Professional Documents
Culture Documents
Enhancement of Cooling Capacity Through Open-Type Installation of Cooling Radiant Ceiling Panel Systems
Enhancement of Cooling Capacity Through Open-Type Installation of Cooling Radiant Ceiling Panel Systems
Keywords: Cooling radiant ceiling panel (CRCP) systems have been increasingly applied to modern buildings, owing to high
Cooling radiant ceiling panel thermal comfort, energy-saving potential, and integration with building design. Currently, the cooling capacity
Open-type installation of CRCP is generally evaluated for the closed-type CRCP, wherein the overall ceiling surface is covered with
Opening ceiling panels. However, there have been few previous studies on the evaluation of the cooling capacity for open-
Cooling capacity
type CRCP, which are installed with openings (void areas) between adjacent ceiling panels. This study was
conducted to verify the hypothesis that the open-type CRCP can enhance cooling capacity by utilizing the cooled
plenum air moving through the opening. If the plenum air is cooled by the upper surface of ceiling panels and
descends to the conditioned space, it can contribute to increasing the convective heat transfer and cooling
capacity. A simulation model for open-type CRCP was developed and validated against the mock-up experiment.
Using the simulation model, the cooling capacity of the open-type CRCP was evaluated with respect to the
opening area and panel layout. The results showed that the open-type CRCP could provide 54–80% (average
64%) higher nominal cooling capacity than conventional closed-type CRCP. The enhanced cooling capacity may
lead to reduction in construction costs and energy consumption, because panel installation area could be reduced
and the water temperature can be increased to provide the required cooling capacity. The results of this study
would be able to offer fundamental data about cooling capacity of open-type CRCP.
1. Introduction plenum surface) as a kind of additional heat gain (capacity loss) that
should be minimized. In this context, CRCP systems are installed with
Cooling radiant ceiling panel (CRCP) systems reduce the surface the upper-side thermally insulated in order to maximize heat absorption
temperature of ceiling panels for the purpose of space cooling. For the at the lower surface of the ceiling panels [13,14]. However, non-in-
implementation of a CRCP system, it is usual to install ceiling panels sulated ceiling panels are also applied to many commercial buildings
without open joints in order to conceal the HVAC components in the due to simple installation and low capital cost [15,16].
plenum (e.g., the duct, pipe, electrical equipment) from occupants’ Recently, exposed ceiling designs have been increasingly applied to
view. For this reason, it is a general practice to assume the space below various building types, owing to modern design trends and the devel-
ceiling panels as conditioned space, whereas the plenum space is as- opment of finishing techniques for HVAC components. As a result,
sumed as non-conditioned space [1]. As a result, many studies have open-type CRCP, which are composed of openings (void space between
been conducted to investigate radiant and convective heat transfer in adjacent ceiling panels) as well as ceiling panels, as shown in Fig. 1, are
the conditioned space below ceiling panels [2–10]. In the design pro- often installed in various buildings such as offices, schools, museums,
cess of a CRCP system, much attention has been paid to heat absorption and so on.
at the lower surface of ceiling panels that faces the conditioned space Air can move from the plenum to the conditioned space, and vice
[11,12]. versa, through the openings between ceiling panels. Plenum air cooled
Meanwhile, it is common to assume the heat absorption at the upper by the upper surface of ceiling panels moves down to the occupied
surface of ceiling panels (heat transfer between ceiling panels and space, whereas room air warmed by internal heat gains can rise to the
∗
Corresponding author. Dept. of Architectural Engineering, 45 Yongso-ro, Nam-gu, Busan, 48513, South Korea.
E-mail address: knrhee@pknu.ac.kr (K.N. Rhee).
https://doi.org/10.1016/j.buildenv.2018.11.005
Received 29 August 2018; Received in revised form 4 November 2018; Accepted 10 November 2018
Available online 14 November 2018
0360-1323/ © 2018 Elsevier Ltd. All rights reserved.
M.S. Shin et al. Building and Environment 148 (2019) 417–432
机械通风对冷却能力的影响可以忽略不计
plenum space through the openings. If the density change with air mechanical ventilation has negligible impacts on the cooling capacity
temperature is taken into account, air movement through the opening [20].
would be able to enhance the heat transfer at the panel surface, and the Second, the test method in the standards requires that the inner
consequent cooling capacity of the CRCP. However, few studies have surface temperatures of a test chamber should be equally maintained
been performed to quantitatively evaluate the increase in cooling ca- during the experiment. This requirement cannot reflect the real
pacity due to the open-type installation. Hence, cooling capacity data building situation where the internal surface temperature of perimeter
for the conventional closed-type CRCP system is also used to design the walls or windows is usually higher than that of interior walls. This
open-type CRCP system. Although the number of ceiling panels can be assumes that the cooling capacity determined under the test condition
reduced or the chilled water temperature can be increased owing to the is sufficient to satisfy the required heat absorption rate of ceiling panels
enhanced cooling capacity of ceiling panels, it is difficult to select this in real buildings.
design alternative because there is not enough reference or design data Third, the heat absorption at the upper surface of ceiling panels is
about the cooling capacity with the open-type installation. generally assumed as capacity loss, just as downward heat loss in ra-
Therefore, this study was conducted to establish fundamental data diant floor heating. This assumption would be reasonable in case of
on the cooling capacity of open-type CRCP systems. The objectives of closed-type CRCP because heat absorption above the ceiling panels can
this study are i) to verify the hypothesis that the open-type installation hardly contribute to the cooling of the conditioned space below the
can contribute to the enhancement of the cooling capacity and ii) to ceiling panels.
find factors affecting the cooling capacity of an open-type installation At the moment, CRCP systems are designed with a cooling capacity
and to analyze the variation in the cooling capacity depending on the that is evaluated under the aforementioned conditions, regardless of the
factors. CRCP type. Some studies, meanwhile, have been conducted to show
that the limited conditions need to be corrected depending on the 据称,更大
2. Hypothesis: is the cooling capacity of CRCP enhanced by open- physical characteristics of the CRCP. Kochendorfer [21] proved that the 的冷却能力
是由于更高
type installation? cooling capacity in a real building is greater than the experimental 的表面温度
result by more than 25%. It was claimed that the greater cooling ca- (例如,围
墙或窗户的
2.1. Literature reviews on the cooling capacity of CRCP pacity results from higher surface temperatures (e.g., internal surfaces 内表面)和
of perimeter wall or window) and elevated air velocity due to me- 机械通风系
统导致的空
The evaluation method of the cooling capacity is specified in tech- chanical ventilation system, which are not considered in the test stan- 气速度升高
nical standards of the CRCP (e.g., EN 14240 [17], DIN 4715 [18], NT dards for cooling capacity evaluation. Therefore, it was put forward ,而在冷却
能力评估的
VVS 078 [19]), wherein the capacity is determined by the chilled water that the experimental cooling capacity should be corrected using per- 测试标准中
temperature, globe temperature, and panel heat absorption measured formance data collected from real buildings. In the same context, Jeong 没有考虑这
些因素。
from the closed-type CRCP under specific test conditions. The resultant and Mumma [22,23] suggested a regression equation to predict the
cooling capacity is presented as a cooling capacity curve or table, and cooling capacity of a CRCP system in parallel with mechanical venti-
nominal/standard cooling capacity. According to the ASHRAE Hand- lation. It was claimed that the suspended ceiling panel combined with
book [12], the cooling capacity of radiant panels can be determined mechanical ventilation, or mixed convection, can enhance the cooling
using thermal resistances with the panel types and convective/radiant capacity by 16%–71% depending on chilled water temperature and air
heat transfer at panel surfaces. velocity, compared with the capacity under the natural convection
When evaluating the cooling capacity of ceiling panels based on condition [16]. Tian et al. developed a modified method to estimate the
abovementioned standards and technical documents, some limited cooling capacity of CRCPs installed in a building with relatively higher
conditions are assumed: First, the cooling capacity is determined as- internal surface temperatures due to external conditions. It was con-
suming natural convection conditions without mechanical ventilation. cluded that the actual cooling capacity should be modified by applying
Evaluated ceiling panels are installed in a test chamber without a me- correction coefficients to the manufacturer's data, which are de-
chanical ventilation system. The heat transfer rate is calculated using termined under specific test conditions [24]. Park [25] proposed a test
natural convection heat transfer coefficients, based on the assumption method to evaluate the cooling capacity of CRCPs in a room with high-
that forced convection due to infiltration, occupants’ movement, and temperature surfaces exposed to outdoor air. Karadağ investigated the
418
M.S. Shin et al. Building and Environment 148 (2019) 417–432
419
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Table 1
Experimental data of Fig. 3 (extracted from Ref. [34]).
Parameter CASE 2 (Open type) CASE 3 (Closed type)
a
w = ( w, r + w, s )/2
b
= w, r
w w, s
c
QP = c w m w w where c w = 4.18 J/(gK).
of heat (QP ) from the indoor space; however, the operative temperature
(OT) with CASE 2 was 1.6 °C less than that with CASE 3. In addition,
CASE 2 also resulted in smaller op w , (temperature difference op-
erative temperature and water temperature). This implies that the
cooling capacity of the open-type CRCPs can increase if the same
temperature difference ( op w ) is applied to each CRCP type. The
aforementioned results imply that heat absorption at the upper surface
of ceiling panels could contribute to the cooling of the conditioned
space, if the CRCP is implemented with the open-type installation. In
view of the occupied zone, it can be said that the heat removal rate in
the occupied zone increases through the open-type installation of
CRCPs.
Recent studies [33,34] showed that it would be possible to enhance
the cooling capacity of CRCPs through the open-type installation;
however, as far as the authors know, no study has been conducted to
prove the capacity enhancement under real installation conditions. In
addition, quantitative results have not yet been provided to expect how
much the cooling capacity is enhanced by the open-type installation.
Therefore, it is necessary to investigate whether the cooling capacity
can be enhanced or not and which factors affect the enhancement of
cooling capacity with the open-type installation. To do this, the relation
between the cooling capacity and design parameters (e.g., opening
area, panel layout) was analyzed using a numerical simulation, which
was also validated using measured data from mock-up experiments.
Although simple calculation methods [1,12,20] can be applied to Considering that the cooling capacity can be enhanced by the in-
the estimation of cooling capacity, they are not applicable to open-type creased airflow through the opening, the simulation method should be
CRCP because the opening (void) area or layout of ceiling panels is not able to analyze the air movement between the plenum and conditioned
considered. Furthermore, as the upper surface temperature of ceiling space. In addition, the simulation should be capable of analyzing ra-
panels cannot be analyzed with the simple calculation methods, they diation heat transfer, because the radiation between the ceiling panels
are not suitable for the method of this study, which aims at in- and surrounding surfaces is one of influential factors to determine the
目的是研究上 vestigating the impact of heat absorption at the upper surface on the cooling capacity. For this reason, computational fluid dynamics (CFD)
表面吸热对制
冷量的影响 cooling capacity. However, the test methods would be appropriate for simulations were conducted using the STAR-CCM + program, which
the evaluation of open-type CRCP, because the cooling capacity and can analyze conduction heat transfer in ceiling panels, radiant heat
panel surface temperatures can be directly measured from the eval- transfer between ceiling panels and surrounding surfaces, and air
uated CRCP, even though the ceiling panels are installed with opening movement induced by temperature differences.
areas. It is also possible to install ceiling panels with the open-type and
to change the panel layout flexibly in the laboratory environment. 3.1. Simulation model development and validation
As the cooling capacity of open-type CRCP can be affected by design
factors such as panel/void area, it needs to be analyzed with various 3.1.1. Geometry
configurations of ceiling panels. For the evaluation of various open-type According to the test method of the relevant standard [17], it is
CRCPs, a simulation method would be effective in saving time and cost recommended that the dimensions of test chamber should be
for the evaluation. Therefore, this study adopted a simulation method 4 m (W) × 4 m (D) × 3 m (H) and the ceiling panels should be installed
in order to evaluate the cooling capacity of various open-type CRCPs. at 2.5 m ± 0.02 m above the floor surface or at 0.25–0.3 m below the
The boundary conditions defined by the test methods and several panel ceiling surface. In accordance with the standard, a simulation model
layouts were represented with the numerical simulation. was developed using STAR-CCM+, as schematized in Fig. 4. In order to
420
M.S. Shin et al. Building and Environment 148 (2019) 417–432
simulate the cooling load, 12 cylindrical dummies [17] were uniformly was assumed as adiabatic, such that the cooling load could be removed
deployed in the space, which result in the heat dissipation equivalent to by the ceiling panels only.
135 W/m2. As the arrangement of the room space, dummies, and CRCPs As for the boundary condition of the ceiling panel surfaces, it is
are symmetrical along the center-line of the model space, half of the important to assume an appropriate panel surface temperature that is
space was modeled with the symmetry boundary condition in order to low enough to remove the space cooling load while preventing surface
simplify the simulation model. condensation. Based on previous studies [13,24,30,35] and design
Regarding the geometry of CRCPs, its detailed structure needed to guidelines [11,12], the lower surface temperature of the CRCP was
be simplified in order to reduce the calculation load of the CFD analysis. assumed as 15–20 °C at intervals of 1 °C. 上表面温度su
The lower surface of the ceiling panels does not need the simplification The upper surface temperature s, u would be slightly less than the 会略低于下表
面温度sl,因
owing to its flat and plain surface; however, the upper surface has re- lower surface temperature s, l because the chilled water pipe and heat 为冷冻水管和
导热 板附着
latively complicated details including the chilled water pipe, heat conduction plate are attached to the upper surface without any fin- 在上表面,没
有任何整理材
conduction device, and folded section of ceiling panel. As the size of ishing material. Nonetheless, it was assumed that s, u is equal to s, l in 料。然而,在
these detailed elements is so small compared to the analyzed space, it is this study, because this condition can be regarded as a safety factor for 本研究中,假
设su = sl,
not practically reasonable to make a fully detailed model for the upper the cooling capacity. As the cooling capacity is evaluated on the as- 因为此条件可
视为制冷量的
surface of the CRCPs. Despite with the increased modeling labor and sumption that the upper and lower panel surface temperatures are 安全系数。
calculation time, a fully detailed model can lead to the reduced accu- equal, it would be slightly less than the actual cooling capacity eval-
racy unless the input values (e.g., material properties, contact re- uated under real conditions, wherein the upper surface temperature is
sistance) are properly provided. less than the lower surface temperature. However, this underestimated
Because the heat transfer at the panel surface is mainly determined cooling capacity could be beneficial to the secure design that requires
by panel surface area and temperature, it would be reasonable to as- somewhat conservative values for determining the equipment size.
sume the appropriate surface temperatures and area of the ceiling pa- It needs to be noted that there is a temperature difference at the pipe
nels, even though the detailed structure is not modeled as it is. surface of the outlet and inlet section, resulting in the slightly non-
Therefore, the panel geometry was simplified as a rectangular paralle- uniform upper surface temperature. This non-uniformity is dependent
lepiped whose base is the projected area of the ceiling panel and height on the temperature rise of cooling water, which can be estimated to be
is the thickness of the ceiling panel, as described in Fig. 5. The lower about 2 °C from the experimental result, which is also found in previous
and upper surface temperatures of the simplified panel were assumed to studies [12,14,30]. If the temperature difference in upper panel surface
be the same as those of the real CRCPs. is considered in the CFD simulation model, the heat transfer rate at the
upper surface of the panel can be analyzed more accurately. None-
3.1.2. Boundary conditions theless, the objective of the present study is to find out whether the
In test methods of the CRCP cooling capacity, it is assumed that the cooling capacity increases through open-type installation, rather than
heat transfers through the building envelope are ignored and the to provide the exact amount of heat removal by CRCPs. Thus, this study
cooling load is removed by the ceiling panels only. Similarly, in the assumes the uniform distribution at the panel surface temperature in
developed simulation model, the boundary condition of the six surfaces order to compare the cooling capacity of various CRCP types.
Table 2
Calculation method used in CFD analysis.
Category Calculation method Basis for determining calculation method
421
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Table 4
Results of verification experiments.
Result of measurements Case 1 Case 2 Case 3
simulators.
1.1
qs, l = 8.92 × ( op s, l ) (1)
Second, qP s, l was defined as the cooling load that should be re-
3.1.3. Calculation models
moved to maintain the operative temperature of the conditioned space
For the evaluation of the cooling capacity of open-type CRCPs, it is
at 26 °C when lower panel surface temperature s, l is 16, 18, and 20 °C.
necessary to analyze the radiant heat transfer between the panel sur-
The cooling load with panel surface temperature is as follows:
faces and surrounding room surfaces, convective heat transfer at the
qP 16 = 8.92 × (26 16)1.1 = 112.3 (W / m2) (2) panel surfaces, air movement induced by air density change, and so on.
Considering these requirements, CFD simulations using STAR-CCM+
qP 18 = 8.92 × (26 18)1.1 = 87.9(W / m2) (3) were conducted with the calculation model as summarized in Table 2.
qP 20 = 8.92 × (26 20)1.1 = 64.0(W / m2) (4)
3.1.4. Simulation model validation
Third, the heat quantity Qs , which should be assigned to the load To validate the developed simulation model, mock-up tests were
simulators, can be calculated with the following equation: conducted in a test chamber equipped with open-type CRCPs, which are
Qs = qP × Ap composed of 36 ceiling panels (0.6 m × 0.6 m × 0.03 m for each panel)
(5)
and opening area (width = 0.2 m) between the ceiling panels and walls,
s, l
2
For example, if the panel surface area is 8.0 m and the panel sur- as shown in Fig. 6. Validation tests were performed for three different
face temperature is 16 °C, Qs = qP 16 × Ap = 112.3 × 8.00 = 898.4 W . cases, wherein the cooling load was adjusted from 469.9 W to
This heat output was divided by a dummy surface area and the resultant 1409.8 W, in order to verify the simulation model under various load
heat flux was assigned as the boundary condition of the cooling load conditions. The test conditions are summarized in Table 3.
Table 4 shows the measured temperatures and water flow rate with
Table 3 three verification cases in Table 3. The measured inlet/outlet water
Case design of experiments for the verification of a simulation model. temperature and flow rate were used to calculate temperature rise w ,
No. Case 1 Case 2 Case 3 average temperature w and heat removal by CRCPs, as shown in the
lower part of Table 4. The measured cooling water flow rate and supply
water temperature were slightly different from the predicted values
a
Cooling load Qs (W) 1409.8 939.8 469.9
Cooling water flow rate mw (lpm) 7 7 7
shown in Table 3. However, this difference is acceptable when con-
Cooling water flow rate mw (g/s) 117 117 117
13 15 17
sidering the error of the measurement devices. The cooling water
Supply water Temperature w, s (°C)
Predicted cooling water temp. rise b
(K) 2.89 1.93 0.96 temperature rise and return water temperature were also similar to the
w
Predicted return water temperature w, r
c
(°C) 15.89 16.93 17.96 predicted values by a difference of ±0.2 °C. The simulated cooling load
and heat removal by the cooling water showed marginal differences
a
Qs = Qbulb× the number of activated bulbs, where a power of a bulb Qbulb is (Case 1: 0.8%, Case 2: −3.3%, Case 3: −1.4%), which could be enough
58.78 W. to validate the accuracy of the results.
b
w = Qs /(c w m w ) where c w = 4.18 J/(gK). Fig. 7 shows the temperature distribution of each validation case
c
w, r = w, s + w
422
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Fig. 7. Air temperature distribution at y = 0.4 m section (1.6 m from the room wall).
(y = 0.4 m section). It is shown that the simulation model can analyze under different load conditions. Therefore, the developed simulation
the air movement through the opening between CRCP and room walls, model can be successfully used to represent the thermal behaviors of
resulting in the reduced temperature difference between the plenum open-type CRCPs. Based on the validation results, the cooling capacities
and conditioned space. Table 5 and Figs. 8 and 9 shows the comparison of various CRCP configurations were analyzed using the developed si-
between the simulation and verification experiment results. The “Ex- mulation model and the results are discussed in Section 4.
pected range” column in Table 5 indicates the real values considering
the measurement errors of temperature and flow rate. The expected 3.2. Simulation cases
ranges for air temperature and cooling capacity are expressed with
error bars in Figs. 8 and 9. The simulation model can be considered as In open-type CRCPs, air movement through the opening can en-
validated if the simulated air temperature and cooling capacity fall hance heat transfers at the panel surfaces, which will lead to the in-
within the expected ranges. Figs. 8 and 9 show the simulated values are crease in the cooling capacity of CRCPs. Therefore, the air movement is
in the range of expected values for air temperature and cooling capacity a significant factor to be considered for the evaluation of open-type
Table 5
Comparison between experimental and simulation results.
Case 1 Measured value Expected range1) Simulation result
a
Measurement error for temperature and volumetric flow rate - T-type thermocouple: ± 0.5 K or 0.4%, Flowmeter: ± 0.1 lpm or 1.0%.
423
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Fig. 8. Measured and simulated air temperatures with different load conditions.
424
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Table 6
Simulation case for the evaluation of cooling capacity.
Panel area ( AP ) Panel layout (characterized by Pp and PT)
Centralized Distributed
2 2
AP = 4 m ( AO = 12.0 m ) < Case A-c > < Case A-d >
PP = 8.0 m (PT = 22.0 m) PP = 16.0 m (PT = 32.0 m)
AP = 6.48 m2 ( AO = 9.52 m2) < Case B-c > < Case B-d >
PP = 10.2 m (PT = 26.2 m) PP = 16.0 m (PT = 32.0 m)
AP = 8.0 m2 ( AO = 8.0 m2) < Case C-c > < Case C-d >
PP = 11.4 m (PT = 27.4 m) PP = 22.8 m (PT = 38.8 m)
AP = 12.96 m2 ( AO = 3.04 m2) < Case D-c > < Case D-d >
PP = 14.4 m (PT = 30.4 m) PP = 28.8 m (PT = 44.8 m)
AP : Panel area, AO : Opening area, PP : Panel perimeter length, PT : Total perimeter length (=panel + wall perimeter).
with multiple panel surfaces. Even though the centralized and dis- surface temperature is 16 °C with the Case A-d. It shows the results of
tributed layouts are designed with the same panel area (Ap) and the section at 1.6 m from the room wall. It can be found that air rises
opening area (Ao), the perimeter length (Pp) can be different because in along the wall and descends to the occupied zone once it is cooled by
the distributed layout, each panel is in contact with adjacent air. The CRCPs. Some air moves to the plenum through the opening, and then is
impact of the opening area and perimeter length on the cooling capa- cooled and descends through the opening in the center of the room.
city can be evaluated by analyzing cases of panel area and layout, re- Regarding room air temperature, it shows the relatively uniform dis-
spectively. tribution at approximately 24 °C, except the location close to the ceiling
panels and dummies. In Fig. 11 (b), it can also be found that the cooled
4. Results air descends to the occupied zone because the central region, where the
downward flow is generated, shows somewhat lower temperature than
As the cooling capacity of open-type CRCPs can be affected by in- other regions.
creased natural convection and air movement at the upper side of This result indicates that the open-type CRCP could benefit from the
CRCPs, it is necessary to analyze the airflow and temperature dis- cooling effect of the plenum air that descends to the occupied space.
tribution in a space with open-type CRCPs. Fig. 11 shows the airflow Other cases also resulted in the similar air movement and temperature
and temperature distribution in the indoor space when the panel distribution (Refer to Appendix for the results of other cases).
425
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Fig. 11. Airflow and temperature distribution of Case A-d (y = 0.4 m section).
In general, the basic performance of CRCPs can be evaluated with It is clearly shown that the heat flux of the open-type CRCPs is
the heat removal rate, which can be quantified with the heat flux de- higher than that of the closed-type CRCPs. The increased heat flux of
pending on the temperature difference between room operative tem- the open-type CRCPs implies that more heat can be removed with the
perature ( op ) and the average panel surface temperature ( s, m ). The same ( s, m op ) , or an equivalent heat can be removed with a rela-
heat flux was calculated by dividing the panel heat absorption by the tively small ( s, m op ) , compared with the closed-type CRCPs. It can be
panel surface area. Fig. 12 shows the heat flux curves that were de- also observed that the heat flux of the open-type CRCPs is affected by
veloped using simulation results of each case listed in Table 4. For the opening area and layout (centralized or distributed). The detailed
comparison, the flux curves were plotted together with the heat flux analysis on the impact of the opening area and layout are discussed in
curve of closed-type CRCPs, which was calculated in accordance with Section 5.
ISO 11855-2. Table 7 shows detailed simulation results, including the According to testing method in the standard [17], CRCPs are es-
heat flux of each case when the average panel surface temperature sentially evaluated with the cooling capacity curve, which is expressed
changes from 15 to 20 °C. with specific cooling capacity depending on the temperature difference
Fig. 12. Heat flux curves depending on the difference between room operative and panel surface temperature.
426
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Table 7 (Δθ) between the room operative temperature ( op ) and the average
Simulation results on cooling capacity. water temperature ( w ). Therefore, in order to evaluate the cooling
Case Conditions Simulation results
capacity, the abovementioned heat flux curves were transformed into
cooling capacity curves. Considering that thermal resistance of ceiling
AP s, m QP q mr , oz a, oz op s, m op panels will increase the panel surface temperature by 1–2 °C compared
to the chilled water temperature [30], the average water temperature
(m2) (°C) (W) (W/m2) (°C) (°C) (°C) (K) was assumed as 2 °C lower than panel surface temperature.
A-c 4.00 15.0 557.21 139.30 23.83 24.15 23.99 8.99 Fig. 13 shows cooling capacity curves derived from simulation data
4.00 16.0 504.17 126.04 24.03 24.33 24.18 8.18 on the specific cooling capacity depending on the temperature differ-
4.00 17.0 448.45 112.11 24.14 24.40 24.27 7.27 ence Δθ. When Δθ is 8 K, the cooling capacity is designated as the
4.00 18.0 395.09 98.77 24.32 24.56 24.44 6.44 nominal cooling capacity, which is widely used to design and evaluate
4.00 19.0 342.19 85.55 24.55 24.77 24.66 5.66
CRCPs. The difference in nominal cooling capacity of open-type CRCPs
4.00 20.0 288.61 72.15 24.74 24.94 24.84 4.84
can be shown in the enlarged part in Fig. 13. It is clearly shown that
A-d 4.00 15.0 578.10 144.53 23.24 23.62 23.43 8.43 open-type CRCPs can provide higher nominal cooling capacity com-
4.00 16.0 524.54 131.13 23.62 23.95 23.79 7.79 pared to closed-type CRCPs. It is also found that the amount of capacity
4.00 17.0 466.25 116.56 23.69 24.01 23.85 6.85
increase is affected by the opening area and panel layout (centralized or
4.00 18.0 411.04 102.76 23.93 24.22 24.07 6.07
4.00 19.0 355.61 88.90 24.16 24.42 24.29 5.29 distributed). The cooling capacity of each CRCP type can be approxi-
4.00 20.0 300.26 75.06 24.38 24.60 24.49 4.49 mated as a power function of temperature difference Δθ ( op w ),
which can be formulated as follows:
B-c 6.48 15.0 881.84 136.09 23.52 24.04 23.78 8.78
q = k( n
6.48 16.0 795.45 122.75 23.73 24.21 23.97 7.97 op w)
6.48 17.0 708.88 109.39 23.94 24.37 24.15 7.15
6.48 18.0 624.38 96.35 24.15 24.54 24.35 6.35 where k is a coefficient for the panel heat flux and n is an exponent for
6.48 19.0 539.77 83.30 24.36 24.71 24.53 5.53 the temperature difference between the average panel surface tem-
6.48 20.0 454.98 70.21 24.56 24.86 24.71 4.71 perature and the room operative temperature. This equation is similar
to the characteristic curve of radiant floor heating and ceiling cooling
B-d 6.48 15.0 913.75 141.01 23.11 23.76 23.43 8.43
6.48 16.0 824.56 127.25 23.35 23.95 23.65 7.65 defined in ISO 11855-2. However, this equation offers a more con-
6.48 17.0 735.18 113.45 23.59 24.13 23.86 6.86 venient design process because it yields the cooling capacity based on
6.48 18.0 647.86 99.98 23.83 24.33 24.08 6.08 the mean water temperature, whereas ISO 11855-2 requires the average
6.48 19.0 561.06 86.58 24.17 24.54 24.35 5.35 panel surface temperature for the determination of cooling capacity.
6.48 20.0 473.13 73.01 24.39 24.70 24.54 4.54
Table 8 shows the equation of cooling capacity for each CRCP.
C-c 8.00 15.0 1079.85 134.98 23.54 24.30 23.92 8.92 Fig. 14 shows the distribution of k and n values of each CRCP type,
8.00 16.0 972.72 121.59 23.72 24.40 24.06 8.06 overlapped with the nominal cooling capacity contours that show the
8.00 17.0 867.33 108.42 23.91 24.52 24.21 7.21 cooling capacity when Δθ = 8 K. This graph can be used to compare the
8.00 18.0 761.95 95.24 24.11 24.64 24.38 6.38
cooling capacity depending on k and n of the cooling capacity power
8.00 19.0 657.97 82.25 24.33 24.79 24.56 5.56
8.00 20.0 556.82 69.60 24.57 24.96 24.77 4.77 function. It is found that the open-type CRCPs have more cooling ca-
pacity than the closed-type CRCPs. In addition, more cooling capacity
C-d 8.00 15.0 1115.25 139.41 23.22 24.04 23.63 8.63 can be expected with a larger opening area and a distributed panel
8.00 16.0 1004.26 125.53 23.41 24.14 23.78 7.78 layout.
8.00 17.0 895.34 111.92 23.61 24.25 23.93 6.93
8.00 18.0 786.26 98.28 23.79 24.30 24.04 6.04
8.00 19.0 679.94 84.99 24.04 24.50 24.27 5.27 5. Discussion
8.00 20.0 575.88 71.98 24.29 24.69 24.49 4.49
Through the numerical simulations and validation test, it was found
D-c 12.96 15.0 1676.62 129.37 23.00 24.15 23.58 8.58
that the cooling capacity of CRCPs can show a considerable increase,
12.96 16.0 1511.42 116.62 23.26 24.29 23.78 7.78
12.96 17.0 1346.33 103.88 23.53 24.46 23.99 6.99 once the CRCPs are installed with openings between adjacent panels. It
12.96 18.0 1183.16 91.29 23.80 24.63 24.21 6.21 is thought that the capacity enhancement results from the cooling effect
12.96 19.0 1023.92 79.01 24.07 24.78 24.42 5.42 of the plenum air, which is cooled by the upper surface of ceiling panels
12.96 20.0 864.50 66.71 24.34 24.97 24.66 4.66
and descends to the occupied space. The increased convective heat
D-d 12.96 15.0 1701.67 131.30 23.10 24.46 23.78 8.78 transfers between the panel surfaces and surrounding air, which could
12.96 16.0 1534.62 118.41 23.36 24.62 23.99 7.99 be caused by air movement through the opening, could also contribute
12.96 17.0 1367.27 105.50 23.61 24.75 24.18 7.18 to the capacity enhancement.
12.96 18.0 1201.79 92.73 23.86 24.91 24.39 6.39 Fig. 15 shows the potential ranges of capacity enhancement by
12.96 19.0 1040.43 80.28 24.13 25.06 24.60 5.60
open-type installation, which were evaluated with different Δθ
12.96 20.0 878.86 67.81 24.37 25.19 24.78 4.78
( op w ) . Compared with the conventional closed-type CRCPs, the
open-type CRCPs in this study can provide 54–80% (average 64%)
higher nominal cooling capacity, as shown in Fig. 16. It was also found
427
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Table 8
Equations for nominal cooling capacity of each CRCPs.
Type Case Panel Opening Panel layout
area (m2) area (m2)
Centralized Distributed
428
M.S. Shin et al. Building and Environment 148 (2019) 417–432
429
M.S. Shin et al. Building and Environment 148 (2019) 417–432
Appendix
430
M.S. Shin et al. Building and Environment 148 (2019) 417–432
References radiant panel with inclined fins, Energy Build. 62 (2013) 522–529.
[7] F. Causone, S. Corgnati, M. Filippi, B.W. Olesen, Experimental evaluation of heat
transfer coefficients between radiant ceiling and room, Energy Build. 41 (2009)
[1] ISO, ISO DIS 18566-2, Building Environment Design–Design, Test Methods and 622–628.
Control of Hydronic Radiant Heating and Cooling Systems, Part 2: Determination of [8] N.F. Diaz, J. Lebrun, P. André, Thermal modeling of the cooling ceiling systems as
Heating and Cooling Capacity of Ceiling Mounted Radiant Panels, (2015). commissioning tool, Proceedings of the 11th International Building Performance
[2] H.E. Feustel, C. Stetiu, Hydronic radiant cooling - preliminary assessment, Energy Simulation Association Building Simulation Conference, Glasgow, Scotland, 2009,
Build. 22 (1995) 193–205. pp. 27–30.
[3] S.J. Rees, P. Haves, An experimental study of air flow and temperature distribution [9] B. Kilkis, Coolp: a computer program for the design and analysis of ceiling cooling
in a room with displacement ventilation and a chilled ceiling, Build. Environ. 59 panels, ASHRAE Transactions Symposium. SD 95–4–4, 1995, pp. 705–710.
(2013) 358–368. [10] N. Fonseca, Experimental analysis and modeling of hydronic radiant ceiling panels
[4] J. Miriel, L. Serres, A. Trombe, Radiant ceiling panel heating–cooling systems: ex- using transient-state analysis, Int. J. Refrig. 34 (4) (2011) 958–967.
perimental and simulated study of the performances, thermal comfort and energy [11] J. Babiak, B.W. Olesen, D. Petras, Low Temperature Heating And High Temperature
consumptions, Appl. Therm. Eng. 22 (2002) 1861–1873. Cooling: embedded Water Based Surface Heating and Cooling Systems. Rehva.
[5] S. Okamoto, H. Kitora, H. Yamaguchi, T. Oka, A simplified calculation method for Brussels, (2009).
estimating heat flux from ceiling radiant panels, Energy Build. 42 (2010) 29–33. [12] ASHRAE, ASHRAE Handbook-hvac Systems and Equipment, American Society of
[6] L. Zhang, X. Liu, Y. Jiang, Experimental evaluation of a suspended metal ceiling Heating, Refrigerating, and Air Conditioning Engineers, Atlanta, GA, 2012.
431
M.S. Shin et al. Building and Environment 148 (2019) 417–432
[13] M. Andrés-Chicote, A. Tejero-González, E. Velasco-Gómez, F.J. Rey-Martínez, transfer coefficients at the ceiling in a cooled ceiling room, Energy Convers. Manag.
Experimental study on the cooling capacity of a radiant cooled ceiling system, 50 (1) (2009) 1–5.
Energy Build. 54 (2012) 207–214. [28] A. Novoselac, B.J. Burley, J. Srebric, New convection correlations for cooled ceiling
[14] G. Yu, L. Xiong, C. Du, H. Chen, Simplified model and performance analysis for top panels in room with mixed and stratified airflow, HVAC R Res. 12 (2) (2006)
insulated metal ceiling radiant cooling panels with serpentine tube arrangement, 279–294.
Case Studies in Thermal Engineering, 11 2018, pp. 35–42. [29] C. Karmann, F. Bauman, P. Raftery, S. Schiavon, M. Koupriyanov, Effect of acous-
[15] https://www.halton.com/en_IQ/health/products/-/product/AVP (last accessed on tical clouds coverage and air movement on radiant chilled ceiling cooling capacity,
October 2018). Energy Build. 158 (2017) 939–949.
[16] J. Jeong, S. Mumma, Practical cooling capacity estimation model for a suspended [30] B. Ning, Y. Chen, H. Liu, S. Zhang, Cooling capacity improvement for a radiant
metal ceiling radiant cooling panel, Build. Environ. 42 (9) (2007) 3176–3185. ceiling panel with uniform surface temperature distribution, Build. Environ. 102
[17] CEN, EN 14240:2004 Ventilation for Buildings–Chilled Ceiling–Testing and Rating, (2016) 64–72.
(2004). [31] R. Li, T. Yoshidomi, R. Ooka, B.W. Olesen, Field evaluation of performance of ra-
[18] DIN, DIN 4715–1: Cooling Surfaces for Rooms–part 1: Measuring of the diant heating/cooling ceiling panel system, Energy Build. 86 (2015) 58–65.
Performance with Free Flow, (1997). [32] S. Park, D. Kim, M. Yeo, K. Kim, A study on the evaluation of the cooling capacity of
[19] NORDTEST, NT VVS 078 Ceiling Cooling Systems: Cooling Capacity, (1999). radiant ceiling panel according to the panel type, J. Arch. Ins. Korea 30 (12) (2014)
[20] ISO, ISO DIS 18566-3: Building Environment Design-Design, Test Methods and 299–306.
Control of Hydronic Radiant Heating and Cooling Systems, Part 3: Design of Ceiling [33] M. Shin, M. Yeo, W. Kim, Effects on the air temperature in the occupied zone by the
Mounted Radiant Panels, (2015). insulation, installation and arrangement of cooled radiant ceiling panels,
[21] C. Kochendoerfer, Standardized testing of cooling panels and their use in system Proceedings of Annual Conference of AIK, Busan, 2015, pp. 473–474.
planning, Build. Eng. 102 (1) (1996) 651–658. [34] M. Shin, Cooling Capacity Estimation and Design Process for the Open-type
[22] J. Jeong, S.A. Mumma, Ceiling radiant cooling panel capacity enhanced by mixed Installation of Ceiling Radiant Cooling Panels, Ph.D Dissertation Seoul National
convection in mechanically ventilated spaces, Appl. Therm. Eng. 23 (18) (2003) University, 2016.
2293–2306. [35] T. Cholewa, R. Anasiewicz, A. Siuta-Olcha, M.A. Skwarczynski, On the heat transfer
[23] J. Jeong, S.A. Mumma, Impact of mixed convection on ceiling radiant cooling panel coefficients between heated/cooled radiant ceiling and room, Appl. Therm. Eng.
capacity, HVAC R Res. 9 (3) (2003) 251–257. 117 (2017) 76–84.
[24] Z. Tian, X. Yin, Y. Ding, C. Zhang, Research on the actual cooling performance of [36] ISO, ISO 11855-2:2012(E) Building Environment Design – Design, Dimensioning,
ceiling radiant panel, Energy Build. 47 (2012) 636–642. Installation and Control of Embedded Radiant Heating and Cooling Systems. Part 2:
[25] S. Park, Establishing Boundary Condition for Evaluating the Cooling Capacity of Determination of the Design Heating and Cooling Capacity, International
Ceiling Radiant Cooling Panel, Ph.D Dissertation Seoul National University, 2016. Organization for Standard, Geneve, Switzerland, 2012.
[26] R. Karadağ, New approach relevant to total heat transfer coefficient including the [37] K. Kim, B.W. Olesen, Radiant heating and cooling systems: part 1, ASHRAE J. 57
effect of radiation and convection at the ceiling in a cooled ceiling room, Appl. (2015) 28–37.
Therm. Eng. 29 (8–9) (2009) 1561–1565. [38] W. Xu, Q. Chen, A two-layer turbulence model for simulating indoor airflow: Part I.
[27] R. Karadağ, The investigation of relation between radiative and convective heat Model development, Energy Build. 33 (6) (2001) 613–625.
432