sight from the in talled and permanently connected to a branch circuit.
luminaires or lamps, or it shall be permitted to be Only lighting track fittings shall be installed on lighting
located elsewhere if it is lockable in accordance with track. Lighting track fittings shall not be equipped with
1.10.1.25 . general-purpose receptacles.

4.10.13.3 Lamp Terminals and Lampholders. Parts (B) Connected Load. The connected load on lighting
that must be removed for lamp replacement shall be track shall not exceed the rating of the track. Lighting
hinged or held captive. Lamps or lampholders shall be track shall be supplied by a branch circuit having
designed so that there are no exposed live parts when a rating not more than that of the track. The load
lamps are being inserted or removed. calculation in 2.20.3.4(A) shall not be required to
limit the length of track on a single branch circuit,
4.10.13.4 Transformers. and it shall not be required to limit the number of
luminaires on a single track.
(A) Type. Transformers shall be enclosed, identified for
the use, and listed. (C) Locations Not Permitted. Lighting track shall not
be installed in the following locations:
(B) Voltage. The secondary circuit voltage shall not
exceed 15 000 volts, nominal, under any load condition. (1) Where likely to be subjected to physical damage
The voltage to ground of any output terminal of the (2) In wet or damp locations
secondary circuit shall not exceed 7500 volts under any
(3) Wbere subject to conosive vapors
load conditions.
(4) In storage battery rooms
(C) Rating. Transformers shall have a secondary hort-
circuit current rating of not more than 150 mA if the (5) In hazardous (classified) location
open-circuit voltage is over 7 500 volts, and not more
(6) Wber cone aled
than 300 mA if the open-circuit voltag rating i 7 500
volts or less. ( ) Where extend d thro gh wall or partition
(D) Secondary Connections. Secondary circuit output ( ) Le than 1 500 mm aboY the fini bed flo or
shall not be com1ected in parallel or in series. except where protect d from physical damage or
track operating at le than 30 \-olts nns open-
4.10.13.5 Transformer Locations. circuit voltage
(A) Accessible. Transformers shall be accessible after (9) Where prohibited b 4.10.2. l(D)
installation. (D) Support. Fittings identified for use on lighting track
(B) Secondary Conductors. Transformers shall be shall be designed specifically for the track on which
installed as near to the lamps as practicable to keep the they are to be installed. They shall be securely fastened
secondary conductors as short as possible. to the track, shall maintain polarization and connections

316
ARTICLE 4.11 - LIGHTING SYSTEMS OPERATING AT 30 VOLTS OR LESS AND LIGHTING
to the equipment grounding conductor, and shall be 4.11.1.3 Low-Voltage Lighting Systems.
designed to be suspended directly from the track.
(A) General. Low-voltage lighting systems shall
consist of an isolating power supply, low-voltage
4.10.14.3 Heavy-Duty Lighting Track. Heavy-
luminaires, and associated equipment that are all
duty lighting track is lighting track identified for use
identified for the use. The output circuits of the power
exceeding 20 amperes. Each fitting attached to a heavy-
supply shall be rated for 25 amperes maximum under
duty lighting track shall have individual overcurrent
all load conditions.
protection.
4.11 .1.4 Listing Required. Low-voltage lighting shall
4.10.14.4 Fastening. Lighting track shall be securely comply with 4.1 l. l .4(A) or 4 . l l .1.4(B).
mounted so that each fastening is suitable for supporting (A) Listed System. The luminaires, power supply,
the maximum weight ofluminaires that can be installed. and luminaire fittings (including the exposed bare
Unless identified for supports at greater intervals, a conductors) of an exposed bare conductor lighting
single section 1 200 mm or shmier in length shall have system shall be listed for the use as part of the same
two supports, and, where installed in a continuous row, identified lighting system.
each individual section of not more than 1 200 mm in
length shall have one additional support. (B) Assembly of Listed Parts. A lighting system
assembled from the following listed parts shall be
4.10.14.5 Construction Requirements. permitted:

(A) Construction. The housing for the lighting track ( 1) Low-\'oltage luminaires
system hall be of substantial construction to maintain (2) Power supply
rigidity. The conductors shall be installed within the
track housing permitting insertion of a luminaire, and (3) Low-voltage luminaire fittings
designed to pre\'ent tampering and accidental contact (4 ) Suitably rated cord, cable, conductors in conduit,
\Yith liYe parts. Components of lighting track sy terns or other fixed Chapter 3 wiring method for the
of different voltages shall not be interchangeable. The secondary circuit
track condu tor shall be a minimum 3.5 mm2 or equal
and hall be copper. The tra k y tern ends -hall be
4.11 .1.5 Specific Location Requirements.
insulated and capped. (A) ,vans, Floors, and Ceilings. Conductors concealed
(B) Grounding. Ligh ·ng rra k hall be grounded in or extended through a wall, floor, or ceiling shall be in
accordance \Yith (1) or (2):
accordan e with Arti le - · -o. and he uck e ion
shall be urely oupled o a· tain on i · of the ( 1) Installed using any of the wiring methods
circuitry. polarizarion. a d groun · g throughou . specified in Chapter 3
(2) Installed using wiring supplied by a listed Class
4.10.15 Decorative Lighting and Similar Accessories
2 power source and installed in accordance with
7.25.3.10
4.10.15.1 Listing of Decorati.-e Lighting. Decorative
lighting and similar accessorie used for holiday lighting (B) Pools, Spas, Fountains, and Similar Locations.
and similar purposes, in accordance with : .90 . l.3(8 ), Lighting systems shall be installed not less than 3 000
shall be listed. mm horizontally from the nearest edge of the water,
unless permitted by Article 6.80.
ARTICLE 4.11-LIGHTING SYSTE:\1S 4.11.1.6 Secondary Circuits.
OPERATING AT 30 VOLTS OR LESS A~D
LIGHTING EQUIPMENT CONNECTED TO (A) Grounding. Secondary circuits shall not be
grounded.
CLASS 2 POWER SOURCES
(B) Isolation. The secondary circuit shall be insulated
4.11 .1.1 Scope. This article covers lighting systems and from the branch circuit by an isolating transformer.
their associated components operating at no more than (C) Bare Conductors. Exposed bare conductors and
30 volts ac or 60 volts de. Where wet contact is likely to current-carrying parts shall be permitted for indoor
occur, the limits are 15 volts ac or 30 volts de. installations only. Bare conductors shall not be installed
FPN: Refer to Article 6.80 for applications involving immersion.
less than 2100 mm above the finished floor, unless
specifically listed for a lower installation height.

31 7
ARTICLE 4.22 - APPLIANCES
(D) Insulated Conductors. Insulated secondary (B) Type. The GFCI shall be readily accessible, listed,
circuit conductors shall be of the type, and installed as, and located in one or more of the following locations:
described in (1), (2), or (3):
( 1) Within the branch circuit overcurrent device
(1) Class 2 cable supplied by a Class 2 power source
(2) A device or outlet within the supply circuit
and installed in accordance with Parts 7 .25 .1 and
7 .25.3. (3) An integral part of the attachment plug

(2) Conductors, cord, or cable of the listed system (4) Within the supply cord not more than 300 mm
and installed not less than 2 100 mm above the from the attachment plug
finished floor unless the system is specifically (5) Factory installed within the appliance
listed for a lower installation height.
(3) Wiring methods described in Chapter 3. 4.22.1.6 Listing Required. All appliances operating at
50 volts or more shall be listed.
4.11.1.7 Branch Circuit. Lighting systems covered
by this article shall be supplied from a maximum
4.22.2 Installation
20-ampere branch circuit.
4.11.1.8 Hazardous (Classified) Locations. Where 4.22.2.1 Branch-Circuit Rating. This section specifies
installed in hazardous (classified) locations, these the ratings of branch circuits capable of carrying
systems shall conform with Articles 5.0 through 5.17 in appliance current without overheating under the
addition to this article. conditions specified.
ARTICLE 4.22 -APPLIANCES (A) Individual Circuits. The rating of an individual
branch circuit shall not be less than the marked rating
4.22.1 General
of the appliance or the marked rating of an appliance
4.22.1.1 Scope. This article covers electrical appliances having combined loads as provided in 4.22.5.3.
used in any occupancy.
The rating of an individual branch circuit for motor-
4.22.1.3 Other Articles. The requirements of Article
4.30 shall apply to the installation of motor-operated operated appliances not having a marked rating shall be
appliances, and the requirements of Article 4.40 shall in accordance with Part 4.30.2.
apply to the installation of appliances containing a
hermetic refrigerant motor-compressor(s), except as The branch-circuit rating for an appliance that is a
specifically amended in this article. continuous load other than a motor-operated appliance,
shall not be less than 125 percent of the marked rating,
4.22.1.4 Live Parts. Appliances shall have no live
or not less than 100 percent of the marked rating if the
parts normally exposed to contact other than those parts
branch-circuit device and its assembly are listed for
functioning as open-resistance heating elements, such
continuous loading at 100 percent of its rating.
as the heating element of a toaster, which are necessarily
exposed. Branch circuits and branch-circuit conductors for
household ranges and cooking appliances shall be
4.22.1.5 Ground-Fault Circuit-Interrupter (GFCI)
permitted to be in accordance with Table 2.20.3.16 and
Protection for Personnel.
shall be sized in accordance with 2.10.2.l(A)(3).
(A) General. Appliances identified in 4.22.1.5(A)(l)
(B) Circuits Supplying Two or More Loads. For
through (5) rated 250 volts or less and 60 amperes or
branch circuits supplying appliance and other loads, the
less, single- or 3-phase, shall be provided with GFCI
rating shall be determined in accordance with 2.10.2.6.
protection for personnel. Multiple GFCI protective
devices shall be permitted but shall not be required.
4.22.2.2 Overcurrent Protection. Appliances shall
( 1) Automotive vacuum machines provided for be protected against overcurrent in accordance with
public use 4.22.2.2(A) through (G) and 4.22.2.1 .
(2) Drinking water coolers (A) Branch-Circuit Overcurrent Protection. Branch
circuits shall be protected in accordance with 2.40.1.4.
(3) High-pressure spray washing machines - cord-
and-plugconnected If a protective device rating is marked on an appliance,
the branch-circuit overcurrent device rating shall not
(4) Tire inflation machines provided for public use
exceed the protective device rating marked on the
(5) Vending machines appliance.

318
ARTICLE 4.22 -APPLIANCES
(B) Household-Type Appliances with Surface for branch-circuit protection.
Heating Elements. Household-type appliances with
The main conductors supplying these overcurrent
surface heating elements having a maximum demand
protective devices shall be considered branch-circuit
of more than 60 amperes calculated in accordance
conductors.
with Table 2.20.3.16 shall have their power supply
subdivided into two or more circuits, each of which (2) Commercial Kitchen and Cooking Appliances.
shall be provided with overcurrent protection rated at Commercial kitchen and cooking appliances
not over 50 amperes. using sheathed-type heating elements not covered
in 4.22.2.2(D) shall be permitted to be subdivided
(C) Infrared Lamp Commercial and Industrial
into circuits not exceeding 120 amperes and
Heating Appliances. Infrared lamp commercial and
protected at not more than 150 amperes where
industrial heating appliances shall have overcurrent
one of the following is met:
protection not exceeding 50 amperes.
( 1) Elements are integral with and enclosed within
(D) Open-Coil or Exposed Sheathed-Coil Types of
a cooking surface.
Surface Heating Elements in Commercial-Type
Heating Appliances. Open-coil or exposed sheathed- (2) Elements are completely contained within an
coil types of surface heating elements in commercial- enclosure identified as suitable for this use.
type heating appliances shall be protected by overcurrent (3) Elements are contained within an ASME-rated
protective devices rated at not over 50 amperes. and stamped vessel.
(E) Single Non- Motor-Operated Appliance. If the (3) Water Heaters and Steam Boilers. Resistance-
branch circuit supplies a single non- motor-operated type immersion electric heating elements shall
appliance, the rating of overcurrent protection shall be permitted to be subdivided into circuits not
comply with the following: exceeding 120 amperes and protected at not more
(1) ot exceed that marked on the appliance. than 150 amperes as follows:
(2) Not exceed 20 amperes if the oYercurrent (1) Where contained in ASME-rated and stamped
protection rating is not marked and the appliance vessels
is rated 13.3 amperes or le s; or (2) Where included in listed instantaneous water
(3) ?\ot exceed 150 percent of the appliance rated heaters
current if the oYercurrent protection rating is (3) Where installed in low-pressure water heater
not marked and the appliance is rated over 13.3 tanks or open-outlet water heater vessels
amperes. 'here 150 percent of the appliance
FPN: Low-pressure and open-outlet heaters are atmospheric
rating does not correspond to a standard
pressure water heaters as defined in IEC 60335-2-21, Household
overcurrent device ampere rating, the next higher and similar electrical appliances - Safe(v ·- Particular
standard rating shall be permitted. requirements for storage water heaters.

(F) Electric Heating Appliances Employing (G) Motor-Operated Appliances. Motors of motor-
Resistance-Type Heating Elements Rated More operated appliances shall be provided with overload
Than 48 Amperes. protection in accordance with Part 4.30.3. Hermetic
(1) Electric Heating Appliances. Electric heating refrigerant motor-compressors in air-conditioning
appliances employing resistance-type heating or refrigerating equipment shall be provided with
elements rated more than 48 amperes, other overload protection in accordance with Part 4.40.6.
than household appliances with surface heating Where appliance overcurrent protective devices that
elements covered by 4 .22.2 .2(B ), and commercial- are separate from the appliance are required, data
type heating appliances covered by 4.22.2.2(D), for selection of these devices shall be marked on the
shall have the heating elements subdivided. Each appliance. The minimum marking shall be that specified
subdivided load shall not exceed 48 amperes and in 4.30.1. 7 and 4.40.1.4.
shall be protected at not more than 60 amperes.
4.22.2.3 Central Heating Equipment. Central heating
These supplementary overcurrent protective devices equipment other than fixed electric space-heating
shall be (1) factory-installed within or on the heater equipment shall be supplied by an individual branch
enclosure or provided as a separate assembly by the circuit.
heater manufacturer; (2) accessible; and (3) suitable

319
ARTICLE 4.22 - APPLIANCES
Exception No. 1: Auxiliary equipment, such as a Exception: A listed in-sink waste disposer distinctly
pump, valve, humidifi,er, or electrostatic air cleaner marked to identify it as protected by a system of doub e
directly associated with the heating equipment, shall be insulation shall not be required to be terminated 11"ith a
permitted to be connected to the same branch circuit. grounding-type attachment plug.
Exception No. 2: Permanently connected air- (2} The length of the cord shall not be less than 4.'."0
conditioning equipment shall be permitted to be mm and not over 900 mm.
connected to the same branch circuit.
(3) Receptacles shall be located to protect again-t
physical damage to the flexible cord.
4.22.2.4 Storage-Type Water Heaters. A fixed storage-
type water beater that has a capacity of 450 L or less (4) The receptacle shall be accessible.
shall be considered a continuous load for the purposes (2) Built-in Dishwashers and Trash Compactors.
of sizing branch circuits. Built-in dishwashers and trash compactors shall
FPN: For branch-circuit rating, see 4.22.2.1. be permitted to be cord-and-plug-connected
with a :flexible cord identified as suitable for the
4.22.2.6 Central Vacuum Outlet Assemblies. purpose in the installation instructions of the
(A) Listed central vacuum outlet assemblies shall appliance manufacturer where all of the following
be permitted to be connected to a branch circuit in conditions are met:
accordance with 2.10.2.6(A). (1) The flexible cord shall be terminated with a
(B) The ampacity of the connecting conductors shall grounding-type attachment plug.
not be less than the ampacity of the branch circuit Exception: A listed dishwasher or trash compactor
conductors to which they are connected. distinctly marked to identify it as protected by a
(C) Accessible non-current-canying metal part of system of double insulation shall not be required to be
the central vacuum outlet assembly likely to become terminated with a grounding-type attachment plug.
energized shall be connected to an equipment grounding (2) For a trash compactor, the length of the cord
conductor in accordance with 2.50.6.1. Incidental shall be 900 mm to 1 200 mm measured from
metal parts such as screws or rivets installed into or the face of the attachment plug to the plane of
on msulating material shall not be con idered likely to the rear of the appliance.
become energized.
(3) For a built-in dishwasher, the length of the cord
shall be 900 mm to 2 000 mm measured from
4.22.2.7 Flexible Cords.
the face of the attachment plug to the plane of
(A) General. Flexible cord shall be permitted (1) the rear of the appliance.
for the connection of appliances to facilitate their
(4} Receptacles shall be located to protect against
frequent inter-change or to prevent the transmission
physical damage to the flexible cord.
of noise or vibration or (2) to facilitate the removal or
disconnection of appliances that are fastened m place, (5) The receptacle for a trash compactor shall be
where the fastening means and mechanical connections located in the space occupied by the appliance
are specifically designed to permit ready removal for or adjacent thereto.
maintenance or repair and the appliance is intended or
(6) The receptacle for a built-in dishwasher shall
identified for flexible cord connection.
be located in the space adjacent to the space
(B) Specific Appliances. occupied by the dishwasher.
(1) Electrically Operated In-Sink Waste (7) The receptacle shall be accessible.
Disposers. Electrically operated in-sink waste
(3) Wan-Mounted Ovens and Counter-Mounted
disposers shall be permitted to be cord-and
Cooking Units. Wall-mounted ovens and
plug-connected with a flexible cord identified
counter-mounted cooking units complete with
as suitable in the installation instrnctions of the
provisions for mounting and for making electrical
appliance manufacturer where all of the following
connections shall be permitted to be permanently
conditions are met:
connected or, only for ease in servicing or for
(1) The flexible cord shall be terminated with a installation, cord-and-plug-connected.
grounding-type attachment plug.
A separable connector or a plug and recepta · e

320
ARTICLE 4.22 - APPLIANCES
combination in the supply line to an oven or cooking 4.22.2.12 Covering of Combustible Material at
unit shall be approved for the temperature of the space Outlet Boxes. Any combustible ceiling finish that
in which it is located. is exposed between the edge of a ceiling-suspended
(paddle) fan canopy or pan and an outlet box and that
(4) Range Hoods. Range hoods shall be permitted
has a surface area of 1160 mm2 or more shall be covered
to be cord-and-plug-connected with a flexible
with noncombustible material.
cord identified as suitable for use on range hoods
in the installation instructions of the appliance 4.22.2.13 Other Installation Methods. Appliances
manufacturer, where all of the following employing methods of installation other than covered
conditions are met: by this article shall not be permitted to be used.
(1 ) The flexible cord is terminated with a 4.22.3 Disconnecting Means
grounding-type attachment plug. 4.22.3.1 General. A means shall be provided to
Exception: A listed range hood distinctZv marked to simultaneously disconnect each appliance from
identify it as protected by a system ofdouble insulation, all ungrounded conductors in accordance with the
or its equivalent, shall not be required to be terminated following sections of Part 4.22.3 . If an appliance is
supplied by more than one branch circuit or feeder,
with a grounding-type attachment plug.
these disconnecting means shall be grouped and
(2) The length of the cord is not less than 450 mm identified as being the multiple disconnecting means
and not over 1200 mm. for the appliance. Each disconnecting means shall
simultaneously disconnect all ungrounded conductors
(3) Receptacles are located to protect against that it controls.
physical damage to the flexible cord.
4.22.3.2 Disconnection of Permanently Connected
(4) The receptacle is accessible. Appliances.
(5) The receptacle is supplied by an indiYidual (A) Rated at Not over 300 Volt-Amperes or 118
branch circuit. Horse-power. For permanently connected appliances
rated at not over 300 volt-amperes or 1/8 hp, the branch-
4.22.2.8 Protection of Combustible ~1aterial. Each
electrically heated appliance that is intended by ize. w ight.
circuit overcurrent device shall be pennitted to serve
and service to be located in a fixed position shall be placed as the disconnecting means where the switch or circuit
so as to provide ample protection between the appliance and breaker is within sight from the appl iance or is lockable
adjacent combustible material. in accordance vvith 1.10.1.25.
4.22.2.9 Support of Ceiling-Suspended (Paddle) (B) Appliances Rated over 300 Volt-Amperes. For
Fans. Ceiling-suspended (paddle) fans shall be permanently connected appliances rated over 300 volt-
supported independently of an outlet box or by one of amperes, the branch-circuit switch or circuit breaker
the following: shall be permitted to serve as the disconnecting means
where the switch or circuit breaker is within sight
(1) A listed outlet box or listed outlet box system
from the appliance or is lockable in accordance with
identified for the use and installed in accordance
1.1 0.1.25 .
with 3.14.2.13(C).
f P:-.;: For appliances employing unit switches, see 4.22.3.5.
(2) A listed outlet box system, a listed locking support
and mounting receptacle, and a compatible (C) Motor-Operated Appliances Rated over 118
factory installed attachment fitting designed for Horsepower. The disconnecting means shall comply
support, identified for the use and installed in with 4.30.9.9 and 4.30.9. 10. Forpennanently connected
accordance with 3.14.2.13(E) motor-operated appliances with motors rated over 1/8
hp, the disconnecting means shall be within sight from
4.22.2.10 Space for Conductors. Canopies of ceiling- the appliance or be capable of being locked in the open
suspended (paddle) fans and outlet boxes taken position in compliance with 1.10.1.25.
together shall provide sufficient space so that
conductors and their connecting devices are capable Exception: Ifan appliance ofmore than 1/8 hp is provided
of being installed in accordance with 3.14.2.2. with a unit switch that complies with 4.22.3.6(A), (BJ,
(C), or (D), the switch or circuit breaker serving as the
4.22.2.11 Outlet Boxes to Be Covered. In a completed other disconnecting means shall be p ermitted to be out
1l 1allation, each outlet box shall be provided with ofsight from the appliance.
.:,. oYer unless covered by means of a ceiling-
d d (paddle) fan canopy.
321
ARTICLE 4.22 - APPLIANCES
4.22.3.4 Disconnection of Cord-and-Plug-Connected (D) Other Occupancies. In other occupancies, the
or Attachment Fitting-Connected Appliances. branch-circuit switch or circuit breaker, where readily
accessible for servicing of the appliance, shall be
(A) Separable Connector or an Attachment Plug (or
permitted as the other disconnecting means.
Attachment Fitting) and Receptacle. For cord-and-
plug-connected (or attachment fitting-) appliances, an 4.22.3.6 Switch and Circuit Breaker to Be Indicating.
accessible separable connector or an accessible plug Switches and circuit breakers used as disconnecting
(or attachment fitting) and receptacle combination means shall be of the indicating type.
shall be permitted to serve as the disconnecting means.
4.22.4 Construction
The attachment fitting shall be a factory installed part
of the appliance and suitable for disconnection of the 4.22.4.1 Polarity in Cord-and Plug-Connected
appliance. Where the separable connector or plug (or Appliances. If the appliance is provided with a manually
attachment fitting) and receptacle combination are not operated, line-connected, single-pole switch for
accessible, cord-and-plug-connected or attachment appliance on-off operation, an Edison-base lampholder,
fitting-and-plug connected appliances shall be provided or a 15- or 20-ampere receptacle, the attachment plug
with disconnecting means in accordance with 4.22.3.2. shall be of the polarized or grounding type.
(B) Connection at the Rear Base of a Range. For A 2-wire, nonpolarized attachment plug shall be permit-
cord-and-plug-connected household electric ranges, an ted to be used on a listed double-insulated shaver.
attachment plug and receptacle connection at the rear FP:\': For polarity ofEdison-base lamp-holders, see 4.10.7.13(A).
base of a range, accessible from the front by removal of
a drawer, shall meet the intent of 4.22.3.4(A). 4.22.4.2 Cord-and Plug-Connected Appliances
Sublect to Immersion. Cord-and plug-connected
(C) Rating. The rating of a receptacle or of a separable portable, freestanding hydromassage units and hand-
connector shall not be less than the rating of any held hair dryers shall be constructed to provide
appliance connected thereto. protection for personnel against electrocution when
Exception: Demand factors authorized elsewhere in immersed while in the "on" or "off" position.
this Code shall be permitted to be applied to the rating 4.22.4.3 Signals for Heated Appliances. In other than
of a receptacle or of a separable connector. dwelling-type occupancies, each electrically heated
appliance or group of appliances intended to be applied
4.22.3.5 Unit Switch(es) as Disconnecting ::\ileans. to combustible material shall be provided with a signal
A unit switch(es) with a marked-off position that is a or an integral temperature-limiting device.
part of an appliance and disconnects all ungrounded
conductors shall be permitted as the disconnecting 4.22.4.4 Flexible Cords.
means required by this article where other means for (A) Heater Cords. All cord-and plug-connected
disconnection are provided in occupancies specified in smoothing irons and electrically heated appliances that
4.22.3.5(A) through (D). are rated at more than 50 watts and produce temperatures
(A) Multifamily Dwellings. In multifamily dwellings, in excess of 121 °C on surfaces with which the cord is
the other disconnecting means shall be within the likely to be in contact shall be provided with one of the
dwelling unit, or on the same floor as the dwelling types of approved heater cords listed in Table 4.0.1.4.
unit in which the appliance is installed, and shall be (B) Other Heating Appliances. All other cord-and
permitted to control lamps and other appliances. plug-connected electrically heated appliances shall be
(B) Two-Family Dwellings. In two-family dwellings, connected with one of the approved types of cord listed
the other disconnecting means shall be permitted in Table 4.0.1.4, selected in accordance with the usage
either inside or outside of the dwelling unit in which specified in that table.
the appliance is installed. In this case, an individual 4.22.4.5 Cord-and Plug-Connected Immersion
switch or circuit breaker for the dwelling unit shall be Heaters. Electric heaters of the cord-and plug-connected
permitted and shall also be permitted to control lamps immersion type shall be constructed and installed so that
and other appliances. current-carrying parts are effectively insulated from electrical
contact with the substance in which they are immersed.
(C) One-Family Dwellings. In one-family dwellings,
the service disconnecting means shall be permitted to 4.22.4.6 Stands for Cord-and Plug-Connected
be the other disconnecting means. Appliances. Each smoothing iron and other cord-and
plug-connected electrically heated appliance intended

322
ARTICLE 4.22-APPLIANCES
to be applied to combustible material shall be equipped Where motor overload protection external to the
with an approved stand, which shall be permitted to be appliance is required, the appliance shall be so marked.
a separate piece of equipment or a part of the appliance. FPN: See 4.22.2.2 for overcurrent protection requirements.
4.22.4.7 Flatirons. Electrically heated smoothing (B) To Be Visible. Marking shall be located so as to be
irons shall be equipped with an identified temperature- visible or easily accessible after installation.
limi ting means.
4.22.5.2 Marking of Heating Elements. All heating
4.22.4.8 Water Heater Controls. All storage or elements that are rated over one ampere, replaceable
instantaneous-type water heaters shall be equipped with in the field, and a part of an appliance shall be legibly
a temperature-limiting means in addition to its control marked with the ratings in volts and amperes, or in volts
thermostat to disconnect all ungrounded conductors. and watts, or with the manufacturer's part number.
Such means shall comply with both of the following:
( 1) Installed to sense maximum water temperature. 4.22.5.3 Appliances Consisting of Motors and Other
Loads.
(2) Be either a trip-free, manually reset type or a
type having a replacement element. Such water (A) Nameplate Horsepower Markings. Where
heaters shall be marked to require the installation a motor-operated appliance nameplate includes a
of a temperature and pressure relief valve. horsepower rating, that rating shall not be less than the
horsepower rating on the motor nameplate. Where an
Exception No. 1: Storage water heaters that are appliance consists of multiple motors, or one or more
identified as being suitable for use with a supply water motors and other loads, the nameplate value shall not be
temperature of 82°C or above and a capacity of 60 kW less than the equivalent horse-power of the combined
or above. loads, calculated in accordance with 4.30.9 .1 O(C)(l ).
Exception No. 2: Instantaneous-type water heaters that (B) Additional Nameplate Markings. Appliances,
are identified as being suitable for such use, with a other than those factory-equipped with cords and
capacity of 4 L or less. attachment plugs and with nameplates in compliance
FP ·: See ANSI Z21.22-1999/CSA 4.4-M99, Relief Valves for with 4.22.5.1 , shall be marked in accordance with
Hot Water Supply Systems. 4.22.5.3(B)( l) or (B)(2).
4.22.4.9 Infrared Lamp Industrial Heating (1) Marking. In addition to the marking required in
Appliances. 4.2- .5.1, the marking on an appliance consisting
(A) 300 Watts or Less. Infrared heating lamps rated at of a motor with other load(s) or motors with or
300 watts or less shall be permitted with lampholders without other load(s) shall specify the minimum
of the medium-base, unswitched porcelain type or other supply circuit conductor ampacity and the
types identified as suitable for use with infrared heating maximum rating of the circuit overcurrent
lamps rated 300 watts or less. protective device. This requirement shall not apply
to an appliance \.vith a nameplate in compliance
(B) Over 300 Watts. Screw shell lampholders shall not with 4.22.5.1 where both the minimum supply
be used with infrared lamps rated over 300 watts, unless
circuit conductor ampacity and maximum rating
the lampholders are identified as being suitable for use
of the circuit overcurrent protective device are
with infrared heating lamps rated over 300 watts. not more than 15 amperes.
4.22.4.11 Cord-and Plug-Connected Pipe Heating (2) Alternate Marking Method. An alternative
Assemblies. Cord-and plug-connected pipe heating marking method shall be permitted to specify the
assemblies in-tended to prevent freezing of piping shall rating of the largest motor in volts and amperes,
be listed.
and the additional load(s) in volts and amperes,
4.22.5 Marking or volts and watts in addition to the marking
required in 4.22.5 .1. The ampere rating of a
4.22.5.1 Nameplate.
motor l;8 horsepower or less or a nonmotor load
(A) Nameplate Marking. Each electrical appliance 1 ampere or less shall be permitted to be omitted
shall be provided with a nameplate giving the identifying unless such loads constitute the principal load.
name and the rating in volts and amperes, or in volts
and watts. If the appliance is to be used on a specific
frequency or frequencies, it shall be so marked.

323
ARTICLE 4.24 - - FIXED ELECTRIC SPACE-HEATll\U EQUI PME T
ARTICLE 4.24 - FIXED ELECTRIC SPACE- shall be protected in an approved manner.
HEATING EQUIPMENT
(B) Damp or Wet Locations. Heaters and relar · :
4.24.1 General equipment installed in damp or wet locations ha'.:
be listed for such locations and shall be constru ~t c
4.24.1.l Scope. This article covers fixed electric
and installed so that water or other liquids ca1mot
equipment used for space heating. For the purpose of
enter or accumulate in or on wired sections, electri 'a;
this article, heating equipment shall include heating
components, or ductwork.
cable, unit heaters, boilers, central systems, or other
approved fixed electric space-heating equipment. This FP No. I: See 1.10. 1.11 for equipment exposed to deteriorating
agents.
article hall not apply to proce heating and room air
conditioning. FPN No. 2: See 6.80.2.S(C) for pool deck areas.

4.24.1.2 Other Articles. Fixed electric pace-heating 4.24.2.5 Spacing from Combustible Materials. Fixed
equipment incorporating a he1metic refrigerant motor- electric space-heating equipment shall be installed to
compressor shall also comply with A1iicle 4.40 . provide the required spacing between the equipment
and adjacent combustible material unless it is listed to
4.24.1.3 Branch Circuits.
be installed in direct contact with combustible material.
(A) Branch-Circuit Requirements. lndiYidual branch
circuit shall be pem1itted to supply any volt-amp re or 4.24.3 Control and Protection of Fixed Electric
wattage rating of fixed electric space-heating equipment Space-Heating Equipment
for which they are rated.
4.24.3.1 Disconnecting Means. Means shall be
Branch circuits supplying two or more outlets for fixed provided to simultaneously discom1ect the heater,
electric space-heating equipment shall be rated not owr motor controller(s) and supplementary overcurrent
30 amperes. In other than a dwelling unit. fixed infrar d protective device(s) of all fixed electric space-heating
heating equipment shall be pennitted to be upplied equipment from all ungrounded conductors. Where
from branch circuits rated not over 50 ampere . . heating equipment is supplied by more than one source,
fi eder. or branch circuit, the disconnecting means
(B) Branch-Circuit Sizing. Fixed electric pace-
hall be grouped and identified as having multiple
heating equipment and motors shall be con idered
di. conne ting means . Each disconnecting means shall
continuous load.
~imultan ously di connect all ungrounded conductors
4.24.1.6 Listed Equipment. Electric ba eboard hearer . that it control . The disconnecting means specified in
heating cables, duct heaters, and radiant heating y tern 4.-4 .3 . l (A) and (B) shall have an ampere rating not
shall be listed and labeled. 1 than l _5 percent of the total load of the motors and
4.24.2 Installation th heat r and shall be lockable in accordance with
1.10.1._-,
4.24.2.1 General. Permanently installed electric
baseboard heaters equipped with factory-installed (A) Heating Equipment with Supplementary
receptacle outlets, or outlets provided as a separate Overcurrent Protection. The disconnecting means
listed assembly, shall be pennitted in lieu of a receptacl for fixed electric space-heating equipment with
outlet(s) that is required by 2.10.3.1 (B). Such receptacle supplementary overcurrent protection shall be within
outlets shall not be connected to the heater circuit . ight from the supplementary overcurrent protective
d \'ice( ), on the supply side of these devices, if fuses, and, in
FPN: Listed ba eboard heaters include instructions that may not addition, shall comply with either 4.24.3 . 1(A)(l) or (A)(2).
pem1it their installation below receptacle outlet .
(1) Heater Containing No Motor Rated over
4.24.2.3 Supply Conductors. Fixed electric space- 118 Horse-power. The disconnecting means
heating equipment requiring upply conductor · with specified in 4.24.3.1 or unit switche complying
over 60°C in ulation shall be clearly and pe1manently with 4.24.3 .1 (C) shall be permitted to serve as
marked. This marking shall be plainly visible after the required disconnecting means for both the
in tallation and shall be permitted to be adjacent to the motor controller(s) and heater under either of the
fiel d connection box. following conditions:
4.24 .2.4 Locations. ( 1) The disconnecting means provided is also
within sight from the motor controller(s) and
(A) Exposed to Physical Damage. Where subject to
tl1e heater.
physical damage, fixed electric space-heating equipment
324
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPM ENT
(2) The disconnecting means is lockable in an individual switch or circuit breaker for the
accordance with 1.10.1.25. dwelling unit shall be permitted and shall also be
permitted to control lamps and appliances.
(2) Heater Containing a Motor(s) Rated over 118
Horsepower. The above disconnecting means (3) One-Family Dwellings. In one-family dwellings,
shall be pennitted to serve as the required the service disconnecting means shall be
disconnecting means for both the motor permitted to be the other disconnecting means.
controller(s) and heater under either of the
(4) Other Occupancies. In other occupancies, the
following conditions:
branch-circuit switch or circuit breaker, where
( 1) Where the disconnecting means is in sight readily accessible for servicing of the fixed heater,
from the motor controller(s) and the heater and shall be permitted as the other disconnecting
complies with Part 4.30.9. means.
(2) Where a motor(s) of more than 1/8 hp and the 4.24.3 .2 Thermostatically Controlled Switching
heater are provided with a single unit switch Devices.
that complies with 4.22.3.5(A), (B), (C), or (D),
(A) Serving as Both Controllers and Disconnecting
the disconnecting means shall be pennitted to
Means. Thennostatically controlled switching devices
be out of sight from the motor controller.
and combination thermostats and manually controlled
(B) Heating Equipment Without Supplementary switches shall be pennitted to serve as both controllers
Overcurrent Protection. and disconnecting means, provided they meet all of the
following conditions:
(1 ) Without Motor or with Motor Not over 118
Horsepower. For fixed electric space-heating ( 1) Provided with a marked "off'' position
equipment without a motor rated over 1/8 hp, the
(2) Directly open all ungrounded conductors when
branch-circuit switch or circuit breaker shall be
manually placed in the "off'' position
permitted to serve as the disconnecting means
where the switch or circuit breaker is within sight (3) Designed so that the circuit carmot be energized
from the heater or is lockable in accordance with automatically after the device has been manually
1.10.1.25. placed in the "off'' position
(2) Over 118 Horsepower. For motor-driven electric (4) Located as specified in 4.24.3.1
space-heating equipment with a motor rated over (B) Thermostats That Do Not Directly Interrupt
1/8 hp, a disconnecting means shall be located All Ungrounded Conductors. Thennostats that do
within sight from the motor controller or shall not directly intenupt all ungrounded conductors and
be permitted to comply with the requirements in thermostats that operate remote-control circuits shall
4.24.3.1 (A)(2). not be required to meet the requirements of 4.24.3.2(A).
(C) Unit Switch(es) as Disconnecting Means. A unit These devices shall not be pennitted as the disconnecting
switch(es) with a marked "off'' position that is part of a means .
fixed heater and disconnects all ungrounded conductors 4.24.3.3 Switch and Circuit Breaker to Be Indicating.
shall be permitted as the disconnecting means required Switches and circuit breakers used as disconnecting
by this article where other means for disconnection are means shall be of the indicating type .
provided in the types of occupancies in 4.24.3. l (C )(l)
through (C)(4). 4.24.3.4 Overcurrent Protection.
(1) Multifamily Dwellings. In multifamily (A) Branch-Circuit Devices. Electric space-heating
dwelling . the other disconnecting means shall equipment, other than such motor-operated equipment
be within the dwelling unit, or on the same floor as required by Articles 4.30 and 4.40 to have additional
as the dwelling unit in which the fixed heater is overcurrent protection, shall be pem1itted to be
installed, and shall also be permitted to control protected against overcurrent where supplied by one of
lamps and appliances. the branch circuits in Article 2. 10.
(2) Two-Family Dwellings. In two-family dwellings, (B) Resistance Elements. Resistance-type heating
the other disconnecting means shall be pe1mitted elements in electric space-heating equipment shall be
either inside or outside of the dwelling unit in protected at not more than 60 amperes. Equipment rated
which the fixed heater is installed. In this case,

325
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPMENT
more than 48 amperes and employing such elements of field-wired conductors between the heater and the
shall have the heating elements subdivided, and each supplementary overcurrent protective devices shall be
subdivided load shall not exceed 48 amperes. Where permitted to be not less than 100 percent of the load of
a subdivided load is less than 48 amperes, the rating their respective subdivided circuits, provided all of the
of the supplementary over-current protective device following conditions are met:
shall comply with 4.24.1.3(B). A boiler employing
(1) The heater is marked with a minimum conductor
resistance-type immersion heating elements contained
size.
in anASME-rated and stamped vessel shall be permitted
to comply with 4.24.7.3(A). (2) The conductors are not smaller than the marked
mmimum size.
(C) Overcurrent Protective Devices. The
supplementary overcurrent protective devices for the (3) A temperature-activated device controls the
subdivided loads specified in 4.24.3.4(B) shall be (1) cyclic operation of the equipment.
factory-installed within or on the heater enclosure or
supplied for use with the heater as a separate assembly 4.24.4 Marking of Heating Equipment
by the heater manufacturer; (2) accessible, but shall not
be required to be readily accessible; and (3) suitable for 4.24.4.1 Nameplate.
branch-circuit protection. (A) Marking Required. Each unit of fixed electric
FPN: See 2.40.1.10. space-heating equipment shall be provided with a
Where cartridge fuses are used to provide this nameplate gi\·ing the identifying name and the nonnal
overcurrent protection, a single disconnecting means rating in Yolt a d wam or in volts and amperes.
shall be per-mitted to be used for the several subdivided Electric space-hea ing equipment intended for use on
loads. alternating current only, direct current only, or both shall
FPN No. 1: For supplementary overcurrent protection, see be marked to so i di ate. The marking of equipment
2.40.1.10. consisting of motors owr hp and other loads shall
FPN No. 2: For disconnecting means for cartridge fuses in circuits specify the ra~ing o the motor in volts, amperes, and
of any voltage, see 2.40.4.1. frequency, and the heating load in volts and watts or in
volts and am ere-.
(D) Branch-Circuit Conductors. The conductors
supplying the supplementary overcurrent protective (B) Location. Thi nameplate shall be located so as to
devices shall be considered branch-circuit conductors. be Yisible or easih· accessible after installation.
Where the heaters are rated 50 kW or more, the 4.24.4.2 :\larking of Heating Elements. All heating
conductors supplying the supplementary overcurrent elemen • a are replaceable in the field and are part
protective devices specified in 4.24.3.4(C) shall be of an elec ·c heater shall be legibly marked with the
permitted to be sized at not less than 100 percent of ratings · Yol and watts or in volts and amperes.
the nameplate rating of the heater, provided all of the
following conditions are met: 4.24.5 Electric Space-Heating Cables
( 1) The heater is marked with a minimum conductor
4.24.5.1 Hea ting Cable Construction. Factory-
size.
assembled nonheating leads of heating cables, if any,
(2) The conductors are not smaller than the marked shall be at least _ 100 mm in length.
mmimum size.
4.24.5.2 M arking of Heating Cables. Each unit shall
(3) A temperature-actuated device controls the cyclic be marked with the identifying name or identification
operation of the equipment. symbol, catalog number, and ratings in volts and watts
or in volts and amperes.
(E) Conductors for Subdivided Loads. Field-wired
conductors between the heater and the supplementary 4.24.5.3 Clearances of Wiring in Ceilings. Wiring
overcurrent protective devices shall be sized at not less located above heated ceilings shall be spaced not less
than 125 percent of the load served. The supplementary than 50 mm above the heated ceiling. The ampacity of
overcurrent protective devices specified in 4.24.3.4(C) conductors shall be calculated on the basis of an assumed
shall protect these conductors in accordance with ambient temperature of 50°C, applying the correction
2.40.1.4. factors shown in the O - 2000 volt ampacity tables of
Article 3 .10. If this wiring is located above thermal
Where the heaters are rated 50 kW or more, the ampacity
326
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPMENT
insulation having a minimum thickness of 50 mm, the (B) Adjacent Runs. Adjacent runs of heating cable
wiring shall not require correction for temperature. shall be installed in accordance with the manufacturer's
instructions.
4.24.5.5 Area Restrictions.
(C) Surfaces to Be Applied. Heating cables shall
(A) Extending Beyond the Room or Area. Heating
be applied only to gypsum board, plaster lath, or
cables shall be permitted to extend beyond the room or
other fire-resistant material. With metal lath or other
area in which they originate.
electrically conductive surfaces, a coat of plaster or
(B) Uses Not Permitted. Heating cables shall not be other means employed in accordance with the heating
installed as follows: cable manufacturer's instructions shall be applied to
(1) In closets, other than as noted in 4.24.5 .S(C) completely separate the metal lath or conductive surface
from the cable.
(2) Over the top of walls where the wall intersects the
FPN: See also 4.24.5.8(F).
ceiling
(D) Splices. All heating cables, the splice between
(3) Over partitions that extend to the ceiling, unless
the heating cable and nonheating leads, and 75-mm
they are isolated single runs of embedded cable
minimum of the nonheating lead at the splice shall be
(4) Under or through walls embedded in plaster or dry board in the same manner as
the heating cable.
(5) Over cabinets whose clearance from the ceiling
is less than the minimum horizontal dimension of (E) Ceiling Surface. The entire ceiling surface shall
the cabinet to the nearest cabinet edge that is open have a finish of thermally noninsulating sand plaster
to the room or area that has a nominal thickness of 13 mm, or other
noninsulating material identified as suitable for this
(6) In tub and shmver ,valls
use and applied according to specified thickness and
(7) C"nder cabinets or similar built-ins having no directions.
clearance to the n oo
(F) Secured. Cables shall be secured by means of
(C) In Closet Ceilings as Low-Temperature Heat approved stapling, tape, plaster, nonmetallic spreaders,
Sources to Control Relatrre Humidity. The provisions or other approved means either at intervals not
) h · o reven- - e e of cable in closet exceeding 400 mm or at intervals not exceeding 1 800
e T gs as ow- rarure heat sources to control mm for cables identified for such use. Staples or metal
u=ry. . ,ide they are used only in those
0

.UUCU..U.' -• •
fasteners that straddle the cable shall not be used with
portions of th · · g that are unobstructed to the floor metal lath or other electrically conductive surfaces.
by she ·es or o- er permanent luminaires.
(G) Dry Board Installations. In dry board installations,
4.24.5.6 Oearance from Other Objects and the entire ceiling below the heating cable shall be
Openings... Hearing elements of cables installed in covered with gypsum board not exceeding 13 mm
ce ·· · gs s a I be separated at least 200 mm from the thickness. The void between the upper layer of gypsum
edge o o e boxes and junction boxes that are to be board, plaster lath, or other fire-resistant material and
used ro ounting surface luminaires. A clearance of the surface layer of gypsum board shall be completely
not les:- dian 50 mm shall be provided from recessed filled with thermally conductive, nonshrinking plaster
luminaires and their trims, ventilating openings, and or other approved material or equivalent thermal
others ch openings in room surfaces. No heating cable conductivity.
shall be overed by any surface-mounted equipment.
(H) Free from Contact with Conductive Surfaces.
4.24..5.7 Splices. The length of heating cable shall only Cables shall be kept free from contact with metal or
be altered using splices identified in the manufacturer's other electrically conductive surfaces.
instructions.
(I) Joists. In dry board applications, cable shall be
4.24.5.8 Ceiling Installation of Heating Cables on installed parallel to the joist, leaving a clear space
Dry Board, in Plaster, and on Concrete Ceilings. centered under the joist of 65 mm (width) between
(A) In Walls. Cables shall not be installed in walls centers of adjacent runs of cable. A surface layer of
unless it is necessary for an isolated single run of gypsum board shall be mounted so that the nails or
cable to be installed down a vertical surface to reach a other fasteners do not pierce the heating cable.
dropped ceiling.

327
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPME T
(J) Crossing Joists. Cables shall cross joists only at the electrically heated floors of bathrooms and kitchen a-:-
ends of the room unless the cable is required to cross in hydromassage bathtub locations.
joists elsewhere in order to satisfy the manufacturer's
4.24.5.12 Installation of Cables Under Floor
instructions that the installer avoid placing the cable too
Coverings.
close to ceiling penetrations and luminaires.
(A) Identification. Heating cables for installatio::r
4.24.5.9 Finished Ceilings. Finished ceilings shall not
under floor cove1ing shall be identified as suitable f :
be covered with decorative panel or beams constructed
installation under floor covering.
of materials that have thermal insulating properties,
such as wood, fiber, or plastic. Finished ceilings shall be (B) Expansion Joints. Heating cables shall not · -c
permitted to be co, ered with paint, wallpaper, or other installed where they bridge expansion joints unle s
approved surface finishes . provided with expansion and contraction fitting
applicable to the manufacture of the cable.
4.24.5.10 Installation of Nonheating Leads of Cables. (C) Connection to Conductors. Heating cables . hal
(A) Free Nonheating Leads. be connected to branch-circuit and supply wiring by
wiring methods described in the installation instruction
Free nonheating leads of cables shall be installed in or as recognized in Chapter 3.
accordance with approved wiring methods from the
junction box to a location within the ceiling. Such (D) Anchoring. Heating cables shall be positioned
installations shall be permitted to be single conductors or secured in place under the floor covering, per the
in approved raceways, single or multiconductor Type manufacturer's in tructions .
UF, Type NM , Type MI, or other approved conductor . (E) Ground-Fault Circuit-Interrupter Protection.
(B) Leads in Junction Box. Not less than 150 mm of Ground-fault circuit-interrupter protection for personnel
free nonheating lead shall be within the junction box. shall be pro\·ided.
The marking of the leads shall be visible in the junction (F) Grounding Braid or Sheath. Grounding means,
box. such a copper braid, metal sheath, or other approved
(C) Excess Leads. Excess leads of heating cables shall mean , hall be provided as part of the heated length.
not be cut but shall be secured to the underside of the 4.24.5.13 Inspection and Tests. Cable installations
ceiling and embedded in plaster or other approved hall be made \Vith due care to prevent damage to the
material, leaving only a length sufficient to reach the cable a embly and shall be inspected before cables are
junction box with not less than 150 mm of free lead coYered or concealed.
within the box.
4.24.5.14 Label Provided by Manufacturer. The
manufacturers of electric space-heating cables shall
4.24.5.11 Installation of Cables in Concrete or prO\ide marking labels that indicate that the space-heating
Poured Masonry Floors. in tallation incorporates electric space-heating cables and
(A) Adjacent Runs. Adjacent runs of heating cable in tructions that the labels shall be affixed to the panelboards
shall be installed in accordance with the manufacturer' to identify , hich branch circuits supply the circuits to those
space-heating installations. If the electric space-heating cable
instructions.
in tallations are visible and distingui hable after installation,
(B) Secured in Place. Cable hall be ecured in place the labels shall not be required to be provided and affixed to
by nonmetallic frames or spreaders or other approved the panelboards.
means while the concrete or other finish is applied. 4.24.6 Duct Heaters
(C) Leads Protected. Lead shall be protected where 4.24.6.1 General. Part 4.24.6 shall apply to any heater
they leave the floor by rigid metal conduit, intennediate mounted in the airstream of a forced-air system where
metal conduit rigid nonmetallic conduit el ctrical the air-moving unit is not provided as an integral part of
metallic tubing, or by other approved means. the equipment.
(D) Bushings or Approved Fittings. Bushings or 4.24.6.2 Identification. Heaters installed in an air duct
approved fittings shall be used where the leads emerge shall be identified as suitable for the installation.
within the floor slab.
4.24.6.3 Airflow. Means shall be provided to ensure
(E) Ground-Fault Circuit-Interrupter Protection. uniform airflow over the face of the heater in accordan e
Ground-fault circmt-mterrupter protection for with the manufacturer's instructions.
personnel shall be provided for cables installed in
328
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPMENT
FPN: Heaters installed within 1200 mm of the outlet of an air- Ventilating Systems, and NFPA 90B~2015, Standard for the
moving device, heat pump, air conditioner, elbows, baffle plates, Installation of Warm Air Heating and Air-Conditioning Systems.
or other obstructions in duct-work may require turning vanes,
pressure plates, or other devices on the inlet side of the duct heater 4.24.7 Resistance-Type Boilers
to ensure an even distribution of air over the face of the heater.
4.24. 7 .1 Scope. The provisions in Part 4.24. 7 shall apply
4.24.6.4 Elevated Inlet Temperature. Duct heaters to boilers employing resistance-type heating elements.
intended for use with elevated inlet air temperature See Part 4.24.8 for electrode-type boilers.
shall be identified as suitable for use at the elevated
4.24.7.2 Identification. Resistance-type boilers shall
temperatures.
be identified as suitable for the installation.
4.24.6.5 Installation of Duct Heaters with Heat
4.24.7.3 Overcurrent Protection.
Pumps and Air Conditioners. Heat pumps and air
conditioners having duct heaters closer than 1 200 Mm (A) Boiler Employing Resistance-Type Immersion
to the heat pump or air conditioner shall have both the Heating Elements in an ASME-Rated and Stamped
duct heater and heat pump or air conditioner identified Vessel. A boiler employing resistance-type immersion
as suitable for such installation and so marked. heating elements contained in an ASME-rated and
stamped vessel shall have the heating elements protected
4.24.6.6 Condensation. Duct heaters used with air
at not more than 150 amperes. Such a boiler rated more
conditioners or other air-cooling equipment that could
than 120 amperes shall have the heating elements
result in condensation of moisture shall be identified as
subdivided into loads not exceeding 120 amperes.
suitable for use with air conditioners.
Where a subdivided load is less than 120 amperes, the
4.24.6.7 Fan Circuit Interlock. Means shall be
rating of the overcurrent protective device shall comply
provided to ensure that the fan circuit is energized
with 4.24.1.3(B).
when any heater circuit is energized. However, time-
or temperature-controlled delay in energizing the fan (B) Boiler Employing Resistance-Type Heating
motor shall be permitted. Elements Rated More Than 48 Amperes and Not
Contained in an ASME-Rated and Stamped Vessel.
4.24.6.8 Limit Controls. Each duct heater shall be
A boiler employing resistance-type heating elements not
provided with an approved, integral, automatic-reset
contained in an ASME-rated and stamped vessel shall
temperature-limiting control or controllers to de-
have the heating elements protected at not more than
energize the circuit or circuits.
60 amperes. Such a boiler rated more than 48 amperes
In addition, an integral independent supplementary shall baYe the heating elements subdivided into loads
control or controllers shall be provided in each duct not exceeding 48 amperes.
heater that disconnects a sufficient number of conductors
Where a subdivided load is less than 48 amperes, the
to interrupt current flow. This device shall be manually
rating of the overcurrent protective device shall comply
resettable or replaceable.
\Tith 4.24. l .3(B).
4.24.6.9 Location of Disconnecting M eans. Du t
(C) Supplementary Overcurrent Protective Devices.
heater controller equipment shall be either ac e ible
The supplementary overcurrent protective devices for
with the dis-connec ing mean installed at or within
the subdivided loads as required by 4.24.7 .3(A) and (B)
sight from the controller or as permined by 4.A.3. l(a).
shall be as follows:
4.24.6.10 Installation.
(1) Factory-installed within or on the boiler enclosure
(A) General. Duct hearers shall be installed in or provided as a separate assembly by the boiler
accordance v-.ith the manufacturer's instructions in such manufacturer
a manner that operation does not create a hazard to
(2) Accessible, but need not be readily accessible
persons or property. Furthermore, duct heaters shall be
located with respect to building construction and other (3) Suitable for branch-circuit protection
equipment so as to permit access to the heater. Sufficient Where cartridge fuses are used to provide this
clearance shall be maintained to permit replacement of overcurrent protection, a single disconnecting means
controls and heating elements and for adjusting and shall be per-mitted for the several subdivided circuits.
cleaning of controls and other parts requiring such See 2.40.4.1.
attention. See 1.10.2.1.
(D) Conductors Supplying Supplementary
FPN: For additional installation information, see NFPA 90A-
2015, Standard for the Installation of Air-Conditioning and
Overcurrent Protective Devices. The conductors

329
ARTICLE 4.24 FIXED ELECTRIC SPACE-HEATI G EQUIPME T
supplying these supplementary overcurrent protective ungrounded conductors to the heating elements. Such
devices shall be considered branch-circuit conductors. means shall be in addition to a pressure-regulating
system and other devices protecting the tank against
Where the heaters are rated 50 kW or more, the
excessive pressure.
conductors supplying the overcurrent protective device
specified in 4.24. 7 .3(C) shall be permitted to be sized at
4.24.8 Electrode-Type Boilers
not less than I 00 percent of the nameplate rating of the
heater, provided all of the following conditions are met: 4.24.8.1 Scope. The provisions in Part 4.24.8 shall
apply to boilers for operation at 600 volts, nominal, or
(1) The heater is marked with a minimum conductor
less, in which heat is generated by the passage of current
size.
between electrode through the liquid being heated .
(2) The conductors are not smaller than the marked FPN: For over 600 volts, see Part 4.90.5 .
minimum size.
(3) A temperature- or pressure-actuated device 4.24.8.2 Identification. Electrode-type boilers shall be
controls the cyclic operation of the equipment. identified as suitable for the installation.
(E) Conductors for Subdivided Loads. Field-wired
4.24.8.3 Branch-Circuit Requirements. The size of
conductors between the heater and the supplementary
branch-circuit conductors and overcurrent protective
overcurrent protective devices shall be sized at not less
devices shall be calculated on the basis of 125 percent of
than 125 percent of the load served. The supplementary
the total load (motors not included). A contactor, relay,
overcurrent protective devices specified in 4 .24.7.3 (C)
or other device, approved for continuous operation at
shall protect these conductors in accordance with
100 percent of its rating, shall be permitted to supply
2.40.1.4.
its full-rated load. See 2.10.2.2(A), Exception. The
Where the heaters are rated 50 kW or more, the ampacity provisions of this section shall not apply to conductors
of field-wired conductors between the heater and the that form an integral part of an approved boiler.
supplementary overcurrent protective devices shall be
Where an electrode boiler is rated 50 kW or more, the
permitted to be not less than 100 percent of the load of
conductors supplying the boiler electrode(s) shall be
their respective subdivided circuits, provided all of the
permitted to be sized at not less than 100 percent of tl1e
following conditions are met:
name-plate rating of the electrode boiler, provided all
(1) The heater is marked with a minimum conductor the following conditions are met:
size.
( 1) The electrode boiler is marked with a mininmm
(2) The conductors are not smaller than the marked conductor size.
minimum size.
(2) The conductors are not smaller than the marked
(3) A temperature-activated device controls the minimum size.
cyclic operation of the equipment.
(3) A temperature- or pressure-actuated device
controls the cyclic operation of the equipment.
4.24.7.4 Overtemperature Limit Control. Each boiler
designed so that in normal operation there is no change
4.24.8.4 Overtemperature Limit Control. Each boiler,
in state of the heat transfer medium shall be equipped
de-signed so that in normal operation there i no change
with a temperature-sensitive limiting means. It shall
in state of the heat transfer medium. shall be equipped
be installed to limit maximum liquid temperature and
with a temperature- ensiti,·e limiting means. It shall
shall directly or in-directly disconnect all ungrounded
be installed to limit maximum liquid temperature and
conductors to the heating elements. Such means shall
shall directly or in-directly interrupt all current flow
be in addition to a temperature-regulating system and
throuoh
~
the electrodes. Such means shall be in addition
.
other devices protecting the tank against excessive
to the temperature-regulating system and other devices
pressure.
protecting the tank against excessive pressure.
4.24.7.5 Overpressure Limit Control. Each boiler
4.24.8.5 Overpressure Limit Control. Each boiler,
designed so that in normal operation there is a change
designed so that in nonnal operation there is a change in
in state of the heat transfer medium from liquid to
state of the heat transfer medium from liquid to vapor,
vapor shall be equipped with a pressure-sensitive
shall be equipped with a pressure-sensitive limiting
limiting means. It shall be installed to limit maximum
means. It shall be installed to limit maximum pressure
pressure and shall directly or indirectly disconnect all
330
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPMENT
and shall directly or indirectly interrupt all current flow (B) Identified as Suitable. Each unit shall be identified
through the electrodes. Such means shall be in addition as suitable for the installation.
to a pressure-regulating system and other devices
(C) Required Markings. Each unit shall be marked
protecting the tank against excessive pressure.
with the identifying name or identification symbol,
catalog number, and rating in volts and watts or in volts
4.24.8.6 Grounding. For those boilers designed such
and amperes.
that fault currents do not pass through the pressure
vessel and the pressure vessel is electrically isolated
4.24.9.4 Installation.
from the electrodes, all exposed non- current-carrying
metal parts. including the pressure vessel, supply, and (A) General.
return connecting piping, hall be grounded. (1) Manufacturer's Instructions. Heating panels
For all other de ign the pressure vessel containing the and heating panel sets shall be installed in
electrode hall be i elated and electrically insulated accordance with the manufacturer's instructions.
from gro d. (2) Locations Not Permitted. The heating portion
4.24.8. :'.\.Iarkings. All electrode-type boilers shall be shall not be installed as follows:
mark d -how the following: ( 1) In or behind surfaces where subject to physical
(1 ) Th :nan a turer's name. damage
(2 ) Th :io rating in volts, amperes, and (2) Run through or above walls, pa1titions,
kilo;,.· cupboards, or similar portions of structures that
extend to the ceiling
· al upply required specifying
number of phases, and number of (3) Rtm in or through thermal insulation, but shall
be permitted to be in contact with the surface of
thermal insulation
4 = ··Electrode-Type Boiler."
(3) Separation from Outlets for Luminaires. Edges
: I --\. ·i.-aming marking, ··...\11 Power Supplies Shall
of panels and panel sets shall be sepanted by not
B D" ed B fore Servicing, Including
less than 200 mm from the edges of any outlet
cc\-, Pr sur \"e el." A field-applied
boxes and junction boxes that are to be used for
·;,. ar.::: ;-= wa.-k· or label hall comply with
mounting surface luminaires. A clearance of not
:.:o__ _:: B .
less than 50 mm shall be provided from recessed
ated o as to be visible after luminaires and their trims, ventilating openings,
and other such openings in room surfaces, unless
the heating panels and panel sets are listed and
4.24.9 Electri Radiant Heatino Panels and Heating
marked for lesser clearances, in which case they
Panel e
shall be permitted to be installed at the marked
o: Part 4 __4 _9 shall clearances. Sufficient area shall be provided to
en ure that no heating panel or heating panel set
i t0 be covered b any urface-mounted units.

( 4) Surfaces CoYering Heating Panels. After


the h atin2: panel or heating panel sets are
installed and inspected, it shall be permitted to
install a urface that has been identified by the
Heating Panel manufacrurer·s instructions as being suitable for
pro, ided v.i- the installation. The surface shall be secured so
that th nails or other fastenings do not pierce the
assemb y id
beating panel or beating panel sets.
a wmng y tern.
(5) Surface Coverings. Surfaces permitted by
4.24.9.3 ::\Iarkings.
4.24.9.4(A)(4) shall be pemlitted to be covered
(A) Location. Marking hall be permanent and in with paint, wallpaper, or other approved surfaces
a location that is vi ible prior to application of panel identified in the manufacturer's instructions as
finish. being suitable.
331
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPMENT
(B) Heating Panel Sets. panel sets shall be connected to branch-circ •
wiring by a method identified as being suitable
(1) Mounting Location. Heating panel sets shall be
for the purpose.
per-mitted to be secured to the lower face of joists
or mounted in between joists, headers, or nailing (2) Panel Sets with Terminal Junction Assembly.
strips. A heating panel set provided with termina~
junction assembly shall be permitted to ha\·
(2) Parallel to Joists or Nailing Strips. Heating
the nonheating leads attached at the time of
panel sets shall be installed parallel to joists or
installation in accordance with the manufacturer 's
nailing strips.
instructions.
(3) Installation of Nails, Staples, or Other
4.24.9.8 Nonheating Leads. Excess nonheating
Fasteners. Nailing or stapling of heating panel
leads of heating panels or heating panel sets shall be
sets shall be done only through the unheated
permitted to be cut to the required length as indicated in
portions provided for this purpose. Heating panel
the manufacturer's installation instructions. Nonheating
sets shall not be cut through or nailed through
leads shall be an integral part of a heating panel and
any point closer than 6 mm to the element. Nails,
a heating panel set, either attached or provided by the
staples, or other fasteners shall not be used where
manufacturer as part of a terminal junction assembly,
they penetrate current-carrying parts.
shall not be subjected to the an1pacity requirements of
(4) Installed as Complete Unit. Heating panel 4.24. l .3(B) for branch circuits.
sets shall be installed as complete units unless
4.24.9.9 Installation in Concrete or Poured Masonry.
identified as suitable for field cutting in an
approved manner. (A) Secured in Place and Identified as Suitable.
4.24.9.5 Clearances of Wiring in Ceilings. Wiring Heating panels or heating panel sets shall be secured
located above heated ceilings shall be spaced not less in place by means specified in the manufacturer's
than 50 mm above the heated ceiling. The ampacity instructions and identified as suitable for the installation.
shall be calculated on the basis of an assumed ambient
(B) Expansion Joints. Heating panels or heating panel
temperature 50°C, applying the correction factors given
sets shall not be installed where they bridge expansion
in the O - 2000 volt ampacity tables of Article 3.10. If
joints unless provision is made for expansion and
this wiring is located above thermal insulations having
contraction.
a minimum thickness of 50 mm, the wiring shall not
require correction for temperature. (C) Spacings. Spacings shall be maintained between
heating panels or heating panel sets and metal embedded
4.24.9.6 Location of Branch-Circuit and Feeder
in the floor. Grounded metal-clad heating panels shall
Wiring in Walls.
be permitted to be in contact with metal embedded in
(A) Exterior Walls. Wiring methods shall comply with the fl oor.
Article 3.0 and 3.10.2.6(A)(3).
(D) Protection of Leads. Leads shall be protected where
(B) Interior Walls. The ampacity of any wiring behind they leave the floor by rigid metal conduit, intermediate
heating panels or heating panel sets located in interior metal conduit, rigid nonmetallic conduit, or electrical
walls or partitions shall be calculated on the basis of metallic tubing, or by other approved means.
an assumed ambient temperature of 40°C, applying
(E) Bushings or Fittings Required. Bushings or
correction factors given in the O - 2000 volt ampacity
approved fittings shall be used where the leads emerge
tables of Article 3.10.
within the floor slabs.
4.24.9.7 Connection to Branch-Circuit Conductors.
4.24.9.10 Installation Under Floor Covering.
(A) General. Heating panels or heating panel sets
(A) Identification. Heating panels or heating panel sets
assembled together in the field to form a heating
for installation under floor covering shall be identified
installation in one room or area shall be connected in
as suitable for installation under floor covering.
accordance with the manufacturer's instructions .
(B) Installation. Listed heating panels or panel sets. i~-
(B) Heating Panels. Heating panels shall be connected
installed under floor covering, shall be installed on fl oor
to branch-circuit wiring by an approved wiring method.
surfaces that are smooth and flat in accordance with '_~
(C) Heating Panel Sets. manufacturer's instructions and shall also complY w::::
4.24.9.lO(B)(l) through (C)(5).
(1) Connection to Branch-Circuit Wiring. Heating
332
ARTICLE 4.24 - FIXED ELECTRIC SPACE-HEATING EQUIPMENT
(1) Expansion Joints. Heating panels or heating electric space-heating equipment shall be listed as a
panel sets shall not be installed where they bridge complete system.
expansion joints unless protected from expansion
4.24.10.4 Installation.
and contraction.
(A) General. Equipment shall be installed per the
(2) Connection to Conductors. Heating panels and
manufacturer's installation instructions.
heating panel sets shall be connected to branch-
circuit and supply wiring by wiring methods (B) Ground. Secondary circuits shall not be grounded.
recognized in Chapter 3. (C) Ground-Fault Protection. Ground-fault protection
(3) Anchoring. Heating panels and heating panel shall not be required.
sets shall be firmly anchored to the floor using an 4.24.10.5 Branch Circuit.
adhesive or anchoring system identified for this
use. (A) Equipment shall be permitted to be supplied from
branch circuits rated not over 30 amperes.
(4) Coverings. After heating panels or heating panel
sets are installed and inspected, they shall be (B) The equipment shall be considered a continuous
permitted to be covered by a floor covering that duty load.
has been identified by the manufacturer as being
suitable for the installation. ARTICLE 4.25 - FIXED RESISTANCE AND
ELECTRODE INDUSTRIAL PROCESS
(5) GFCI Protection. Branch circuits supplying the HEATING EQUIPMENT
heating panel or heating panel sets shall have
ground-fault circuit-interrupter protection for 4.25.1 General
personnel.
4.25.1.1 Scope. This article covers fixed industrial
(6) Grounding Braid or Sheath. Excluding nonheating process heating employing electric resistance or
leads, grounding means, such as copper braid, electrode heating technology. For the purpose of
metal sheath, or other approved means, shall be this article, heating equipment shall include boilers,
provided with or as an integral part of the heating electrode boilers, duct heaters, strip heaters, immersion
panel or heating panel set. heaters, process air heaters, or other approved fixed
4.24.10 Low-\ oltage Fixed Electric Space-Heating electric equipment used for industrial process heating.
Equipment This article shall not apply to heating and room air
conditioning for personnel spaces covered by Article
4.24.10.1 Scope. Low-voltage fixed electric space-
4.24, fixed heating equipment for pipelines and vessels
heating equipment shall consist of an isolating power
covered by Article 4.27, induction and dielectric heating
supply, low-voltage heaters, and associated equipment
equipment covered by Article 6.65, and industrial
that are all identified for use in dry locations.
furnaces incorporating silicon carbide, molybdenum, or
4.24.10.2 Energy Source. graphite process heating elements.
(A) Power Unit. The power unit shall be an isolating
4.25.1.2 Other Articles. Fixed industrial process
type with a rated output not exceeding 25 amperes, 30
heating equipment incorporating a hermetic refrigerant
volts (42.4 volts peak) ac, or 60 volts de under all load
motor-compressor shall also comply with Article 4.40.
conditions.
(B) Alternate Energy Sources. Listed low-voltage 4.25.1.3 Branch Circuits.
fixed electric space-heating equipment shall be
(A) Branch-Circuit Requirements. Individual branch
permitted to be supplied directly from an alternate
circuits shall be permitted to supply any volt-ampere
energy source such as solar photovoltaic (PV) or wind
or wattage rating of fixed industrial process heating
power. When supplied from such a source, the source
equipment for which they are rated.
and any power conversion equipment between the
source and the heating equipment and its supply shall (B) Branch-Circuit Sizing. Fixed industrial process
be listed and comply with the applicable section.of the heating equipment and motors shall be considered
PEC for the source used. The output of the source shall continuous loads.
meet the limits of 4.24.10.2(A).
4.25.1.6 Listed Equipment. Fixed industrial process
4.24.10.3 Listed Equipment. Low-voltage fixed
heating equipment shall be listed.
333
ARTICLE 4.25 - FIXED RESISTANCE AND ELECTRODE INDUSTRIAL PROCESS
4.25.2 Installation (B) Damp or Wet Locations. Fixed industrial process
heating equipment installed in damp or wet locations
4.25.2.1 General. shall be listed for such locations and shall be constructed
and installed so that water or other liquids cannot
(A) Location. Fixed industrial process heating
enter or accumulate in or on wired sections electrical
equipment shall be located with respect to building
components, or ductwork.
construction and other equipment so as to permit
access to the equipment. Sufficient clearance shall FPN: See 1.10.1.11 for equipment exposed to deteriorating
agents.
be maintained to permit replacement of controls and
heating elements and for adjusting and cleaning of 4.25.2.6 Spacing from Combustible Materials. Fixed
controls and other parts requiring such attention. industrial process heating equipment shall be installed
(B) Working Space. Working space about electrical to provide the required spacing between the equipment
enclosures for fixed industrial process heating equipment and adjacent combustible material, unless it is listed to
that require examination, adjustment, servicing, or be installed in direct contact with combustible material.
maintenance while energized shall be accessible, and 4.25.2.7 Infrared Lamp Industrial Heating
the work space for personnel shall comply with 1.10.2.1 Equipment. In industrial occupancies, infrared
and 1.10.3.5, based upon the utilization voltage to industrial process heating equipment lampholders shall
ground. be permitted to be operated in series on circuits of over
Exception: In industrial establishments only, where 150 volts to ground, provided the voltage rating of the
conditions of maintenance and supervision ensure that lampholders is not less than the circuit voltage.
only qual[fied persons will service the installation, Each section, panel, or strip carrying a number of
working space less than that required in 1.10.2.1 or infrared lampholders, including the terminal wiring
1.10.3. 5 shall be permitted. of such section, panel, or strip, shall be considered as
(A) Above Grade Level, Floor, or Work Platform. infrared industrial heating equipment. The terminal
Where the enclosure is located above grade, the floor, connection block of each assembly shall be considered
or a work platform, of the following shall apply: an individual outlet.

(1) The enclosure shall be accessible. 4.25.3 Control and Protection of Fixed Industrial
(2) The width of the working space shall be the Process Heating Equipment
width of the enclosure or a minimum of762 mm, 4.25.3.1 Disconnecting Means. Means shall be
whichever is greater. provided to simultaneously disconnect the heater,
(3) The depth of the workspace shall comply with motor controller(s), and supplementary overcurrent
1.10.2.l(A) or 1.10.3.5 based upon the voltage to protective device(s) of all fixed industrial process
ground. heating equipment from all ungrounded conductors.
Where heating equipment is supplied by more than
(4) All doors or hinged panels shall open to at least one source, feeder, or branch circuit, the disconnecting
90 degrees. means shall be grouped and identified as having multiple
disconnecting means. Each disconnecting means shall
4.25.2.2 Approval. All fixed industrial process heating simultaneously disconnect all ungrounded conductors
equipment shall be installed in an approved manner. that it controls. The disconnecting means specified in
4.25.3.l(A) and (B) shall have an ampere rating not
4.25.2.4 Supply Conductors. Fixed industrial process less than 125 percent of the total load of the motors and
heating equipment requiring supply conductors with the heaters and shall be lockable in accordance with
over 60°C insulation shall be clearly and permanently 1.10.1.25
marked. This marking shall be plainly visible after
installation and shall be permitted to be adjacent to the (A) Heating Equipment with Supplementary
field connection box. Overcurrent Protection. The disconnecting means
for fixed industrial process heating equipment with
4.25.2.5 Locations. supplementary overcurrent protection shall be within
sight from the supplementary over-current protective
(A) Exposed to Physical Damage. Where subject device(s), on the supply side of these devices, if fuses,
to physical damage, fixed industrial process heating and, in addition, shall comply with either 4.25.3.l(A)
equipment shall be protected in an approved manner. (1) or (A)(2) .

334
ARTICLE 4.25 - FIXED RESISTANCE AND ELECTRODE INDUSTRIAL PROCESS
(1) Heater Containing No Motor Rated over other disconnecting means.
'l8 Horsepower. The disconnecting means
4.25.3.3 Switch and Circuit Breaker to Be Indicating.
specified in 4.25.3.1 or unit switches complying
Switches and circuit breakers used as disconnecting
with 4.25.3.l(C) shall be permitted to serve as
means shall be of the indicating type.
the required disconnecting means for both the
motor controller(s) and heater under either of the 4.25.3.4
following conditions: (A) Branch-Circuit Devices. Fixed industrial process
( 1) The disconnecting means provided is also heating equipment other than such motor-operated
within sight from the motor controller(s) and equipment as required by Articles 4.30 and 4.40 to have
the heater. additional overcurrent protection shall be pe1mitted to
be protected against overcurrent where supplied by one
(2) The disconnecting means is lockable in
of the branch circuits in Article 2.10.
accordance with 1.10.1.25.
(B) Resistance Elements. Resistance-type heating
(2) Heater Containing a Motor(s) Rated over 'l8
elements in fixed industrial process heating equipment
Horsepower. The above disconnecting means
shall be protected at not more than 60 amperes.
shall be permitted to serve as the required
Equipment rated more than 48 amperes and employing
disconnecting means for both the motor
such elements shall have the heating elements
controller(s) and heater under either of the
subdivided, and each subdivided load shall not exceed
following conditions: 48 amperes. Where a subdivided load is less than 48 amperes,
( 1) The disconnecting means is in sight from the the rating of the supplementary overcurrent protective
motor controller(s) and the heater and complies device shall comply with 4.25. l.3(8). A boiler employing
with Part 4.30.9. resistance-type immersion heating elements contained in an
ASME-rated and stamped vessel shall be permitted to
(2) Motor(s) of more than ~ hp and the heater comply with 4.25.6.3(A).
are provided with a single unit switch that
complies with 4 .22.3.5(A), (B), (C), or (D), the (C) Overcurrent Protective Devices. The
disconnecting means shall be permitted to be supplementary over-current protective devices for the
out of sight from the motor controller. subdivided loads specified in 4.25.3.4(B) shall be (1)
factory installed within or on the heater enclosure or
(B) Heating Equipment Without Supplementary supplied for use with the heater as a separate assembly
Overcurrent Protection. by the heater manufacturer; (2) accessible, but shall not
(1) Without )lotor or with '1:otor Not over ~ be required to be readily accessible; and (3) suitable for
Horsepower. For fixed industrial process heating branch-circuit protection.
equipment without a motor rated over 1 hp, the FP:-J No. 1: See 2."T0.1.10. V.'here cartridge fuses are used to
branch-circui ""itch or circuit breaker shall be prO\ide this overcurrem protection, a single disconnecting means
shall be permitted to be u ed for the several subdivided loads.
p rmitted o en·e as rhe di onnecting mean
where the witch or ir uit breaker i within ight FP:"-i ~ o. 2: For supplementary overcurrent protection, see
from the heater or is lockable in accordance with _.40.1.IO.
1.1 0.1._-. FP~ Ko. 3: disconnecting means for cartridge fuses in circuits of
any rnltage, see 2.40.4.1.
(2) Over ~ Horsepower. For motor-driven fixed
industrial process heating equipment \ ith a (D) Branch-Circuit Conductors. The conductors
motor rated over 18 hp, a disconnecting means supplying the supplementary overcurrent protective
hall be located within sight from the motor devices shall be considered branch-circuit conductors.
controller or shall be permitted to comply with Where the heaters are rated 50 kW or more, the
the requirements in 4.25.3 .l(A)(2). conductors supplying the supplementary overcurrent
(C) Unit Switch(es) as Disconnecting Means. A protective devices specified in 4.25.3.4(C) shall be
unit switch(es) with a marked "off'' position that is permitted to be sized at not less than 100 percent of
part of a fixed heater and disconnects all ungrounded the nameplate rating of the heater, provided all of the
conductors shall be permitted as the disconnecting following conditions are met:
means required by this article. The branch circuit ( 1) The heater is marked with a minimum conductor
switch or circuit breaker, where readily accessible for size.
servicing of the fixed heater, shall be permitted as the

335
ARTICLE 4.25 - FIXED RESISTANCE AND ELECTRODE INDUSTRIAL PROCESS
(2) The conductors are not smaller than the marked equipment and shall be inspected before heating
rrummum size. equipment is covered or concealed.
(3) A temperature-actuated device controls the cyclic
4.25.5 Fixed Industrial Process Duct Heaters
operation of the equipment.
(E) Conductors for Subdivided Loads. Field-wired 4.25.5.1 General. Part V shall apply to any heater
conductors between the heater and the supplementary mounted in the airstream of a forced-air system where
overcurrent protective devices for fixed industrial the air-moving unit is not provided as an integral part of
process heating equipment shall be sized at not less the equipment.
than 125 percent of the load served. The supplementary
overcurrent protective devices specified in 4.25.3.4(C) 4.25.5.2 Identification. Heaters installed in an air duct
shall protect these conductors in accordance with shall be identified as suitable for the installation.
2.40.1.4. Where the heater are rated 50 kW or more the
ampacity of field-wired conductors between the heater 4.25.5.3 Airflow. Means shall be provided to ensure
and the supplementary overcurrent protective devices uniform airflow over the face of the heater in accordance
shall be permitted to be not less than 100 percent of the with the manufacturer's instructions.
load of their respective subdivided circuits provided all FPN: Some heaters installed within 1200 mm of the outlet of an
of the following conditions are met: air-moving device, elbows, baffle plates, or other obstructions in
ductwork use turning vanes, pressure plates, or other devices on
(1) The heater is marked with a minimum conductor the inlet side of the duct heater to ensure an even distribution of
.~ size. air over the face of the heater.
(2) The conductors are not smaller than the marked
mm1mum size. 4.25.5.4 Elevated Inlet Temperature. Duct heaters
intended for use with elevated inlet air temperature
(3) A temperature-activated device controls the shall be identified as suitable for use at the elevated
cyclic operation of the equipment. temperatures.
4.25.4 Marking of Heating Equipment
4.25.5.7 Fan Circuit Interlock. Means shall be
4.25.4.1 Nameplate. provided to ensure that the fan circuit, where present,
(A) Marking Required. Fixed industrial process is energized when any heater circuit is energized.
heating equipment shall be provided with a nameplate However, time- or temperature-controlled delay in
giving the identifying name and the normal rating in energizing the fan motor shall be permitted.
volts and watts or in volts and amperes.
4.25.5.8 Limit Controls. Each duct heater shall be
Fixed industrial process heating equipment intended
provided with an approved, integral, automatic-reset
for use on alternating current only, direct current only,
temperature limiting control or controllers to de-
or both shall be marked to so indicate. The marking of
energize the circuit or circuits. In addition, an integral
equipment consisting of motors over Y8 hp and other
independent supplementaiy control or controllers shall
loads shall specify the rating of the motor in volts,
be provided in each duct heater that disconnects a
amperes, and frequency and the heating load in volts
sufficient number of conductors to interrupt cunent flow.
and watts or in volts and amperes.
This device shall be manually resettable or replaceable.
(B) Location. This nameplate shall be located so as to
4.25.5.9 Location of Disconnecting Means. Duct
be visible or easily accessible after installation.
heater controller equipment shall be either accessible
with the disconnecting means installed at or within
4.25.4.2 Marking of Heating Elements. All heating
sight from the controller or as permitted by 4.25 .3. 1(A.).
elements that are replaceable in the field and are part
of industrial process heating equipment shall be legibly 4.25.6 Fixed lndustriaJ Process Resistance-Type
marked with the ratings in volts or watts or in volts or Boilers
amperes. 4.25.6.1 Scope. The provisions in Part 4.2 -.6 shall
apply to boilers employing resistance-type heating
4.25.4.18 Concealed Fixed lndustdal Heating elements. Electrode-type boilers shall not be considered
Equipment - Inspection and Tests. Concealed fixed as employing resistance-type heating elements. See
industrial heating equipment installations shall be Part 4.25.7.
made with due care to prevent damage to the heating
336
ARTICLE 4.25 - FIXED RESISTANCE AND ELECTRODE INDUSTRIAL PROCESS
4 ~5.6.2 Identification. Resistance-type boilers shall (2) The conductors are not smaller than the marked
identified as suitable for the installation. rrummum size.
4.25.6.3 Overcurrent Protection. (3) A temperature- or pressure-actuated device
controls the cyclic operation of the equipment.
(A) Boiler Employing Resistance-Type Immersion
Heating Elements in an ASME-Rated and Stamped (F) Conductors for Subdivided Loads. Field-wired
Vessel. A boiler employing resistance-type immersion conductors between the heater and the supplementary
heating elements contained in an ASME-rated and overcurrent protective devices shall be sized at not less
stamped vessel shall have the heating elements protected than 125 percent of the load served. The supplementary
at not more than 150 amperes. Such a boiler rated more overcurrent protective devices specified in 4.25.6.3(C)
than 120 amperes shall have the heating elements shall protect these conductors in accordance with
subdivided into loads not exceeding 120 amperes. 2.40.1.4. Where the heaters are rated 50 kW or more, the
Where a subdivided load is less than 120 amperes, the ampacity of field-wired conductors between the heater
rating of the overcmrent protective device shall comply and the supplementary overcurrent protective devices
with 4.25 .1.3(B). shall be permitted to be not less than 100 percent of the
load of their respective subdivided circuits, provided all
(B) Boiler Employing Resistance-Type Heating
of the following conditions are met:
Elements Rated More Than 48 Amperes and Not
Contained in an ASME-Rated and Stamped Vessel. (I) The heater is marked with a minimum conductor
A boiler employing resistance-type heating elements not size.
contained in an ASME-rated and stamped vessel shall
(2) The conductors are not smaller than the marked . ,
have the heating elements protected at not more than
mmimum size.
60 amperes . Such a boiler rated more than 48 amperes
shall have the heating elements subdivided into loads (3) A temperature-activated device controls the
not exceeding 48 amperes. Where a subdivided load cyclic operation of the equipment.
is less than 48 amperes, the rating of the overcurrent 4.25.6.4 Overtemperature Limit Control. Each boiler
protective device shall comply with 4.25.1.3(B). designed so that in normal operation there is no change
(C) Supplementary Overcurrent Protective Devices. in state of the heat transfer medium shall be equipped
The supplementary overcurrent protective devices for with a temperature-sensitive limiting means. It shall
the subdivided loads as required by 4.25.6.3(A) and (B) be installed to limit maximum liquid temperature and
shall be as follows: shall directly or indirectly disconnect all ungrounded
conductors to the heating elements. Such means shall
( 1) Factory-installed within or on the boiler enclosure
be in addition to a temperature-regulating system and
or provided as a separate assembly by the boiler
other devices protecting the tank against excessive
manufacturer.
pressure.
(2) Accessible, but need not be readily accessible.
4.25.6.5 Overpressure Limit Control. Each boiler
(D) Suitable for Branch-Circuit Protection. Where designed so that in normal operation there is a change
cartridge fuses are used to provide this overcurrent in state of the heat transfer medium from liquid to
protection, a single disconnecting means shall be vapor shall be equipped with a pressure-sensitive
permitted for the several subdivided circuits. See limiting means. It shall be installed to limit maximum
2.40.4.1. pressure and shall directly or indirectly disconnect all
ungrounded conductors to the heating elements. Such
(E) Conductors Supplying Supplementary
means shall be in addition to a pressure-regulating
Overcurrent Protective Devices. The conductors
system and other devices protecting the tank against
supplying these supplementary overcurrent protective
excessive pressure.
devices shall be considered branch-circuit conductors.
Where the heaters are rated 50 kW or more, the
4.25. 7 Fixed Industrial Process Electrode-Type
conductors supplying the overcurrent protective device
Boilers
specified in 4.24. 7.3(C) shall be permitted to be sized at
not less than 100 percent of the nameplate rating of the
4.25.7.1 Scope. The provisions in 4.25.7 shall apply
heater, provided all of the following conditions are met:
to boilers for operation at 600 volts, nominal, or less,
( I ) The heater is marked with a minimum conductor in which heat is generated by the passage of current
size. between electrodes through the liquid being heated.

337
ARTICLE 4.25 - FIXED RESISTANCE AND ELECTRODE INDUSTRIAL PROCESS
4.25.7.2 Identification. Electrode-type boilers shall be 4.25.7.7 Markings. All electrode-type boilers shall be
identified as suitable for the installation. marked to show the following:
4.25.7.3 Branch-Circuit Requirements. The size of ( 1) The manufacturer's name.
branch-circuit conductors and overcurrent protective
(2) The normal rating in volts, amperes, and kilowatts.
devices shall be calculated on the basis of 125 percent of
the total load (motors not included). A contactor, relay, (3) The electrical supply required specifying
or other device, approved for continuous operation at frequency, number of phases, and number of
100 percent of its rating, shall be permitted to supply its WlfeS.

full-rated load. See 2.10.2.2(A). (4) The marking "Electrode-Type Process Heating
Exception: The provisions ofthis section shall not apply Boiler."
to conductors that form an integral part ofan approved (5) A warning marking, "All Power Supplies Shall
boiler. Where an electrode boiler is rated 50 kW or more, Be Disconnected Before Servicing, Including
the conductors supplying the boiler electrode(s) shall Servicing the Pressure Vessel." A field-applied
be permitted to be sized at not less than I 00 percent of warning marking or label shall comply with
the nameplate rating of the electrode boiler, provided 1.10.1.2l(B).
all the following conditions are met:
The nameplate shall be located so as to be visible after
(I) The electrode boiler is marked with a minimum installation.
conductor size.
(2) The conductors are not smaller than the marked ARTICLE 4.27 - Fixed Electric Heating
minimum size. Equipment for Pipelines and Vessels
(3) A temperature- or pressure-actuated device
4.27.1 General
controls the cyclic operation of the equipment.
4.25.7.4 Overtemperature Limit Control. Each boiler, 4.27.1.1 Scope. The requirements of this article shall
designed so that in nonnal operation there is no change apply to electrically energized heating systems and
in state of the heat transfer medium, shall be equipped the installation of these systems used with pipelines or
with a temperature-sensitive limiting means. It shall vessels or both.
be installed to limit maximum liquid temperature and FPN: For further information, see Al'\SLTEEE 515-2002,
shall directly or indirectly interrupt all current flow Standardfor the Testing, Design, Installation and J1aimenance of
through the electrodes. Such means shall be in addition Electrical Resistance Trace Heating for Industrial Applications;
to the temperature regulating system and other devices A SI/IEEE 844-2011, Recommended Practice f or Electrical
Impedance, Induction, and Skin Effect Heating of Pipelines and
protecting the tank against excessive pressure. Vessels; and ANSI ECA 202-20 13, Standard fo r Insmlling and
4.25.7.5 Overpressure Limit Control. Each boiler, .Maintaining Industrial Heat Tracing Systems.
designed so that in normal operation there is a change in 4.27.1.2 Definitions.
state of the heat transfer medium from liquid to vapor,
shall be equipped with a pressure-sensitive limiting Impedance Heating System. A system in whi h heat is
means. It shall be installed to limit maximum pressure generated in a pipeline or \·essel wall by causing current
and shall directly or indirectly interrupt all current flow to flow through the pipeline or Yessel wall by direct
through the electrodes. Such means shall be in addition connection to an ac \·oltage . ource from a dual-winding
to a pressure-regulating system and other devices transformer.
protecting the tank against excessive pressure. Induction Heating System. A system in which heat
is generated in a pipeline or ·essel wall by inducing
4.25.7.6 Grounding. For those boilers designed such current and hysteresis effect in the pipeline or vessel
that fault currents do not pass through the pressure wall from an external isolated ac field source.
vessel, and the pressure vessel is electrically isolated
Pipeline. A length of pipe including pumps, valves,
from the electrodes, all exposed non- current-carrying
flanges, control devices, strainers, and/or similar
metal parts, including the pressure vessel, supply,
equipment for conveying fluids.
and return connecting piping, shall be grounded. For
all other designs, the pressure vessel containing the Resistance Heating Element. A specific separate
electrodes shall be isolated and electrically insulated element to generate heat that is applied to the pipeline
from ground. or vessel externally or internally.

338
ARTICLE 4.27 - FIXED ELECTRIC HEATING EQUIPMENT FOR PIPELINES AND VESSELS
FP : Tubular heaters, strip heaters, heating cable, heating design of the heater assembly is such that its temperature
tape, heating blankets, and immersion heaters are examples of limitations will not be exceeded.
resistance heaters.
4.27.3.3 Expansion and Contraction. Heating
Skin-Effect Heating System. A system in which heat
elements and assemblies shall not be installed where
is generated on the inner surface of a ferromagnetic
they bridge expansion joints unless provisions are made
envelope attached to a pipeline or vessel, or both.
for expansion and contraction.
FPN: Typically, an electrically insulated conductor is routed
through and connected to the envelope at the other end. The 4.27.3.4 Flexural Capability. Where installed on
envelope and the electrically insulated conductor are connected :flexible pipelines, the heating elements and assemblies
to an ac voltage source from a dual-winding transformer. shall have a :flexural capability that is compatible with
Vessel. A container such as a barrel, drum, or tank for the pipeline.
holding fluids or other material. 4.27 .3.5 Power Supply Leads.
4.27.1.3 Application of Other Articles. Cord- (A) Nonheating Leads. Power supply nonheating leads
connected pipe heating assemblies intended for specific (cold leads) for resistance elements shall be suitable
use and identified as suitable for this use shall be for the temperature encountered. Not less than 150
installed according to Article 4.22. mm of nonheating leads shall be provided within the
4.27.1.4 Continuous Load. Fixed electric heating junction box. Preassembled factory-supplied and field-
equipment for pipelines and vessels shall be considered assembled non-heating leads on approved heaters shall
continuous load. be permitted to be shortened if the markings specified in
4.27 .3 .7 are retained.
4.27 .2 Installation
(B) Power Supply Leads Protection. Nonheating
4.27.2.1 General. Equipment for pipeline and vessel power supply leads shall be protected where they
electric heating shall be identified as being suitable for emerge from electrically heated pipeline or vessel
(1) the chemical, thermal, and physical environment and heating units by rigid metal conduit, intermediate metal
(2) installation in accordance ,,-ith the manufacturer 's conduit, electrical metallic tubing, or other raceways
drawings and instructions. identified as suitable for the application.

4.27.2.2 LSe. Electric heating equi men~ shall be (C) Interconnecting Leads. Interconnecting
installed · . uch a manner as o be affo ded protection nonheating leads connecting portions of the heating
from phy-i l damage. system shall be permitted to be covered by thermal
insulation in the same manner as the heaters.
4.27.2.3 T herm al Protection. External surfaces of
pipe e d Yessel hearing equipment that operates 4.27.3.6 Electrical Connections.
at empera e- ex eeding 60°C shall be physically (A) Nonheating Interconnections. Nonheating
guarde isolated. or thermally insulated to protect interconnections, where required under thermal
against oma y ersonnel in the area. insulation, shall be made with insulated connectors
identified as suitable for this use.
4.2 .2.4 Identifica tion. The presence of electrically
heated pipeline . ,;essels, or both, shall be evident by (B) Circuit Connections. Splices and terminations
the posting of appropriate caution signs or markings at outside the thermal insulation shall be installed in a box
interi.-als not exceeding 6000 mm along the pipeline or or fitting in accordance with 1.10 .1.14 and 3. 0 .1.15.
vessel and on or adjacent to equipment in the piping 4.27.3.7 Marking. Each factory-assembled heating unit
system that requires periodic servicing. shall be legibly marked within 75 mm of each end of
the nonheating leads with the permanent identification
4.27.3 Resistance Heating Elements symbol, catalog number, and ratings in volts and watts
4.27.3.1 Secured. Heating element assemblies shall be or in volts and amperes.
secured to the surface being heated by means other than 4.27.3.9 Ground-Fault Protection of Equipment.
the thermal insulation. Ground-fault protection of equipment shall be provided
4.27.3.2 Not in Direct Contact. Where the heating for electric heat tracing and heating panels. This
element is not in direct contact with the pipeline or requirement shall not apply in industrial establishments
vessel being heated, means shall be provided to prevent where there is alarm indication of ground faults and the
overtemperature of the heating element unless the following conditions apply:

339
ARTICLE 4.27 - FIXED ELECTRIC HEATING EQUIPMENT FOR PIPELINES AND VESSELS
( 1) Conditions of maintenance and supervision voltage not greater than 132 volts ac to ground wher '
ensure that only qualified persons service the all of the following conditions app~v:
installed systems.
(]) Conditions of guarding, maintenance, w za
(2) Continued circuit operation is necessary for safe supervision ensure that only qualified person~
operation of equipment or processes. service the installed systems.
(2) Ground-fault protection of equipmeni
4.27.3.10 Grounded Conductive Covering. Electric
provided.
heating equipment shall be listed and have a grounded
conductive covering in accordance with 4 .2 7.3.10(A) or (3) The pipeline or vessel being heated is complete~•:
(B). The conductive covering shall provide an effective enclosed in a grounded metal enclosure.
ground path for equipment protection. (4) The transformer secondary connections to the
(A) Heating Wires or Cables. Heating wires or pipeline or vessel being heated are complete(i.·
cables shall have a grounded conductive covering that enclosed in a grounded metal mesh or metal
surrounds the heating element and bus wires, if any, and enclosure.
their electrical insulation.
4.27.4.4 Induced Currents. All current-carrying
(B) Heating Panels. Heating panels shall have a
components shall be installed in accordance with
grounded conductive covering over the heating element
3.0.1.20.
and its electrical insulation on the side opposite the side
attached to the surface to be heated.
4.27.4.5 Grounding. The pipeline, vessel, or both, that
is being heated and operating at a voltage greater than
4.27.4 Impedance Heating
30 but not more than 80 shall be grounded at designated
points.
4.27.4.1 Personnel Protection. All accessible external
surfaces of the pipeline, vessel, or both, being heated
4.27.4.6 Secondary Conductor Sizing. The ampacity
shall be physically guarded, isolated, or thermally
of the conductors connected to the secondary of the
insulated (with a weatherproof jacket for outside
transformer shall be at least 100 percent of the total load
installations) to protect against contact by personnel in
of the heater.
the area.
4.27.5 Induction Heating
4.27.4.2 Isolation Transformer. A dual-winding
transformer with a grounded shield between the primary 4.27.5.1 Scope. This part covers the installation of line
and secondary windings shall be used to isolate the frequency induction heating equipment and accessories
distribution system from the heating system. for pipelines and vessels.
FPK: See Article 6.65 for other applications.
4.27.4.3 Voltage Limitations. The secondary winding
of the isolation transformer connected to the pipeline 4.27.5.2 Personnel Protection. Induction coils that
or vessel being heated shall not have an output voltage operate or may operate at a voltage greater than 30 volts
greater than 30 volts ac. ac shall be enclosed in a nonmetallic or split metallic
enclosure, isolated, or made inaccessible by location to
Exception No. 1: In industrial establishments, the protect personnel in the area.
isolation transformer connected to the pipeline or
vessel being heated shall be p ermitted to have an output 4.27.5.3 Induced Current. Induction coils shall
voltage greater than 30 but not more than 80 volts ac be prevented from inducing circulating currents in
to ground where all of the following conditions apply: surrounding metallic equipment, supports, or structures
by shielding, isolation, or insulation of the current paths.
(1) Conditions of guarding, maintenance, and Stray current paths shall be bonded to prevent arcing.
supervision ensure that only qualified persons
have access to the installed systems. 4.27.6 Skin-Effect Heating

(2) Ground-fault protection ofequipment is provided. 4.27.6.1 Conductor Ampacity. The ampacity of the
electrically insulated conductor inside the fenomagnetic
Exception No. 2: In industrial establishments, the envelope shall be permitted to exceed the values given
isolation transformer connected to the pipeline or in Article 3.10, provided it is identified as suitable for
vessel being heated shall be permitted to have an output this use.

340
ARTICLE 4.27- FIXED ELECTRIC HEATING EQUIPMENT FOR PIPELINES AND VESSELS
4.27.6.2 Pull Boxes. Pull boxes for pulling the ungrounded conductors and shall not be pennitted to
electrically insulated conductor in the ferromagnetic serve as the disconnecting means.
envelope shall be permitted to be buried under the
(C) Remote Temperature Controller. Remote
thermal insulation, provided their locations are indicated
controlled temperature-actuated devices sh al I not be
by permanent markings on the insulation jacket surface
required to meet the requirements of 4.27 .7.2(A) and
and on drawings. For outdoor installations, pull boxes
(B). These devices shall not be permitted to serve as the
shall be of watertight construction.
disconnecting means.
4.27.6.3 Single Conductor in Enclosure. The
(D) Combined Switching Devices. Switching devices
provisions of3.0. l.20 shall not apply to the installation
consisting of combined temperature-actuated devices
of a single conductor in a ferromagnetic envelope
and manually controlled switches that serve both as the
(metal enclosure).
controllers and the disconnecting means shall comply
with all the following conditions:
4.27.6.4 Grounding. The ferromagnetic envelope shall
be grounded at both ends, and, in addition, it shall be (1) Open all ungrounded conductors when manually
permitted to be grounded at intermediate points as placed in the "off'' position
required by its design. The ferromagnetic envelope shall (2) Be designed so that the circuit cannot be energized
be bonded at all joints to ensure electrical continuity. automatically if the device has been manually
The provisions of 2.50.2.11 shall not apply to the placed in the "off'' position
installation of skin-effect heating systems. (3) Be capable of being locked in the open position
FPN: See Article 2.50 for grounding methods.
4.27.7.3 Overcurrent Protection. Heating equipment
shall be considered as protected against overcmTent
4.27.7 Control and Protection
where supplied by a branch circuit as specified in
2.10.2.1 and 2.10.2.6.
4.27.7.1 Disconnecting Means.
(A) Switch or Circuit Breaker. Means shall be ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS,
provided to simultaneously disconnect all fixed AND CONTROLLERS
electric pipeline or vessel heating equipment from all
4.30.1 General
ungrounded conductors. The branch-circuit switch or
circuit breaker, where readily accessible to the user 4.30.1.1 Scope. This article covers motors, motor
of the equipment, shall be permitted to serve as the branch-circuit and feeder conductors and their
disconnecting means. The disconnecting means shall protection, motor overload protection, motor control
be of the indicating type and shall be capable of being circuits motor controllers, and motor control centers.
locked in the open (off) position. The disconnecting FP'( . o. 1: Installation requirements for motor control centers
means shall be installed in accordance with 1.10. l .~5. are co\·ered in 1.10.2.i(E). Air-conditioning and refrigerating
eq ipmenr are co,·ered in Anicle ~.40.
(B) Cord-and-Plug-Connected Equipment. The
FPi'\ "\o. ~: Figure -UO. l. l is for information only.
factory-installed attachment plug of cord-and-plug-
connected equipment rated 20 amperes or le and 4.30.1.2 Definitions.
150 volts or less to ground shall be permitted to be the Controller. For the purpose of this article, a controller
disconnecting means. is any switch or device that is normally used to start and
4.27.7.2 Controls. stop a motor by making and breaking the motor circuit
current.
(A) Temperature Control with "Off'' Position.
Part-Winding Motors. A part-winding start induction
Temperature-controlled switching devices that indicate
or synchronous motor is one that is arranged for starting
an "off'' position and that interrupt line current shall by first energizing part of its primary (armature)
open all ungrounded conductors when the control winding and, subsequently, energizing the remainder
device is in this "off'' position. These devices shall not of this winding in one or more steps. A standard part-
be permitted to serve as the disconnecting means unless winding start induction motor is an-anged so that one-
capable of being locked in the open position. half of its primary winding can be energized initially,
and, subsequently, the remaining half can be energized,
(B) Temperature Control Without "Off'' Position. both halves then can7ing equal current. A hermetic
Temperature controlled switching devices that do not refrigerant compressor motor shall not be considered a
have an "off'' position shall not be required to open all standard part-winding start induction motor.
341
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
General. 4.30. l.l through 4.30.1.18 Part4.30.l (armature) winding and, subsequently, energl.Zlng
Motor Circuit Conductors, 4.30.2. l through 4.30.2.9 Part 4.30.2 the remainder of this winding in one or more steps. _-\.
Motor and Branch-Circuit Overload Protection, Part4.30.3
standard part-winding start induction motor is arrange ·
4.30.3.l through 4.30.3. 14 so that one-half of its primary winding can be energized
Motor Branch-Circuit Short-Circuit and Ground-Fault Part 4.30.4 initially, and, subsequently, the remaining half can be
Protection, 4.30.4.l through 4.30.4.8
energized, both halves then carrying equal current. A
Motor Feeder Short-Circuit and Ground-Fault Part 4.30.5
Protection, 4.30.5.l through 4.30.5.3 hermetic refrigerant compressor motor shall not be
Motor Control Circuits, 4.30.6. l through 4.30.6.5 Part4.30.6 considered a standard pai1-winding start induction
Motor Controllers, 4.30.7.l through 4.30.7. 10 Part4.30.7 motor.
Motor Control Centers, 4.30.8.l through 4.30.8.7 Part4.30.8 Where separate overload devices are used with a
Disconnecting Means, 4.30.9.l through 4.30.9.13 Part4.30.9 standard part-winding start induction motor, each half
of the motor winding shall be individually protected
Adj ustable-Speed Dri\'e S)'Stems, 4.30.10. l through Part 4.30.10
4.30.10.12 in accordance with 4.30.3.2 and 4.30.3.7 with a trip
Over 1000 Volts, Nominal, 4.30.11.l through 4.30.11.7 Part 4.30.11
current one-half that specified.
Protection of Live Parts-All Voltages, 4.30.12.l Part 4.30.12 Each motor-winding connection shall have branch-
through 4.30.12.3
circuit short-circuit and ground-fault protection rated at
Grounding-All Voltages, 4.30.13.l through 4.30.13.5 Part430.13 not more than one-half that specified by 4.30.4.2.
Tables, Tables 4.30.14.l through 4.30.14.5(B) Part 4.30.14
Exception: A short-circuit and ground-fault protective
To Supply
Part 4.30.2 device shall be permitted.for both windings ifthe device
4.30.2.4.
Motor feeder 4.30.2 .5, 4 .30.2.6 will allow the motor to start. Where time-delay (dual-
Motor feeder element) fuses are used, they shall be permitted to have a
short-circuit and rating not exceeding 150 percent of the motor full-load
ground-fault protection Part 4.30.5 current.
Motor disconnecting means Part4.30.9
Motor branch-circuit
4.30.1.5 Other Articles. Motors and controllers shall
short-circuit and also comply with the applicable provisions of Table
ground-fault protection Part 4.30.4 4 .3 0.1.5 .
Motor circuit conductor Part4.30.2
Motor controlier Part 4.30.7 4.30.1.6 Ampacity and Motor Rating Determination.
Motor control circuits Part 4.30.6 The size of conductors supplying equipment covered
Motor overload protection Part 4.30.3 by Article 4.30 shall be selected from the allowable
Motor Part 4.30 1 ampacity tables in accordance with 3 .10.2.6(B) or shall
Thermal protection Part4.30.3 be calculated in accordance with 3.10.2.6(C). Where
Secondary controller Part 4.30.2 :flexible cord is used, the size of the conductor shall
Secondary conductors 4.30.2.3
be selected in accordance with 4.0.1.5. The required
Secondary resistor Part 4.30.2 ampacity and motor ratings shall be determined as
4.30.2.3 a nd Article 4.70
specified in 4.30. l .6(A), (B), (C), and (D).
Figure 4.30.1.1 Article 4.30 Contents.
(A) General Motor Applications. For general motor
System Isolation Equipment. A redundantly
monitored, remotely operated contactor-isolating applications, current ratings shall be determined based
system, packaged to provide the disconnection/isolation on (A)(l) and (A)(2).
function, capable of verifiable operation from multiple (1) Table Values. Other than for motors built for low
remote locations by means of lockout switches, each
speeds (less than 1200 RPM) or high torques, and
having the capability of being padlocked in the "off"
for multispeed motors, the values given in Table
(open) position.
4.30.14.1 Table 4.30.14.2, Table 4.30.14.3 , and
Valve Actuator Motor (VAM) Assemblies. A Table 4.30.14.4 shall be used to determine the
manufactured assembly, used to operate a valve, ampacity of conductors or ampere ratings of
consisting of an actuator motor and other components
switches, branch-circuit short-circuit and ground-
such as controllers, torque switches, limit switches, and
fault protection, instead of the actual current
overload protection.
rating marked on the motor nameplate. Where a
FPN: VAMs typically have short-time duty and high-torque motor is marked in amperes, but not horsepov,-er.
characteristics.
the horsepower rating shall be assumed to be
4.30.1.4 Part-Winding Motors. A part-winding start that corresponding to the value gi\ en in Tab e
induction or synchronous motor is one that is arranged 4.30.14.1, Table 4.30.14.2 , Table 4.30.1-+.3 . a:1 •
for starting by first energizing part of its primary
342
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CO TROLLERS
Table 4.30.1.5 Other Articles less than the current marked on the fan or blower motor
nameplate.
Equipment/Occupancy Article Section
Exception No. 3: For a listed motor-operated appliance
Air-conditioning and refrigerating
4.40 that is marked with both motor horsepower and fiill-
equipment
4.60.1.8,
load current, the motor full-load current marked on
Capacitors the nameplate of the appliance shall be used instead of
4.60.1.9
Commercial garages; aircraft the horsepmver rating on the appliance nameplate to
hangars; motor fuel dispensing 5.11, 5.13, determine the ampacity or rating of the disconnecting
facilities; bulk storage plants; 5.14, 5.15, means, the branch-circuit conductors, the controlle,;
spray applications, dipping, and 5.16, and
the branch-circuit short-circuit and ground:fault
coating processes; and inhalation 5.17.4
anesthetizing locations protection, and any separate overload protection.

Cranes amd hoist 6.10 (2) Nameplate Values. Separate motor overload
protection shall be based on the motor nameplate
Electrically driven or controlled
irrigation machines
6.75 current rating.
Elevators. dumbwaiters, escalators, (B) Torque Motors. For torque motors, the rated cun-ent
moving walks, wheelchair lifts, and 6.20 shall be locked-rotor current, and this nameplate current
stairway chair lifts
shall be used to determine the ampacity of the branch-
Fire pumps 6.95 circuit conductors covered in 4.30.2.2 and 4.30.2.4, the
5.0 - 5.3, ampere rating of the motor overload protection, and the
Hazardous (classified) locations
5.5, and 5.6 ampere rating of motor branch-circuit short-circuit and
ground-fault protection in accordance with 4.30.4.2(B).
Industrial machinery 6.70
FPN : For motor controllers and disconnecting means, see
5.40.2.2 4.30.7.3 (D) and 4.30.9 .10.
Motion picture projectors and
: .40.2.l (C) Alternating-Current Adjustable Yoltage Motors.
:\1otion icrure and re eYi ion
5.30
For motor~ used in alternating-current, adjustable
studios and simil rions ,·ol age. variabl o 1e ,. y terns. the ampacity
Resistors an reac: IS 4.-o of o ors. or am ere rat'n.::, - o S\\·itches, branch-
.. ir uit hon - ir i a d =- o nd-fault protection, and so
Theaters. ~ area.so:
i rure ar. "' ~r:e, :S: Ll -i;,: ; - a::tl : .20.:' .9 fonh. hall ased on aximum operating current
similar !oca:io:::.s marked on the mo-or or ontrol nameplate, or both. If
T:cISior:::re:s a:;;:: =sfo=er the maximum operating urrent doe not appear on the
\ ·a - ~ ..:o nameplate, the ampacity determination shall be based
on 1 -o percent of the \·alues giYen in Table 4.30.14.3
Ta .. " O. 4.4, imerpolated if necessary. Motors
and Table 4.3 0.14.4.
· - fo low peeds (less than 1200 RPM) or high
o es may haYe higher full-load currents, and (D) Valve Actuator :\Iotor Assemblies. For valve
tispeed motors will ha e full-load current actuator motor assemblies (YA.Ms), the rated current
Ya!)ing ,,;ith speed, in which case the nameplate shall be the nameplate full-load current, and this
current ratings shall be used. current shall be used to determine the maximum rating
or setting of the motor branch-circuit short-circuit and
Exception So. 1: Multispeed motors shall be in
ground-fault protecti\·e deYice and the ampacity of the
accordance with 4.30.2.2(B) and 4.30.4.2.
conductors.
Exception _ o. 2: For equipment that employs a shaded-pole
4.30.1.7 Marking on Motors and Multimotor
or permanent-split capacitor-type fan or blower motor that is
marked with the motor type, the full load current for such Equipment.
motor marked on the nameplate of the equipment in which (A) Usual Motor Applications. A motor shall be
the fan or blower motor is employed shall be used instead of marked with the following information:
the horsepower rating to determine the ampacity or rating
of the disconnecting means, the branch-circuit conductors, (1) Manufacturer's name.
the controller, the branch-circuit short-circuit and ground-
(2) Rated volts and full-load current. For a multispeed
fault protection, and the separate overload protection.
motor, full-load current for each speed, except
This marking on the equipment nameplate shall not be
shaded-pole and permanent-split capacitor

343
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
motors where amperes are required only for condensation prevention heaters shall
maximum speed. marked with the rated heater voltage, num -
of phases and the rated power in watts.
(3) Rated frequency and number of phases if an ac
motor. (B) Locked-Rotor Indicating Code Letters. C oci;:
letters marked on motor nameplates to show mot :
(4) Rated full-load speed.
input with locked rotor shall be in accordance \'·;iti.
(5) Rated temperature rise or the insulation system Table 4.30.1. 7(B).
class and rated ambient temperature.
The code letter indicating motor input with locke
(6) Time rating. The time rating shall be 5, 15, 30, or rotor shall be in an individual block on the nameplate.
60 minutes, or continuous. properly designated.
(7) Rated horsepower if ~ hp or more. For (1) Multispeed Motors. Multispeed motors shall
a multispeed motor ~ hp or more, rated be marked with the code letter designating
horsepower for each speed, except shaded-pole the locked-rotor kilovolt-ampere (kVA) per
and permanent-split capacitor motors ~ hp or horsepower (hp) for the highest speed at which
more where rated horsepower is required only the motor can be started.
for maximum speed. Motors of arc welders are
Exception: Constant horsepower multispeed motors
not required to be marked with the horsepower
shall be marked with the code letter giving the highest
rating.
locked-rotor kilovolt-ampere (kVA) per horsepower
(8) Code letter or locked-rotor amperes if an (hp).
alternating-cunent motor rated \12 hp or more. On
(2) Single-Speed Motors. Single-speed motors
polyphase wound-rotor motors, the code letter
starting on wye connection and running on delta
shall be omitted.
connections shall be marked with a code letter
FPN: See4.30.l.7(B). corresponding to the locked-rotor kilovolt-
(9) Design letter for design B, C, or D motors. ampere (kVA) per horsepower (hp) for the wye
connection.
FPN: Motor design letter definitions are found in ANSI/NEMA
MG 1-1 993, Motors and Generators, Part 1, Definitions, and in (3) Dual-Voltage Motors. Dual-voltage motors that
IEEE l 00-1996, Standard Dictionary ofElectrical and Electronic
have a different locked-rptor kilovolt-ampere
Terms.
(kVA) per horsepower (hp) on the two voltages
(10) Secondary volts and full-load current if a shall be marked with the code letter for the
wound-rotor induction motor. voltage giving the highest locked-rotor kilovolt-
( 11) Field current and voltage for de excited ampere (kVA) per horsepower (hp).
synchronous motors. (4) 50/60 Hz Motors. Motors with 50- and 60-
(12) Winding - straight shunt, stabilized shunt, Hz ratings shall be marked with a code letter
compound, or series, if a de motor. Fractional designating the locked-rotor kilovolt-ampere
horsepower de motors 17 5 mm or less in (kVA) per horsepower (hp) on 60 Hz.
diameter shall not be required to be marked. (5) Part-Winding Motors. Part-winding start motors
(13) A motor provided with a thermal protector shall be marked with a code letter designating
complying with 4.30.3.2(A)(2) or (B)(2) shall the locked-rotor kilovolt-ampere (kVA) per
be marked "Thermally Protected." Thermally horsepower (hp) that is based on the locked-rotor
protected motors rated 100 watts or less current for the full winding of the motor.
and complying with 4.30.3.2(B)(2) shall be (C) Torque Motors. Torque motors are rated for
permitted to use the abbreviated marking "T.P." operation at standstill and shall be marked in accordance
(14) A motor complying with 4.30.3.2(B)(4) shall with 4.30.l.7(A), except that locked-rotor torque shall
be marked "Impedance Protected." Impedance- replace horsepower.
protected motors rated 100 watts or less (D) Multimotor and Combination-Load Equipment.
and complying with 4.30.3.2(B)(4) shall be
(1) Factory-Wired. Multimotor and combination-
permitted to use the abbreviated marking "Z.P."
load equipment shall be provided with a visib e
( l -) Motors equipped with electrically powered nameplate marked with the manufacturer ' na e.
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
the rating in volts, frequency, number of phases, of the controller shall not be required if the necessary
minimum supply circuit conductor ampacity, data are on the nameplate. For controllers that are an
and the maximum ampere rating of the circuit integral part of equipment approved as a unit, the above
short-circuit and ground-fault protective device. marking shall be permitted on the equipment nameplate.
The conductor ampacity shall be calculated in FPN: See 1.10.1.10 for infotmation on circuit impedance and
accordance with 4.30.2.4 and counting all of other characteristics.
the motors and other loads that will be operated
4.30.1.9 Terminals.
at the same time. The short-circuit and ground-
fault protective device rating shall not exceed (A) Markings. Terminals of motors and controllers
the value calculated in accordance with 4.30.4.3. shall be suitably marked or colored where necessary to
Multimotor equipment for use on two or more indicate the proper connections.
circuits shall be marked with the preceding
(B) Conductors. Motor controllers and terminals of
information for each circuit.
control circuit devices shall be connected with copper
(2) Not Factory-Wired. Where the equipment is not conductors unless identified for use with a different
factory-wired and the individual nameplates of conductor.
motors and other loads are visible after assembly
(C) Torque Requirements. Control circuit devices
of the equipment, the individual nameplates shall
with screw-type pressure terminals used with 2.0 mm2
be permitted to serve as the required marking.
or smaller copper conductors shall be torqued to a
4.30.1.8 Marking on Controllers. A controller shall be minimum of 0.8 N·m unless identified for a different
marked with the manufacturer's name or identification, torque value.
the voltage, the current or horsepower rating, the
4.30.1.10 Wiring Space in Enclosures.
short-circuit current rating, and other necessary data
to properly indicate the applications for which it is (A) General. Enclosures for motor controllers and
suitable. disconnecting means shall not be used as junction
boxes, auxiliary gutters, or raceways for conductors
Exception No. I : The short-circuit current rating is not
feeding through or tapping off to the other apparatus
required for controllers applied in accordance with
unless designs are employed that provide adequate
4.30.7.J(A) or (BJ.
space for this purpose.
Exception No. 2: The short-circuit rating is not required FPN: See 3.12.1.8 for switch and overcurrentdevice enclosures.
to be marked on the controller when the short-circuit
current rating of the controller is marked elsewhere on Table 4.30.1.7(B) Locked-Rotor Indicating Code
the assembly. Letters
Exception ,\o. 3: The short-circuit rating is not required Code Kilovolt-Amperes per Horsepower with
to be marked on the controller when the assembly into Letter locked Rotor
w·hich it is installed has a marked short-circuit current A 0 -3.14
rating. B 3.1 5 - 3.54
C 3.55 - 3.99
Exception No. 4: Short-circuit ratings are not required
D 4.0 - 4.49
for controllers rated less than 2 hp at 300 V or less and
E 4.5 - 4.99
listed exclusively for general-purpose branch circuits.
F 5.0 - 5.59
A controller that includes motor overload protection G 5.6 - 6.29
suitable for group motor application shall be marked H 6.3 · 7.09
with the motor overload protection and the maximum J 7.1 - 7.99
branch-circuit short-circuit and ground-fault protection K 8.0 - 8.99
for such applications. L 9.0 - 9.99
M 10.0 - 11.19
Combination controllers that employ adjustable 11.2 - 12.49
instantaneous trip circuit breakers shall be clearly p 12.5 - 13.99
marked to indicate the ampere settings of the adjustable R 14.0 - 15.99
trip element. s 16.0 -1 7.99
Where a controller is built in as an integral part of a T 18.0 - 19.99
motor or of a motor-generator set, individual marking u 20.0 - 22.39
V 22.4 · and up

345
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CO TROLLERS
(B) Wire-Bending Space in Enclosures. Minimum either inside or outside the motor terminal housing.
wire-bending space within the enclosures for
Exception: Where a motor is installed as a part of
motor controllers shall be in accordance with Table
facto, y wired equipment that is required to be grounded
4.30.1.1 O(B) where measured in a straight line from the
and without additional connection being required at the
end of the lug or wire connector (in the direction the
motor terminal housing during equipment installation,
wire leaves the terminal) to the wall or barrier. Where
a separate means for motor grounding at the motor
alternate wire termination means are substituted for that
terminal housing shall not be required.
supplied by the manufacturer of the controller, they
shall be of a type identified by the manufacturer for use 4.30.1.13 Bushing. Where ,,-ires pass through an
with the controller and shall not reduce the minimum opening in an enclosure, conduit box, or barrier, a
wire-bending space. bushing shall be used to protect the conductor from the
edges of openings having harp edge . The bushing shall
4.30.1.11 Protection Against Liquids. Suitable guards
have smooth, well-rounded surf. ce where it mav be in
or enclosures shall be provided to protect exposed
contact with the conductor-. If - \\. ere oil . grea es,
current-carrying parts of motors and the insulation of
or other contaminants may ' e e·en-. ·he bu hing shall
motor leads where installed directly under equipment,
be made of material not de e e. ·o .. · aff... ted.
or in other locations where dripping or spraying oil,
water, or other liquid is capable of occmTing, unless the FPN: For conductors ex_ sed · ce:e:-:c:-z:::i= a"'ems. ee
motor is designed for the existing conditions. 3.10.1.IO(G).

4.30.1.12 Motor Terminal Housings. 4.30.1.14 Location of :.'\Io tors.


(A) Material. Where motors are provided with (A) Ventilation and ~Iaintenance.
tenninal housings, the housings shall be of metal and of located so that ad qua e · _::·ar:cn =
, :'-
substantial construction. that maintenance.
Exception: In other than hazardous (classified)
locations, substantial, nonmetallic, noncombustible Exception: Ventila1 ·or. sr.:;_·_- >:G::- -;.= r · _:1~red fo r
housings shall be permitted, provided an internal
submersible types of11 o:or.
grounding means between the motor frame and the
equipment grounding connection is incorporated within (B) Open !\-lotor . Ope:: = c:~.:: :.::.:::: ._.,._.~ .: Dnu·ators
the housing. or collector ring -ha . · e : .:::.:e-: :::-: ; : , :ec:e so that
(B) Dimensions and Space - Wire-to-Wire sparks cannot rea a :a ~:.: ==-~-:::::e =a:e 'al.
Connections. Where these terminal housings enclose
wire-to-wire connections, they shall have minimum Table 4.30.1.IO(B) . lininmm \\ire-Bending Space
dimensions and usable volumes m accordance with
at the Terminals of Ea fo_ed ,1oror Controllers
Table 4.30.l.12(B).
(C) Dimensions and Space - Fixed Tenninal \\ rre per Terminal"'
Connections. Where these terminal housings enclose Size of Wire [mmz (mm)1 l (mm ) I - lmm)
rigidly mounted motor terminal , the terminal housing
shall be of sufficient size to provide minimum terminal
5.5 (:2.6) and l c, .
- c: s::: ==·- :I -
spacings and usable volumes in accordance with Table
4.30 . l.12(C)(l) and Table 4.30.l .12(C)(2).
.0 (3.2) - 4 I -·- I -

-- ~o -
(D) Large Wire or Factory Connections. For motors ,0 .- -
with larger ratings, greater number of leads or larger --
3 - -
wire sizes, or where motors are installed as a part of
:o -
factory-wired equipment without additional connection
being required at the motor terminal housing during
I ·-- 125

equipment installation, the terminal housing hall be


60 I 1-0 150
of ample size to make connections but the foregoing 0 - 100 1 - 175
provisions for the volumes of terminal housings shall L - 200 200
not be considered applicable. 1-0 250 250
(E) Equipment Grounding Connections. A means 1 5 -ro 300 300
for attachment of an equipment grounding conductor
termination in accordance with 2.50.1.8 shall be 300 - 350 350 400
provided at motor terminal housings for wire-to-wire 375 - 450 450 475
connections or fixed terminal connections. The means .. . .
*Where prov1s10n for three or more wrres per termmal exists, the nummum
for such connections shall be permitted to be located wire-bending space shall be in accordance with the requirements of Article
3.1 2.

346
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Exception: Installation of these motors on wooden Table 4.30.l.I2(B) Terminal Housings - Wire-to-
floors or supports shall be permitted. Wire Connections
4.30.1.16 Exposure to Dust Accumulations. In Motors 275 mm in Diameter or Less
locations where dust or flying material collects on or in Cover
motors in such quantities as to seriously interfere with Opening
the ventilation or cooling of motors and thereby cause Minimum Usable Volume
dangerous temperatures, suitable types of enclosed Dimension Minimum
motors that do not overheat under the prevailing Horsepower (mm) (cm 3)
conditions shall be used. 1and smaller 41 170
1 1/2, 2, and 3b 45 275
FPN: Especially severe conditions may require the use of enclosed
pipe-ventilated motors, or enclosure in separate dusttight rooms, 5 and 7 1/2 50 365
properly ventilated from a source of clean air. 10 and 15 65 595

4.30.1.17 Highest Rated or Smallest Rated Motor. In Motors Over 275 mm in Diameter -Alternating-
determining compliance with 4.30.2.4, 4.30.4.3(B), and Current Motors
4.30.4.3(C), the highest rated or smallest rated motor Maximum Full Typical
shall be based on the rated full-load current as selected Load Current Terminal Maximum
for 3-Phase Box Cover Horsepower
from Table 4.30.14.1, Table 4.30.14.2, Table 4.30.14.3,
Motors with Opening Usable 3-Phase
and Table 4.30.14.4.
Maximum Minimum Volume 230 460
4.30.1.18 Nominal Voltage of Rectifier Systems. The of 12 Leads Dimension Minimum Volt Volt
nominal value of the ac voltage being rectified shall (Amperes) (mm) (cm3)
be used to determine the voltage of a rectifier derived 45 65 595 15 30
system. 70 84 1265 25 50
110 100 2295 40 75
Exception: The nominal de voltage of the rectifier shall
160 125 4135 60 125
be used if it exceeds the peak value of the ac voltage
being rectified. 250 150 7380 100 200
400 175 13775 150 300
4.30.2 :\1otor Circuit Conductors _oo
600 25255 250 500
4.30.2.1 General. Part 4." 0._ specifies ampacities of Direct-Current \fotors
cond a are capable of carrying the mo or urrent \faximum Full
witho o.-e e · g under the :onditions specified. Load Current
for 3-Phase Terminal Box
The ro, 10 or Part 4 . .., Q__ nm apply to motor
Motors with Cover Opening
Clii i- ra ed OYer IOOO .-ol -, nominal.
Maximum Minimum Usable Volume
fP_ ·: f - O\'eT 000 ml· . nominal see Part 2.30. 11 of6 Leads Dimension Minimum
(Amperes) (mm) (cm 3 )
The prO\ · io of Articles 2.5 0, 3.0, and 3.10 shall
68 65 425
not apply m conductors that form an integral part of
105 84 900
equip e t, such as motors, motor controllers, motor
control centers, or other factory-assembled control 165 100 1640

equipment. 240 125 2950


375 150 5410
FP:\': See l.10.l.14(C) and 4.30. l.9(B) for equipment device
terminal requirements. 600 175 9840
900 200 18040
4.3 0.2.2 Single Motor. Conductors that supply a single Note: Auxiliary leads tor such items as brakes, tllermostats, space heaters,
motor used in a continuous duty application shall have and exciting fields shall be permitted to be neglected if their current-carrying
area does not exceed 25 percent of the current-carrying area of the machine
an ampacity of not less than 125 percent of the motor
power leads.
full-load current rating, as determined by 4.30. I .6(A) 'For motors rated 1 hp and smaller, and with the terminal housing partially
(1), or not less than specified in 4.30.2.2(A) through or wholly integral with the frame or end shield, the volume of the terminal
housing shall not be less than 18.0 cm3 per wire-to-wire connection. The
(G). minimum cover opening dimension is not specified.
bfor motors rated 1-1/2, 2, and 3 hp, and with the terminal housing partially
(A) Direct-Current Motor-Rectifier Supplied. For or wholly integral with the frame or end shield, the volume of the terminal
de motors operating from a rectified power supply, the housing shall not be less than 23.0 cm3 per wire-to-wire connection. The
conductor ampacity on the input of the rectifier shall not minmum cover opening dimension is not specified.

347
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Table 4.30.1.12(C)(l) Terminal Spacings-Fixed be less than 125 percent of the motor full-load curr :::
Terminals as determined by 4.30.l.6(A)(l). The ampacity of 1--,e
Minimum Spacing conductors between the controller and the motor h3::
not be less than 62.5 percent of the motor full- Jo3...:
Between Between Line Terminals
Line and Other Uninsulated current rating as dete1mined by 4.30. l .6(A)(l ).
Terminals Metal Parts FPN: The multiplier of 62.5 percent is obtained by multipl: i-:g
Nominal Volts (mm) (mm) 50 percent by 1.25 .
250 or less 6 6 (E) Other Than Continuous Duty. Conductors for a
Over 250 - 1000 10 10 motor used in a short-time, intenuittent, periodic. o_
Table 4.30.1.12(C)(2) Usable Volumes - Fixed varying duty application shall have an ampacity of nor
Terminals less than the percentage of the motor nameplate cmTen-
Power-Supply Minimum sable Volume per Power- rating shown in Table 4.30.2.2(E).
Conductor Size Supply Conductor
(mm 2 (mm)) (cm 3)
(F) Separate Terminal Enclosure. The conductors
between a stationary motor rated 1 hp or less and the
2.0 (1.6) 16
separate terminal enclosure permitted in 4.30.13.S(B)
3.5 (2.0) and 5.5 (2.6) 20
shall be permitted to be smaller than 2.0 mm2 (1.6 mm
8.0 (3.2) and 14 37
dia.) but not smaller than 0.75 mm2 (1.0 mm dia.),
be less than 125 percent of the rated input current to the provided they have an ampacity as specified in 4.30.2.2 .
rectifier. For de motors operating from a rectified single- (G) Conductors for Small Motors. Conductors for
phase power supply, the conductors between the field small motors shall not be smaller than 2.0 mm2 (1.6 mm
wiring output terminals of the rectifier and the motor dia.) unless otherwise permitted in 4.30.2.2(G)(l) or
shall have an ampacity of not less than the following (G)(2) .
percentages of the motor full-load current rating:
(1) 0.75 mm 2 (1.0 mm dia.) Copper. 0.75 mm2 (1.0
( 1) Where a rectifier bridge of the single-phase half- mm dia.) individual copper conductors installed
wave type is used, 190 percent. in a cabinet or enclosure, copper conductors
(2) Where a rectifier bridge of the single-phase, full- that are part of a jacketed multiconductor cable
wave type is used, 150 percent. assembly, or copper conductors in a flexible cord
shall be permitted, under either of the following
(B) Multispeed Motor. For a multispeed motor the sets of conditions:
selection of branch-circuit conductors on the line side
of the controller shall be based on the highest of the (1) The circuit supplies a motor with a full-load
full-load cunent ratings shown on the motor nameplate. current rating, as determined by 4.30 . l .6(A)
The ampacity of the branch-circuit conductors between (I), of greater than 3.5 amperes, and less than
the controller and the motor shall not be less than 125 or equal to 5 amperes, and all the following
percent of the current rating of the winding(s) that the conditions are met:
conductors energize. a. The circuit is protected in accordance with
(C) Wye-Start, Delta-Run Motor. For a wye-start, 4.30.4.2.
delta-run connected motor, the ampacity of the branch- a. The circuit is provided with maximum Class
circuit conductors on the line side of the controller IO or Class 1OA overload protection m
shall not be less than 125 percent of the motor full-load accordance with 4.30.3.2.
cun-ent as determined by 4.30.l .6(A)(l). The ampacity
of the conductors between the controller and the motor b. Overcurrent protection is provided m
shall not be less than 72 percent of the motor full-load accordance with 2.40. l .4(D)(2)(b).
current rating as determined by 4.30.1.6(A)(l ). (2) The circuit supplies a motor with the full load
FPN: The individual motor circuit conductors of a wye-start, current rating, as determined by 4.30.1.6(A)( 1).
delta-run connected motor carry 58 percent of the rated load of 3.5 amperes or less, and all the following
current. The multiplier of 72 percent is obtained by multiplying conditions are met:
58 percent by 1.25.
a. The circuit is protected in accordance with
(D) Part-Winding Motor. For a part-winding
4.30.4.2.
connected motor, the ampacity of the branch-circuit
conductors on the line side of the controller shall not

348
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
b. The circuit is provided with maximum Class Table 4.30.2.2(E) Duty-Cycle Service
20 overload protection in accordance with ~ameplate Current Rating Percentages
4.30.3.2. 30- & 60-
5-.Minute IS-Minute Minute Continuous
c. Overcurrent protection is provided m Classification of Rated Rated Rated Rated
accordance with 2.40. l .4(D)(2)(b). Service Motor Motor Motor Motor
Short-time l 10 120 150
(2) 1.25 mm 2 Copper. 1.25 mm2 individual copper duty operating
conductors installed in a cabinet or enclosure, valves, raising or
copper conductors that are part of a jacketed lowering rolls, etc

multiconductor cable assembly, or copper Intermittent 85 85 90 140


duty freight
conductors in a flexible cord shall be permitted and passenger
under either of the following sets of conditions: elevators, tool
heads, pumps,
(1) The circuit supplies a motor with a full-load drawbridges,
turntables, etc.
current rating, as determined by 4.30.1.6(A) (for arc welders,
(1), of greater than 5.5 amperes, and less than see 6.30.2. l)
or equal to 8 amperes, and all the following Periodic duty 85 90 95 140
conditions are met: rolls, ore- and
coal- handling
a. The circuit is protected in accordance with machines, etc.
4.30.4.2. Varying duty 11 0 120 150 200
Note: Any motor appl1catton shall be considered as contmuous duty unless the nature
b. The circuit is provided with maximum Class 10 of the apparatus it drives is such that the motor will not operate continuously w ith load
under any condition of use.
or Class 1OA overload protection in accordance
ampacity of the conductors between controller and
with 4.30.3.2.
resistor shall not be less than that shown in Table
c. Overcurrent protection is provided m 4.30.2.3(C).
accordance with 2.40. l .4(D)(2)(b).
4.30.2.4 Several Motors or a Motor(s) and Other
(2) The circuit supplies a motor with a full-load Load(s). Conductors supplying several motors, or a
current rating, as dete1mined by 4.30.1.6(A)(l ), motor(s) and other load(s), shall have an ampacity not
of 5.5 amperes or less, and all the following less than the sum of each of the following:
conditions are met:
(1) 125 percent of the full-load current rating of the
a. The circuit is protected in accordance with highest rated motor, as determined by 4.30. l .6(A)
4.30.4.2.
(2) Sum of the full-load current ratings of all the
b. The circuit is provided with maximum Class other motors in the group, as determined by
20 overload protection in accordance with 4.30. l .6(A)
4.30.3.2.
(3) 100 percent of the noncontinuous non-motor load
c. Overcurrent protection 1s provided m
(4) 125 percent of the continuous non-motor load.
accordance with 2.40.1 .4(D)(2)(b).
FPN: See Appendix D, Example DlO.
4.30.2.3 Wound-Rotor Secondary.
(A) Continuous Duty. For continuous duty, the
conductors connecting the secondary of a wound-rotor Table 4.30.2.3(C) Secondary Conductor
ac motor to its controller shall have an ampacity not Ampacity of Conductor
less than 125 percent of the full-load secondary current in Percent of Full-Load
Resistor Duty Classification Secondary Current
of the motor.
Light starting duty 35
(B) Other Than Continuous Duty. For other than Heavy starting Duty 45
continuous duty, these conductors shall have an
Extra-heavy starting duty 55
ampacity, in percent of full-load secondary current, not
Light intermittent duty 65
less than that specified in Table 4.30.2.2(E).
Medium intermittent duty 75
(C) Resistor Separate from Controller. Where the Heavy intermittent duty 85
secondary resistor is separate from the controller, the Continuous duty 11 0
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Exception No. 1: Where one or more of the motors ensure that only qualified persons service the sysrems.
of the group are used for short-time, intermittent, conductors tapped to a feeder shall be p erm ··-ed ·o be
periodic, or varying duty, the ampere rating of such not over 7500 mm long horizontally and nor oi-er 30.0
motors to be used in the summation shall be determined m in total length where all of the following con >·ow
in accordance with 4.30.2.2(E). For the highest rated are met:
motor, the greater of either the ampere rating from (1) The ampacity ofthe tap conductors is not less ,1 r.
4.30.2.2(E) or the largest continuous duty motor full- one-third that of the feeder conductors.
load current multiplied by 1.25 shall be used in the
summation. (2) The tap conductors terminate with a single circu ·-
breaker or a single set offuses comply ing ·with f I,
Exception No. 2: The ampacity of conductors supplying Part 4.30.4 where the load-side conductors are a
motor-operated fixed electric space-heating equipment shall branch circuit, or (2) Part 4.30.5, where the load-
comply with 4.24.l.3(B). side conductors are a feeder.

Exception No. 3: Where the circuitry is interlocked so as to (3) The tap conductors are suitably protected from
prevent simultaneous operation of selected motors or other physical damage and are installed in raceways.
loads, the conductor ampacity shall be permitted to be based (4) The tap conductors are continuous from end-to-
on the summation of the currents of the motors and end and contain no splices.
other loads to be operated simultaneous(),· that results
(5) The tap conductors shall be 14 mm 2 copper or 22
in the highest total current.
mm1 aluminum or larger.
4.30.2.5 Multimotor and Combination-Load (6) The tap conductors shall not p enetrate walls,
Equipment. The arnpacity of the conductors supplying floors, or ceilings.
multimotor and combination-load equipment shall not
(7) The tap shall not be made less than 9000 mm from
be less than the minimum circuit ampacity marked on
the.floor.
the equipment in accordance with 4.30.1. (D). Where
the equipment is not factory-wired and the individual 4.30.2.9 Constant Voltage Direct-Current Motors
nameplates are visible in accordance v.ith 4.30.1. 7(D) - Power Resistors. Conductors connecting the motor
(2), the conductor ampacity shall be determined in controller to separately mounted power accelerating
accordance with 4.30.2.4. and dynamic braking resistors in the armature circuit
shall have an ampacity not less than the value calculated
4.30.2.7 Capacitors \"\ith :'.\-lotors. Where apacitors
are installed in motor circuits. conductors shall comply from Table 4.30.2.9 using motor full-load current. If an
with 4.60.1.8 and 4.60.1.9. annature shunt resistor is used, the power accelerating
resistor conductor ampacity shall be calculated using
4.30.2.8 Feeder Tap . Feeder ·ap conductor shall the total of motor full-load current and annature shunt
have an ampacity not less than that required by Part
resistor current.
4.30 .2 shall terminate in a branch-circuit protective
device, and in addition, hall meet one of the following Armature shunt resistor conductors shall have an
requirements: ampacity of not less than that calculated from Table
(1) Be enclosed either b an enclosed controller 4.30.2.9 using rated shunt resistor current as full-load
or by a raceway, be not more than 3000 mm in current.
length and for field installation be protected
4.30.3 Motor and Branch-Circuit Overload
by an o ercurrent de,ice on the line side of the
tap conductor the rating or setting of which shall Protection
not exceed 1000 percent of the tap conductor
ampacity 4.30.3.1 General. Part 4.30.3 specifies overload de...-ices
intended to protect motors, motor-control appararus.
(2) Have an ampacity of at least one-third that of the
and motor branch-circuit conductors against excessi...-e
feeder conductors be suitably protected from
physical damage or enclosed in a raceway, and be heating due to motor overloads and failure to start
not more than 7500 mm in length FPN No. 1: See Appendix D, Examples D9 and D l 0.

(3) Have an ampacity not less than the feeder FPN No. 2: See the definition of Overload in Arri I ., .
conductors
These provisions shall not require overload protec ion
Exception: Feeder taps over 7500 mm long. In high-bay where a power loss would cause a hazard. uch as in the
manufacturing buildings (over 11000 mm high at walls), case of fire pumps.
where conditions of maintenance and supervision FPN: For protection offire pump supply conductors, see 6.95.1.7.

350
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
The provisions of Part 4.30.3 shall not apply to motor failure to start. The ultimate trip current of a
circuits rated over 1000 volts, nominal. thermally protected motor shall not exceed the
FPN: For over 1000 volts, nominal, see Part 4.30.11. following percentage of motor full-load current
given in Table 4.30.14.2, Table 4.30.14.3 , and
4.30.3.2 Continuous-Duty Motors. Table 4.30.14.4.

(A) More Than 1 Horsepower. Each motor used in a Motor full-load current 9 amperes 170%
continuous duty application and rated more than 1 hp or less
shall be protected against overload by one of the means Motor full-load current from 9.1 to, and 156%
in 4.30.3.2(A)(l) through (A)(4). including, 20 amperes
(1) Separate Overload Device. A separate overload Motor full-load current greater than 140%
device that is responsive to motor current. This 20 amperes
device shall be selected to trip or shall be rated at
no more than the following percent of the motor If the motor current-interrupting device is separate
nameplate full-load current rating: from the motor and its control circuit is operated by
a protective device integral with the motor, it shall be
Motors with a marked service factor 125% arranged so that the opening of the control circuit will
1.15 or greater result in interruption of current to the motor.

Motors with a marked temperature 125% (1) Integral with Motor. A protective device integral
rise 40°C or less with a motor that will protect the motor against
damage due to failure to start shall be permitted
All other motors 115% if the motor is part of an approved assembly that
Modification of this value shall be permitted as provided does not normally subject the motor to overloads.
in 4.30.3.2(C). For a multispeed motor, each winding (2) Larger Than 1500 Horsepower. For motors
connection shall be considered separately. larger than 1500 hp, a protective device having
Where a separate motor overload device is connected embedded temperature detectors that cause
so that it does not carry the total current designated on current to the motor to be interrupted when
the motor nameplate, such as for wye-delta starting, the the motor attains a temperature rise greater
proper percenta2:e of nameplate current applying to the than marked on the nameplate in an ambient
selection or etting of the OYerload de\·ice shall be clearly temperature of 40°C.
designated on th ipme r. or the manufacrurer · (B) One Horsepower or Less, Automatically Started.
election table shall take · into a ,-\ny moto of 1 hp or less that is tarted automatically
FP:\": \\ "here pm1;er fa ro:- co -um: a imrs are ;, sra.j on ha 1 e pro e te against overload by one of the
the loads· p of the o-or OY oa e,i . see 4.60. · .9. rollo ;•;i .g mea
(2) Thermal Protector. A. thermal prOt -or in egral (1) Separate Onrload Device. By a separate
with the motor, approwd for use with the moror it O\-erload e\i e follo,,·ing the requirements of
protects on the ba is that it wi ll pre\·ent dangerou 4.3 0."' __ (_.\ )( 1).
oYerheating of the motor due to overload and
For a multi peed motor, each winding connection
shall be considered separately. Modification of this
Table 4.30-2.9 Conductor Rating Factors for Power
value shall be permitted as provided in 4 .30.3 .2(C) .
Resistors
Time in Seconds Ampacity of Conductor
(2) Thermal Protector. A thermal protector integral
in Percent of Full-Load with the motor, approved for use with the motor
On Off Current that it protects on the basis that it will prevent
5 75 35 dangerous o erheating of the motor due to
10 70 45 overload and failure to start. Where the motor
15 75 55 current-intenupting device is separate from the
15 45 65
motor and its control circuit is operated by a
protective device integral with the motor, it shall
15 30 75
be arranged so that the opening of the control
15 15 85
circuit results in intenuption of cunent to the
Continuous Duty 110
motor.
351
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
(3) Integral with Motor. A protective device integral (D) One Horsepower or Less, Nonautomatically
with a motor that protects the motor against Started.
damage due to failure to start shall be permitted
(1) Permanently Installed. Overload protection
( 1) if the motor is part of an approved assembly
shall be in accordance with 4.30.3.2(B).
that does not subject the motor to overloads, or
(2) if the assembly is also equipped with other (2) Not Permanently Installed.
safety controls (such as the safety combustion (a) Within Sight from Controller. Overload
controls on a domestic oil burner) that protect protection shall be permitted to be furnished
the motor against damage due to failure to start. by the branch-circuit short-circuit and ground-
Where the assembly has safety controls that fault protective device· such device, however,
protect the motor, it shall be so indicated on the shall not be larger than that specified in Part
nameplate of the assembly where it will be visible 4.30.4.
after installation.
Exception: Any such moror shall be permitted on a
(4) Impedance-Protected. If the impedance of nominal 230-volt or 115-volt branch circuit protected
the motor windings is sufficient to prevent at not over 20 amperes.
overheating due to failure to start, the motor
shall be permitted to be protected as specified (b) ot Within Sia-ht from Controller. Overload
in 4.30.3.2(D)(2)(a) for manually started motors protection shall be in accordance with
if the motor is part of an approved assembly in 4.30." .2(B).
which the motor will limit itself so that it will not (E) Wound-Rotor Secondaries. The secondary circuits
be dangerously overheated. of ·wound-rotor a o·o . including conductors,
FPN: Many ac motors ofless than Y20 hp, such as clock motors, controllers. re-i tor . and o forth. shall be permitted
series motors, and so forth, and also some larger motors such as to b p o ected a= o · rload by the motor-overload
torque motors, come within this classification. It does not include
split-phase motors having automatic switches that disconnect the de\ic .
starting windings.

(C) Selection of Overload Device. Where the


sensing element or setting or sizing of the overload
device selected in accordance with 4.30.3.2(A)( 1)
and 4.30.3.2(B)(l) is not sufficient to start the motor
or to cany the load, higher size sensing elements or
incremental settings or sizing shall be permitted to be \ · e. pro,-ided the protective
used, provided the trip cunent of the overload device o exceed that pecified in
does not exceed the following percentage of motor
nameplate full-load current rating:
Any
Motors with marked service factor 1.15 140%
contin o es the nature of the apparatus it
or greater drive- i su h Iha the mom an.not operate continuously
Motors with a marked temperature rise 140% \\ ith load der any on ·rion of use.
40°C or less
4.30.3.5 Shunting During Starting Period.
All other motors 130%
(A) I'i onautomatically Started. For a nonautomatically
If not shunted during the starting period of the motor started motor. the OYerload protection shall be permitted
as provided in 4.30.3 .5, the overload device shall have to be shunted or cut out of the circuit during the starting
sufficient time delay to permit the motor to start and period of the motor if the device by which the overload
accelerate its load. protection is shunted or cut out cannot be left in the
FPN: A Class 20 overload relay will pro- vide a longer motor starting position and if fuses or inverse time circuit
acceleration time than a Class 10 or Class 1OA overload relay. breakers rated or set at not over 400 percent of the full-
A Class 30 overload relay will provide a longer motor
acceleration time than a Class 20 overload relay. Use of a load current of the motor are located in the circuit so as
higher class overload relay may preclude the need for selection of to be operative during the starting period of the motor.
a higher trip current.
(B) Automatically Started. The motor overload
protection shall not be shunted or cut out during the
starting period if the motor is automatically started .
.-
J -
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Exception: The motor overload protection shall be the overload devices shall be protected in accordance
permitted to be shunted or cut out during the starting with this marking.
period on an automatically started motor where the
4.30.3.12 Motors on General-Purpose Branch
following apply:
Circuits. Overload protection for motors used on
(a) The motor starting period exceeds the time delay general-purpose branch circuits as permitted in Article
of available motor overload protective devices, 2.10 shall be provided as specified in 4.30.3.12(A), (B),
and (C), or (D).
(b) Listed means are provided to perform the (A) Not over 1 Horsepower. One or more motors
following: without individual overload protection shall be permitted
to be connected to a general-purpose branch circuit
(1) Sense motor rotation and automatically prevent
only where the installation complies with the limiting
the shunting or cutout in the event that the
conditions specified in 4.30.3.2(B) and 4.30.3.2(D) and
motor fails to start, and
4.30.4.3(A)(l) and (A)(2).
(2) Limit the time of overload protection shunting
or cutout to less than the locked rotor time
rating of the protected motor, and
(3) Provide for shutdown and manual restart if Table 4.30.3.7 Overload Units ·
motor running condition is not reached.
Number and
4.30.3.6 Fuses - In Which Conductor. Where fuses Location of
are used for motor overload protection, a fuse shall Overload Units,
be inserted in each ungrounded conductor and also in Such as Trip
the grounded conductor if the supply system is 3-wire, Kind of Motor Supply System Coils or Relays
, -pha e ac ,,ith one conductor grounded. 2-wire, I-phase
1 in either
I -phase ac or de ac or de
4.30.3. De,ices Other Than Fuses - In ·w hich conductor
ungrounded
Cond uctor. \lin re e,i es other than fuses are used 2-wire, I -phase
·ecrion. Table -+.30.3. shall ac or de, one I in ungrounded
gowm - e ·ab e r and location of 1-phase ac or de
conductor conductor
oYerload grounded
3-wire, I-phase
4.30.3.8 ~ umber of Conductors Opened by I in either
ac or de,
1-phase a or de ungrounded
Overload De,ice. .. fo or oYe o e,i s. o her than grounded neutral
conductor
fuses or thermal prote ors, ha im raneo ly open a conductor
sufficient number or ungrounded condu ors to interrupt 1 in ungrounded
current fl.ow to the motor. 1-phase ac Any 3-phasc
conductor
4.30.3.9 Motor Controller as Overload Protection. 3-wire, 2-phase 2, one in each
A motor controller shall also be permitted to en-e as _-phase ac
ac, ungrounded phase
an overload device if the number of owrload units
3-wire, 2-phase
complies with Table 4.30.3.7 and if these units are 2 in ungrounded
2-phase ac ac, one conductor
operative in both the starting and running position in conductors
grounded
the case of a de motor, and in the running position in the
2, one for
case of an ac motor. 4-wire, 2-phase
each phase in
2-phase ac ac, grounded or
4.30.3.10 Overload Relays. Overload relays and other ungrounded
ungrounded
devices for motor overload protection that are not conductors
capable of opening short circuits or ground faults shall 2, one for each
Grounded neutral
be protected by fuses or circuit breakers with ratings phase in any
2-phase ac or 5-wire, 2-phase
or settings in accordance with 4.30.4.2 or by a motor ungrounded
ac, ungrounded
phase wire
short-circuit protector in accordance with 4.30.4.2.
3, one in each
Exception: Where approved for group installation and 3-phase ac Any 3-phase
phase*
marked to indicate the maximum size offuse or inverse ~r;xcep tion: An over/oat unit in each p1hase shati not be required where
time circuit breaker by which they must be p rotected, overload protection is provided by other approved means.

353
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
(B) Over 1 Horsepower. Motors of ratings larger 4.30.4 Motor Branch-Circuit Short-Circuit and
than specified in 4.30.4.3(A) shall be permitted to be Ground-Fault Protection
connected to general-purpose branch circuits only
4.30.4.1 General. Part 4.30.4 specifies devices
where each motor is protected by overload protection
intended to protect the motor branch-circuit conductor .
selected to protect the motor as specified in 4.30.3.2.
the motor control apparatus, and the motors against
Both the controller and the motor overload device
overcurrent due to short circuits or ground faults. These
shall be approved for group installation with the short-
rules add to or amend the provisions of Article 2.40. The
circuit and ground-fault protective device selected in
devices specified in Part 4.30.4 do not include the types
accordance with 4.30.4.3 .
of devices required by 2.10.1.8, 2.30.7.6, and 5.90.1.6.
(C) Cord-and Plug-Connected. Where a motor is FPN: See Appendix D, Examples D9 and DIO.
connected to a branch circuit by means of an attachment
plug and a receptacle or a cord connector, and The provisions of Part 4.30.4 shall not apply to motor
individual overload protection is omitted as provided circuits rated over 1000 volts, nominal.
in 4.30.3.12(A), the rating of the attachment plug and FPN: For over 1000 volts, nominal, see Part 4.30 .11
receptacle or cord connector shall not exceed 15 amperes
4.30.4.2 Rating or Setting for Individual Motor
at 125 volts or 250 volts. Where individual overload
Circuit.
protection is required as provided in 4.30.3.12(B) for
a motor or motor-operated appliance that is attached (A) General. The motor branch-circuit short-circuit
to the branch circuit through an attachment plug and and ground-fault protective device shall comply with
a receptacle or a cord connector, the overload device 4.30.4.2(B) and either 4.30.4.2(C) or (D), as applicable.
shall be an integral part of the motor or of the appliance. (B) All Motors. The motor branch-circuit shmt-circuit
The rating of the attachment plug and receptacle or the and ground-fault protective device shall be capable of
cord connector shall determine the rating of the circuit carrying the starting current of the motor.
to which the motor may be connected, as provided in
2.10.2.4(B). (C) Rating or Setting.

(D) Time Delay. The branch-circuit short-circuit and (1) In Accordance with Table 4.30.4.2. A protective
ground-fault protective device protecting a circuit to device that has a rating or setting not exceeding
which a motor or motor-operated appliance is connected the value calculated according to the values given
shall have sufficient time delay to permit the motor to in Table 4.30.4.2 hall be used.
start and accelerate its load. Excep tion o. 1: Where the values for branch-circuit
4.30.3.13 Automatic Restarting. A motor overload short-circuit and ground-fault protective devices
device that can restart a motor automatically after determined by Table 4.30.4.2 do not correspond to
overload tripping shall not be installed unless approved the standard sizes or ratings of fuses, nonacijustable
for use with the motor it protects. A motor overload circuit breakers, thermal protective devices, or possible
device that can restart a motor automatically after settings of acijustable circuit breakers, a higher size,
overload tripping shall not be installed if automatic rating, or possible setting that does not exceed the next
restarting of the motor can result in injury to persons. higher standard ampere rating shall be permitted.

4.30.3.14 Orderly Shutdown. If immediate automatic Exception No. 2: Where the rating specified in Table
shutdown of a motor by a motor overload protective 4.30.4.2, or the rating modified by Exception No. 1, is
device(s) would introduce additional or increased not sufficient for the starting current of the motor:
hazard(s) to a person(s) and continued motor operation (a) The rating of a nontime-delay fuse not exceeding
is necessary for safe shutdown of equipment or process, 600 amperes or a time-delay Class CC fuse shall
a motor overload sensing device(s) complying with be permitted to be increased but shall in no case
the provisions of Part 4.30.3 of this article shall be exceed 400 percent of the full-load current.
permitted to be connected to a supervised alarm instead
of causing immediate interruption of the motor circuit, (b) The rating of a time-delay (dual-element) fuse
so that corrective action or an orderly shutdown can be shall be permitted to be increased but shall in no
initiated. case exceed 225 percent of the full-load current.
(c) The rating of an inverse time circuit breaker
shall be permitted to be increased but shall in no
case exceed 400 percent for full-load currents of

354
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
JOO amperes or less or 300 percentforfull-load amperes or less in a listed combination motor controller
currents greater than I 00 amperes. that provides coordinated motor branch-circuit overload and
short-circuit and ground-fault protection shall be permitted
(d) The rating of a fuse of 601- 6000 ampere to be increased to the value marked on the controlle1:
classification shall be permitted to be increased
but shall in no case exceed 300 percent ofthefull- (4) Multispeed Motor. For a multispeed motor, a
load current. single short-circuit and ground-fault protective
device shall be permitted for two or more
FPN: See Appendix D, Examples D9 and DlO, and Figure
4.30.1. 1. windings of the motor, provided the rating of
the protective device does not exceed the above
(2) Overload Relay Table. Where maximum branch- applicable percentage of the nameplate rating of
circuit short-circuit and ground-fault protective the smallest winding protected.
device ratings are shown in the manufacturer's
overload relay table for use with a motor controller Exception: For a multispeed motor, a single short-
or are otherwise marked on the equipment, they circuit and ground-fault protective device shall be
shall not be exceeded even if higher values are permitted to be used and sized according to the full-
allowed as shown above. load current of the highest current winding, where all
of the following conditions are met:
(3) Instantaneous Trip Circuit Breaker. An
instantaneous trip circuit breaker shall be (a) Each winding is equipped with individual
used only if adjustable and if part of a listed overload protection sized according to its full-
combination motor controller having coordinated load current.
motor overload and short-circuit and ground- (b) The branch-circuit conductors supplying each
fault protection in each conductor, and the setting winding are sized according to the full-load
is adjusted to no more than the value specified in current of the highest full-load current winding.
Table 4.30.4.2.
(c) The controllerfor each winding has a horsepower
FPN No. 1: Instantaneous trip circuit breakers are also known as
rating not less than that required for the winding
motor-circuit protectors (MCPs).
having the highest horsepower rating.
FPN _ o. 2: For the purpose of this article, instantaneous trip
circuit breakers may include a damping means to accommodate (5) Power Electronic Devices. Semiconductor
a transient motor inrush current without nuisance tripping of the fuses intended for the protection of electronic
circuit breaker. devices shall be permitted in lieu of devices listed
Exception So. 1: Where the setting specified in Table in Table 4.30.4.2 for power electronic devices,
4.30.4._ is not sufficient for the starting current of associated electromechanical devices (such as
the motor, the seffina of an instantaneous trip circuit bypass contactors and isolation contactors),
breaker shall be permitted to be increased but shall and conductors in a solid-state motor controller
in no case exceed 1300 percent of the motor full- system, provided that the marking for replacement
load currem for other han Design B energy-efficient fuses is provided adjacent to the fuses.
motors and no more rhan 1700 percent of full-load (6) Self-Protected Combination Controller. A
moior current for Design B energy-efficient motors. listed self-protected combination controller shall
Trip settinas aboYe 00 percent for other than Design be permitted in lieu of the devices specified in
B ene,gy-e.fficient motors and aboi·e 1100 percent for Table 4.30.4.2. Adjustable instantaneous-trip
Design B energy-effzcient motors shall be permitted settings shall not exceed 1300 percent of full-load
1i·here rhe need has been demonstrated by engineering motor current for other than Design B energy-efficient
evaluation. In such cases, it shall not be necessary to motors and not more than 1700 percent of full-load
first apply an instantaneous-trip circuit breaker at 800 motor current for Design B energy-efficient motors.
p ercent or 1100 percent. FPN: Proper application of self-protected combination controllers
FPN: For additional information on the requirements for a on 3-phase systems, other than solidly grounded wye, particularly
motor to be classified "energy efficient," see NEMA Standards on comer grounded delta systems, considers the self-protected
Publication 1\'.o. MGl -1993, Revision, Motors and Generators, combination controllers' individual pole-interrupting capability.
Part 12.59.
(7) Motor Short-Circuit Protector. A motor short-
Exception No. 2: Where the motor full-load current is circuit protector shall be permitted in lieu of
8 amperes or less, the setting of the instantaneous-trip devices listed in Table 4.30.4.2 if the motor short-
circuit breaker with a continuous current rating of 15 circuit protector is part of a listed combination

355
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Table 4.30.4.2 Maximum Rating or Setting of Motor Branch-Circuit Short-Circuit and Ground-Fault
Protective Devices
Percentage of Full-Load Current
Type of Motor Nontime Delay Dual Element Instantaneous Trip Inverse Time
Fuse1 (Time-Delay) Fuse1 Breaker Breaker2
Single-phase motors 300 175 800 250
AC polyphase motors other than wound- 300 175 800 250
rotor
Squirrel cage - other than Design B energy- 300 175 800 250
efficient
Design B energy-efficient 300 175 1100 250
Synchronous 3 300 175 800 250
Wound-rotor 150 150 800 150
DC (constant voltage) 150 150 250 150
Note: For certam exceptions to the values specrtied, see 4.30.4.4.
'The values in the Nontime Delay Fuse column apply to time-delay Class CC fuses.
2The values given in the last column also cover the ratings of nonadjustable inverse time types of circuit breakers that may be modified as in 4.30.4.2(C)(I),

Exceptions No. 1 and No. 2.


' Synchronous motors of the low-torque, low-speed type (usually 450 rpm or lower), such as are used to drive reciprocating compressors, pumps, and so forth, that
start unloaded, do not require a fuse rating or circuit-breaker setting in excess of200 percent of full-load current.

motor controller having coordinated motor (3) Individual overload protection conforms to
overload protection and short-circuit and ground- 4.30.3.2.
fault protection in each conductor and it will open
(B) If Smallest Rated Motor Protected. If the branch-
the circuit at currents exceeding 1300 percent of
circuit short-circuit and ground-fault protective device
motor full-load current for other than Design
is selected not to exceed that allowed by 4.30.4.2 for
B energy-efficient motors and 1700 percent
the smallest rated motor, two or more motors or one or
of motor full-load motor current for Design B
more motors and other load(s), with each motor having
energy-efficient motors.
individual overload protection, shall be permitted to be
FPN: A motor short-circuit protector, as used in this section, is a connected to a branch circuit where it can be determined
fused device and is not an instantaneous trip circuit breaker.
that the branch-circuit short-circuit and ground-fault
(D) Torque Motors. Torque motor branch circuits shall protective device will not open under the most severe
be protected at the motor nameplate current rating in normal conditions of service that might be encountered.
accordance with 2 .40. l .4(B). (C) Other Group Installations. Two or more motors
of any rating or one or more motors and other load(s),
4.30.4.3 Several Motors or Loads on One Branch with each motor having individual overload protection,
Circuit. Two or more motors or one or more motors shall be permitted to be connected to one branch circuit
and other loads shall be permitted to be connected to
where the motor controller(s) and overload device(s) are
the same branch circuit under conditions specified in
(1) installed as a listed factory assembly and the motor
4.30.4.3(D) and in 4.30.4.3(A), (B), or (C). The branch-
branch-circuit short-circuit and ground-fault protective
circuit protective device shall be fuses or inverse time device either is provided as part of the assembly or is
circuit breakers.
specified by a marking on the assembly, or (2) the motor
(A) Not Over 1 Horsepower. Several motors, each branch-circuit short-circuit and ground-fault protective
not exceeding 1 hp in rating, shall be permitted on a device, the motor controller(s), and overload device(s)
nominal 230-volt or 115-volt branch circuit protected at are field-installed as separate assemblies listed for such
not over 20 amperes or a branch circuit of 1 000 volts, use and provided with manufacturers' instructions
nominal, or less, protected at not over 15 amperes, if all for use with each other, and (3) all of the following
of the following conditions are met: conditions are complied with:
( 1) The full-load rating of each motor does not exceed (1) Each motor overload device is either (a) listed
6 amperes. for group installation with a specified maxim
rating of fuse, inverse time circuit breaker. o
(2) The ratings of the branch-circuit short-circuit and
both, or (b) selected such that the ampere rating of
ground-fault protective device marked on any of
the motor-branch short-circuit and ground-faut
the controllers is not exceeded.
356
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
protective device does not exceed that permitted (1) Conductors from the point of the tap from the
by 4.30.4.2 for that individual motor overload branch circuit to a listed manual motor controller
device and corresponding motor load. additionally marked " Suitable for Tap Conductor
Protection in Group Installations," or to a branch-
(2) Each motor controller is either (a) listed for group
circuit protective device, shall be permitted to
installation with a specified maximum rating of
have an ampacity not less than one-tenth the
fuse, circuit breaker, or both, or (b) selected such
rating or setting of the branch-circuit short-
that the ampere rating of the motor-branch short-
circuit and ground-fault protective device. The
circuit and ground-fault protective device does
conductors from the controller to the motor shall
not exceed that permitted by 4.30.4.2 for that
have an ampacity in accordance with 4.30.2.2.
individual controller and corresponding motor
The conductors from the point of the tap to the
load.
controller(s) shall (1) be suitably protected from
(3) Each circuit breaker is listed and is of the inverse physical damage and enclosed either by an
time type. enclosed controller or by a raceway and be not
(4) The branch circuit shall be protected by fuses more than 3 000 mm long or (2) have an ampacity
or inverse time circuit breakers having a rating not less than that of the branch-circuit conductors.
not exceeding that specified in 4.30.4.2 for the (2) Conductors from the point of the tap from the
highest rated motor connected to the branch branch circuit to a listed manual motor controller
circuit plus an amount equal to the sum of the additionally marked "Suitable for Tap Conductor
full-load current ratings of all other motors and Protection in Group Installations," or to a branch-
the ratings of other loads connected to the circuit. circuit protective device, shall be permitted to
Where this calculation results in a rating less than have an ampacity not less than one-third that of the
the ampacity of the branch-circuit conductors, branch-circuit conductors. The conductors from
it shall be permitted to increase the maximum the controller to the motor shall have an ampacity
rating of the fuses or circuit breaker to a value not in accordance with 4.30.2.2. The conductors from
exceeding that permitted by 2.40. l .4(B). the point of the tap to the controller(s) shall (1)
(5) The branch-circuit fuses or inverse time circuit be suitably protected from physical damage and
breakers are not larger than allowed by 4.30.3.10 enclosed either by an enclosed controller or by
for the overload relay protecting the smallest a raceway and be not more than 7 500 mm long
rated motor of the group. or (2) have an ampacity not less than that of the
branch-circuit conductors.
( 6) Overcurrent protection for loads other than motor
loads shall be in accordance with Parts 2.40. 1 4.30.4.4 Multimotor and Combination-Load
through 2.40 .. Equipment. The ratings of the branch-circuit short-
circuit and ground-fault protective device form ultimo tor
FP~: See 1.10.1.10 for cir uit impedance and other characteristics.
and combination-load equipment shall not exceed the
(D) Single Motor Taps. For group installations rating marked on the equipment in accordance with
described above, the conductors of any tap supplying a 4.30. l .7(D).
single motor shall not be required to ha ·e an indiYidual
4.30.4.5 Combined Overcurrent Protection. Motor
branch-circuit short-circuit and ground-fault protective
branch-circuit short-circuit and ground-fault protection
device, provided they comply with one of the following:
and motor overload protection shall be permitted to be
(1) No conductor to the motor shall have an ampacity combined in a single protective device where the rating
less than that of the branch-circuit conductors. or setting of the device provides the overload protection
specified in 4.30.3.2.
(2) No conductor to the motor shall have an ampacity
less than one-third that of the branch-circuit 4.30.4.6 Branch-Circuit Protective Devices - In
conductors, with a minimum in accordance Which Conductor. Branch-circuit protective devices
with 4.30.2.2. The conductors from the point shall comply with the provisions of 2 .40 .1.15.
of the tap to the motor overload device shall be
4.30.4.7 Size of Fuseholder. Where fuses are used for
not more than 7500 mm long and be protected
motor branch-circuit short-circuit and ground-fault
from physical damage by being enclosed in an
protection, the fuseholders shall not be of a smaller size
approved raceway or by use of other approved
than required to accommodate the fuses specified by
means.
Table 4.30.4.2.

357
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Exception: Where fi1ses having time delay appropriate (B) Other Installations. Where feeder conductors have
for the starting characteristics of the motor are used, an ampacity greater than required by 4 .30.2.4, the rating
it shall be permitted to use fuseholders sized to fit the or setting of the feeder overcurrent protective device
fuses that are used. shall be permitted to be based on the ampacity of the
feeder conductors.
4.30.4.8 Rating of Circuit Breaker. A circuit breaker
for motor branch-circuit short-circuit and ground-fault
4.30.5.3 Rating or Setting - Motor Load and Other
protection shall have a current rating in accordance with
Load(s). Where a feeder supplies a motor load and
4.30.4.2 and 4.30.9.10.
other load(s), the feeder protective device shall have a
4.30.5 Motor Feeder Short-Circuit and Ground- rating not less than that required for the sum of the other
Fault Protection load(s) plus the following:
4.30.5.1 General. Part 4.30.5 specifies protective (1) For a single motor, the rating permitted by
devices intended to protect feeder conductors supplying 4.30.4.2
motors against overcurrents due to short circuits or
(2) For a single hermetic refrigerant motor-
grounds.
compressor, the rating permitted by 4.40.3.2
FPN: See Appendix D, Examples D9 and DIO.
(3) For two or more motors, the rating permitted by
4.30.5.2 Rating or Setting - Motor Load. 4.30.5.2
(A) Specific Load. A feeder supplying a specific fixed Exception: Pf/here the feeder overcurrent device
motor load(s) and consisting of conductor sizes based provides the overcwTent protection for a motor control
on 4.30.2.4 shall be provided with a protective device cente1; the provisions of 4. 30.8. 3 shall apply.
having a rating or setting not greater than the largest
rating or setting of the branch-circuit short-circuit and 4.30.6 ~1otor Control Circuits
ground-fault protective device for any motor upplied
by the feeder [based on the maximum permitted value 4.30.6.1 General. Part 4.30.6 contains modifications of
for the specific type of a protective device in accordance the general requirement and applies to the particular
with 4.30.4.2, or 4.40.3 .2(A) for hermetic refrigerant condition of motor control cir uit .
motor-compressors], plus the um of the full-load 4.30.6.2 Overcurrent Protection.
currents of the other motors of the group.
(A) G:!neral. A motor control circuit tapped from the
Where the same rating or setting of the branch-circuit load ide of a motor branch-circuit short-circuit and
short-circuit and ground-fault protecti,·e deYice i u ed ground-fault protectiYe device(s) and functioning to
on two or more of the branch circuit upplied b_ the control the motor(s) connected to that branch circuit
feeder, one of the protective devices shall be considered shall be protected against overcurrent in accordance
the largest for the above calculations. with 4.30.6.2. Such a tapped control circuit shall not be
Exception No. 1: Where one or more instantaneous considered to be a branch circuit and shall be permitted
trip circuit breakers or motor short-circuit p rotectors to be protected by either a supplementary or branch-
are used for motor branch-circuit short-circuit and circuit overcurrent protective device(s). A motor control
ground-fault protection as permitted in 4.30.4.2(c), circuit other than such a tapped control circuit shall
the procedure provided above for determining the be protected against overcurrent in accordance with
maximum rating of the feeder protective device shall 7.25.2.3 or the notes to Table 10.1.1.ll(A) and Table
apply with the following provision: For the purpose of 10.1. 1.11 (B) as applicable.
the calculation, each instantaneous trip circuit breaker (B) Conductor Protection. The overcurrent protection
or motor short-circuit protector shall be assumed to for conductors shall be provided as specified in
have a rating not exceeding the max.imum p ercentage 4.30.6.2(B)(l) or (B)(2) .
of motor full-load current permitted by Tab le 4.30.4.2
for the type offeeder protective device employed. Exception No. 1: Where the opening of the control
circuit would create a hazard asJor example, the control
Exception No. 2: Where the feeder overcurrent circuit of a fire pump motor, and the like, conductors
protective device also provides overcurrent protection of control circuits shall require only short-circuit and
for a motor control center, the provisions of 4.30.8.3 ground-fault protection and shall be permitted to be
shall apply. protected by the motor branch-circuit short-circuit and
FPN: See Appendix D, Examples D9 and DIO. ground-fault protective device(s) .

358
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Exception No . 2: Conductors supplied by the secondary (VA) and that are an integral part of the motor
side of a single-phase transformer having only a two- controller and located within the motor controller
wire (single-voltage) secondary shall be permitted to enclosure shall be permitted to be protected by
be protected by overcurrent protection provided on primary overcunent devices, impedance limiting
the primary (supply) side of the transformer, provided means, or other inherent protective means.
this protection does not exceed the value determined
(4) Primary Less Than 2 Amperes. Where the
by multipZying the appropriate maximum rating of the control circuit transformer rated primary current
overcurrent device for the secondary conductor from is less than 2 amperes, an overcunent device
Table 4.30.6.2(B) by the secondary-to-prima,y voltage rated or set at not more than 500 percent of the
ratio. Transformer secondary conductors (other than rated primary current shall be permitted in the
two-wire) shall not be considered to be protected by the primary circuit.
primary overcurrent protection.
(5) Other Means. Protection shall be permitted to be
(1) Separate Overcurrent Protection. Where the provided by other approved means.
motor branch-circuit short-circuit and ground-
fault protective device does not provide protection 4.30.6.3 Protection of Conductors from Physical
in accordance with 4.30.6.2(B)(2), separate Damage. Where damage to a motor control circuit
overcurrent protection shall be provided. The would constitute a hazard, all conductors of such a
overcurrent protection shall not exceed the values remote motor control circuit that are outside the control
specified in Column A of Table 4.30.6.2(B). device itself shall be installed in a raceway or be
otherwise protected from physical damage.
(2) Branch-Circuit Overcurrent Protective
Device. Conductors shall be permitted to be 4.30.6.4 Electrical Arrangement of Control Circuits.
protected by the motor branch-circuit short- Where one conductor of the motor control circuit is
circuit and ground-fault protective device and grounded, the motor control circuit shall be ananged
shall require only short-circuit and ground-fault so tbat a ground fault in the control circuit remote from
the motor controller will (1) not start the motor and
protection. Where the conductors do not extend
(2) not bypass manually operated shutdown devices or
beyond the motor control equipment enclosure,
automatic safety shutdown devices.
the rating of the protective device(s) shall not
exceed the value specified in Column B of Table 4.30.6.5 Disconnection.
4.30.6.2(B). Where the conductors extend beyond
(A) General. Motor control circuits shall be arranged
the motor control equipment enclosure, the rating
so that they will be disconnected from all sources of
of the protective device(s) shall not exceed the
supply when the disconnecting means is in the open
\·alue pecified in Column C of Table 4.30.6.2(B).
position. The disconnecting means shall be permitted
(q Control Circuit Transformer. Where a motor to consist of two or more separate devices, one of
which disconnects the motor and the controller from
the source(s) of power supply for the motor, and the
other(s), the motor control circuit(s) from its power
supply. Where separate de ·ices are used, they shall be
Exception: Overcurrem protecrion shall be omif1ed
located immediately adjacent to each other.
ld zere 1he ope1 ii a of he comrol c ·rcui ·w ould crea-e a
ha:::ard asJor e,ample, the comrol iri uit ofafire pump Exception 7\o. 1: Where more than 12 motor control
motor and rhe like. circuit conductors are required to be disconnected, the
disconnecting means shall be permitted to be located
(1) Compliance ~ith Article .25. \\ bere the other than immediately adjacent to each other where all
transformer upplies a Class 1 power-limited
of the following conditions are complied with:
cir uit, Cla s ~, or Clas "' remote-control circuit
complying \.,,·ith the requirements of Article 7.25, (a) Access to energized parts is limited to qualified
protection shall compl) ,, ith Article 7 .25. persons in accordance with Part 4.30.12 of this
article.
(2) Compliance with Article 4.50. Protection shall
be permitted to be provided in accordance with (b) A warning sign is permanently located on the
4.50.1.3. outside ofeach equipment enclosure door or cover
permitting access to the live parts in the motor
(3) Less Than 50 Volt-Amperes. Control circuit
control circuit(s), warning that motor control
transformers rated less than 50 volt-amperes

359
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Table 4.30.6.2(B) Maximum Rating of Overcurrent Protective Device in Amperes
Protection Provided by Motor Branch-Circuit Protective Device(s)
Column A Separate Protection Column B Conductors Within Column C Conductors Extend
Control Circuit Provided Enclosure Beyond Enclosure
Conductor Size Aluminum or Copper-Clad Aluminum or Copper-Clad Aluminum or Copper-Clad
[mm 2 (mm dia.)J Copper Aluminum Copper Aluminum Copper Aluminum
I
0.75 (1.0)
1.25 (1.2)
7
10
25
40
7
10
I
2.0 (1.6) (Note 1) 100 45
3.5 (2.0) (Note 1) (Note 1) 120 100 60 45
5.5 (2.6) (Note I) (Note 1) 160 140 90 75
Larger than 10 (Note !) (Note !) (Note 2) (Note 2) (Note 3) (Note 3)
Notes:
1. Value specified in 3.10.2.6 as applicable.
2. 400 percent of value specified in Table 3.10.2.6(B )(l 7) for 60°C conductors.
3. 300 percent of value specified in Table 3.I0.2.6(B)(I6) for 60°C conductors.

circuit disconnecting means are remotely located 4.30.7.2 Controller Design.


and specifying the location and identification
(A) Starting and Stopping. Each controller shall be
of each disconnect. Where energized parts are
capable of starting and stopping the motor it controls
not in an equipment enclosure as p ermitted b;
and shall be capable of interrupting the locked-rotor
4.30.12.2 and 4.30.12.3, an additional warning cmTent of the motor.
sign(s) shall be located where visible to persons
who may be working in the area of the energized (B) Autotransformer. An autotransformer starter shall
parts. provide an "off" position, a running position, and at
least one starting position. It shall be designed so that
Exception No. 2: The motor control circuit it cannot rest in the starting position or in any position
disconnecting means shall be p ermitted to be remote that will render the overload device in the circuit
from the motor controller power supply disconnecting inoperative.
means where the opening of one or more motor control
circuit disconnecting means is capable of resulting in (C) Rheostats. Rheostats shall be in compliance with
potentially unsafe conditions for personnel or prop erty the following:
and the conditions of items (a) and (b) ofException o. (1) Motor-starting rheostats shall be designed so that
1 are complied with. the contact arm cannot be left on intermediate
(B) Control Transformer in Controller Enclosure. segments. The point or plate on which the arm
Where a transformer or other device is used to obtain rests when in the starting position shall have no
a reduced voltage for the motor control circuit and is electrical connection with the resistor.
located in the controller enclosure, such transformer or (2) Motor-starting rheostats for de motors operated
other device shall be connected to the load side of the from a constant voltage supply shall be equipped
disconnecting means for the motor control circuit. with automatic devices that will interrupt the
4.30.7 Motor Controllers supply before the speed of the motor has fallen to
less than one-third its normal rate.
4.30.7.1 General. Part 4.30.7 is intended to require
suitable controllers for all motors. 4.30.7.3 Ratings. The controller shall have a rating as
specified in 4.30 .7.3(A), unless otherwise permitted
(A) Stationary Motor of 'l'8 Horsepower or Less. For in 4.30 .7.3(B) or (C), or as specified in (D), under the
a stationary motor rated at \18 hp or less that is normally
conditions specified.
left running and is constructed so that it cannot be
damaged by overload or failure to start, such as clock (A) General.
motors and the like, the branch-circuit disconnecting
means shall be permitted to serve as the controller. (1) Horsepower Ratings. Controllers, other than
inverse time circuit breakers and molded ca e
(B) Portable Motor of Y3 Horsepower or Less. For a switches, shall have horsepower ratings at the
portable motor rated at 1/3 hp or less, the controller shall
application voltage not lower than the horsepower
be permitted to be an attachment plug and receptacle or
rating of the motor.
cord connector.

360
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
(2) Circuit Breaker. A branch-circuit inverse time 4.30.7.5 In Grounded Conductors. One pole of the
circuit breaker rated in amperes shall be permitted controller shall be permitted to be placed ina permanently
as a controller for all motors. Where this circuit grounded conductor, provided the controller is designed
breaker is also used for overload protection, it so that the pole in the grounded conductor cannot be
shall conform to the appropriate provisions of opened without simultaneously opening all conductors
this article governing overload protection. of the circuit.
(3) Molded Case Switch. A molded case switch 4.30.7.7 Number of Motors Served by Each
rated in amperes shall be permitted as a controller Controller. Each motor shall be provided with an
for all motors. individual controller.
(B) Small Motors. Devices as specified in 4.30.7.l(A) Exception No. I: For motors rated I 000 volts or less,
and (B) shall be permitted as a controller. a single controller rated at not less than the equivalent
horsepower, as determined in accordance with
(C) Stationary Motors of 2 Horsepower or Less. For
4.30.9.IO(C)(I), of all the motors in the group shall be
stationary motors rated at 2 hp or less and 300 volts or
permitted to serve the group under any of the following
less, the controller shall be permitted to be either of the
conditions:
following:
(a) Where a number of motors drive several parts
(1) A general-use switch having an ampere rating not of a single machine or piece of apparatus, such
less than twice the full-load current rating of the as metal and woodworking machines, cranes,
motor hoists, and similar apparatus
(2) On ac circuits, a general-use snap switch suitable (b) Where a group of motors is under the protection
only for use on ac (not general-use ac- dc snap of one overcurrent device as permitted in
switches) where the motor full-load current rating 4.30.4.3(A)
is not more than 80 percent of the ampere rating {c) Where a group of motors is located in a single
of the switch room within sight from the controller location
(D) Torque Motors. For torque motors, the controller Exception No. 2: A branch-circuit disconnecting means
shall have a continuous-duty, full-load current rating serving as the controller as allowed in 4.30. 7.1(A) shall
not less than the nameplate current rating of the motor. be permitted to serve more than one motor.
For a motor controller rated in horsepower but not
marked with the foregoing current rating, the equivalent 4.30.7.8 Adjustable-Speed Motors. Adjustable-speed
current rating shall be determined from the horsepower motors that are controlled by means of field regulation
shall be equipped and connected so that they cannot be
rating by using Table 4.30.14.1, Table 4.30.14.2, Table
started under a weakened field.
4.30.14.3, and Table 4.30.14.4.
Exception: Starting under a weakened field shall be
(E) Voltage Rating. A controller with a straight voltage
permitted where the motor is designed for such starting.
rating, for example, 230 volts or 460 volts, shall be
permitted to be applied in a circuit in which the nominal 4.30.7.9 Speed Limitation. Machines of the following
voltage between any two conductors does not exceed types shall be provided with speed-limiting devices or
the controller's voltage rating. A controller with a other speed-limiting means:
slash rating, for example, 115/230 volts or 460Y/265 ( 1) Separately excited de motors
volts, shall only be applied in a solidly grounded
circuit in which the nominal voltage to ground from (2) Series motors
any conductor does not exceed the lower of the two (3) Motor-generators and converters that can be
values of the controller's voltage rating and the nominal driven at excessive speed from the de end, as by a
voltage between any two conductors does not exceed reversal of current or decrease in load
the higher value of the controller's voltage rating.
Exception: Separate speed-limiting devices or means
4.30.7.4 :\"eed :\lot Open All Conductors. The shall not be required under either of the following
controller shall not be required to open all conductors conditions:
to the motor.
(]) Where the inherent characteristics of the
Exception: Where the cont!'oller serves also as a machines, the system, or the load and the
disconnecting means, it shall open all ungrounded mechanical connection thereto are such as to
conductors to the motor as provided in 4.30.9.11. safely limit the speed

361
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
(2) Where the machine is always under the manual 4.30.8.6 Busbars and Conductors.
control ofa qualified operator
(A) Support and Arrangement. Busbars shall be
4.30.7.10 Combination Fuseholder and Switch as protected from physical damage and be held firmly in
Controller. The rating of a combination fuseholder place.
and switch used as a motor controller shall be such that
Other than for required interconnections and control
the fuseholder will accommodate the size of the fuse
wiring, only those conductors that are intended for
specified in Part 4.30.3 for motor overload protection.
tem1ination in a vertical section shall be located in that
Exception: Where fuses having time delay appropriate section.
for the starting characteristics of the motor are used,
Exception: Conductors shall be permitted to travel
fuseholders ofsmaller size than specified in Part 4.30.3
horizontal(v through vertical sections where such
shall be permitted.
conductors are isolated from the busbars by a barrier.
4.30.8 Motor Control Centers
(B) Phase Arrangement. The phase an-angement on
4.30.8.1 General. Part 4.30.8 covers motor control 3-phase horizontal common power and vertical buses
centers installed for the control of motors, lighting, and shall be A, B, C from front to back, top to bottom, or
power circuits. left to right, as viewed from the front of the motor
control center. The B phase shall be that phase having
4.30.8.3 Overcurrent Protection. Motor control the higher voltage to ground on 3-phase, 4-wire, delta-
centers shall be provided with overcun-ent protection connected systems. Other busbar arrangements shall
in accordance with Parts 2.40.1, 2.40.2 and 2.40.8. The be permitted for additions to existing installations and
ampere rating or setting of the overcun-ent protective shall be marked.
device shall not exceed the rating of the common
Exception: Rear-mounted units connected to a vertical
power bus. This protection shall be provided by (1)
bus that is common to front-mounted units shall be
an overcun-ent protective device located ahead of the
permitted to have a C, B, A phase arrangement where
motor control center or (2) a main overcurrent protective
properly identified.
device located within the motor control center.
(C) Minimum Wire-Bending Space. The minimum
4.30.8.4 Service Equipment. Where used as service wire-bending space at the motor control center terminals
equipment, each motor control center shall be provided and minimum gutter space shall be as required in Article
with a single main disconnecting means to disconnect 3.12(D).
all ungrounded service conductors. (D) Spacings. Spacings between motor control center
Exception: A second service disconnect shall be bus terminals and other bare metal parts shall not be
permitted to supply additional equipment. less than specified in Table 4.30.8.6(D).
Where a grounded conductor is provided, the motor (E) Barriers. Barriers shall be placed in all service-
control center shall be provided with a main bonding entrance motor control centers to isolate service busbars
jumper, sized in accordance with 2.50.2.9(D), within and terminals from the remainder of the motor control
one of the sections for connecting the grounded center.
conductor, on its supply side, to the motor control center 4.30.8.7 Marking.
equipment ground bus.
(A) Motor Control Centers. Motor control centers
Exception: High-impedance grounded neutral systems shall be marked according to 110.21 , and the marking
shall be permitted to be connected as provided in shall be plainly visible after installation. Marking shaL
2.50.2.17. also include common power bus current rating and
motor control center short-circuit rating.
4.30.8.5 Grounding. Multisection motor control
centers shall be connected together with an equipment (B) Motor Control Units. Motor control unit in a
grounding conductor or an equivalent equipment motor control center shall comply with 4.30. 1.8.
grounding bus sized in accordance with Table 2.50.6. 13. 4.30.8.8 Available Fault Current. The available short
Equipment grounding conductors shall be connected circuit current at the motor control center and the date
to this equipment grounding bus or to a grounding the short circuit cun-ent calculation was performed shall
termination point provided in a single-section motor be documented and made available to those authorized
control center. to inspect the installation.
362
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Table 4.30.8.6(D) Minimum Spacing Between Bare accordance with 1.10.1.25.
Metal Parts
(B) Motor. A disconnecting means shall be provided
Opposite for a motor in accordance with (B)(l) or (B)(2).
Polarity
Where Opposite (1) Separate Motor Disconnect. A disconnecting
Mounted on Polarity means for the motor shall be located in sight from
the Same Where Held Live Parts the motor location and the driven machinery
Nominal Surface Free in Air to Ground location.
Voltage (mm) (mm) (mm)
Not over 125
(2) Controller Disconnect. The controller
19.l 12.7 12.7 disconnecting means required in accordance with
volts, nominal
Not over250 4.30.9.2(A) shall be permitted to serve as the
31.8 19.1 12.7
volts, nominal disconnecting means for the motor if it is in sight
Not over 600
50.8 25.4 25.4 from the motor location and the driven machinery
volts, nominal
location.
FP : Spacing Standards of IEC is different from NEMN
UL Standards. For more information, refer to appropriate IEC
Exception to (]) and (2): The disconnecting means for
Standards. the motor shall not be required under either condition
(a) or condition (b), which follow, provided that the
4.30.9 Disconnecting Means controller disconnecting means required in 4.30.9.2(A)
4.30.9.1 General. Part 4.30.9 is intended to require is lockable in accordance with 1.10.1.25.
disconnecting means capable of disconnecting motors (a) Where such a location ofthe disconnecting means
and controllers from the circuit. for the motor is impracticable or introduces
4.30.9.2 Location. additional or increased hazards to persons or
property
(A) Controller. An individual disconnecting means
shall be proYided for each controIler and shall disconnect FPN: Some examples of increased or additional hazards
include, but are not limited to, motors rated in excess of
the controller. The disconnecting means shall be located 100 hp, multimotor equipment, submersible motors, motors
in sight from the controller location. associated with adjustable speed drives, and motors located in
hazardous (classified) locations.
Exception So. 1: For motor circuits oi-er 1 000 volts,
nominal, a controller disconnecting means lockable in (b) In industrial installations, with written safety
accordance ·with l.JO.J. _ - shall be permitted to be out procedures, where conditions ofmaintenance and
ofsight ofthe controller. prm·ided rhar ihe controller is supervision ensure that only qualified persons
marked with a warning label giving the location of the service the equipment
disconnecting means. FP~: For information on lockout"tagout procedures, see NFPA
70£ -_0L, Standard for Elecflical Safety in the Workplace.
Exception No. 2: A single disconnecting means shall
be permitted for a group of coordinated controllers 4.30.9.3 Operation. The disconnecting means shall
that drive several parts of a single machine or piece of open all ungrounded supply conductors and shall be
apparatus. The disconnecting means shall be located in designed so that no pole can be operated independently.
sight from the controllers, and both the disconnecting The disconnecting means shall be permitted in the
means and the controllers shall be located in sightJ,-om same enclosure with the controller. The disconnecting
the machine or apparatus. means shall be designed so that it cannot be closed
Exception No. 3: The disconnecting means shall not automatically.
be required to be in sight from valve actuator motor FPN: See 4.30.9.13 for equipment receiving energy from more
(VAM) assemblies containing the controller where such than one source.
a location introduces additional or increased hazards 4.30.9.4 To Be Indicating. The disconnecting means
to p ersons or property and conditions (a) and (b) are shall plainly indicate whether it is in the open (oft) or
met closed (on) position.
(a) The valve actuator motor assembly is marked
with a warning label giving the location of the 4.30.9.5 Grounded Conductors. One pole of the
disconnecting means. disconnecting means shall be permitted to disconnect
a permanently grounded conductor, provided the
(a) The disconnecting means is lockable in disconnecting means is designed so that the pole in

363
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
the grounded conductor cannot be opened without (B) Stationary Motors of 'l8 Horsepower or Less. For
simultaneously disconnecting all conductors of the stationary motors of 1!8 hp or less, the branch-circuit
circuit. over-current device shall be permitted to serve as the
disconnecting means.
4.30.9.7 Readily Accessible. At least one of the
disconnecting means shall be readily accessible. (C) Stationary Motors of 2 Horsepower or Less. For
stationary motors rated at 2 hp or less and 300 volts or
4.30.9.8 Every Disconnecting Means. Every
less, the disconnecting means shall be permitted to be
disconnecting means in the motor circuit between the
one of the devices specified in (1), (2), or (3):
point of attachment to the feeder or branch circuit and
the point of connection to the motor shall comply with (1) A general-use switch having an ampere rating not
the requirements of 4.30.9.9 and 4.30.9.10. less than twice the full-load current rating of the
motor
4.30.9.9 Type. The discom1ecting means shall be a type
(2) On ac circuits, a general-use snap switch suitable
specified in 4.30.9.9(A), unless otherwise permitted in
only for use on ac (not general-use ac-dc snap
4.30.9.9(B) through (G), under the conditions specified.
switches) where the motor full-load current rating
(A) General. is not more than 80 percent of the ampere rating
of the switch
(1) Motor Circuit Switch. A listed motor-circuit
switch rated in horsepower. (3) A listed manual motor controller having a
horsepower rating not less than the rating of
(2) Molded Case Circuit Breaker. A listed molded the motor and marked "Suitable as Motor
case circuit breaker. Disconnect"
(3) Molded Case Switch. A listed molded case (D) Autotransformer-Type Controlled Motors.
switch. For motors of over 2 hp to and including 100 hp, the
(4) Instantaneous Trip Circuit Breaker. An separate di connecting means required for a motor with
instantaneous trip circuit breaker that is part of a an auto-transformer type controller shall be permitted
listed combination motor controller. to be a general-use sv, itch where all of the following
proYisions are met:
(5) Self-Protected Combination Controller. Listed
self-protected combination controller. (1) The motor driYe a generator that is provided
\\i th oYerload rotection.
(6) Manual Motor Controller. Listed manual
motor controllers additionally marked "Suitable (- ) The control i- capable of interrupting the
as Motor Disconnect" shall be permitted as a lo ked-ro or curren of the mornr-. is proYided
disconnecting means where installed between with a no rn rage rele . .,._ and i proYided \Yith
the final motor branch-circuit short-circuit running oYerload protection no~ exceeding 125
protective device and the motor. Listed manual percent of the motor ful -load current rating.
motor controllers additionally marked "Suitable C) eparare fu e or an inYerse time circuit breaker
as Motor Disconnect" shall be permitted as rated or -er at not more than 150 percent of the
disconnecting means on the line side of the fuses motor full-load current is provided in the motor
permitted in 4.30.4.2(C)(5). In this case, the fuses branch circuit.
permitted in 4.30.4.2(C)(5) shall be considered
supplementary fuses, and suitable branch-circuit (E) Isolating Switches. For stationary motors rated
short-circuit and ground-fault protective devices at more than 40 hp de or 100 hp ac, the disconnecting
shall be installed on the line side of the manual means shall be permitted to be a general-use or isolating
motor controller additionally marked "Suitable as switch where plainly marked "Do not operate under
Motor Disconnect." load."

(7) System Isolation Equipment. System isolation (F) Cord-and-Plug-Connected Motors. For a
equipment shall be listed for disconnection cord-andplug-connected motor, a horsepower-rated
purposes. System isolation equipment shall attachment plug and receptacle, flanged surface inlet
be installed on the load side of the overcurrent and cord connector, or attachment plug and cord
protection and its disconnecting means. The connector having ratings no less than the motor ratings
disconnecting means shall be one of the types shall be permitted to serve as the disconnecting means.
permitted by 4.30.9.9(A)(l) through (A)(3). Horsepower-rated attachment plugs, flanged surface
inlets, receptacles, or cord connectors shall not be

364
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
required for cord-and-plug-connected appliances in motors that can be started simultaneously and the
accordance with 4.22.3.4, room air conditioners in full-load currents of other concurrent loads shall
accordance with 4.40.7.4, or portable motors rated Y.3 be pennitted to be used to determine the equivalent
hp or less. locked-rotor current for the simultaneous
combined loads. In cases where different current
(G) Torque Motors. For torque motors, the
ratings are obtained when applying these tables,
disconnecting means shall be permitted to be a general-
the largest value obtained shall be used.
use switch.
Exception: Where part of the concurrent load is
4.30.9.10 Ampere Rating and Interrupting Capacity.
resistance load, and where the disconnecting means is
(A) General. The disconnecting means for motor a switch rated in horsepower and amperes, the switch
circuits rated 1000 volts, nominal, or less shall have an used shall be permitted to have a horsepower rating
ampere rating not less than 115 percent of the full-load that is not less than the combined load of the motor(s),
current rating of the motor. if the ampere rating of the switch is not less than the
locked-rotor current of the motor(s) plus the resistance
Exception: A listed unfused motor-circuit switch having
load.
a horsepower rating not less than the motor horsepower
shall be permitted to have an ampere rating less than (2) Ampere Rating. The ampere rating of the
115 percent of the full-load current rating of the motor. disconnecting means shall not be less than 115
percent of the sum of all currents at the full-
(B) For Torque Motors. Disconnecting means for a
load condition determined in accordance with
torque motor shall have an ampere rating of at least 115
4.30.9. lO(C)(l).
percent of the motor nameplate current.
(C) For Combination Loads. Where two or more Exception: A listed nonfused motor-circuit Slvitch
motors are used together or where one or more motors having a horsepower rating equal to or greater than
are used in combination with other loads, such as the equivalent horsepower of the combined loads,
resistance heaters, and where the combined load may determined in accordance with 4.30.9.JO(C)(J), shall
be simultaneous on a single disconnecting means, the be permitted to have an ampere rating less than 115
ampere and horsepower ratings of the combined load percent of the sum of all currents at the full-load
shall be determined as follows. condition.

(1) Horsepower Rating. The rating of the (3) Small Motors. For small motors not covered by
disconnecting means shall be detennined from Table 4.30.14.1, Table 4.30.14.2, Table 4 .30.14.3,
the sum of all currents, including resistance and Table 4.30.14.4, the locked-rotor current shall
loads, at the full-load condition and also at the be assumed to be six times the full-load current.
locked-rotor condition. The combined full-load
current and the combined locked-rotor current so 4.30.9.11 Switch or Circuit Breaker as Both
obtained hall be considered as a single motor for Controller and Disconnecting Means. A switch or
the purpose ofthi requirement as follo-ws. circuit breaker shall be permitted to be used as both
the controller and disconnecting means if it complies
The full-load current equinlent to the horsepO\ er
with 4.30.9.ll (A) and is one of the types specified in
rating of each motor shall be elected from Table
4.30.9. l l (B).
4.30.14.1 , Table 4.30. 14.2, Table 4.30.14.3, and
Table 4.30.14.4. These full-load currents shall (A) General. The switch or circuit breaker complies
be added to the rating in amperes of other loads with the requirements for controllers specified in
to obtain an equivalent full-load current for the 4.30.7.3, opens all ungrounded conductors to the
combined load. motor, and is protected by an overcurrent device in
each ungrounded conductor (which shall be permitted
The locked-rotor current equivalent to the
to be the branch-circuit fuses). The overcurrent device
horsepower rating of each motor shall be selected
protecting the controller shall be permitted to be part
from Table 4.30.14.S(A) or Table 4.30.14.S(B).
of the controller assembly or shall be permitted to be
The locked-rotor currents shall be added to the
separate. An autotransformer-type controller shall be
rating in amperes of other loads to obtain an
provided with a separate disconnecting means.
equivalent locked-rotor current for the combined
load. Where two or more motors or other loads (B) Type. The device shall be one of the types specified
cannot be started simultaneously, the largest sum in 4.30.9 .11 (B)(l ), (B)(2), or (B)(3).
of locked-rotor currents of a motor or group of
365
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
(1) Air-Break Switch. An air-break switch, operable
directly by applying the hand to a lever or handle. 4.30.10 Adjustable-Speed Drive Systems
(2) Inverse Time Circuit Breaker. An inverse time 4.30.10.1 General. The installation provisions of
circuit breaker operable directly by applying the Part 4.30.1 through Part 4.30.9 are applicable unless
hand to a lever or handle. The circuit breaker modified or supplemented by Part 4.30.10.
shall be permitted to be both power and manually
4.30.10.3 Conductors - Minimum Size and
operable.
Ampacity.
(3) Oil Switch. An oil switch used on a circuit
(A) Branch/Feeder Circuit Conductors. Circuit
whose rating does not exceed 1000 volts or 100
conductors supplying power conversion equipment
amperes. The oil switch shall be permitted to be
included as part of an adjustable-speed drive system
both power and manually operable.
shall have an ampacity not less than 125 percent of the
rated input cun-ent to the power conversion equipment.
4.30.9.12 Motors Served by Single Disconnecting
Means. Each motor shall be provided with an individual FPN: Power conversion equipment can have multiple power
ratings and corresponding input currents.
disconnecting means.
(B) Bypass Device. For an adjustable-speed drive
Exception: A single disconnecting means shall be
system that utilizes a bypass device, the conductor
permitted to serve a group ofmotors under any one ofthe
ampacity shall not be less than required by 4.30.1.6.
conditions of (a), (b), and (c) . The single disconnecting
The ampacity of circuit conductors supplying power
means shall be rated in accordance with 4.30.9.JO(C).
conversion equipment included as part of an adjustable-
(a) Where a number of motors drive several parts of speed drive system that utilizes a bypass device shall be
a single machine or piece of apparatus, such as the larger of either of the following:
metal- and woodworking machines cranes, and
( 1) 125 percent of the rated input current to the power
hoists.
conversion equipment
(b) Where a group of motors is under the protection
(2) 125 percent of the motor full-load current rating
of one set of branch-circuit protectfre devices as
as determined by 4.30.1.6
permitted by 4.30.4.3(A).
4.30.10.5 Overload Protection. Overload protection of
(c) Where a group of motors is in a single room the motor shall be provided.
within sight from the location ofthe disconnecting
means. (A) Included in Power Conversion Equipment.
Where the power conversion equipment is marked to
indicate that motor overload protection is included,
4.30.9.13 Energy from More Than One Source.
additional overload protection shall not be required.
Motor and motor-operated equipment receiving electric
energy from more than one source shall be provided (B) Bypass Circuits. For adjustable-speed drive
with disconnecting means from each source of electric systems that utilize a bypass device to allow motor
energy immediately adjacent to the equipment served. operation at rated full-load speed, motor overload
protection as described in Part 4.30.3 shall be provided
Each source shall be permitted to have a separate
in the bypass circuit.
disconnecting means. Where multiple disconnecting
means are provided, a permanent warning sign shall be (C) Multiple Motor Applications. For multiple motor
provided on or adjacent to each disconnecting means. application, individual motor overload protection shall
be provided in accordance with Part 4.30.3 .
Exception No. 1: Where a motor receives electric
4.30.10.7 Motor Overtemperature Protection.
energy from more than one source, the disconnecting
means for the main power supply to the motor shall not (A) General. Adjustable-speed drive systems shall
be required to be immediately adjacent to the motor, protect against motor over temperature conditions where
provided that the controller disconnecting means is the motor is not rated to operate at the nameplate rated
current over the speed range required by the application.
lockable in accordance with 1.10.1.25.
This protection shall be provided in addition to the
Exception No. 2: A separate disconnecting means shall conductor protection required in 4.30.3.2. Protection
not be required for a Class 2 remote-control circuit shall be provided by one of the following means.
conforming with Article 7.25, rated not more than 30 (1) Motor thermal protector in accordance with
volts, and isolated and ungrounded. 4.30.3.2

366
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
(2) Adjustable-speed drive system with load and ( 1) The rating and type of protection shall be
speed-sensitive overload protection and thermal determined by 4.30.4.2(C)(l), (C)(3), (C)(S), or
memory retention upon shutdown or power loss (C)(6), using the full-load current rating of the
motor load as determined by 4.30.1.6.
Exception to (2): Thermal memory retention upon
shutdown or power loss is not required for continuous (2) Where maximum branch-circuit short-circuit and
duty loads. ground-fault protective ratings are stipulated
(1) Over temperature protection relay utilizing for specific device types in the manufacturer's
thermal sensors embedded in the motor and instructions for the power conversion
meeting the requirements of 4.30.3.2(A)(2) or equipment or are otherwise marked on the
(B)(2) equipment, they shall not be exceeded even if
higher values are permitted by 4.30.10.lO(A)
(2) Thermal sensor embedded in the motor whose
communications are received and acted upon by (1).
an adjustable-speed drive system (3) A self-protected combination controller shall
FPN: The relationship between motor current and motor only be pennitted where specifically identified
temperature changes when the motor is operated by an adjustable- in the manufacturer's instructions for the power
speed drive. In certain applications, overheating of motors can
occur when operated at reduced speed, even at current levels less
conversion equipment or if otherwise marked on
than a motor's rated full-load current. The overheating can be the the equipment.
result of reduced motor cooling when its shaft-mounted fan is
FPN: The type of proteciive device, its rating, and its setting
operating less than rated nameplate RPM. As part of the analysis
are often marked on or provided with the power conversion
to determine whether overheating will occur, it is necessary to
consider the continuous torque capability curves for the motor equipment.
given the application requirements. This will assist in determining
whether the motor overload protection will be able, on its own,
( 1) Where an instantaneous hip circuit breaker or
to provide protection against overheating. These overheating semiconductor fuses are permitted in accordance
protection requirements are only intended to apply to applications with the drive manufacturer 's instructions for use
where an adjustable-speed drive, as defined in Article 1.1, is used.
as the branch-circuit short-circuit and ground-
For motors that utilize external forced air or liquid cooling fault protective device for listed power conversion
ysterns, over temperature can occur if the cooling system is not
operating. Although thi issue is not unique to adjustable speed
equipment, they shall be provided as an integral
app icario , externally cooled motors are most often encountered part of a single listed assembly incorporating
with su h appli ations. In the e instance , over temperature both the protectfre de\'ice and power conversion
prorecrion using dir r temp rature sensing is recommended [i.e ..
-U O. 0.7(A)(I ).lA.)( 3 . or (..\)(4) . or adclitional mean hould be
equipment.
prO\;ded IO ensure that - e oo · g sys em is operating ( ow or
(B) Bypass Circuit/De,ice. Branch-circuit short-
pressur ensing. inter! king of adj table- ed dri,·e . · em
and cooling ysrem. etc.). circuit and ground-fault protection shall also be
prO\ided for a bypa s circuit'device(s). Where a single
(B) Multiple :Motor Applications. For multiple branch-circuit hart- ircuit and ground-fault protective
motor applications, individual motor o er temperature de, i ce is prO\ided for circuits contammg both
protection shall be provided as required in 4.30.10.7(A) . power com:er ion equipment and a bypass circuit,
(C) Automatic Restarting and Orderly Shutdown. the branch-circuit protective device type and its
The provisions of 4.30.3.13 and4.30.3.14 shall apply to rating or setting shall be in accordance with those
the motor over temperature protection means. determined for the power conversion equipment and
for the bypass circui device(s) equipment.
4.30.10.9 Disconnecting Means. The disconnecting
means shall be permitted to be in the incoming line to 4.30.10.11 Several Motors or Loads on One Branch
the conversion equipment and shall have a rating not Circuit Including Power Conversion Equipment.
less than 115 percent of the rated input cmTent of the For installations meeting all the requirements of
conversion unit. 4.30.4.3 that include one or more power converters,
4.30.10.10 Branch-Circuit Short-Circuit and the branch-circuit short- circuit and ground-fault
Ground-Fault Protection for Single Motor Circuits protective fuses or inverse time circuit breakers
Containing Power Conversion Equipment. shall be of a type and rating or setting permitted
(A) Circuits Containing Power Conversion for use with the power conversion equipment using
Equipment. Circuits containing power conversion the full-load current rating of the connected motor
equipment shall be protected by a branch-circuit short- load in accordance with 4.30.4.3. For the purposes of
circuit and ground-fault protective device in accordance 4.30.4.3 and 4.30.10.11, power conversion equipment
with the following: shall be considered to be a motor controller.

367

L
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
4.30.11 Over 1000 Volts, Nominal (a) A circuit breaker of suitable type and ratin~
arranged so that it can be serviced witho :
4.30.11.1 General. Part 4.30 .11 recognizes the
additional hazard due to the use of higher voltages. It hazard. The circuit breaker shall simultaneou Y
adds to or amends the other provisions of this article. disconnect all ungrounded conductors. The
circuit breaker shall be permitted to sense the
4.30.11.2 Marking on Controllers. In addition to the fault current by means of integral or external
marking required by 4.30.1.8, a controller shall be sensing elements.
marked with the control voltage.
(b) Fuses of a suitable type and rating placed in
4.30.11.3 Raceway Connection to Motors. Flexible
metal conduit or liquidtight flexible metal conduit not each ungrounded conductor. Fuses shall be
exceeding 1 800 mm in length shall be permitted to be used with suitable disconnecting means, or
employed for raceway connection to a motor terminal they shall be of a type that can also serve as the
enclosure. disconnecting means. They shall be arranged
so that they cannot be serviced while they are
4.30.11.4 Size of Conductors. Conductors supplying
motors shall have an ampacity not less than the current energized.
at which the motor overload protective device(s) is (2) Reclosing. Fault-current interrupting devices
selected to trip. shall not automatically reclose the circuit.
4.30.11.5 Motor-Circuit Overcurrent Protection. Exception: Automatic reclosing of a circuit shall be
(A) General. Each motor circuit shall include permitted where the circuit is exposed to transient faults
coordinated protection to automatically interrupt and where such automatic reclosing does not create a
overload and fault currents in the motor, the motor- hazard to persons.
circuit conductors, and the motor control apparatus.
(3) Combination Protection. Overload protection
Exception: Where a motor is critical to an operation and fault-current protection shall be permitted to
and the motor should operate to failure if necessary be provided by the same device.
to prevent a greater hazard to persons, the sensing
device(s) shall be permitted to be connected to a 4.30.11.6 Rating of Motor Control Apparatus. The
supervised annunciator or alarm instead ofinterrupting ultimate trip current of overcurrent (overload) relays or
the motor circuit. other motor-protective devices used shall not exceed
115 percent of the controller 's continuous current
(B) Overload Protection. rating. Where the motor branch-circuit disconnecting
(1) Type of Overload Device. Each motor shall means is separate from the controller, the disconnecting
be protected against dangerous heating due to means current rating shall not be less than the ultimate
motor overloads and failure to start by a thermal trip setting of the overcurrent relays in the circuit.
protector integral with the motor or external 4.30.11.7 Disconnecting Means. The controller
current-sensing devices, or both. Protective disconnecting means shall be lockable in accordance
device settings for each motor circuit shall be with 1.10.1.25.
determined under engineering supervision.
4.30.12 Protection of Live Parts -All Voltages
(2) Wound-Rotor Alternating-Current Motors.
The secondary circuits of wound-rotor ac motors, 4.30.12.1 General. Part 4.30.12 specifies that live parts
including conductors, controllers, and resistors shall be protected in an approved manner for the hazard
rated for the application, shall be considered involved.
as protected against overcurrent by the motor 4.30.12.2 Where Required. Exposed live pai1s of
overload protection means. motors and controllers operating at 50 volts or more
(3) Operation. Operation ofthe overload interrupting between terminals shall be guarded against accidental
device shall simultaneously disconnect all contact by enclosure or by location as follows :
ungrounded conductors.
(1) By installation in a room or enclosure that is
(4) Automatic Reset. Overload sensing devices shall accessible only to qualified persons
not automatically reset after trip unless resetting
of the overload sensing device does not cause (2) By installation on a suitable balcony, gallery, or
automatic restarting of the motor or there is no platform, elevated and arranged so as to exclude
hazard to persons created by automatic restarting unqualified persons
of the motor and its connected machinery.
(3) By elevation 2500 mm or more above the floor
(C) Fault-Current Protection.
Exception: Live parts ofmotors operating at more than
(1) Type of Protection. Fault-current protection shall
50 volts between terminals shall not require additim ·
be provided in each motor circuit as specified by
either (l)(a) or (l)(b). guarding for stationary motors that have commuw or.:.

368
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
collectors, and brush rigging located inside of motor- 4.30.13.4 Controllers. Controller enclosures shall
end brackets and not conductively connected to supply be connected to the equipment grounding conductor
circuits operating at more than 150 volts to ground regardless of voltage. Controller enclosures shall have
means for attachment of an equipment grounding
4.30.12.3 Guards for Attendants. Where live parts of conductor termination in accordance with 2.50.1.8.
motors or controllers operating at over 50 volts to ground Exception: Enclosures attached to ungrounded portable
are guarded against accidental contact only by location equipment shall not be required to be grounded.
as specified in 4 .30.12.2, and where adjustment or other 4.30.13.5 Method of Grounding. Connection to the
attendance may be necessary during the operation of the equipment grounding conductor shall be done in the
apparatus, suitable insulating mats or platforms shall be manner specified in Part 2.50.6.
provided so that the attendant cannot readily touch live
(A) Grounding Through Terminal Housings. Where
parts unless standing on the mats or platforms. the wiring to motors is metal-enclosed cable or in metal
FPN: For working space, see 1.10.2.1 and 1.10.3.5. raceways,junction boxes to house motor terminals shall
be provided, and the armor of the cable or the metal
4.30.13 Grounding -All Voltages raceways shall be connected to them in the manner
specified in 2.50.5.7(A) and 2.50.5.8.
4.30.13.1 General. Part 4.30.13 specifies the grounding
of exposed non-current-carrying metal parts, likely to (B) Separation of Junction Box from Motor. The
junction box required by 4.30.13.5(a) shall be permitted
become energized, of motor and controller frames to
to be separated from the motor by not more than 1800
prevent a voltage aboveground in the event of accidental mm, pro, ided the leads to the motor are stranded
contact between energized parts and frames. Insulation, conductors within Type AC cable, interlocked metal
isolation, or guarding are suitable alternatives to tape Type MC cable where listed and identified in
grounding of motors under certain conditions. accordance with 2.50.6.9(1 O)(a), or armored cord or
are stranded leads enclosed in liquidtight flexible metal
4.30.13.2 Stationary Motors. The frames of stationary conduit, flexible metal conduit, intermediate metal
motors shall be grounded under any of the following conduit rigid metal conduit, or electrical metallic
conditions: tubing not smaller than metric designator 12, the armor
or racewav bein2: connected both to the motor and to
(1) Where supplied by metal-enclosed wiring the box. · -
(2) Where in a wet location and not isolated or Liquidtight flexible nonmetallic conduit and rigid
guarded nonme allic conduit shall be permitted to enclose the
leads to the motor, provided the leads are stranded
(3) If in a hazardous ( classified) location and the required equipment grounding conductor is
(4) If the motor operates with any terminal at 01,.·er connected to both the motor and to the box.
150 volts to ground Where tranded leads are used, protected as specified
Where the frame of the motor is not grounded, it shall be a ove. each strand within the conductor shall be
o larger than 5.5 rnm2 and shall comply with other
permanently and effectively insulated from the ground.
re uirements of this Code for conductors to be used in
4.30.13.3 Portable Motors. The frames of ponable
motors that operate over 150 volts to ground shall b {C) Grounding of Controller-Mounted Devices.
guarded or grounded. Instrument transformer secondaries and exposed non-
FPN No. 1: See 2.50.6.5(4) for grounding of ponable a i m: · curremcarrying metal or other conductive parts or
in other than residential occupancie . cases of instrument transformers, meters, instruments,
and relays shall be grounded as specified in 2.50.9.1
FPN No. 2: See 2.50.6.1 O(C) for color of e i men· ::: 0 1 nding
through 2.50.9.9.
conductor.

Exception No. 1: Listed motor-operaied tools, listed


motor-operated appliances, and listed motor-operated
equipment shall not be required to be grounded
where protected b_v a s_vstem of double insulation or
its equivalent. Double-insulated equipment shall be
distinctively marked.
Exception o. 2: Listed motor-operated tools, listed
motor-operated appliances, and listed motor-operated
equipment connected by a cord and attachment plug
other than those required to be grounded in accordance
w ith 2.50.6.5.

369
ARTICLE 4.30 - MOTORS , MOTOR CIRCUITS AND CONTROLLERS
4.30.14 Tables
Table 4.30.14.1 Full-Load Current in Amperes, Direct-Current Motors
The following values of full-load cu1Tents· are for motors running at base speed.

Armature Voltage Rating 1


Horsepower 90 Volts 115 Volts 180 Volts 230 Volts 500 Volts 550 Volts
1/4 4.0 3. 1 2.0 1.6 - -

1/ 3 5.2 4. 1 2.6 2.0 - -


1/2 6.8 5.4 3.4 2.7 - -
3/4 9.6 7.6 4.8 3.8 - 1.6
1 12.2 9.5 6.1 4.7 - 2.0
1 1/2 - 13.2 8.3 6.6 - 2.7
2 - 17 10.8 8.5 - 3.6
3 - 25 16 12.2 - 5.2

5 - 40 27 20 - 8.3
7 1/2 - 58 - 29 13.6 12.2
10 - 76. - 38 18 16
15 - uo· - 55 27 24
20 - 148" - 72 34 31
25 - 184. - 89 43 38
30 - 220· - 106 51 46
40 - 292· - 140 67 61
50 - 360" - 173 83 75
60 - - - 206 99 90
75 - - - 255 123 J 11

100 - - - 341 164 148


125 - - - 425 205 185
150 - - - 506 246 222
200 - - - 675 330 294
inese are average UL quantities.
·Based on UL 508

Table 4.30. 14.2 Full-Load Currents in Amperes, Single-Phase Alternating-Current Motors


The following values of full-load currents are for motors running at usual speeds and motors with normal torque
characteristics. The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage
ranges of 110 to 120 and 220 to 240 volts.
Horsepower US Volts 200 Volts 208 Volts 230 Volts Horsepower 115 Volts 200 Volts 208 Volts 230 Volts
1/6 4.4 2.5 2.4 2.2 I 1/2 20 11.5 11.0 10
1/4 5.8 3.3 3.2 2.9 2 24 13.8 13.2 12
1/3 7.2 4.1 4.0 3.6 3 34 19.6 18.7 17
1/2 9.8 5.6 5.4 4.9 5 56 32.2 30.8 28
3/4 13 .8 7.9 7.6 6.9 7 1/2 80 46.0 44.0 40
1 16 9.2 8.8 8.0 10 100 57.5 55.0 50

370
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Table 4.30.14.3 Full-Load Current, Two-Phase Alternating-Current Motors (4-Wire)
The following values of full-load current are for motors nmning at speeds usual for belted motors and motors with
normal torque characteristics. Current in the common conductor of a 2-phase, 3-wire system will be 1.41 times the value
given. The voltages listed are rated motor voltages. The currents listed shall be pem1itted for system voltage ranges of
110 to 120,220 to 240,440 to 480, and 550 to 600 volts .

Induction-Type Squirrel Cage and Wound Rotor


(Amperes)
Horsepower 11 5 Volts 230 Volts 460 Volts 575 Volts 2300 Volts
1/2 4.0 2.0 1.0 0.8 -
3/4 4.8 2.4 1.2 1.0 -
1 6.4 3.2 l.6 1.3 -
11/2 9.0 4.5 2.3 1.8 -
2 11.8 5.9 3.0 2.4 -
3 - 8.3 4.2 3.3 -
5 - 13.2 6.6 5.3 -
7 1/2 - 19 9.0 8.0 -
10 - 24 12 10 -
15 - 36 18 14 -
20 - 47 23 19 -
25 - 59 29 24 -
30 - 69 35 28 -
40 - 90 45 36 -
50 - 113 56 4- -
60 - 133 67 53 14
r - 166 83 66 18
100 - 218 109 23
L - - 2 0 135 10 28
-o - "1 2 1-6 p_)- 32
_QO - -+ 16 _o 16 43

371
ARTICLE 4.30 - MOTORS, MOTOR CIRCUITS AND CONTROLLERS
Table 4.30.14.4 Full-Load Current, Three-Phase Alternating-Current Motors
The following values of full-load currents are typical for motors running at speeds usual for belted motors and motors
with normal torque characteristics.
The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 t1.:
120,220 to 240,440 to 480, and 550 to 600 volts.
Induction-Type Squirrel Cage and Wound Rotor Synchronous-Type Unity Power
(Amperes) Factor 1 (Amperes)
115 200 208 230 400 460 575 2300 230 460 575 2300
Horsepower Volts Volts Volts Volts Volts Volts Volts Volts Volts Volts Volts Volts
1/2 4.4 2.5 2.4 2.2 1.3 1.1 0.9 - - - - -
3/4 6.4 3.7 3.5 3.2 1.8 1.6 1.3 - - - - -
1 8.4 4.8 4.6 4.2 2.3 2.1 1.7 - - - - -
1 1/2 12.0 6.9 6.6 6.0 3.3 3.0 2.4 - - - - -
2 13.6 7.8 7.5 6.8 4.3 3.4 2.7 - - - - -
3 19.2' 11.0 10.6 9.6 6.1 4.8 3.9 - - - - -
5 30.4' 17.5 16.7 15.2 9.7 7.6 6.1 - - - - -
7 1/2 44.0' 25.3 24.2 22 14 11 9 - - - - -
10 56.0' 32.2 30.8 28 18 14 11 - - - - -
15 84.0' 48.3 46.2 42 27 21 17 - - - - -
20 108.0" 62.1 59.4 54 34 27 22 - - - - -
25 136.0' 78.2 74.8 68 44 34 27 - 53 26 21 -
30 160.0' 92 88 80 51 40 32 - 63 32 26 -
40 208.0' 120 114 104 66 52 41 - 83 41 33 -
50 260.0' 150 143 130 83 65 52 - 104 52 42 -
60 - 177 169 154 103 77 62 16 123 61 49 12
75 - 221 211 192 128 96 7 20 155 78 62 15
100 - 285 273 248 165 124 99 26 202 101 81 20
125 - 359 343 312 208 156 12 - 31 253 126 101 25
150 - 414 396 360 240 180 144 37 302 151 121 30
200 - 552 528 480 320 240 192 49 400 201 161 40
250 - - - 604' 403 302 242 60 - - - -
300 - - - 722" 482 361 289 72 - - - -

350 - - - 828' 560 414 336 83 - - - -


400 - - - 954' 636 477 382 95 - - - -
450 - - - 1030" - 515 412 103 - - - -
500 - - - 1180' 786 590 472 118 - - - -
•ror ~u and ~Upercent power factor, the tigures shall be mult1puea by 1.1 ana 1.25, respecnvely.
'Based on UL 508

Table 4.30.14.S(A) Conversion Table of Single-Phase Locked-Rotor Currents for Selection of Disconnecting
Means and Controllers as Determined from Horsepower and Voltage Rating
For use only with 4.30.9.10, 4.40.1.2, 4.40.5.1 , and 4.55. l .8(C).
Maximum Locked-Rotor Current in Maximum Locked-Rotor Current in
Rated Rated
Amperes, Single Phase Amperes, Single Phase
Horsepower Horsepower
115 Volts 208 Volts 230 Volts 115 Volts 208 Volts 230 Volts
1/2 58.8 32.5 29.4 3 204 113 102
3/4 82.8 45.8 41.4 5 336 186 168
1 96 53 48 7 1/2 480 265 240
1 1/2 120 66 60 10 1000 332 300
2 144 80 72

372
ARTICLE 4.40 - AIR-CONDITIONING AND REFRIGERATING EQUIPMENT
Table 4.30.14.S(B) Conversion Table of Polyphase Design B, C, and D Maximum Locked-Rotor Currents for
Selection of Disconnecting Means and Controllers as Determined from Horsepower and Voltage Rating and
Design Letter
For use only with 4.30.9.10, 4.40.1.2, 4.40.5.1 and 4.55.1.S(C).

Maximum Motor Locked-Rotor Current in Amperes, Two- and Three-Phase,


Design B, C, and D*
Rated 115 Volts 200 Volts 208 Volts 230 Volts 400 Volts 460 Volts 575 Volts
Horsepower B,C,D B,C,D B,C,D B,C,D B,C,D B,C,D B,C,D
1/2 40 23 22.1 20 20 10 8
3/4 50 28.8 27.6 25 20 12.5 10
l 60 34.5 33 30 20 15 12
1 1/2 80 46 44 40 27 20 16
2 100 57.5 55 50 34 25 20
"I
.:, 128 73.6 71 64 43 32 25.6
5 184 105.8 102 92 61 46 36.8
7 1/2 254 146 140 127 84 63.5 50.8
10 324 186.3 179 162 107 81 64.8
15 464 267 257 232 154 116 93
20 580 334 321 290 194 145 116
25 730 420 404 365 243 183 146
30 870 500 481 435 289 218 174
40 1160 667 641 580 387 290 232
50 1450 834 802 725 482 363 290
60 - 1001 962 870 578 435 348
75 - 1248 1200 1085 722 543 434
100 - 1668 1603 1450 965 725 580
125 - 2087 2007 1815 1207 908 726
150 - 2496 2400 2170 1441 1085 868
200 - 3335 3207 2900 1927 1450 1160
250 - - - 3650 - 1825 1460
300 - - - 4400 - 2200 1760
350 - - - 5100 - 2550 2040
400 - - - 5800 - 2900 2320
450 - - - 6500 - 3250 2600
500 - - - 7250 - 3625 2900
*Design A motors are not hm1ted to a maxunum starting current or locked rotor current.

ARTICLE 4.40 -AIR-CONDITIONING AND


REFRIGERATING EQUIPMENT .
4.40.1.1 Scope. The provisions of this article
apply to electric motor-driven air-conditioning and
refrigerating equipment and to the branch circuits and
controllers for such equipment. It provides for the
special considerations necessary for circuits supplying
hermetic refrigerant motor-compressors and for any air-
conditioning or refrigerating equipment that is supplied
from a branch circuit that supplies a hermetic refrigerant
motor-compressor.

373
ARTICLE 4.40 - AIR-CONDITIONING AND REFRIGERATING EQUIPME T
4.40.1.2 Definitions. Table 4.40.1.3(D) Other Articles
Branch-Circuit Selection Current. The value in Equipment/Occupancy Article Section
amperes to be used instead of the rated-load current
Capacitors 4.60.1.9
in determining the ratings of motor branch-circuit
conductors, disconnecting means, controllers, and Commercial garages; aircraft 5.11, 5.13,
branch-circuit short-circuit and ground-fault protective hangars; motor fuel dispensing 5.14, 5.15,
facilities; bulk storage plants; 5.16, and
devices wherever the · running overload protective
spray applications, dipping, 5.17.4
device permits a sustained current greater than the and coating processes; and
specified percentage of the rated-load current. The inhalation anesthetizing
value of branch-circuit selection current will always be locations
equal to or greater than the marked rated-load current. Hazardous (classified) locations 5.0 - 5.3,
Rated-Load Current. The current of a hermetic 5.5 , and 5.6
refrigerant motor-compressor resulting when it is Motion picture and television 5.30
operated at the rated load, rated voltage, and rated studios and similar locations
frequency of the equipment it serves. Resistors and reactors 4.70
4.40.1.3 Other Articles.
used. The locked-rotor current of each single-phase
(A) Article 4.30. These provisions are in addition to or motor-compressor having a rated-load current of more
amendatory of, the provisions of Article 430 and other than 9 amperes at 115 volts, or more than 4.5 amperes at
articles in this Code, which apply except as modified in 230 volts, and each polyphase motor-compressor shall
this article. be marked on the motor-compressor nameplate. Where
(B) Articles 4.22, 4.24, or 4.30. The rules of Articles a thermal protector complying with 4.40.6.2(A)(2) and
4.22, 4.24, or 4.30, as applicable, shall apply to air- (B)(2) is used, the motor-compressor nameplate or the
conditioning and refrigerating equipment that does not equipment nameplate shall be marked with the words
incorporate a hermetic refrigerant motor-compressor. "thermally protected." Where a protective system
This equipment includes devices that employ com pl_ing with 4.40.6.2(A)(4) and (B)(4) is used and is
refrigeration compressors driven by conventional fumi hed with the equipment, the equipment nameplate
motors, furnaces with air-conditioning evaporator hall be marked with the words, "thermally protected
coils installed, fan-coil units, remote forced air-cooled ystem." \\ "here a protective system complying w ith
condensers, remote commercial refrigerators, and so 4.40.6.- (A)(4) and (B)(4) is specified, the equipment
forth. nameplate hall be appropriately marked.

(C) Article 4.22. Equipment such as room air (B) Multimotor and Combination-Load Equipment.
conditioners, household refrigerators and freezers, Multimotor and combination-load equipment shall be
proYided v,:ith a ,isible nameplate marked \,·ith the
drinking water coolers, and beverage dispensers shall
maker s name. the rating in Yolt . frequency and number
be considered appliances and the provisions of Article
of phases minimum upply circuit conductor ampacity,
4.22 shall also apply. the maximum rating of the branch-circuit short-circuit
(D) Other Applicable Articles. Hermetic refrigerant and ground-fault protectiYe de,·ice. and the short-circuit
motor-compressors, circuits, controllers, and equipment current rating of the motor controllers or industrial
shall also comply with the applicable provisions of control panel. The ampacity hall be calculated by using
Part 4.40.4 and counting all the motors and other loads
Table 4.40.1.3(D).
that will be operated at the ame time. The branch-
4.40.1.4 Marking on Hermetic Refrigerant Motor- circuit short-circuit and ground-fault protective device
Compressors and Equipment. rating shall not exceed the value calculated by using
Part 4.40.3 . Multimotor or combination-load equipment
(A) Hermetic Refrigerant Motor-Compressor for use on two or more circuits shall be marked with the
Nameplate. A hermetic refrigerant motor-compressor abo e information for each circuit.
shall be provided with a nameplate that shall indicate the
Exception No. 1: Multimotor and combination-load
manufacturer's name, trademark, or symbol· identifying
equipment that is suitable under the provisions of this
designation; phase; voltage; and frequency. The rated-
article for connection to a single 15- or 20-ampere,
load current in amperes of the motor-compressor shall
230-volt or 115-volt, or a 15-ampere, 208- or 230-volt,
be marked by the equipment manufacturer on either or
single-phase branch circuit shall be p ermitted to be
both the motor-compressor nameplate and the nameplate
marked as a single load.
of the equipment in which the motor-compressor is
... , 4
ARTICLE 4.40 - AIR-CONDITIONING AND REFRIGERATING EQUIPMENT

Exception No. 2: The minimum supply circuit conductor Exception No. 2: For cord-and-plug-connected
ampacity and the maximum rating ofthe branch-circuit equipment, the nameplate marking shall be used in
short-circuit and ground-fault protective device shall accordance with 4.40.3.2(B), Exception No. 2.
not be required to be marked on a room air conditioner
complying with 4.40. 7.3(A). (B) Multimotor Equipment. Formultimotorequipment
employing a shaded-pole or permanent split-capacitor-
Exception No. 3: Multimotor and combination-load type fan or blower motor, the full-load current for such
equipment used in one- and two-family dwellings, cord- motor marked on the nameplate of the equipment in
and attachment-plug-connected equipment shall not which the fan or blower motor is employed shall be
be required to be marked with a short-circuit current used instead of the horsepower rating to determine
rating.
the ampacity or rating of the disconnecting means, the
(C) Branch-Circuit Selection Current. A hermetic branch-circuit conductors, the controller, the branch-
refrigerant motor-compressor, or equipment containing circuit short-circuit and ground-fault protection, and
such a compressor, having a protection system that is the separate overload protection. This marking on the
approved for use with the motor-compressor that it equipment nameplate shall not be less than the current
protects and that permits continuous current in excess marked on the fan or blower motor nameplate.
of the specified percentage of nameplate rated-load
current given in 4.40.6.2(B)(2) or (B)(4) shall also be 4.40.1.7 Highest Rated (Largest) Motor. In
marked with a branch-circuit selection current that determining compliance with this article and with
complies with 4.40.6.2(B)(2) or (B)(4). This marking 4.30.2.4, 4.30.4.3(B) and 4.30.4.3(C), and 4.30.5.2(A),
shall be provided by the equipment manufacturer and the highest rated (largest) motor shall be considered
shall be on the nameplate(s) where the rated-load to be the motor that has the highest rated-load current.
current(s) appears. Where two or more motors have the same highest
4.40.1.5 Marking on Controllers. A controller shall rated-load current, only one of them shall be considered
be marked with the manufacturer's name, trademark, as the highest rated (largest) motor. For other than
or symbol; identifying designation; voltage; phase; full- hermetic refrigerant motor-compressors, and fan or
load and locked-rotor current (or horsepower) rating; blower motors as covered in 4.40.1.6(B), the full-load
and other data as may be needed to properly indicate the current used to determine the highest rated motor shall
motor-compressor for which it is suitable. be the equivalent value corresponding to the motor
horsepower rating selected from Table 4.30.14.2, Table
4.40.1.6 Ampacity and Rating. The size of conductors
4.30.14.3, or Table 4.30.1 4.4.
for equipment covered by this article shall be selected
from Table 3.I0.2.6(B)( l6) through Table 3.10.2.6(B) Exception: Where so marked, the branch-circuit
(19) or calculated in accordance \\·ith 3.10.2.6 as selection current shall be used instead of the rated-
applicable. The required ampacity of conductors and load current in determining the highest rated (largest)
rating of equipment hall be determined according to motor-compresso1:
4.40.1 .6(A) and 4.40. l .6(B).
4.40.1.8 Single '.\1achine. An air-conditioning or
(A) Hermetic Refrigerant Motor-Compressor. For a refrigerating s:y stem shall be considered to be a single
hermetic refrigerant motor-compres or, the rated-load
machine under the provisions of 4.30.7.7, Exception
current marked on the nameplate of the equipment
">lo. 1 and 4.30.9.12, Exception. The motors shall be
in which the motor-compressor is employed shall
permitted to be located remotely from each other.
be used in determining the rating or ampacity of the
disconnecting means, the branch-circuit conductors, the 4.40.1.9 Grounding and Bonding. Where multimotor
controller, the branch-circuit short-circuit and ground- and combination-load equipment is installed outdoors
fault protection, and the separate motor overload on a roof, an equipment grounding conductor of the
protection. Where no rated-load current is shown on the wire type shall be installed in outdoor portions of
equipment nameplate, the rated-load current shown on metallic raceway systems that use non-threaded fittings.
the compressor nameplate shall be used.
4.40.1.10 Short-Circuit Current Rating.
Exception No. 1: Where so marked, the branch-circuit
selection current shall be used instead of the rated- (A) Installation. Motor controllers of multimotor and
load current to determine the rating or ampacity of the combination-load equipment shall not be installed
disconnecting means, the branch-circuit conductors, where the available short-circuit current exceeds its
the controller, and the branch-circuit short-circuit and short-circuit current rating as marked in accordance
ground-fault protection. with 4.40. 1.4(B).

375
ARTICLE 4.40 -AIR-CONDITIONING AND REFRIGERATING EQUIPMENT
(B) Documentation. When motor controllers or (B) Combination Loads. Where the combined load o:-
industrial control panels of multimotor and combination two or more hermetic refrigerant motor-compressor:;
load equipment are required to be marked with a short or one or more hermetic refrigerant motor-compres or
circuit current rating, the available short circuit current with other motors or loads may be simultaneou-
and the date the short circuit current calculation was on a single disconnecting means, the rating for the
performed shall be documented and made available to disconnecting means shall be determined in accordance
those authorized to inspect the installation. with 4.40.2.2(B)(l) and (B)(2).
4.40.2 Disconnecting Means (1) Horsepower Rating. The horsepower rating of
the disconnecting means shall be determined
4.40.2.1 General. The provisions of Part 4.40.2 are
from the sum of all currents, including resistance
intended to require disconnecting means capable
loads, at the rated-load condition and also at the
of disconnecting air-conditioning and refrigerating
locked-rotor condition. The combined rated-load
equipment, including motor-compressors and
current and the combined locked-rotor current so
controllers from the circuit conductors.
obtained shall be considered as a single motor for
4.40.2.2 Rating and Interrupting Capacity. the purpose of this requirement as required by (1)
(A) Hermetic Refrigerant Motor-Compressor. A (a) and (l)(b).
disconnecting means serving a hermetic refrigerant (a) The full-load current equivalent to the
motor-compressor shall be selected on the basis of the horsepower rating of each motor, other than
nameplate rated-load current or branch-circuit selection a hermetic refrigerant motor-compressor, and
current, whichever is greater, and locked-rotor current, fan or blower motors as covered in 4.40. l .6(B)
respectively, of the motor-compressor as follows. shall be selected from Table 4.30.14.2, Table
(1) Ampere Rating. The ampere rating shall be 4.30.14.3, or Table 4.30.14.4. These full-load
at least 115 percent of the nameplate rated- currents shall be added to the motor-compressor
load current or branch-circuit selection current, rated-load current(s) or branch-circuit selection
whichever is greater. current(s), whichever is greater, and to the
rating in amperes of other loads to obtain an
Exception: A listed unfused motor circuit switch, equivalent full-load current for the combined
without fuseholders, having a horsepower rating not load.
less than the equivalent horsepower determined in
accordance with 4.40.2.2(A)(2) shall be permitted to (b) The locked-rotor current equivalent to the
have an ampere rating less than 115 percent of the horsepower rating of each motor, other than a
specified current. hermetic refrigerant motor-compressor, shall
be selected from Table 4.30.14.S(A) or Table
(2) Equivalent Horsepower. To determine the 4.30.14.S(B), and, for fan and blower motors
equivalent horsepower in complying with the of the shaded-pole or permanent split-capacitor
requirements of 4.30.9.9, the horsepower rating type marked with the locked-rotor current, the
shall be selected from Table 4.30.14.2, Table marked value shall be used. The locked-rotor
4.30.14.3, or Table 4.30.14.4 corresponding to cunents shall be added to the motor-compressor
the rated-load current or branch-circuit selection locked-rotor current(s) and to the rating in
current, whichever is greater, and also the amperes of other loads to obtain an equivalent
horsepower rating from Table 4.30.14.S(A) or locked-rotor cmTent for the combined load.
Table 4.30.14.S(B) corresponding to the locked- Where two or more motors or other loads such
rotor current. In case the nameplate rated-load as resistance heaters, or both, cannot be started
current or branch-circuit selection current simultaneously, appropriate combinations of
and locked-rotor current do not correspond to locked-rotor and rated-load current or branch-
the currents shown in Table 4.30.14.2, Table circuit selection current, whichever is greater,
4.30.14.3, Table 4.30 .14.4, Table 4.30.14.S(A), shall be an acceptable means of determining
or Table 4.30.14.S(B), the horsepower rating the equivalent locked-rotor cmTent for the
corresponding to the next higher value shall be simultaneous combined load.
selected. In case different horsepower ratings
are obtained when applying these tables, a Exception: Where part of the concurrent load is a
horsepower rating at least equal to the larger of resistance load and the disconnecting means is a s,i:itch
the values obtained shall be selected. rated in horsepower and amperes, the switch used

376
ARTICLE 4.40-AIR-CONDITIONING AND REFRIGERATING EQUIPMENT
shall be permitted to have a horsepower rating not less Exception No. 1: Where the disconnecting means
than the combined load to the motor-compressor(s) provided in accordance with 4.30.9.2(A) is lockable
and other motor(s) at the locked-rotor condition, if the in accordance with 1.10.1.25 and the refrigerating or
ampere rating of the switch is not less than this locked- air-conditioning equipment is essential to an industrial
rotor load p lus the resistance load. process in a facility with written safety procedures, and
where the conditions of maintenance and supervision
(2) Full-Load Current Equivalent. The ampere
ensure that only qualifiedpersons service the equipment,
rating of the disconnecting means shall be at least
a disconnecting means within sight.from the equipment
115 percent of the sum of all currents at the rated-
shall not be required.
load condition determined in accordance with
4.40.2.2(B)(l ). Exception No. 2: Where an attachment plug and
receptacle serve as the disconnecting means in
Exception: A listed unfused motor circuit switch, without
accordance with 4.40.2.3, their location shall be
fuseholders, having a horsepower rating not less than
accessible but shall not be required to be readily
the equivalent horsepower determined by 4.40.2.2(B)
accessible.
(]) shall be permitted to have an ampere rating less
than 115 percent of the sum ofall currents. FPNNo. l: SeeParts4.30.7 and 4.30.9 for additional requirements.
FPN No. 2: See 1.10.2.l.
(C) Small Motor-Compressors. For small motor-
compressors not having the locked-rotor current marked 4.40.3 Branch-Circuit Short-Circuit and Ground-
on the nameplate, or for small motors not covered by Fault Protection
Table 4.30.14.1 , Table 4.30.14.2, Table 4.30.14.3 ,
4.40.3.1 General. The provisions of Part 4.40.3
or Table 4.30.14.4, the locked-rotor current shall be
specify devices intended to prote t the branch-circuit
assumed to be six times the rated-load current.
conductors, control apparatus, and motors in circuits
(D) Disconnecting Means. Every disconnecting means supplying hermetic refrigerant motor-compressors
in the refrigerant motor-compressor circuit between against oYercurrent due to hort circuits and ground
the point of attachment to the feeder and the point of faults. They are in addition to or amendatory of the
connection to the refrigerant motor-compressor shall pro,·isio of Anicle '""..40.
comply with the requirements of 4.40._.2.
4.40.3.2 Application and Selection.
(E) Disconnecting M eans Rated in Excess of
(A ) Rating or Setting for Individual Motor-
100 Horsepower. Where the rate.d-load or ked-
Compressor. The motor-compressor branch-circuit
roto clllTent as de ermined aboYe wo ld in ·ca-e a
hart-circuit and ground-fault protective device shall
disconnecting means rared in x ss of 100 hp. the
be capable of carrying the starting current of the
prm 10 of 4. "'0.9.9 E ) h a ply.
motor. A protective device having a rating or setting
4.40.2.3 Cord-Connected Equipment. For cord- not exceeding 175 percent of the motor-compressor
connec ed _ ·pmen su h a room air conditioners, rated-load current or branch-circuit selection current,
o e old refrigerators and freezers. drinking water whichever is greater, shall be permitted, provided that,
oole . and eYerage di pensers, a separable connector where the protection specified is not sufficient for the
or an arra hmen plug and receptacle shall be permitted starting current of the motor, the rating or setting shall
to erYe as the disconnecting means. be permitted to be increased but shall not exceed 225
FP:'.\: For room air conditioners, see 4.40.7.4. percent of the motor rated-load current or branch-circuit
selection current, whichever is greater.
4.40.2.4 Location. Disconnecting means shall be
located within sight from and readily accessible from Exception: The rating ofthe branch-circuit short-circuit
the air-conditioning or refrigerating equipment. The and ground-fault protective device shall not be required
disconnecting means shall be permitted to be installed to be less than 15 amperes.
on or within the air-conditioning or refrigerating (B) Rating or Setting for Equipment. The equipment
equipment. branch-circuit short-circuit and ground-fault protective
The disconnecting means shall not be located on panels device shall be capable of carrying the starting current
that are designed to allow access to the air-conditioning of the equipment. Where the hermetic refrigerant motor-
or refrigeration equipment or to obscure the equipment compressor is the only load on the circuit, the protection
nameplate(s). shall comply with 4.40.3.2(A). Where the equipment
incorporates more than one hermetic refrigerant motor-

377
ARTICLE 4.40-AIR-CONDITIONING AND REFRIGERATING EQUIPMENT
compressor or a hermetic refrigerant motor-compressor not exceed the manufacturer's values marked on the
and other motors or other loads, the equipment short- equipment.
circuit and ground-fault protection shall comply with
4.40.4 Branch-Circuit Conductors
4.30.4.3 and 4.40.3.2(B)(l) and (B)(2).
4.40.4.1 General. The provisions of Part 3.10.4 specify
(1) Motor-Compressor Largest Load. Where a
ampacities of conductors required to carry the motor
hermetic refrigerant motor-compressor is the
cun-ent without overheating under the conditions
largest load connected to the circuit, the rating
specified, except as modified in 4.40.1.6(A), Exception
or setting of the branch-circuit short-circuit
No. 1.
and ground-fault protective device shall not
exceed the value specified in 4.40.3.2(A) for the The provisions of these articles shall not apply to
largest motor-compressor plus the sum of the integral conductors of motors, to motor controllers and
rated-load current or branch-circuit selection the like, or to conductors that form an integral part of
current, whichever is greater, of the other motor approved equipment.
compressor(s) and the ratings of the other loads 4.40.4.2 Single Motor-Compressor. Branch-circuit
supplied. conductors supplying a single motor-compressor shall
(2) Motor-Compressor Not Largest Load. Where a have an ampacity not less than 125 percent of either
hermetic refrigerant motor-compressor is not the the motor-compressor rated-load current or the branch-
largest load connected to the circuit, the rating circuit selection cun-ent whichever is greater.
or setting of the branch-circuit short-circuit and For a wye-stan, delta-run connected motor-compressor, the
ground-fault protective device shall not exceed a selection of branch-circuit conductors between the controller
value equal to the sum of the rated-load current and the motor-compressor hall be permitted to be based on
or branch-circuit selection current, whichever is 72 percent of either the motor-compressor rated-load cunent
greater, rating(s) for the motor-compressor(s) plus or the branch-circuit selection current whichever is greater.
the value specified in 4.30.4.3(C)(4) where other FPN: The individual motor circuit conductors of wye-start,
motor loads are supplied, or the value specified in delta-run connected motor-compressors carry 58 percent of the
2.40.1.4 where only nonmotor loads are supplied rated load current. The multiplier of 72 percent is obtained by
in addition to the motor-compressor(s). multiplying 58 percent by 1.25.

Exception No. 1: Equipment that starts and operates on 4.40.4.3 Motor-Compressor(s) With or Without
a 15- or 20-ampere, 230-volt or 115-volt, or 15-ampere Additional Motor Loads. Conductors supplying
208- or 230-volt single-phase branch circuit, shall one or more motor-compressor(s) with or without an
be permitted to be protected by the 15- or 20-ampere additional motor load(s) shall have an ampacity not less
overcurrent device protecting the branch circuit, but if than the sum of each of the following:
the maximum branch-circuit short-circuit and ground- (1) The sum of the rated-load or branch-circuit
fault protective device rating marked on the equipment selection current, whichever is greater, of all
is less than these values, the circuit protective device motor-compressors
shall not exceed the value marked on the equipment
nameplate. (2) The sum of the full-load current rating of all other
motors
Exception No. 2: The nameplate marking of cord-
andplug-connected equipment rated not greater than (3) 25 percent of the highest motor-compressor or
25 0 volts, single-phase, such as household refrigerators motor full load current in the group.
and freezers, drinking water coolers, and beverage Exception No. 1: Where the circuitry is interlocked
dispensers, shall be used in determining the branch- so as to prevent the starting and running of a second
circuit requirements, and each unit shall be considered motor-compressor or group of motor-compressors, the
as a single motor unless the nameplate is marked conductor size shall be determined from the largest
otherwise. motor-compressor or group of motor-compressors that
(C) Protective Device Rating Not to Exceed the is to be operated at a given time.
Manufacturer's Values. Where maximum protective Exception No. 2: The branch-circuit conductors for
device ratings shown on a manufacturer's overload room air conditioners shall be in accordance with Part
relay table for use with a motor controller are less 4.40.7.
than the rating or setting selected in accordance with
4.40.3.2(A) and (B), the protective device rating shall

378
ARTICLE 4.40 - AIR-CONDITIONING AND REFRIGERATING EQUIPMENT
4.40.4.4 Combination Load. Conductors supplying a 4.40.6.2 Application and Selection.
motor-compressor load in addition to other load(s) as
(A) Protection of Motor-Compressor. Each motor-
calculated from Article 2.20 and other applicable articles
compressor shall be protected against overload and
shall have an ampacity sufficient for the other load(s)
failure to start by one of the following means:
plus the required ampacity for the motor-compressor
load determined in accordance with 4.40.4.3 or, for a (1) A separate overload relay that is responsive to
single motor-compressor, in accordance with 4.40.4.2. motor-compressor cun-ent. This device shall be
selected to trip at not more than 140 percent of
Exception: Where the circuitry is interlocked so as the motor-compressor rated-load current.
to prevent simultaneous operation of the motor-
compressor(s) and all other loads connected, the (2) A thermal protector integral with the motor-
conductor size shall be determined from the largest size compressor, approved for use with the motor-
required for the motorcompressor(s) and other loads to compressor that it protects on the basis that it
be operated at a given time. will prevent dangerous overheating of the motor-
compressor due to overload and failure to start.
4.40.4.5 Multimotor and Combination-Load If the current-interrupting device is separate from
Equipment. The ampacity of the conductors supplying the motor-compressor and its control circuit is
multimotor and combination-load equipment shall not operated by a protective device integral with the
be less than the minimum circuit ampacity marked on motor-compressor, it shall be arranged so that
the equipment in accordance with 4.40.1 A(B). the opening of the control circuit will result in
4.40.5 Controllers for Motor-Compressors interruption of current to the motor-compressor.
(3) A fuse or inverse time circuit breaker responsive
4.40.5.1 Rating. to motor current, which shall also be permitted
(A) Motor-Compressor Controller. A motor- to serve as the branch-circuit short-circuit and
compressor controller shall have both a continuous- ground-fault protective device. This device shall
duty full-load current rating and a locked-rotor current be rated at not more than 125 percent of the
rating not less than the nameplate rated-load current motor-compressor rated-load current. It shall
or branch-circuit selection current, whichever is have sufficient time delay to permit the motor-
greater, and locked-rotor current, respectively, of the compressor to start and accelerate its load. The
compressor. In case the motor controller is rated in equipment or the motor-compressor shall be
horsepO\\'er but is without one or both of the foregoing marked with this maximum branch-circuit fuse
or inverse time circuit breaker rating.
current ratings, equivalent currents shall be determined
from the ratings as follows. Table 4.30.14.2, Table (4) A protective system, furnished or specified and
4.30. 14.3, and Table 4.30.14.4 shall be used to approved for use with the motor-compressor
determine the equivalent full-load current rating. Table that it protects on the basis that it will prevent
4.30. l 4.5(A) and Table 4.30.14.S(B) shall be used to dangerous overheating of the motor-compressor
determine the equivalent locked-rotor current ratings. due to overload and failure to start. If the current-
interrupting device is separate from the motor-
(B) Controller Serving More Than One Load. A
compressor and its control circuit is operated by
controller serving more than one motor-compressor
a protective device that is not integral with the
or a motor-compressor and other loads shall have a
current-interrupting device, it shall be arranged
continuous-duty full-load current rating and a locked-
so that the opening of the control circuit will
rotor current rating not less than the combined load as
result in interruption of current to the motor-
determined in accordance with 4.40.2.2(B).
compressor.
4.40.6 Motor-Compressor and Branch-Circuit (B) Protection of Motor-Compressor Control
Overload Protection Apparatus and Branch-Circuit Conductors. The
motor-compressor controller(s), the disconnecting
4.40.6.1 General. The provisions of Part 4.40.6 specify means, and the branch-circuit conductors shall be
devices intended to protect the motor-compressor, protected against overcurrent due to motor overload and
the motor-control apparatus, and the branch-circuit failure to start by one of the following means, which
conductors against excessive heating due to motor shall be permitted to be the same device or system
overload and failure to start. protecting the motor-compressor in accordance with
4.40.6.2(A):
FPN: See 2.40.1.4(G) for application of Parts 4.40.3 and 4.40.6.

379
ARTICLE 4.40 - AIR-CONDITIONING AND REFRIGERATING EQUIPME T
Exception: Overload protection of motor-compressors 4.40.6.5 Cord- and Attachment-Plug-Connected
and equipment on 15- and 20-ampere, single-phase, Motor-Compressors and Equipment on 15- or
branch circuits shall be permitted to be in accordance 20-Ampere Branch Circuits. Overload protectio
with 440.54 and 4.40.6.5. for motor-compressors and equipment that are cord-
and attachment-plug-connected and used on 1:- or
( 1) An overload relay selected in accordance with
20-ampere 230-volt or 115-volt, or 15-ampere 20 -
4.40.6.2(A)(l)
or 230-volt, single-phase branch circuits as permitted
(2) A thermal protector applied in accordance with in Article 2.10 shall be permitted as indicated in
4.40.6.2(A)(2), that will not permit a continuous 4.40.6.5(A), (B), and (C).
current in excess of 156 percent of the marked
(A) Overload Protection. The motor-compressor shall
rated-load current or branch-circuit selection
be provided with overload protection as specified in
current
4.40.6.2(A). Both the controller and the motor overload
(3) A fuse or inverse time circuit breaker selected in protective device shall be identified for installation with
accordance with 4.40.6.2(A)(3) the short-circuit and ground-fault protective device for
(4) A protective system, in accordance with the branch circuit to which the equipment is connected.
4.40.6.2(A)(4), that will not permit a continuous (B) Attachment Plug and Receptacle or Cord
current in excess of 156 percent of the marked Connector Rating. The rating of the attachment plug
rated-load current or branch-circuit selection and receptacle or cord connector shall not exceed 20
current amperes at 125 volts or 15 amperes at 250 volts.
4.40.6.3 Overload Relays. Overload relays and other (C) Time Delay. The short-circuit and ground-fault
devices for motor overload protection that are not protective device protecting the branch circuit shall have
capable of opening short circuits shall be protected by sufficient time delay to permit the motor-compressor
fuses or inverse time circuit breakers with ratings or and other motors to start and accelerate their loads.
settings in accordance with Part 4.40.3 unless identified
4.40.7 Provisions for Room Air Conditioners
for group installation or for part-winding motors and
marked to indicate the maximum size of fuse or inverse 4.40.7.1 General. The provisions of Part 4.40.7 shall
time circuit breaker by which they shall be protected. apply to electrically energized room air conditioners
that control temperature and humidity. For the purpose
Exception: The fuse or inverse time circuit breaker
of Part 4.40.7, a room air conditioner (with or without
size marking shall be permitted on the nameplate of
provisions for heating) shall be considered as an ac
the equipment in which the overload relay or other
appliance of the air-cooled window, console, or in-
overload device is used.
wall type that is installed in the conditioned room
4.40.6.4 Motor-Compressors and Equipment on 15- and that incorporates a hermetic refrigerant motor-
or 20-Ampere Branch Circuits - Not Cord- and compressor(s). The provisions of Part 4.40.7 cover
Attachment-Plug-Connected. Overload protection equipment rated not over 250 volts, single phase,
for motor-compressors and equipment used on 15- or and the equipment shall be permitted to be cord- and
20-ampere, 230-volt or ll5-volt, or 15-ampere 208- attachment plug-connected.
or 230-volt single-phase branch circuits as permitted
A room air conditioner that is rated 3-phase or rated
in Article 2.10 shall be permitted as indicated in
over 250 volts shall be directly connected to a \,'iring
4.40.6.4(A) and 4.40.6.4(B).
method recognized in Chapter 3, and provisions of Part
(A) Overload Protection. The motor-compressor 4.40.7 shall not apply.
hall be provided with overload protection selected
4.40.7.2 Grounding. The enclosures of room air
as specified in 4.40.6.2(A). Both the controller and
conditioners shall be connected to the equipment
motor overload protective device shall be identified
grounding conductor in accordance with 2.50.6.1,
or installation with the short-circuit and ground-fault
2.50.6.3, and 2.50.6.5.
rotective device for the branch circuit to which the
. ·pment is connected. 4.40.7.3 Branch-Circuit Requirements.
) Time Delay. The short-circuit and ground-fault (A) Room Air Conditioner as a Single Motor Unit.
_?:"Oective device protecting the branch circuit shall have A room air conditioner shall be considered as a single
5ITffi ient time delay to permit the motor-compressor motor unit in determining its branch-circuit requirements
~ other motors to start and accelerate their loads. where all the following conditions are met:
ARTICLE 4.45 - GENERATORS
(1) It is cord- and attachment-plug-connected. 4.45.1.11 Marking. Each generator shall be provided
with a nameplate giving the manufacturer's name, the
(2) Its rating is not more than 40 amperes and 250
rated frequency, the number of phases if ac, the rating
volts, single phase.
in kilowatts or kilovolt-amperes, the power factor, the
(3) Total rated-load current is shown on the room normal volts and amperes corresponding to the rating,
air-conditioner nameplate rather than individual the rated ambient temperature, and the rated temperature
motor currents. nse.
(4) The rating of the branch-circuit short-circuit and Nameplates or manufacturer's instructions shall provide
ground-fault protective device does not exceed the following information for all stationary generators
the ampacity of the branch-circuit conductors or and portable generators rated more than 15000 W:
the rating of the receptacle, whichever is less.
(1) Subtransient, transient, synchronous, and zero
(B) Where No Other Loads Are Supplied. The total sequence reactances
marked rating of a cord- and attachment-plug-connected (2) Power rating category
room air conditioner shall not exceed 80 percent of
the rating of a branch circuit where no other loads are (3) Insulation system class
supplied. (4) Indication if the generator is protected against
overload by inherent design, an overcurrent
(C) Where Lighting Units or Other Appliances Are protective relay, circuit breaker, or fuse
Also Supplied. The total marked rating of a cord- and
attachment plug-connected room air conditioner shall (5) Maximum short-circuit current for inverter-
not exceed 50 percent of the rating of a branch circuit based generators, in lieu of the synchronous,
subtransient, and transient reactances
where lighting outlets, other appliances, or general-
use receptacles are also supplied. Where the circuitry Marking shall be provided by the manufacturer to
is interlocked to prevent simultaneous operation of the indicate whether or not the generator neutral is bonded
room air conditioner and energization of other outlets its frame. Where the bonding is modified in the field,
on the same branch circuit, a cord- and attachment additional marking shall be required to indicate whether
plug-connected room air conditioner shall not exceed the neutral is bonded to the frame.
80 percent of the branch-circuit rating.
4.45.1.12 Overcurrent Protection.
4.40.7.4 Disconnecting Means. An attachment plug
(A) Constant-Voltage Generators. Constant-voltage
and receptacle or cord connector shall be pennitted to
generators, except ac generator exciters, shall be
serve as the disconnecting means for a single-phase
protected from overload by inherent design, circuit
room air conditioner rated 250 volts or less if (1) the
breakers, fuses, protective relays, or other identified
manual controls on the room air conditioner are readily
overcurrent protective means suitable for the conditions
accessible and located within I 800 mm of the floor,
of use.
or (2) an approved manually operable disconnecting
means is installed in a readily accessible location within (B) Two-Wire Generators. Two-wire, de generators
sight from the room air conditioner. shall be permitted to have overcurrent protection in one
conductor only if the overcurrent device is actuated by
4.40.7.5 Supply Cords. Where a flexible cord is used
the entire current generated other than the current in the
to supply a room air conditioner, the length of such cord
shunt field. The overcurrent device shall not open the
shall not exceed 3000 mm for a nominal, 115- ·oh rating
shunt field.
or 1800 mm for a nominal, 208- or 230-volt rating.
(C) 65 \ olts or Less. Generators operating at 65 volts or
ARTICLE 4.45 - GENERATORS
less and driven by individual motors shall be considered
4.45.1.1 Scope. This article contains installation and as protected by the overcurrent device protecting the
other requirements for generators. motor if these devices will operate when the generators
are delivering not more than 150 percent of their full-
4.45.1.10 Location. Generators shall be of a type
load rated current.
suitable for the locations in which they are installed.
They shall also meet the requirements for motors in (D) Balancer Sets. Two-wire, de generators used in
4.30.1.14. conjunction with balancer sets to obtain neutral points
FPN: See NFPA 37, Standard for the Installation and Use for 3-wire systems shall be equipped with overcurrent
of Stationary Combustion Engines and Gas Turbines, for devices that disconnect the 3-wire system in case of
information on the location of generator exhaust. excessive unbalancing of voltages or currents.
381
ARTICLE 4.45 - GENERATORS
(E) Balancer Sets. Two-wire, de generators used in If used where oils, grease, or other contaminants may
conjunction with balancer sets to obtain neutral points be present, the bushing shall be made of a material nor
for 3-wire systems shall be equipped with overcurrent deleteriously affected.
devices that disconnect the 3-wire system in case of
4.45.1.17 Generator Terminal Housings. Generator
excessive un-balancing of voltages or currents.
terminal housings shall comply with 4.30.1.12. Where a
Exception to (A) through (E): Where a generator is horsepower rating is required to detennine the required
vital to the operation of an electrical system and the minimum size of the generator terminal housing, the
generator should operate to failure to prevent a greater full-load current of the generator shall be compared
hazard to persons, the overload sensing device(s) shall with comparable motors in Table 4.30.14.l through
be permitted to be connected to an annunciator or Table 4.30.14.4. The higher horsepower rating of Table
alarm supervised by authorized personnel instead of 4.30.14.1 and Table 4.30 .14.4 shall be used whenever
interrupting the generator circuit. the generator selection is between two ratings.
4.45.1.13 Ampacity of Conductors. Exception: This section shall not apply to generators
rated over 600 volts.
(A) General. The ampacity of the conduct0rs from
the generator output terminals to the first distribution 4.45.1.18 Disconnecting Means and Shutdown of
device( s) containing overcurrent protection shall not be Prime Mover.
less than 115 percent of the nameplate current rating of
(A) Disconnecting Means. Generators other than
the generator. It shall be permitted to size the neutral
cord-andplug-connected portable shall have one or
conductors in accordance with 2.20.3.22. Conductors
more disconnecting means. Each disconnecting means
that must carry ground-fault cunents shall not be smaller
shall simultaneously open all associated ungrounded
than required by 2.50.2.ll(A). Neutral conductors of de
conductor . Each disconnecting means shall be lockable
generators that must carry ground-fault currents shall
in the open position in accordance with 1.10.1.25.
not be smaller than the minimum required size of the
largest conductor. (B) Shutdown of Prime Mover. Generators shall have
provisions to shut down the prime mover. The means of
Exception: Where the design and operation of the
shutdown shall comply with all of the following:
generator prevent overloading, the ampacity of the
conductors shall not be less than 100 percent of the ( 1) Be equipped with provisions to disable all prime
nameplate current rating of the generator. mover start control circuits to render the prime
mo er incapable of starting
(B) Overcurrent Protection Provided. Where the
generator set is equipped with a listed overcurrent (2) Initiate a shutdown mechanism that requires a
protective device or a combination of a current mechanical reset
transformer and overcurrent relay, conductors shall
The provisions to shut down the prime mover shall be
be permitted to be tapped from the load side of the permitted to satisfy the requirements of 4.45 . l. l 8(A)
protected terminals in accordance with 2.40.2.l(B). where it is capable of being locked in the open position
Tapped conductors shall not be permitted for portable in accordance with 1.10 .1. 2 5 .
generators rated 15 kW or less where field wiring
Generators ·w ith greater than 15 kW rating shall be
connection terminals are not accessible.
provided with an additional requirement to shut down
4.45.1.14 Protection of Live Parts. Live parts of the prime mover. This additional shutdown means shall
generators operated at more than 50 volts ac or 60 volts be located outside the equipment room or generator
de to ground shall not be exposed to accidental contact enclosure and shall also meet the requirements of
where accessible to unqualified persons. 4.45.1.18(B)(l) and (B)(2) .
4.45.1.15 Guards for Attendants. Where necessary for
(C) Generators Installed in Parallel. Where a
the safety of attendants, the requirements of 4.30.12.3
generator is installed in parallel with other generators,
shall apply.
the provisions of 4.45.1.18(A) shall be capable of
4.45.1.16 Bushings. Where field-installed wiring isolating the generator output terminals from the
passes through an opening in an enclosure, a conduit paralleling equipment. The disconnecting means shall
box, or a barrier, a bushing shall be used to protect the not be required to be located at the generator.
conductors from the edges of an opening having sharp
edges. The bushing shall have smooth, well-rounded
urfaces where it may be in contact with the conductors.
382
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)
4.45.1.20 Ground-Fault Circuit-Interrupter Exception No. 7: Transformers used for power-limited
Protection for Receptacles on 15000 W or Smaller fire alarm circuits that comply with Part 7. 60.3.
Portable Generators. Receptacle outlets that are a
Exception No. 8: Transformers used for research,
part of a 15000 W or smaller portable generator shall
development, or testing, where effective arrangements
have listed ground-fault circuit-interrupter protection
are provided to safeguard persons from contacting
(GFCI) for personnel integral to the generator or
energized parts.
receptacle as indicated in either (A) or (B).
(A) Unbonded (Floating Neutral) Generators. This a11icle covers the installation of transfonners
Unbonded generators with both 125-volt and dedicated to supplying power to a fire pump installation
125/250-volt receptacle outlets shall have listed as modified by Article 6.95 .
GFCI protection for personnel integral to the This article also covers the installation of transformers
generator or receptacle on all 125-volt, 15- and in hazardous (classified) locations as modified by
20-ampere receptacle outlets. Articles 5.1 through 5.4.

Exception: GFCI protection shall not be required where 4.50.1.2 Definition. For the purpose of this article, the
the 125-volt receptacle outlets(s) is interlocked such following definition shall apply.
that it is not available for use when any 125/250-volt Transformer. An individual transformer, single- or
receptacle(s) is in use. polyphase, identified by a single nameplate, unless
(B) Bonded Neutral Generators. Bonded generators otherwise indicated in this article.
shall be provided with GFCI protection on all 125- and 4.50.1.3 Overcurrent Protection. Overcurrent
250-volt, 15- and 20-ampere receptacle outlets. protection of transformers shall comply with
FPN: Refer to 5.90.1.6(A)(3) for GFCI requirements for 15-kW 4.50.1.3(A), (B), or (C). As used in this section, the word
or smaller portable generators used for temporary electric power trarzsformer shall mean a transformer or polyphase bank
and lighting.
of two or more single-phase transformers operating as
Exception to (A) and (B): If the generator was a unit.
manufactured or remanufactured prior to January 1, FPN No. 1: See 2.40.1.4, 2.40.2.1, 2.40.9.1, and 2.40.9.2 for
2015, listed cord sets or devices incorporating listed overcurrent protection of conductors.
GFCI protection for personnel identified for portable FPN No. 2: Nonlinear loads can increase heat in a transformer
use shall be permitted. without operating its overcurrent protective device.

(A) Transformers Over 1000 Volts, Nominal.


ARTICLE 4.50 - TRANSFORMERS AND
Overcurrent protection shall be provided in accordance
TR-\..,SFOR'1ER VAULTS (INCLUDING
with Table 4.50.1.3(A).
SECO~-UARY TIES)
4.50.1 General Pro,isions (B) Transformers 1000 Volts, Nominal, or Less.
Over-current protection shall be provided in accordance
4.50.I.J Scope. Thi- arti l oYers the installation of all with Table 4.50. l .3(B).
transforme .
Exception: Where the transformer is installed as a
Exception .Yo. 1: C wTenI tran.s.1ormers. motor control circuit transformer in accordance with
Exception So. _: Dry-tvpe transformers that constitute 4.30.6.2(C}(l) through (C)(5).
a component part of other apparatus and comply with (C) Voltage (Potential) Transformers. Voltage
the requirements for such apparatus. (potential) transformers installed indoors or enclosed
Exception o. 3: Transformers that are an integral part shall be protected with primary fuses.
of an X-ray, high-frequency, or electrostatic-coating FPN: For protection of instrument circuits including voltage
apparatus. transformers, see 4.8.4.3 .

Exception No. 4: Transformers used with Class 2 and 4.50.1.4 Autotransformers 1000 Volts, Nominal, or
Class 3 circuits that comply with Article 7.25. Less.

Exception No. 5: Transformers for sign and outline (A) Overcurrent Protection. Each autotransfonner
lighting that comply with Article 6. 0. 1000 volts, nominal, or less shall be protected by an
individual overcurrent device installed in series with
Exception No. 6: Transformers for electric-discharge each ungrounded input conductor. Such overcurrent
lighting that comply with Article 4. 10.
383
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)
device shall be rated or set at not more than 125 percent neutral rating. Delayed nipping for temporary
ofthe rated full-load input current of the autotransformer. overcurrents sensed at the autotransfonncr
Where this calculation does not correspond to a standard overcurrent device shall be pe1mitted for the
rating of a fuse or nonadjustable circuit breaker and the purpose of allowing proper operation of branc
rated input current is 9 amperes or more, the next higher or feeder protective devices on the 4-wire sy tern.
standard rating described in 2.40.1 .6 shall be permitted.
(3) Transformer Fault Sensing. A fault-sen i g
An overcurrent device shall not be installed in series
system that causes the opening of a main switch or
with the shunt winding (the winding common to both
common-trip overcurrent device for the 3-pha c.
the input and the output circuits) of the autotransformer
4-wire system shall be provided to guard agains
between Points A and Bas shown in Figure 4.50.1.4(A).
single-phasing or internal faults.
Exception: Where the rated input current of the FPN: This can be accomplished by the use of two subtractive-
autotransformer is less than 9 amperes, an overcurrent connected donut-type cunent transformers installed to sense
device rated or set at not more than 167 percent of the and signal when an unbalance occurs in the line current to the
input current shall be permitted. autotransformer of 50 percent or more of rated current.

(B) Transformer Field-Connected as an (4) Rating. The autotransformer shall have a


Autotransformer. A transformer field-connected as an continuous neutral-current rating that is not less
autotransformer shall be identified for use at elevated than the maximum possible neutral unbalanced
voltage. load current of the 4-wire system.

FPN: For information on permitted uses of autotransformer , see (B) Ground Reference for Fault Protection Devices.
2.10.1.9 and 2.15.1.11. A grounding autotransformer used to make available
a specified magnitude of ground-fault current for
4.50.1.5 Grounding Autotransformers. Grounding
operation of a ground-responsive protective device on
autotransformers covered in this section are zigzag
a 3-phase, 3-wire ungrounded system shall conform to
or T-connected transfom1ers connected to 3-phase,
4.50. l .5 (B)( 1) and (B)(2).
3-wire ungrounded systems for the purpose of creating
a 3-phase, 4-wire distribution system or providing a (1) Rating. The autotransfo1mer shall have a
neutral point for grounding purposes. Such transformers continuous neutral-current rating not less than the
shall have a continuous per-phase current rating and a specified ground-fault current.
continuous neutral current rating. Zigzag-connected (2) Overcurrent Protection. Overcurrent protection
transformers shall not be installed on the load side shall comply with (a) and (b).
of any system grounding connection, including those
made in accordance with 2.50.2.S(B), 2.50.2.ll (A)(l). (a) Operation and Interrupting Rating. An
or 2.50.2.13(B), Exception No. 1. overcurrent protective device having an
interrupting rating in compliance with
FPN: The phase current in a grounding autotransformer i one-
third the neutral current. 1.10 .1. 9 and that will open simultaneously all
ungrounded conductors when it operates shall
(A) Three-Phase, 4-Wire System. A grounding be applied in the grounding autotI·ansfotmer
autotransformer used to create a 3-phase 4-wire branch circuit.
distribution system from a 3-phase, 3-wire ungrounded
system shall conform to 4.50.l.5(A)(l) through (A)(4). (b) Ampere Rating. The overcurrent protection
shall be rated or set at a current not exceeding
(1) Connections. The transformer shall be directly 125 percent of the autotransformer continuous
connected to the ungrounded phase conductors per-phase current rating or 42 percent of
and shall not be switched or provided with
overcurrent protection that is independent of
the main switch and common-trip overcurrent
protection for the 3-phase, 4-wire system.
(2) Overcurrent Protection. An overcurrent sensing
device shall be provided that will cause the main Shunt winding(s)

switch or common-trip overcurrent protection


referred to in 4.50.1.S(A)(l) to open if the load B
on the autotransformer reaches or exceeds 125
percent of its continuous current per-phase or Figure 4.50.1.4(A) Autotransformer.
384
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)
Table 4.50.1.3(A) Maximum Rating or Setting of Overcurrent Protection for Transformers Over 1000 Volts (as
a Percentage of Transformer-Rated Current)

Secondary Protection (See Note 2.)


Primary Protection over 1000 Volts Over 1000 Volts 1000 Volts or Less
Location Transformer Rated Circuit Breaker Circuit Breaker Circuit Breaker or
Fuse Rating Fuse Rating
Limitations Impedance (See Note 4.) (See Note 4.) Fuse Rating
600% 300% 300% 250% 125%
Not more than 6%
(See Note 1.) (See Note 1.) (See ote 1.) (See Note 1.) (See Note 1.)
Any location
More than 6% and 400% 300% 250% 225% 125%
not more than 10% (See Note I.) (See Note 1.) (See 1 ·ote 1.) (See Note I.) (See Note 1.)
300% 250%
Any );ot required Not required Not required
Supervised (See Note I.) (See Note 1.)
locations ~00% 250% 250%
Not more than 6% 600% 300%
only (See Note 5.) (See Note 5.) (See Note 5.)
(See ote 3.) More than 6% and 2 - 0% 225% 250%
400% ~00°0
not more than 10% (See Kote .-.) (See Note 5.) (See Note 5.)
Notes:
1. Where me required fuse raring or ·rcui breaker se · "' d not orres. nd o a srandard raring or setting, a higher rating or setting that does not exceed the
follm\in0 shall be permirred:

a.The next 'gher standanl ,.; g or se:Iing "'or fuses ai:d circ: i hreak rs I 000 ..-a • and below, or

b.The nex higi:e: mmercially a\'l!.i .e raring or - · g ·o r fuses and circuit breakers aboYe 1000 YO!ts.

__\\l!eP secontlaiy o;;ercurrcnr rorection is required. the secondary O\'ercurrent device shall be permitted to consist of not more than six circuit breakers or six sets
o:: fu..-es grouped in one ocarion.. Where m tip!e overcurrent de\ices are utilized, the total of all the device ratings shall not exceed the allowed value of a single
m·e:-'"'= dev1 . Ifbom circuit breakers and fuses are used as the overcurrent device, the total of the device ratings shall not exceed that allowed for fuses.
supen isec! location is a location where conditions of maintenance and supervision ensure that only qualified persons monitor and service the transformer
~ . _.>,.
insrallation.

4 . Electronically actuated fuses that may be set to open at a specific current shall be set in accordance with settings for circuit breakers.

5. A transformer equipped with a coordinated thermal overload protection by the manufacturer shall be permitted to have separate secondary protection omitted.

Table 4.50.l.3(B) Maximum Rating or Setting of Overcurrent Protection for Transformers 1000 Volts and Less
(as a Percentage of Transformer-Rated Current)

Primary Protection Secondary Protection (See Note 2.)


Protection
Method Currents of 9 Currents Less Currents Less Currents of 9 Currents Less
Amperes or More Than 9 Amperes Than 2 Amperes Amperes or More Than 9 Amperes
Primary only
125% (See Note 1.) 167% 300% Not required Not required
protection
Primary and
secondary 250% (See Note 3.) 250% (See Note 3.) 250% (See Note 3.) 125% (See Note 3.) 167%
protection
Notes:

1. Where 125 percent of this current does not correspond to a standard rating of a fuse or nonadjustable circuit breaker, a higher rating that does not exceed the next
higher standard rating shall be permitted.

2. Where secondary overcurrent protection is required, the secondary overcurrent device shall be permitted to consist of not more than six circuit breakers or six sets
of fuses grouped in one location. Where multiple overcurrent devices are utilized, the total of all the device ratings shall not exceed the allowed value of a single
overcurrent device.

3. A transformer equipped with coordinated thermal overload protection by the manufacturer and arranged to intem1pt the primary current shall be pem1itted to
have primary overcurrent protection rated or set at a current value that is not more than six times the rated current of the transformer for transformers having not
more than 6 percent impedance and not more than four times the rated current of the transformer for transformers having more than 6 percent but not more than 10
percent impedance.

385
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECO DARY TIES)
the continuous-current rating of any series- (2) Loads Connected Between Transformer
connected devices in the autotransformer neutral Supply Points. Where load is conn ed o the tie
connection. Delayed tripping for temporary at any point between transformer -upp y poin s
overcurrents to permit the proper operation of and overcurrent protection is not proYided ·
ground-responsive tripping devices on the main accordance with Patis 2.40.1, 2.40.2 and _...,.O. ,
system shall be permitted but shall not exceed the rated ampacity of the tie shall not be le-
values that would be more than the short-time than 100 percent of the rated secondary curren-
current rating of the grounding autotransformer of the highest rated transformer supplying the
or any series connected devices in the neutral secondary tie system.
connection thereto.
Exception: Tie circuits comprised ofmultiple conductors
Exception: For high-impedance grounded systems p er phase shall be permitted to be sized and protected
covered in 2.50.2.17, where the maximum ground-fault in accordance with 4.50.1.6(A)(4).
current is designed to be not more than IO amperes,
(3) Tie Circuit Protection. Under the conditions
and where the grounding autotransformer and the
described in 4.50.1.6(A)(l) and (A)(2), both
grounding impedance are rated for continuous duty, an
supply ends of each ungrounded tie conductor
overcurrent device rated not more than 20 amperes that
shall be equipped with a protective device that
will simultaneously open all ungrounded conductors
opens at a predetermined temperature of the tie
shall be permitted to be installed on the line side of the
conductor under short-circuit conditions. This
grounding autotransformer.
protection shall consist of one of the following:
(C) Ground Reference for Damping Transitory (I) a fusible link cable connector, terminal, or
Over-voltages. A grounding autotransformer used to lug, commonly known as a limiter, each being of
limit transitory overvoltages shall be of suitable rating a size corresponding with that of the conductor
and connected in accordance with 4.50.1.S(A)(I). and of construction and characteristics according
to the operating voltage and the type of insulation
4.50.1.6 Secondary Ties. As used in this article, a
on the tie conductors or (2) automatic circuit
secondary tie is a circuit operating at 1 000 volts,
breakers actuated by devices having comparable
nominal, or less between phases that connects two power
time- current characteristics.
sources or power supply points, such as the secondaries
of two transformers. The tie shall be permitted to (4) Interconnection of Phase Conductors Between
consist of one or more conductors per phase or neutral. Transformer Supply Points. Where the tie
Conductors connecting the secondaries of transformers consists of more than one conductor per phase or
in accordance with 4.50.1.7 shall not be considered neutral, the conductors of each phase or neutral
secondary ties. shall comply with one of the following provisions.
As used in this section, the word transformer means (a) Interconnected. The conductors shall be
a transformer or a bank of transformers operating as a interconnected in order to establish a load
unit supply point, and the protective device
specified in 4.50.l.6(A)(3) shall be provided in
(A) Tie Circuits. Tie circuits shall be provided with
each ungrounded tie conductor at this point on
over-current protection at each end as required in Parts
both sides of the interconnection. The mean of
2.40.1, 2.40.2, and 2.40.8.
interconnection shall have an ampacity not less
Under the conditions described in 4.50.1.6(A)(l) and than the load to be served.
4.50.1.6(A)(2), the overcurrent protection shall be
(b) Not Interconnected. The loads shall be
permitted to be in accordance with 4.50.1.6(A)(3).
connected to one or more indi,·idual
(1) Loads at Transformer Supply Points Only. conductors of a paralleled conductor tie
Where all loads are connected at the transformer without interconnecting the conductors of each
supply points at each end of the tie and overcurrent phase or neutral and \\'ithout the protection
protection is not provided in accordance with Parts specified in 4. ~O. l .6(A)(3) at load connection
2.40.1, 2.40.2, and 2.40.8, the rated ampacity points. Where this is done, the tie conductors
of the tie shall not be less than 67 percent of of each phase or neutral shall have a combined
the rated secondary current of the highest rated capacity ampacity of not less than 133 percent
transformer supplying the secondary tie system. of the rated secondary current of the highest

386
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)
rated transformer supplying the secondary (C) Exposed Energized Parts. Switches or other
tie system, the total load of such taps shall equipment operating at 1 000 volts, nominal, or less and
not exceed the rated secondary current of the serving only equipment within a transformer enclosure
highest rated transformer, and the loads shall shall be permitted to be installed in the transformer
be equally divided on each phase and on the enclosure if accessible to qualified persons only. All
individual conductors of each phase as far as energized parts shall be guarded in accordance with
practicable. 1.10.2.2 and 1.10.3 .5.
(5) Tie Circuit Control. Where the operating voltage (D) Voltage Warning. The operating voltage of
exceeds 150 volts to ground, secondary ties exposed live parts of transformer installations shall be
provided with limiters shall have a switch at each indicated by signs or visible markings on the equipment
end that, when open, de-energizes the associated or structures.
tie conductors and limiters. The current rating 4.50.1.9 Ventilation. The ventilation shall dispose of
of the switch shall not be less than the rated the transformer full-load heat losses without creating
current ampacity of the conductors connected to a temperature rise that is in excess of the transformer
the switch. It shall be capable of interrupting its rating.
rated current, and it shall be constructed so that it FPN No. 1: See ANSI/IEEE C57.12.00- 1993, General
will not open under the magnetic forces resulting Requirements fo r Liquid-Immersed Distribution, Power, and
from short-circuit current. Regulating Transformers, and ANSI/IEEE C57.12.0l -1989,
General Requirements fo r Dry-Type Distribution and Power
(B) Overcurrent Protection for Secondary Transformers .
Connections. Where secondary ties are used, an FPN No. 2: Additional losses may occur in some transformers
overcurrent device rated or set at not more than 250 where nonsinusoidal currents are present, resulting in increased
heat in the transformer above its rating. See ANSI/IEEE C57 .110-
percent ofthe rated secondary current ofthe transformers 1993, Recommended Practice f or Establishing Transformer
shall be provided in the secondary connections of each Capability When Supplying Nonsinusoidal Load Currents, where
transformer supplying the tie system. In addition, an transformers are utilized with nonlinear loads.
automatic circuit breaker actuated by a reverse-current Transformers with ventilating openings shall be installed
relay set to open the circuit at not more than the rated so that the ventilating openings are not blocked by walls
secondary current of the transformer shall be provided or other obstructions. The required clearances shall be
in the secondary connection of each transformer. clearly marked on the transformer.
(C) Grounding. Where the secondary tie system 4.50.1.10 Grounding.
is grounded, each transformer secondary supplying
the tie system shall be grounded in accordance with (A) Dry-Type Transformer Enclosures. Where
the requirements of 2.50.2.11 for separately derived separate equipment grounding conductors and supply-
systems. side bonding jumpers are installed, a terminal bar
for all grounding and bonding conductor connections
4.50.1.7 Parallel Operation. Transformers shall be shall be secured inside the transformer enclosure.
permitted to be operated in parallel and switched as The terminal bar shall be bonded to the enclosure in
a unit, provided the overcurrent protection for each accordance with 2.50.1.12 and shall not be installed on
transfonner meets the requirements of 4.50.1.3(A) or over any vented portion of the enclosure.
for primary and secondary protective devices over 1
000 volts, or 4.50.1.3(B) for primary and secondary Exception: Where a dry-type transformer is equipped
protective devices 1 000 volts or less. with wire-type connections (leads), the grounding and
bonding connections shall be p ermitted to be connected
4.50.1.8 Guarding. Transformers shall be guarded as together using any of the methods in 2.50.1. 8 and shall
specified in 4.50.1.8(A) through (D). be bonded to the enclosure if of metal.
(A) Mechanical Protection. Appropriate provisions (B) Other Metal Parts. Where grounded, exposed
shall be made to minimize the possibility of damage non- current-carrying metal parts of transformer
to transformers from external causes where the installations, including fences, guards, and so forth,
transformers are exposed to physical damage. shall be grounded and bonded under the conditions and
(B) Case or Enclosure. Dry-type transfom1ers shall in the manner specified for electrical equipment and
be provided with a noncombustible moisture-resistant other exposed metal parts in Parts 2.50.5, 2.50.6, and
case or enclosure that provides protection against the 2.50.7.
accidental insertion of foreign objects.

387
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)
4.50.1.11 Marking. 4.50.2 Specific Provisions Applicable to Different
Types of Transformers
(A) Genera]. Each transformer shall be provided with a
nameplate giving the following information: 4.50.2.1 Dry-Type Transformers Installed Indoors.
(1) Name of manufacturer (A) Not Over 11212 kVA. Dry-type transformers
installed indoors and rated 112;,2 kVA or less shall
(2) Rated kilovolt-amperes
have a separation of at least 300 mm from combustible
(3) Frequency material unless separated from the combustibl e material
(4) Primary and secondary voltage by a fire-resistant, heat-insulated barrier.

(5) Impedance of transformers 25 kVA and larger Exception: This rule shall not apply to transformers
rated/or 1 000 volts, nominal, or less that are completely
(6) Required clearances for transformers with enclosed, except for ventilating openings.
ventilating openings
(B) Over 11212 kVA. Individual dry-type transformers
(7) Amount and kind of insulating liquid where used of more than 112;,2 kVA rating shall be installed in
(8) For dry-type transformers, temperature class for a transformer room of fire-resistant construction. Unless
the insulation system specified otherwise in this article, the term fire resistant
means a construction having a minimum fire rating of 1 hour.
(B) Source Marking. A transformer shall be permitted
to be supplied at the marked secondary voltage, Exception No. 1: Transformers with Class 155 or higher
provided that the installation is in accordance with the insulation systems and separated from combustible
manufacturer's instructions. material by afire-resistant, heat-insulating barrier or
by not less than 1800 mm and 3600 mm vertically.
4.50.1.12 Terminal Wiring Space. Th m1Il1Il1um
wire-bending space at fixed, 1000-volt and belo,Y Exception No. 2: Transformers with Class 155 or higher
terminals of tran former line and load connection in u.lation systems and completely enclosed except for
shall be as required in 3.12.1.6. Wiring pa e for pi!rtail ventilating openings.
connections shall conform to Table 3.14. __ (B). fP);: Sec A:'\S ASTM Ell9-15, Method for Fire Tests of
Building Construciion and .\.faterials.
4.50.1.13 Accessibility. All tran former- and
transformer vaults shall be readily accessible to qualified (C) Over 35000 , olts. Dry-type transformers rated
personnel for inspection and maintenance or hall m et m·er 35000 Yolt shall be installed in a
the requirements of 4.50.1. B(A) or 4 .50.1 . l 3(B). vault complying ,vitb Part 4.50.3 .

(A) Open Installations. Dry-type transformers 1 000 4.50.2.2 Dry-Type Transformers Installed Outdoors.
volts, nominal, or less, located in the open on wall , Dry-type tran formers installed outdoors shall have a
columns, or structures, shall not be required to be weatherproof enclosure.
readily accessible. Transformers exceeding 112 ;,2 k VA shall not be located
(B) Hollow Space Installations. Dry-type transformers within 300 mm of combustible materials of buildings
1 000 volts, nominal, or less and not exceeding 50 unle s the transformer has Class 155 insulation systems
kVA shall be permitted in hollow spaces of buildings or higher and is completely enclosed except for
not permanently closed in by structure, provided they entilating openings.
meet the ventilation requirements of 4.50.1.9 and 4.50.2.3 Less-Flammable Liquid-Insulated
separation from combustible materials requirements Transformers. Transformers insulated with listed less-
of 4.50.2.l(A). Transformers so installed shall not be flammable liquids that have a fire point of not less than
required to be readily accessible. 300°C shall be permitted to be installed in accordance
4.50.1.14 Disconnecting Means. Transformers, with 4.50.2.3(A) or 4.50.2.3(B).
other than Class 2 or Class 3 transformers, shall have (A) Indoor Installations. Indoor installations shall be
a disconnecting means located either in sight of the permitted in accordance with one of the following:
transfonner or in a remote location. Where located in
(1) In Type I or Type II buildings, in areas where all
a remote location, the disconnecting means shall be
of the following requirements are met:
lockable in accordance with 1.10.1.25, and its location
shall be field marked on the transformer. a. The transformer is rated 35000 volts or less.
b. No combustible materials are stored.

388
ARTICLE 4.50 - TRANSFORMERS AND TRANSFORMER VAULTS (INCLUDING SECONDARY TIES)
c. A liquid confinement area is provided. indoors and rated over 25 kVA shall be furnished with
a pressure-relief vent. Where installed in a poorly
d. The installation complies with all the restrictions
ventilated place, they shall be furnished with a means
provided for in the listing of the liquid.
for absorbing any gases generated by arcing inside the
FPN: Such restrictions may include, but are not limited to: case, or the pressure-relief vent shall be connected to
maximum pressure of the tank, use of a pressure relief valve,
a chimney or flue that carries such gases outside the
appropriate fuse types and proper sizing of overcurrent protection.
building. Askarel-insulated transformers rated over
( e) With an automatic fire extinguishing system 35000 volts shall be installed in a vault.
and a liquid confinement area, provided the
FPN: Askarel was determined to be a health hazard in 1979.
transformer is rated 35000 volts or less New installations of transfonners and other electrical equipment
containing askarel are not permitted.
(f) In accordance with 4.50.2.6
4.50.2.6 Oil-Insulated Transformers Installed
(B) Outdoor Installations. Less-flammable liquid-
Indoors. Oil-insulated transfonners installed indoors
filled transformers shall be permitted to be installed
shall be install ed in a vault constructed as specified in
outdoors, attached to, adjacent to, or on the roof of
Part 4.50 ..3
buildings, where installed in accordance with (1) or (2):
Exception Ao. I: Where the total capacity does not
(1) For Type I and Type II buildings, the installation
exceed 1121/2 kVA, the vault specified in Part 4.50.3
shall comply with all restrictions provided for in
shall be pennitted to be constructed of reinforced
the listing of the liquid.
concrete that is not less than I 00 mm thick.
FPN o. 1: Installations adjacent to combustible material, fire
escapes, or door and window openings may require additional Exception No . 2: Where the nominal voltage does not
safeguards such as those listed in 4.50.2.7. exceed I 000, a vault shall not be required if suitable
FP No. 2: Such restrictions may include, but are not limited arrangements are made to prevent a transformer oil
to: maximum pressure of the tank, use of a pressure relief fire from igniting other materials and the total capacity
valve, appropriate fuse types, and proper sizing of overcurrent in one location does not exceed JO kVA in a section of
protection. the building classified as combustible or 75 kVA where
(2) In accordance with 4.50.2.7. the surrounding structure is classified as fire-resistant
FPN No. 1: As used in this section, Type I and Type II buildings
construction.
refers to Type I and Type II building construction as defined in Exception No. 3: Electric furna ce transformers that
NFPA 220-2015, Standard on Types of Building Construction.
Combustible materials refers to those materials not classified as
have a total rating not exceeding 75 kVA shall be
noncombustible or limited-combustible as defined in ~lfPA 220- permitted to be installed without a vault in a building
2015, Standard on type of Building Construction. or room offire-resistant construction, provided suitable
FPN No. 2: See definition of Listed in Article 1.1 arrangements are made to prevent a transformer oil fire
fi ·om spreading to other combustible material.
4.50.2.4 Nonflammable Fluid-Insulated
Transformers. Transformers insulated with a dielectric Exception No. 4: A transformer that has a total
fluid identified as nonflammable shall be permitted to be rating not exceeding 75 kVA and a suppZy voltage of
installed indoors or outdoors. Such transformers installed l 000 volts or less that is an integral part of charged-
indoors and rated over 35000 volts shall be installed in a particle-accelerating equipment shall be permitted
vault. Such transformers installed indoors shall be furnished to be installed without a vault in a building or room
with a liquid confinement area and a pressure-relief vent. The of noncombustible or fire- resistant construction,
transformers shall be furnished with a means for absorbing pro ided suitable arrangements are made to prevent a
any gases generated by arcing inside the tank, or the pressure- transfonner oilfire from spreading to other combustible
relief vent shall be connected to a chimney or flue that will material.
carry such gases to an environmentally safe area.
Exception No. 5: Transformers shall be permitted to be
FPN: Safety may be increased if fire hazard installed in a detached building that does not compZv
analyses are performed for such transformer installations.
with Part 4.50.3 if neither the building nor its contents
For the purposes of this section, a nonflammable present a fire hazard to any other building or property,
dielectric fluid is one that does not have a flash point or and if the building is used only in supplying electric
fire point and is not flammable in air. service and the interior is accessible onZv to qualified
4.50.2.5 Askarel-Insulated Transformers Installed p ersons.
Indoors. Askarel-insulated transformers installed Exception No. 6: Oil-insulated transformers shall be

389
ARTICLE 4.50 - TRA SFORMERS AND TRANSFORMER VAULTS (INCLUDING SECO DARY TIES)
permitted to be used without a vault in portable and have approved structural strength for the conditions
mobile surface mining equipment (such as electric with a minimum fire resistance of 3 hours. The floors
excavators) if each of the following conditions is met: of vaults in contact with the earth shall be of concrete
that is not less than 100 mm thick, but, where the \·ault
(a) Provision is made for draining leaking.fluid to the
is constructed with a vacant space or other stories be]o,,·
ground.
it, the floor sha11 have approved structural strength for
(b) Safe egress is provided for personnel. the load imposed thereon and a minimum fire resistance
(c) A minimum 6 mm steel barrier is provided for of 3 hours. For the purposes of this section, studs and
p ersonnel protection. wallboard construction shall not be permitted.

4.50.2.7 Oil-Insulated Transformers Installed Exception: Where transformers are protected with
Outdoors. Combustible material, combustible automatic sprinkler, water spray, carbon dioxide, or
buildings, and parts of buildings, fire escapes, and halon, construction of I-hour rating shall be permitted.
door and window openings shall be safeguarded from FPN No. 1: For additional information, see ANSI/ASTM Ell 9-
fires originating in oil-insulated transformers installed 15, Method/or Fire Tests ofBuilding Construction and Materials.
on roofs, attached to or adjacent to a building or FP No. 2: A typical 3-hour construction is 150 mm thick
combustible material. reinforced concrete.

In cases where the transformer installation presents a 4.50.3.3 Doonvays. Vault doorways shall be protected
fire hazard, one or more of the following safeguards in accordance with 4.50.3.3(A), (B), and (C).
shall be applied according to the degree of hazard (A) Type of Door. Each doorway leading into a vault
involved: from the building interior shall be provided with a tight-
(1) Space separations fitting door that has a minimum fire rating of 3 hours.
It shall be permitted to have such a door for an exterior
(2) Fire-resistant barriers
wall opening where conditions warrant.
(3) Automatic fire suppression systems Exception: Where transformers are protected with
(4) Enclosures that confine the oil of a ruptured automatic sprinkler, water spray, carbon dioxide, or
transformer tank halon, construction of I -hour rating shall be permitted.
Oil enclosures shall be permitted to consist of fire- FPN: For additional information, see NFPA 80-2013 , Standard
f or Fire Doors and Other Opening Protectives .
resistant dikes, curbed areas or basins, or trenches filled
with coarse, crushed stone. Oil enclosures shall be (B) Sills. A door sill or curb that is of an approved height
provided with trapped drains where the exposure and that wi11 confine the oil from the largest transformer
the quantity of oil involved are such that removal of oil within the vault shall be provided, and in no case shall
is important. the height be less than 100 mm.
FPN: For additional information on transformers installed on (C) Locks. Doors shall be equipped with locks, and
poles or structures or underground, see ANSI C2-2007 , National
doors shall be kept locked, acces being allowed only
Electrical Safety Code.
to qualified persons. Personnel doors shall open in the
4.50.2.8 Modification of Transformers. When direction of egress and be equipped with listed panic
modifications are made to a transformer in an existing hardware.
installation that change the type of the transformer
4.50.3 .5 Ventilation Openings. Where required by
with respect to Part II of this article, such transformer
4.50.1.9, openings for ventilation shall be provided in
shall be marked to show the type of insulating liquid
accordance with 4.50.3.5(A) through (F).
installed, and the modified transfonner installation shall
comply with the applicable requirements for that type (A) Location. Ventilation openings shall be located as
of transformer. far as possible from doors, windows, fire escapes, and
combustible material.
4.50.3 Transformer Vaults
(B) Arrangement. A vault ventilated by natural
4.50.3.1 Location. Vaults shall be located where they
circulation of air shall be permitted to have roughly half
can be ventilated to the outside air without using flues
of the total area of openings required for ventilation in
or ducts wherever such an arrangement is practicable.
one or more openings near the floor and the remainder
4.50.3.2 Walls, Roofs, and Floors. The walls and in one or more openings in the roof or in the sidewalls
roofs of vaults shall be constrncted of materials that near the roof, or all of the area required for ventilation

390
ARTICLE 4.55 - PHASE CONVERTERS
shall be permitted in one or more openings in or near Rotary-Phase Converter. A device that consists of a
the roof. rotary transformer and capacitor panel(s) that permits
the operation of 3-phase loads from a single-phase
(C) Size. For a vault ventilated by natural circulation
of air to an outdoor area, the combined net area of all supply.
ventilating openings, after deducting the area occupied Static-Phase Converter. A device without rotating
by screens, gratings, or louvers, shall not be less than parts, sized for a given 3-phase load to permit operation
1900 mm2 per kVA of transformer capacity in service,
from a single-phase supply.
and in no case shall the net area be less than 0.1 m 2 for
any capacity under 50 kVA. 4.55.1.3 Other Articles. Phase converters shall comply
(D) Covering. Ventilation openings shall be covered with this article and with the applicable provisions of
with durable gratings, screens, or louvers, according other articles of this Code.
to the treatment required in order to avoid unsafe
conditions. 4.55.1.4 Marking. Each pha e conYe11er shall be
provided with a permanent nameplate indicating the
(E) Dampers. All ventilation openings to the indoors
shall be provided with automatic closing fire dampers following:
that operate in response to a vault fire. Such dampers ( 1) Manufacturer's name
shall possess a standard fire rating of not less than 112
hours. (2) Rated input and output Yoltages

FPN: See ANSI/UL 555-2011, Standard/or Fire Dampers. (3) Frequency

(F) Ducts. Ventilating ducts shall be constructed of fire- (4) Rated single-phase input full-load amperes

resistant material. (5) Rated minimum and maximum single load m


kilovolt-amperes (kVA) or horsepower
4.50.3.6 Drainage. Where practicable, vaults
containing more than 100 kVA transformer capacity (6) Maximum total load in kiloYolt-amperes (kVA)
shall be provided with a drain or other means that will or horsepower
carry off any accumulation of oil or water in the vault (7) For a rotary-phase converter. 3-phase amperes at
unless local conditions make this impracticable. The full load
floor shall be pitched to the drain where provided.
4.55.1.5 Equipment Grounding Connection. A
4.50.3.7 Water Pipes and Accessories. Any pipe or means for attachment of an equipment grounding
duct system foreign to the electrical installation shall conductor termination in accordance with 2.50.1.8 shail
not enter or pass through a transformer vault. Piping or be provided.
othe facilities provided for vault fire protection, or for
transrormer cooling, shall not be considered foreign to 4.55.1.6 Conductors.
the ele .trical in tallation. (A) Ampacity. The ampacity of the single-phase supply
4.50.3.8 Storage in Vaults. Materials shall not be stored conductors shall be determined by 4.55. l.6(A)(l) or
in transformer Yaul -. (A)(2).
FPN: Single-phase conductors sized to preYent a Yoltage drop
ARTICLE 4.55 - PH.A.SE COI\VERTERS
not exceeding 3 percent from the source of supply to the phase
4.55.1 General converter may help ensure proper starLlll,, and operation of motor
loads.
4.55.1.1 Scope. This article coYers the installation and
(1) Variable Loads. Where the loads to be supplied
u e of phase onYerters.
are variable, the conductor ampacity shall not
4.55.1.2 Definitions. be less than 125 percent of the phase converter
Manufactured Phase. The manufactured or derived nameplate single-phase input full-load amperes.
phase originates at the phase converter and is not (2) Fixed Loads. Where the phase converter supplies
solidly connected to either of the single-phase input specific fixed loads, and the conductor ampacity
conductors. is less than 125 percent of the phase conve1ier
Phase Converter. An electrical device that converts nameplate single-phase input full-load amperes,
single-phase power to 3-phase electric power. the conductors shall have an ampacity not less
than 250 percent of the sum of the full-load,
FPN : Phase converters have characteristics that modify the starting
3-phase current rating of the motors and other
torque and locked-rotor current of motors served, and consideration
is required in selecting a phase converter for a specific load. loads served where the input and output voltages

391
ARTICLE 4.55 - PHASE CONVERTERS

of the phase converter are identical. Where the (2) Horsepower Rated Disconnect. T:::.:
input and output voltages of the phase converter disconnecting means shall be a switch with ~
are different, the current as detennined by this
horsepower rating. The equivalent locked ro,0:-
section shall be multiplied by the ratio of output current of the horsepower rating of the s,\·j-~'.:.
to input voltage.
shall not be less than 200 percent of the sum o~
(B) Manufactured Phase Marking. The manufactured the following:
phase conductors shall be identified in all accessible (1) Nonmotor loads
locations with a distinctive marking. The marking shall
be consistent throughout the system and premises. (2) The 3-phase, locked-rotor current of the large-:
motor as determined from Table 4.30. l 4.5(B)
4.55.1.7 Overcurrent Protection. The single-phase
supply conductors and phase converter shall be protected (3) The full-load current of all other 3-phase motors
from overcurrent by 4.55.l.7(A) or (B). Where the operating at the same time
required fuse or nonadjustable circuit breaker rating or (D) Voltage Ratios . The calculations in 4.55.l.8(C)
settings of adjustable circuit breakers do not correspond shall apply directly where the input and output voltages
to a standard rating or setting, a higher rating or setting of the phase converter are identical. Where the input
that does not exceed the next higher standard rating and output voltages of the phase converter are different,
shall be permitted. the current shall be multiplied by the ratio of the output
(A) Variable Loads. Where the loads to be supplied to input voltage.
are variable, overcurrent protection shall be set at not 4.55.1.9 Connection of Single-Phase Loads. Where
more than 125 percent of the phase converter nameplate single-phase loads are connected on the load side of
single-phase input full-load amperes. a phase converter, they shall not be connected to the
(B) Fixed Loads. Where the phase converter supplies manufactured phase.
specific fixed loads and the conductors are sized in
accordance with 4.55. l .6(A)(2), the conductors shall 4.55.1.10 Terminal Housings. A terminal housing in
be protected in accordance with their ampacity. The accordance with the provisions of 4.30.1.12 shall be
overcunent protection determined from this section provided on a phase converter.
shall not exceed 125 percent of the phase converter 4.55.2 Specific Provisions Applicable to Different
nameplate single-phase input amperes. Types of Phase Converters
4.55.1.8 Disconnecting Means. Means shall be 4.55.2.1 Disconnecting Means. The single-phase
provided to disconnect simultaneously all ungrounded disconnecting means for the input of a static phase
single-phase supply conductors to the phase converter. converter shall be permitted to serve as the disconnecting
(A) Location. The disconnecting means shall be readily means for the phase converter and a single load if the
accessible and located in sight from the phase converter. load is within sight of the disconnecting means.
(B) Type. The disconnecting means shall be a switch 4.55.2.2 Start-Up. Power to the utilization equipment
rated in horsepower, a circuit breaker, or a molded- shall not be supplied until the rotary-phase converter
case switch. Where only nomnotor loads are served, an has been started.
ampere-rated switch shall be permitted. 4.55.2.3 Power Interruption. Utilization equipment
(C) Rating. The ampere rating of the disconnecting supplied by a rotary-phase converter shall be controlled
means shall not be less than 115 percent of the rated in such a manner that power to the equipment will be
maximum single-phase input full-load amperes or, for disconnected in the event of a power interruption.
specific fixed loads, shall be permitted to be selected FPN: Magnetic motor starters, magnetic contactors, and similar
from 4.55.1.8(C)(l) or (C)(2). devices, with manual or time delay restarting for the load, provide
restarting after power interruption.
(1) Current Rated Disconnect. The disconnecting
means shall be a circuit breaker or molded-case 4.55.2.4 Capacitors. Capacitors that are not an integral
switch with an ampere rating not less than 250 part of the rotary-phase conversion system but are
percent of the sum of the following: installed for a motor load shall be collilected to the line
side of that motor overload protective device.
(1) Full-load, 3-phase current ratings of the motors
(2) Other loads served

392
ARTICLE 4.60 - CAPACITORS
ARTICLE 4.60 - CAPACITORS in no case less than 135 percent of the rated current of
the capacitor.
4.60.1.1 Scope. This article covers the installation of
capacitors on electrical circuits. (B) Overcurrent Protection. An overcurrent device
shall be provided in each ungrounded conductor for each
Surge capacitors or capacitors included as a component
capacitor bank. The rating or setting of the overcurrent
part of other apparatus and conforming with the
device shall be as low as practicable.
requirements of such apparatus are excluded from these
requirements. Exception: A separate overcurrent device shall not be
required for a capacitor connected on the load side of a
This article also covers the installation of capacitors in
motor overload protective device.
hazardous (classified) locations as modified by Articles
5.1 through 5.3. (C) Disconnecting Means. A disconnecting means
shall be provided in each ungrounded conductor for
4.60.1.2 Enclosing and Guarding.
each capacitor bank and shall meet the following
(A) Containing More Than 11 L of Flammable requirements:
Liquid. Capacitors containing more than 11 L of
( 1) The disconnecting means shall open all
flammable liquid shall be enclosed in vaults or outdoor ungrounded conductors simultaneously.
fenced enclosures complying with Part 1.10.3. This
limit shall apply to any single unit in an installation of (2) The disconnecting means shall be permitted to
disconnect the capacitor from the line as a regular
capacitors.
operating procedure.
(B) Accidental Contact. Where capacitors are
(., ) The ra ing of the disconnecting means shall not
accessible to unauthorized and unqualified persons, be les than 135 percent of the rated current of
they shall be enclosed, located, or guarded so that th capaci-or.
persons cannot come into accidental contact or bring
conducting materials into accidental contact \\·ith Exception: A separate disconnecting means shall not
exposed energized parts, terminals, or buses as ociated be required n·here a capacitor is connected on the load
with them. However, no additional guarding i required side of a n otor controller.
for enclosures accessible only to aurhoriz d and 4.60.1.9 Rating or Setting of Motor Overload
qualified persons. De,ice. VI nere a motor installation includes a capacitor
4.60.11000 Volts, Nominal, and Under connected on the load side of the motor overload device,
the rating or setting of the motor overload device shall
4.60.1.6 Discharge of Stored Energy. Capacitors shall be based on the improved power factor of the motor
be provided with a means of discharging stored energy. circuit.
(A) Time of Discharge. The residual voltage of The effect of the capacitor shall be disregarded m
a capacitor shall be reduced to 50 volts, nominal, or determining the motor circuit conductor rating m
less within 1 minute after the capacitor is disconnected accordance with 4.30.2.2.
from the source of supply.
4.60.1.10 Grounding. Capacitor cases shall be
(B) Means of Discharge. The discharge circuit connected to the equipment grounding conductor.
shall be either permanently connected to the terminals
of the capacitor or capacitor bank or provided with Exception: Capacitor cases shall not be connected to
automatic means of connecting it to the terminals of the equipment grounding conductor where the capacitor
the capacitor bank on removal of voltage from the units are supported on a structure designed to operate
line. Manual means of switching or connecting the at other than ground potential.
discharge circuit shall not be used. 4.60.1.12 Marking. Each capacitor shall be provided
4.60.1.8 Conductors. with a nameplate giving the name of the manufacturer,
rated voltage, frequency, kilovar or amperes, number
(A) Ampacity. The ampacity of capacitor circuit of phases, and, if filled with a combustible liquid, the
conductors shall not be less than 135 percent of the rated volume of liquid. Where filled with a nonflam.mable
current of the capacitor. The ampacity of conductors liquid, the nameplate shall so state. The nameplate shall
that connect a capacitor to the terminals of a motor or also indicate whether a capacitor has a discharge device
to motor circuit conductors shall not be less than one- inside the case.
third the ampacity of the motor circuit conductors and

393
ARTICLE 4.60 - CAPACITORS

(C) Protected Individually or in Groups. Capacitors


4.60.2 Over 1000 Volts, Nominal
shall be permitted to be protected individually or in
4.60.2.1 Switching. groups.
(A) Load Current. Group-operated switches shall be (D) Protective Devices Rated or Adjusted. Protective
used for capacitor switching and shall be capable of the devices for capacitors or capacitor equipment shall be
following: rated or adjusted to operate within the limits of the safe
(1) Carrying continuously not less than 135 percent zone for individual capacitors. If the protective devices
of the rated current of the capacitor installation are rated or adjusted to operate within the limits for
Zone 1 or Zone 2, the capacitors shall be enclosed or
(2) Interrupting the maximum continuous load isolated.
current of each capacitor, capacitor bank, or
capacitor installation that will be switched as a In no event shall the rating or adjustment of the
unit protective devices exceed the maximum limit of Zone
2.
(3) Withstanding the maximum inrush current,
FPN: For definitions of Safe Zone, Zone 1, and Zone 2, see ANSI/
including contributions from adjacent capacitor IEEE 18-1992, Shunt Power Capacitors.
installations
4.60.2.3 Identification. Each capacitor shall be provided
(4) Carrying currents due to faults on capacitor side with a permanent nameplate giving the manufacturer's
of switch name, rated voltage, frequency, kilovar or amperes,
(B) Isolation. number of phases, and the volume of liquid identified
as flammable, if such is the case.
(1) General. A means shall be installed to isolate
from all sources of voltage each capacitor, 4.60.2.4 Grounding. Capacitor cases shall be connected
capacitor bank, or capacitor installation that will to the equipment grounding conductor. If the capacitor
be removed from service as a unit. The isolating neutral point is connected to a grounding electrode
means shall provide a visible gap in the electrical conductor, the connection shall be made in accordance
circuit adequate for the operating voltage. with Part 2.50.3.

(2) Isolating or Disconnecting Switches with No Exception: Capacitor cases shall not be connected to
Interrupting Rating. Isolating or disconnecting the equipment grounding conductor where the capacitor
switches (with no interrupting rating) shall be units are supported on a structure designed to operate
interlocked with the load-interrupting device or at other than ground p otential.
shall be provided with prominently displayed 4.60.2.5 Means for Discharge.
caution signs in accordance with 4.90.2.2 to (A) Means to Reduce the Residual Voltage. A means
prevent switching load current. shall be provided to reduce the residual -.,;oltag:e of a
(C) Additional Requirements for Series Capacitors. capacitor to -o volts or less "ithin 5 minutes after the
The proper switching sequence shall be ensured by use capacitor is disconnected from the source of supply.
of one of the following: (B) Connection to Terminals. A discharge circuit
shall be either permanently connected to the terminals
(1) Mechanically sequenced isolating and bypass
of the capacitor or pro\ided \\ith automatic means of
switches connecting it to the terminals of the capacitor bank
(2) Interlocks after disconnection of the capacitor from the source of
supply. The windings of motors, transformers, or other
(3) Switching procedure prominently displayed at the equipment directly connected to capacitors without a
switching location switch or overcurrent device interposed shall meet the
requirements of 4.60.2.S(A).
4.60.2.1 Overcurrent Protection.
ARTICLE 4.70 - RESISTORS AND REACTORS
(A) Provided to Detect and Interrupt Fault Current.
A means shall be provided to detect and interrupt fault 4.70.11000 Volts, Nominal, and Under
current likely to cause dangerous pressure within an
4.70.1.1 Scope. This article covers the installation of
individual capacitor.
separate resistors and reactors on electrical circuits.
(B) Single Pole or Multipole Devices. Single-pole or
Exception: Resistors and reactors that are component
multipole devices shall be permitted for this purpose.
parts of other apparatus.

394
ARTICLE 4.80 - STORAGE BATTERIES
This article also covers the installation of resistors and comply with applicable requirements of Article 4.50.
reactors in hazardous (classified) locations as modified
ARTICLE 4.80 - STORAGE BATTERIES
by Articles 5.1 through 5.4.
4.80.1.1 Scope. The provisions of this article shall
4.70.1.2 Location. Resistors and reactors shall not be apply to all stationary installations of storage batteries.
placed where exposed to physical damage. FPN: The following standards are frequently referenced for the
installation of stationary batteries:
4.70.1.3 Space Separation. A thermal barrier shall be (1) IEEE 484, Recommended Practice for Installation Design
required if the space between the resistors and reactors and Installation of Vented Lead-Acid Batteries for Stationary
and any combustible material is less than 300 mm. Applications
(2) IEEE 485 , Recommended Practice for Sizing Vented Lead-
4.70.1.4 Conductor Insulation. Insulated conductors Acid Storage Batteries for Stationary Applications
used for connections between resistance elements and (3) IEEE 1145, Recommended Practice for Installation and
controllers shall be suitable for an operating temperature Maintenance ofNickel-Cadmium Batteries for Photovoltaic (PV)
of not less than 90°C. Systems

Exception: Other conductor insulations shall be (4) IEEE 1187, Recommended Practice for Installation Design,
and Installation of Valve-Regulated Lead- Acid Batteries for
permitted for motor starting service. Stationan Applications
(5) IEEE 1375, IEEE Guide fo r the Protection of Stationary
4.70.2 Over 1000 Volts, Nominal
Battery Systems

4.70.2. lGeneral. (6) IEEE 15 8, Recommended Pracricefor Stationary Battery


Electrolyte Spill Containmem and Management
(A) Protected Against Physical Damage. Resistors (7) IEEE 1635/ ASHR.AE, Guide fo r the Ventilation and Thermal
and reactors shall be protected against physical damage. Management of Baueries fo r Stationary Applications
(B) Isolated by Enclosure or Elevation. Resistors (8) UL 19 3, Standard for Bc.:rmes or 'se in Light Electric Rail (LER)
Applicanons and Starior.ary Ar,- ::ca:,or.s
and reactors shall be isolated by enclosure or elevation
(9) UL Subject 2-136. Out ir.e~ Jr.:esnganonfor Sp1'i Containmentfor Stationary
to protect personnel from accidental contact with Lead Acid Banery Sysrerr.s
energized parts. ( 10) UL 1989, Standard for S:.ir.tiir.· Ba:teries
(C) Combustible Materials. Resistors and reactors
hall not be installed in close enough proximity to 4.80.1.2 Definitions.
combustible materials to constitute a fire hazard and Cell. The basic electrochemical unit, characterized
hall have a clearance of not less than 300 mm from by an anode and a cathode, used to receive, store, and
combustible materials. deliver electrical energy.
(D) Clearances. Clearances from resistors and reactors Container. A vessel that holds the plates, electrolyte,
to grounded surfaces shall be adequate for the voltage and other elements of a single unit in a battery.
involved.
FPN: A container may be ingle-cell or multi-cell and is sometimes
(E) Temperature Rise from Induced Circulating referred to in the industry as a ' j ar."
Currents. Metallic enclosures of reactors and adjacent Electrolyte. The medium that provides the 10n
metal parts shall be installed so that the temperature rise transport mechanism bet\\ een the positive and
from induced circulating currents is not hazardous to negative electrodes of a cell.
personnel or does not constitute a fire hazard.
Intercell Connector. /'ill electrically conductive bar or
4. 70.2.2 Grounding. Resistor and reactor cases cable used to connect adjacent cells.
or enclosures shall be connected to the equipment
grounding conductor. Intertier Connector. An electrical conductor used
to connect two cells on different tiers of the same rack
Exception: Resistor or reactor cases or enclosures or different shelves of the same rack.
supported on a structure designed to operate at other
than ground potential shall not be connected to the Nominal Voltage (Battery or Cell). The value
equipment grounding conductor: assigned to a cell or battery of a given voltage class for
the purpose of convenient designation. The operating
4.70.2.3 Oil-Filled Reactors. Installation of oil-filled voltage of the cell or battery may vary above or below
reactors, in addition to the above requirements, shall this value.
395
ARTICLE 4.80 - STORAGE BATTERIES
FPN: The most common nominal cell voltages are 2 volts per cell this Code applying to wiring and equipment operating
for the lead-acid systems, 1.2 volts per cell for alkali systems, at the same voltage, unless otherwise permitted by
and 3.6 to 3.8 volts per cell for Li-ion systems. Nominal voltages
might vary with different chemistries.
4.80.1.6.

Sealed Cell or Battery. A cell or battery that has no 4.80. l.6 Overcurrent Protection for Prime Movers.
provision for the routine addition of water or electrolyte Over-cunent protection shall not be required for
or for external measurement of electrolyte specific conductors from a battery with a voltage of 60 volts
gravity and might contain pressure relief venting. de or less if the battery provides power for stmting,
ignition, or control of prime movers. Section 3.0.1.3
Storage Battery. A battery comprised of one or more shall not apply to these conductors.
rechargeable cells of the lead-acid, nickel-cadmium, or
other rechargeable electrochemical types. 4.80.1.7 DC Disconnect Methods.

Terminal. That part of a cell, container, or battery (A) Disconnecting Means. A disconnecting means shall
to which an external connection is made (commonly be provided for all ungrounded conductors derived from
identified as post, pillar, pole, or terminal post). a stationary battery ystem with a \'Oltage over 60 volts
de. A disconnecting mean shaII be readily accessible
4.80.1.3 Equipment. Storage batteries and battery and located "·ithin ight of the battery system.
management equipment shall be listed. This requirement
FP:\": See 2.-+0.2. (H I for information on the location of the
shall not apply to lead-acid batteries. o\·ercurrent d \-i e for b3.~~ry ~or:du -..tor:-,.
4.80.1.4 Battery and Cell Terminations. (B) Remote Actuation. \\nere a disconnecting with
(A) Corrosion Prevention. Where mating dissimilar 4.80.1 . (A). i- pro\i' \\ r o e controls to activate
metals, antioxidant material suitable for the battery the disconnec · .g ea - a d the controls for the
connection shall be used where recommended by the disconnecting mean are not lo ated within sight of the
battery manufacturer. stationary ba .ery y -:rem, the disconnecting means
shall be capa l of eing locked in the open position,
FPN: The battery manufacturer's installation and instruction
manual can be used for guidance for acceptable materials. in accordance ,..it. . 0.1 .25, and the location of the
controls sha 1 be neld marked on the disconnecting
(B) lntercell and Intertier Conductors and means.
Connections. The ampacity of field-assembled
intercell and intertier connectors and conductors shall (C) Busway. Where a DC busway system is installed,
be of such cross-sectional area that the temperature the disconne ring ean shaII be permitted to be
rise under maximum load conditions and at maximum incorporated · o -he S\Yay.
ambient temperature shall not exceed the safe (D) Notification. The disconnecting means shall be
operating temperature of the conductor insulation or legibly marked in he field. A label with the marking
of the material of the conductor supports. shaII be placed in a con picuous location near the
FPN: Conductors sized to prevent a voltage drop exceeding 3 percent battery if a disconnecting means is not provided. The
of maximum anticipated load, and where the maximum total marking shaII be of ufficient durability to withstand the
voltage drop to the furthest point of connection does not exceed environment inYoh·ed and shall include the following:
5 percent, may not be appropriate for all battery applications. IEEE
1375-2003, Guide.for the Protection of Stationary Battery Systems, (1 ) ominal battery Yoltage
provides guidance for overcurrent protection and associated cable
sizing. (2) Maximum a ailable short-circuit current derived
from the stationary battery system
(C) Battery Terminals. Electrical connections to the
battery, and the cable(s) between cells on separate (3) Date the calculation \ms performed
levels or racks, shall not put mechanical strain on the FPN No. l: Battery equipment suppliers can provide information
battery terminals. Terminal plates shall be used where about short-circuit current on any particular battery model.
practicable. FP · No. 2: The available short-circuit current marking(s)
FPN: Conductors are commonly pre-formed to eliminate stress addressed in 480.7(D)(2) is related to required short-circuit current
on battery terminations. Fine stranded cables may also eliminate ratings of equipment. NFPA 70E-201 5, Standard.for Electrical
the stress on battery terminations. See the manufactmer's Safety in the Workplace, provides assistance in determining the
instructions for guidance. severity of potential exposure, planning safe work practices, and
selecting personal protective equipment.
4.80.1.5 Wiring and Equipment Supplied from
Batteries. Wiring and equipment supplied from storage 4.80.1.8 Insulation of Batteries. Batteries constructed
batteries shall be subject to the applicable provisions of of an electrically conductive container shall have

"96
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
insulating support if a voltage is present between the FPN: IEEE 1187-2013, IEEE Recommended Practice for
container and ground. Installation Design and Installation of Valve-Regulated Lead-
Acid Batteries for Stationmy Applications, provides guidance for
4.80.1.9 Battery Support Systems . . For battery top clearance of valve-regulated lead-acid batteries, which are
chemistries with corrosive electrolyte, the structure that commonly used in battery cabinets.
supports the battery shall be resistant to deteriorating (E) Egress. A personnel door( s) intended for entrance
action by the electrolyte. Metallic structures shall be to, and egress from, rooms designated as battery
provided with nonconducting support members for rooms shall open in the direction of egress and
the cells, or shall be constrncted with a continuous shall be equipped with listed panic hardware.
insulating material. Paint alone shall not be considered
(F) Piping in Battery Rooms. Gas piping shall not be
as an insulating material.
permitted in dedicated battery rooms.
The terminals of all cells or multi-cell units shall
(G) Illumination. Illumination shall be provided
be readily accessible for readings, inspection, and
cleaning where required by the equipment design. One for working spaces containing battery systems. The
lighting outlets shall not be controlled by automatic
side of transparent batte1y containers shall be readily
means only. Additional lighting outlets shall not be
accessible for inspection of the internal components.
required where the work space is illuminated by an
4.80.1.10 Battery Locations. Battery locations shall adjacent light source. The location of luminaires shall
conform to 4.80.1.1 O(A), (B), and (C). not:
(1) Expose personnel to energized battery
(A) Ventilation. Provisions appropriate to the battery
components while perfonning maintenance on
technology shall be made for sufficient diffusion and
the luminaires in the batte1y space; or
ventilation of gases from the battery, if present, to
prevent the accumulation of an explosive mixture. (2) Create a hazard to the battery upon failure of the
FP No. 1: See FPA 1-2015, Fire Code, Chapter 52, for luminaire.
ventilation considerations for specific battery chemistries.
FP~ o. 2: Some battery technologies do not require ventilation. 4.80.1.11 \ ents.

FP~ No. 3: For additional information on the wntilation of (A) \ ented Cells. Each vented cell shall be equipped
stationary battery systems, see IEEE Srd 1635-_0!2/ ASHRAE with a flame arrester.
Guideline 21-- 01- Guide for rhe iemilarion and Thermal
.".fanagement ofBatteries for St tionary Applicatior.s. FP:\": ..\ flame arrester prevents destruction of the cell due to
ignition of gases within the cell by an external spark or flame.
(B) Live Parts. Guarding of liYe part- hall comply
(B) Sealed Cells. Where the batte1y is constructed such
with 1.10.2.2.
that an excessive accumulation of pressure could occur
(C) Spaces Abont Battery Systems. Spa es about within the cell during operation, a pressure-release vent
battery s, stems shall comply with 1.10.2.1. Working shall be provided.
space shall be measured from the edge of the battery
cabinet, racks, or trays. ARTICLE 4.90 - EQUIPMENT OVER 1000
VOLTS, NOMINAL
For battery racks, there sha11 be a mm1mum
clearance of 25 mm between a cell container and 4.90.1 General
any wall or structure on the side not requiring access
4.90.1.1 Scope. This article covers the general
for maintenance. Battery stands shall be permitted to
requirements for equipment operating at more than
contact adjacent walls or structures provided that the
1000 volts, nominal.
battery shelf has a free air space for not less than 90
percent of its length. FPN No. 1: See NFPA 70£-20 15, Standard for Electrical Safety
in the Wor!..place, for electrical safety requirements for employee
FPN: Additional space is often needed to accommodate workplaces.
battery hoisting equipment, tray removal, or spill containment.
FPN No. 2: For further information on hazard signs and labels,
(D) Top Terminal Batteries. Where top terminal see ANSI 2535.4-2011, Product Signs and Safety Labels.
batteries are installed on tiered racks or on shelves
4.90.1.2 Definition.
battery cabinets, working space in accordance with
the battery manufacturer's instructions shall be High Voltage. For the purposes of this article, more
provided between the highest point on a cell and than 1000 volts, nominal.
the row, shelf, or ceiling above that point.

39
ARTICLE 4.90-EQUIPMENT OVER 1000 VOLTS, NOMINAL
4.90.1.3 Other Articles. manufacturer's name or trademark, manufacturer's
type or identification number, continuous current
(A) Oil-Filled Equipment. Installation of electrical
rating, interrupting rating in megavolt-amperes
equipment, other than transformers covered in Article
(MVA) or amperes, and maximum voltage raring.
4.50, containing more than 38 L of flammable oil per
Modification of a circuit breaker affecting i
unit shall meet the requirements of Parts 4.50.2 and
rating(s) shall be accompanied by an appropriate
4.50.3
change of nameplate information.
(B) Enclosures in Damp or Wet Locations. Enclosures
(4) Rating. Circuit breakers shall have the following
in damp or wet locations shall meet the requirements of
ratings:
3.12.1.2.
(1) The continuous current rating of a circuit
4.90.2 Equipment - Specific Provisions
breaker shall not be less than the maximum
continuous current through the circuit breaker.
4.90.2.1 Circuit-Interrupting Devices.
(2) The interrupting rating of a circuit breaker shall
(A) Circuit Breakers.
not be less than the maximum fault current the
(1) Location. circuit breaker will be required to interrupt,
(1) Circuit breakers installed indoors shall be including contributions from all connected
mounted either in metal-enclosed units or sources of energy.
fire-resistant cell-mounted units, or they shall (3) The closing rating of a circuit breaker shall not
be permitted to be open-mounted in locations be less than the maximum asymmetrical fault
accessible to qualified persons only. current into which the circuit breaker can be
(2) Circuit breakers used to control oil-filled closed.
transformers in a vault shall either be located (4) The momentary rating of a circuit breaker shall
outside the transformer vault or be capable of not be less than the maximum asymmetrical
operation from outside the vault. fault current at the point of installation.
(3) Oil circuit breakers shall be arranged or located (5) The rated maximum voltage of a circuit breaker
so that adjacent readily combustible structures shall not be less than the maximum circuit
or materials are safeguarded in an approved voltage.
manner.
(B) Power Fuses and Fuseholders.
(2) Operating Characteristics. Circuit breakers
(1) Use. Where fuses are used to protect conductors
shall have the following equipment or operating
and equipment, a fuse shall be placed in each
characteristics:
ungrounded conductor. Two power fuses shall
(1) An accessible mechanical or other identified be permitted to be used in parallel to protect the
means for manual tripping, independent of same load if both fuses have identical ratings and
control power both fuses are installed in an identified common
(2) Be release free (trip free) mounting with electrical connections that divide
the current equally. Power fuses of the vented
(3) If capable of being opened or closed manually type shall not be used indoors, underground, or
while energized, main contacts that operate in metal enclosures unless identified for the use.
independently of the speed of the manual
operation (2) Interrupting Rating. The interrupting rating of
power fuses shall not be less than the maximum
(4) A mechanical position indicator at the circuit fault current the fuse is required to interrupt,
breaker to show the open or closed position of including contributions from all connected
the main contacts sources of energy.
(5) A means of indicating the open and closed (3) Voltage Rating. The maximum voltage rating of
position of the breaker at the point(s) from power fuses shall not be less than the maximum
which they may be operated circuit voltage. Fuses having a minimum
(3) Nameplate. A circuit breaker shall have a recommended operating voltage shall not be
permanent and legible nameplate showing applied below this voltage.

398
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
(4) Identification of Fuse Mountings and Fuse (2) Operation. Where fused cutouts are not suitable
Units. Fuse mountings and fuse units shall have to interrupt the circuit manually while carrying
permanent and legible nameplates showing the full load, an approved means shall be installed
manufacturer's type or designation, continuous to interrupt the entire load. Unless the fused
current rating, interrupting current rating, and cutouts are interlocked with the switch to prevent
maximum voltage rating. opening of the cutouts under load, a conspicuous
sign shall be placed at such cutouts identifying
(5) Fuses. Fuses that expel flame in opening the
that they shall not be operated under load.
circuit shall be designed or arranged so that they
function properly without hazard to persons or (3) Interrupting Rating. The interrupting rating
property. of distribution cutouts shall not be less than the
maximum fault current the cutout is required
(6) Fuseholders. Fuseholders shall be designed or
to interrupt, including contributions from all
installed so that they are de-energized while a fuse
connected sources of energy.
is being replaced. A field-applied permanent and
legible sign, in accordance withl.10 .l.2l(B), (4) Voltage Rating. The maximum voltage rating
shall be installed immediately adjacent to the of cutouts shall not be less than the maximum
fuseholders and shall be worded as follows: circuit voltage.
DANGER - DISCONNECT CIRCUIT BEFORE (5) Identification. Distribution cutouts shall have
REPLACING FUSES on their body, door, or fuse tube a permanent and
legible nameplate or identification showing the
Exception: Fuses and faseholders designed to permit
manufacturer's type or designation, continuous
fuse replacement by qualified persons using identified
current rating, maximum voltage rating, and
equipment without de-energizing the fuseholder shall
interrupting rating.
be permitted.
(6) Fuse Links. Fuse links shall have a permanent
(7) High-Voltage Fuses. Switchgear and substations
and legible identification showing continuous
that utilize high-voltage fuses shall be provided
current rating and type.
with a gang-operated disconnecting switch.
Isolation of the fuses from the circuit shall be (7) Structure Mounted Outdoors. The height of
provided by either connecting a switch between cutouts mounted outdoors on structures shall
the source and the fuses or providing roll-out provide safe clearance between lowest energized
switch and fuse-type construction. The switch parts (open or closed position) and standing
shall be of the load-interrupter type, unless surfaces, in accordance with 1.10.3.S(E).
mechanically or electrically interlocked with a
(D) Oil-Filled Cutouts.
load-interrupting de,-ice arranged to reduce the
load to the interrupting capability of the switch. (1) Continuous Current Rating. The continuous
current rating of oil-filled cutouts shall not be less
Exception.- More than one switch shall be permitted as
than the maximum continuous current through
the disconnecting means for one set offuses 1i·here the
the cutout.
switches are installed to provide connection to more
than one set of supply conductors. The switches shall (2) Interrupting Rating. The interrupting rating
be mechanically or electrically interlocked to permit of oil-filled cutouts shall not be less than the
access to the fuses only when all switches are open. A maximum fault current the oil-filled cutout is
conspicuous sign shall be placed at the fuses identifying required to interrupt, including contributions
the presence ofmore than one source. from all connected sources of energy_
(C) Distribution Cutouts and Fuse Links - (3) Voltage Rating. The maximum voltage rating
Expulsion Type. of oil-filled cutouts shall not be less than the
maximum circuit voltage.
(1) Installation. Cutouts shall be located so that
they may be readily and safely operated and re- (4) Fault Closing Rating. Oil-filled cutouts shall
fused, and so that the exhaust of the fuses does have a fault closing rating not less than the
not endanger persons. Distribution cutouts shall maximum asymmetrical fault current that can
not be used indoors, underground, or in metal occur at the cutout location, unless suitable
enclosures. interlocks or operating procedures preclude the
possibility of closing into a fault
399
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
(5) Identification. Oil-filled cutouts shall have a (5) Stored Energy for Opening. The stor -
permanent and legible nameplate showing the energy operator shall be permitted to be left · .
rated continuous current, rated maximum voltage, the uncharged position after the switch has bee
and rated interrupting current. closed if a single movement of the operati g
handle charges the operator and opens the swit .
(6) Fuse Links. Fuse links shall have a permanent
and legible identification showing the rated (6) Supply Terminals. The supply terminals of
continuous cmTent. fused interrupter switches shall be installed at the
top of the switch enclosure, or, if the terminal
(7) Location. Cutouts shall be located so that they
are located elsewhere, the equipment shall
are readily and safely accessible for re-fusing,
have barriers installed so as to prevent person
with the top of the cutout not over I 500 mm
from accidentally contacting energized parts or
above the floor or platform.
dropping tools or fuses into energized parts.
(8) Enclosure. Suitable barriers or enclosures shall
4.90.2.2 Isolating Means. Means shall be provided
be provided to prevent contact with nonshielded
to completely isolate an item of equipment from all
cables or energized parts of oil-filled cutouts.
ungrounded conductors. The use of isolating switches
(E) Load Interrupters. Load-interrupter switches shall shall not be required where there are other ways of de-
be permitted if suitable fuses or circuit breakers are energizing the equipment for inspection and repairs,
used in conjunction with these devices to interrupt fault such as draw-out-type switchgear units and removable
currents. Where these devices are used in combination, truck panels.
they shall be coordinated electrically so that they will
Isolating switches not interlocked with an approved
safely withstand the effects of closing, carrying, or
circuit-interrupting device shall be provided with a sign
interrupting all possible currents up to the assigned
warning against opening them under load. The warning
maximum short-circuit rating.
sign(s) or label(s) shall comply with l.10. l.21(B).
Where more than one switch is installed \\ ith
An identified fuseholder and fuse shall be permitted as
interconnected load terminals to provide for alternate
an isolating switch.
connection to different supply conductors, each switch
shall be provided with a conspicuous sign identifying
4.90.2.3 Voltage Regulators. Proper switching
this hazard.
sequence for regulators shall be ensured by u e of one
(1) Continuous Current Rating. The continuou of the following :
cunent rating of interrupter switches shall equal
(I) Mechanically sequenced regulator bypass
or exceed the maximum continuous current at the
switch(es)
point of installation.
(2) Mechanical interlocks
(2) Voltage Rating. The maximum voltage rating
of interrupter switches shall equal or exceed the (3) Switching procedure promjnently displayed at
maximum circuit voltage. the switching location
(3) Identification. Interrupter switches shall have
4.90.2.4 Minimum Space Separation. In field-
a permanent and legible nameplate including
fabricated installations, the minimum air separation
the following information: manufacturer's
between bare live conductors and between such
type or designation, continuous cmTent rating,
conductors and adjacent grounded surfaces shall not be
intem1pting current rating, fault closing rating,
less than the values given in Table 490.24. These values
maximum voltage rating.
shall not apply to interior portions or exterior terminals
(4) Switching of Conductors. The switching of equipment designed, manufactured, and tested in
mechanism shall be arranged to be operated from accordance with accepted national standards.
a location where the operator is not exposed
4.90.2.5 Backfeed. Installations where the possibility
to energized parts and shall be arranged to
ofbackfeed exists shall comply with (A) and (B), which
open all ungrounded conductors of the circuit
follow.
simultaneously with one operation. Switches hall
be arranged to be locked in the open position. (A) A permanent sign in accordance with 1.10.1.21 (B )
Metal-enclosed switches shall be operable from shall be installed on the disconnecting means enclo ur
outside the enclosure. or immediately adjacent to open disconnecting mea -

400
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
with the following words or equivalent: DANGER - 4.90.3.3 Guarding of High-Voltage Energized Parts
CONTACTS ON EITHER SIDE OF THIS DEVICE Within a Compartment. Where access for other than
MAY BE ENERGIZED BY BACKFEED. visual inspection is required to a compartment that
contains energized high-voltage parts, barriers shall
(B) A permanent and legible single-line diagram of the
be provided to prevent accidental contact by persons,
local switching arrangement, clearly identifying each
tools, or other equipment with energized parts. Exposed
point of connection to the high-voltage section, shall
live parts shall only be permitted in compartments
be provided within sight of each point of connection.
accessible to qualified persons. Fuses and fuseholders
4.90.3 Equipment - Switchgear and Industrial designed to enable future replacement without de-
Control Assemblies energizing the fuseholder shall only be permitted for
4.90.3.1 General. Part 4.90.3 covers assemblies use by qualified persons.
of switchgear and industrial control equipment
including, but not limited to, switches and interrupting 4.90.3.4 Guarding of Energized Parts Operating at
devices and their control, metering, protection, and 1000 Volts, Nominal, or Less Within Compartments.
regulating equipment where they are an integral part Energized bare parts mounted on doors shall be guarded
of the assembly, with associated interconnections and where the door must be opened for maintenance of
supporting structures. equipment or removal of draw-out equipment.

4.90.3.2 Arrangement of Devices in Assemblies. 4.90.3.5 Clearance for Cable Conductors Entering
Arrangement of devices in assemblies shall be such Enclosure. The unobstructed space opposite te1minals
that individual components can safely perform their or opposite raceways or cables entering a switchgear
intended function without adversely affecting the safe or control assembly shall be approved for the type of
operation of other components in the assembly. conductor and method of tennination.

Table 4.90.2.4 Minimum Clearance of Live Parts


.\1inimum Clearance of Live Parts
Impulse Withstand, Basic Phase-to-Phase Phase-to-Ground
Nominal
Voltage Rating Impulse Level B.I.L (kV) Indoors Outdoors Indoors Outdoors
(kV) Indoors Outdoors mm mm mm mm
2.4-4.16 60 95 115 180 80 155
7.2 75 95 140 180 105 155
13.8 95 110 195 305 130 180
14.4 110 110 230 305 170 180
23 125 150 270 385 190 255
34.5 150 150 320 385 245 255
200 200 460 460 335 335
46 - 200 - 460 - 335
- 250 - 535 - 435
69 - 250 - 535 - 435
- 350 - 790 - 635
115 - 550 - 1350 - 1070
138 - 550 - 1350 - 1070
- 650 - 1605 - 1270
161 - 650 - 1605 - 1270
- 750 - 1830 - 1475
230 - 750 - 1830 - 1475
- 900 - 2265 - 1805
- 1050 - 2670 - 2110
~= The \·alues "'oiven are the minimum clearance for rioid
"' p arts and bare conductors under favorable service conditions. Thev. shall be increased for conductor
- ~·="- or under unfavorable service conditions or wherever space limitations pennit. The selection of the associated impulse withstand voltage for a particular
,_ --= -.c,:.tage is determined by the characteristics of the surge protective equipment.
401
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
4.90.3.6 Accessibility of Energized Parts. 4.90.3.12 Location of Industrial Control Equipment
Routinely operated industrial control equipment shall
(A) High-Voltage Equipment. Doors that would
meet the requirements of (A) unless infrequently
provide unqualified persons access to high-voltage
operated, as covered in 4.90.3.12(B).
energized parts shall be locked. Permanent signs in
accordance with l.10.l.2l(B) shall be installed on (A) Control and Instrument Transfer Switch
panels or doors that provide access to live parts Handles or Push Buttons. Control and instrument
over 1 000 volts and shall read DANGER - HIGH transfer switch handles or push buttons shall be in a
VOLTAGE- KEEP OUT. readily accessible location at an elevation of not over
2000mm.
(B) Control Equipment. Where operating at 1 000 volts,
nominal, or less, control equipment, relays, motors, and Exception: Operating handles requiring more than 23
the like shall not be installed in compartments with kg offorce shall be located no higher than 1 700 mm in
exposed high-voltage energized parts or high-voltage either the open or closed position.
wiring, unless either of the following conditions is met:
(B) Infrequently Operated Devices. Where operating
(1) The access means is interlocked with the high- handles for such devices as draw-out fuses, fused
voltage switch or disconnecting means to prevent potential or control transformers and their primary
the access means from being opened or removed. disconnects, and bus transfer and isolating switches
are only operated infrequently, the handles shall be
(2) The high-voltage switch or disconnecting means
permitted to be located where they are safely operable
is in the isolating position.
and serviceable from a portable platform.
(C) High-Voltage Instruments or Control
Transformers and Space Heaters. High-voltage 4.90.3.13 Interlocks - Interrupter Switches.
instrument or control transformers and space heaters Interrupter switches equipped with stored energy
shall be permitted to be installed in the high-voltage mechanisms shall have mechanical interlocks to prevent
compartment without access re triction beyond those access to the switch compartment unless the stored
that apply to the high-voltage compartment generall . energy mechanism is in the discharged or blocked
4.90.3.7 Grounding. Frames of fm.itchgear and position.
control assemblies shall be connected to an equipment
grounding conductor or where permitted. the grounded 4.90.3.14 Stored Energy for Opening. The stored
conductor. energy operator shall be permitted to be left in the
uncharged position after the switch has been closed if
4.90.3.8 Grounding of Devices. The metal case or a single movement of the operating handle charges the
frames, or both, such as those of instruments, relays operator and opens the switch.
meters, and instrument and control transformers 4.90.3.15 Fused Interrupter Switches.
located in or on switchgear or control assemblies, shall
(A) Supply Terminals. The supply terminals of fused
be connected to an equipment grounding conductor or,
interrupter switches shall be installed at the top of
where permitted, the grounded conductor.
the switch enclosure or, if the terminals are located
elsewhere, the equipment shall have barriers installed
4.90.3.9 Door Stops and Cover Plates. External
so as to prevent persons from accidentally contacting
hinged doors or covers shall be provided with stops to
energized parts or dropping tools or fuses into energized
hold them in the open position. Cover plates intended to
parts.
be removed for inspection of energized parts or wiring
shall be equipped with lifting handles and shall not (B) Backfeed. Where fu es can be energized by
exceed 1.1 m 2 in area or 27 kg in weight, unless they backfeed, a sign shall be placed on the enclosure door
are hinged and bolted or locked. identifying this hazard.
(C) Switching Mechanism. The switching mechanism
4.90.3.10 Gas Discharge from Interrupting Devices.
shall be arranged to be operated from a location outside
Gas discharged during operating of interrupting devices
the enclosure where the operator is not exposed to
shall be directed so as not to endanger personnel.
energized parts and shall be arranged to open all
4.90.3.11 Visual Inspection Windows. Windows ungrounded conductors of the circuit simultaneously
intended for visual inspection of disconnecting switches with one operation. Switches shall be lockable in
or other devices shall be of suitable transparent material. accordance with 1.10.1.25.

402
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
4.90.3.16 Circuit Breakers - Interlocks. (6) Guarding live parts
(A) Circuit Breakers. Circuit breakers equipped with (7) Transformers and voltage regulation equipment
stored energy mechanisms shall be designed to prevent
(8) Conductor insulation, electrical and mechanical
the release of the stored energy unless the mechanism
protection, isolation, and terminations
has been fully charged.
(9) Application, arrangement, and disconnection of
(B) Mechanical Interlocks. Mechanical interlocks
circuit breakers, switches, and fuses
shall be provided in the housing to prevent the complete
withdrawal of the circuit breaker from the housing (lO)Provision for oil-filled equipment
when the stored energy mechanism is in the fully (11) Switchgear
charged position, unless a suitable device is provided to
block the closing function of the circuit breaker before (12)Surge arrestors
complete withdrawal. (B) Diagram. A permanent, single-line diagram of
4.90.3.17 Circuit Breaker Locking. Circuit breakers the switchgear shall be provided in a readily visible
shall be capable of being locked in the open position location within the same room or enclosed area with
or, if they are installed in a drawout mechanism, that the switchgear, and this diagram shall clearly identify
mechanism shall be capable of being locked in such a interlocks, isolation means, and all possible sources of
position that the mechanism cannot be mo ed into the voltage to the installation under normal or emergency
connected position. In either case, the provision for conditions, and the marking on the switchgear shall
locking shall be lockable in accordance with 1.10.1.25. cross-reference the diagram.

4.90.3.18 Switchgear Used as Seni ce Equipment. Exception: Where the equipment consists solely of
Switchgear installed as high-voltage erYice equipment a single cubicle or metal-enclosed unit substation
shall include a ground bus for the connection of er..-ice containing only one set of high-voltage switching
cable shields and to facilitate the attachment of safety devices, diagrams shall not be required.
grounds for personnel protection. Thi bus hall be
extended into the compartment v. here the service 4.90.4 Mobile and Portable Equipment
conductors are terminated. \\ 'here the compartment
door or panel provide acce s to parts that can only be 4.90.4.1 General.
de-energized and Yisibly i olated by the serving utility, (A) Covered. The provisions of this part shall apply to
the warning sign required by 4.90.3.6(a) shall include installations and use of high-voltage power distribution
a notice that ace is limited to the serving utility or and utilization equipment that is portable, mobile, or
is permitted only following an authorization of the both, such as substations and switch houses mounted
serving utility. on skids, trailers, or cars; mobile shovels; draglines;
4.90.3. 19 Substations Design, Documentation, and cranes; hoists; drills; dredges; compressors; pumps;
Required Diagram. conveyors; underground excavators; and the like.
(A) Documentation. Substations shall be designed by (B) Other Requirements. The requirements of this
a licensed electrical practitioner. Where components or part shall be additional to, or amendatory of, those
the entirely of the substation are listed by a qualified prescribed in Alticles 1.0 through 7.25 of this Code.
electrical testing laboratory, documentation of internal Special attention shall be paid to Article 2.50.
design features subject to the listing investigation shall (C) Protection. Approved enclosures or guarding, or
not be required. The design shall address but not be both, shall be provided to protect portable and mobile
limited to the following topics and the documentation equipment from physical damage.
of this design shall be made available to the Office of
the Building Official/EE. (D) Disconnecting Means. Disconnecting means
shall be installed for mobile and portable high-voltage
(1) Clearances and exits equipment according to the requirements of Part 2.30.8
(2) Electrical enclosures and shall disconnect all ungrounded conductors.

(3) Securing and support of electrical equipment 4.90.4.2 Overcurrent Protection. Motors driving
single or multiple de generators supplying a system
(4) Fire protection operating on a cyclic load basis do not require overload
(5) Safety ground connection provisions protection, provided that the thermal rating of the ac

403
ARTICLE 4.90 - EQUIPMENT OVER 1000 VOLTS, NOMINAL
drive motor cannot be exceeded under any operating supplied from a grounded system, and shall have the
condition. The branch-circuit protective device(s) shall controls in the ungrounded conductor.
provide short-circuit and locked-rotor protection and 4.90.5.3 Branch-Circuit Requirements.
shall be permitted to be external to the equipment.
(A) Rating. Each boiler shall be supplied from an
4.90.4.3 Enclosures. All energized switching and individual branch circuit rated not less than 100 percent
control parts shall be enclosed in grounded metal of the total load.
cabinets or enclosures. These cabinets or enclosures
shall be marked DANGER - HIGH VOLTAGE - (B) Common-Trip Fault-Interrupting Device. The
KEEP OUT and shall be locked so that only authorized circuit shall be protected by a 3-phase, common-trip
and qualified persons can enter. The danger marking(s) fault-inteITUpting device, which shall be permitted to
or label(s) shall comply with l.10.l.2l(B). ircuit automatically reclose the circuit upon removal of an
breakers and protective equipment shall have the overload condition but shall not reclose after a fault
operating means projecting through the metal cabinet condition.
or enclosure so these units can be reset without opening (C) Phase-Fault Protection. Phase-fault protection
locked doors . With doors closed, safe access for normal shall be provided in each phase, consisting of a separate
operation of these units shall be provided. pha e overcurrent relay connected to a separate current
4.90.4.4 Collector Rings. The collector ring assemblies transformer in the phase.
on revolving-type machines (shovels dragline . etc.) (D) Ground Current Detection. Means shall be
shall be guarded to prevent accidental contact with provided for detection of the sum of the neutral
energized parts by personnel on or off the machine. conductor and equipment grounding conductor currents
4.90.4.5 Power Cable Connections to :\lobile and shall trip the circuit-interrupting device if the sum
Machines. A metallic enclosure shall be pro,·ided of those currents exceeds the greater of 5 amperes or
1 percent of the boiler full-load cuITent for 10 seconds
on the mobile machine for enclosing the terminal of
the power cable. The enclosure shall include terminal or exceeds an instantaneous value of 25 percent of the
connections to the machine frame for the equipment boiler full-load current.
grounding conductor. Ungrounded conductors hall (E) Grounded Neutral Conductor. The grounded
be attached to insulators or be terminated in approved
neutral conductor shall be as follows:
high-voltage cable couplers (which include equipment
grounding conductor connectors) of proper voltage (I) Connected to the pressure vessel containing the
and ampere rating. The method of cabl termination ele trodes
used shall prevent any strain or pull on the cabl from
(2) Insulated for not less than 100 volts
stressing the electrical connections. The enclosure shall
have provision for locking so that only authoriz d and (3) Ha\·e not le than the ampacity of the largest
qualified persons may open it and shall be marked a ungrounded branch-circuit conductor
follows:
(4 ) Installed with the ungrounded conductors in the
DANGER - HIGH VOLTAGE - KEEP O T. ame raceway, cable, or cable tray, or, where
installed as open conductors, in close proximity
The danger marking(s) or label(s) shall comply with to the ungrounded conductors
1.10.1.2 l(B).
(5) ~ ot u ed for any other circuit
4.90.4.6 High-Voltage Portable Cable for Main
Power Supply. Flexible high-voltage cable supplying 4.90.5.4 Pressure and Temperature Limit Control.
power to portable or mobile equipment shall comply Each boiler ball b equipped with a means to limit the
with Article 2.50 and Article 4.0, Part 4.90.3 . maximum temperature, pressure, or both, by directly
or indirectly interrupting all current flow through the
4.90.5 Electrode-Type Boilers electrodes. Such means shall be in addition to the
4.90.5.1 General. The provisions of Pati 4.90.5 shall temperature, pressure, or both, regulating systems and
apply to boilers operating over 1000 volts, nominal, pressure relief or safety valves.
in which heat is generated by the passage of cuITent 4.90.5.5 Bonding. All exposed non- current-carrying
between electrodes through the liquid being heated. metal parts of the boiler and associated exposed metal
4.90.5.2 Electrical Supply System. Electrode-type structures or equipment shall be bonded to the pressure
boilers shall be supplied only from a 3-phase, 4-wire vessel or to the neutral conductor to which the vessel
solidly grounded wye system, or from isolating is connected in accordance with 2.50.5.13 , except the
transformers arranged to provide such a system. Control ampacity of the bonding jumper shall not be less than
circuit voltages shall not exceed 150 volts, shall be the ampacity of the neutral conductor.

404

You might also like